CleaverBrooks CFC-E, CFC-E 500, CFC-E 750, CFC-E 1500, CFC-E 1000 Series Manual

...
CFC-E
ClearFire Condensing Boiler
Boiler Book 02/2018
BOILER BOOK CFC-E
FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PRODUCT OFFERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ENGINEERING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fireside Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Premix Burner Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
ClearFire CE Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Model CFC-E Dimensional Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Efficiencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
Waterside Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-20
High Fire Speed Settings vs. % Glycol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Maximum Firing Rate vs. % Glycol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Condensate Piped Direct to Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Neutralization Capsule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Combo Trap/Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Treatment Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Condensate Piping for Multiple Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Tank Detail, Multiple Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Gas Piping Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Gas Header Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Model CFC-E Minimum Room Clearance Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
CFC-E Seismic Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Two Opening Outside Wall Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Two Opening Ducted Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
One Opening Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Two Opening Engineered Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Boiler Air Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Horizontal through-wall venting using inside air for combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Horizontal flue through-wall with direct vent combustion intake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Inside Air - Vertical Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Vertical Stack with Direct Vent Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
CFC-E Rear Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
CB Falcon Pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Primary/Secondary Piping Schematic, Single Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Primary/Secondary Piping Schematic, Two Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Primary/Secondary Piping Schematic, Three Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Primary Variable Flow Piping Schematic, Single Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Primary Variable Flow Piping Schematic, Two Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Primary Variable Flow Piping Schematic, Three Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Primary Variable Flow Piping Schematic, Single Boiler with Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Primary Variable Flow Piping Schematic, Single Boiler with Heat Exchanger and Dual Return . . . . . . . . . . . . . . . . . . . . . . 59
Table of Contents
List of Figures
List of Tables
U.S. Standard Dimensions Model CFC-E Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions (Metric) Model CFC-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Model CFC-E Boiler Ratings (Sea Level to 2000 Feet) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Altitude Correction for Input Capacity at Various Altitude Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CFC-E Efficiencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Noise level (dBA) measured 3 feet in front of boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14
2
BOILER BOOK CFC-E
Model CFC-E Minimum Over Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Safety Relief Valve Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Model CFC-E Water Chemistry Requirements in accordance with ABMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Glycol Minimum Flow Recommendations for ClearFire Model CFC-E Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Condensate piping for multiple boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Model CFC-E Minimum and Maximum Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Model CFC-E Minimum Required Gas Pressure Altitude Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Stack Sizing Using Outside Air for Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Operating Conditions - Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Operating Conditions - Display/Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
CB Falcon burner sequence (Central Heat) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3
BOILER BOOK CFC-E FEATURES AND BENEFITS
FEATURES AND BENEFITS
Compact Firetube Design
The Model CFC-E boiler is a high mass, vertical down fired robust firetube boiler. The internal extended-heating surface tubes provide very high levels of performance in a compact space. The large water volume makes the CFC-E ideal for variable flow primary pumping systems.
Large Water Volume
The large water volume makes the CFC-E ideal for variable flow primary pumping systems.
Advanced Technology
Tubes, tube sheets, and combustion chamber are constructed from UNS S32101 duplex stainless steel. Tubes feature AluFer tube inserts for optimal heat transfer.
Advanced Fireside Construction
The extended heating surface design provides the ideal solution for the demands of a condensing boiler and helps to recover virtually all the latent heat of the flue gas. Each tube consists of an outer stainless steel tube (waterside) and the AluFer extended heating surface profile on the flue gas side.
High Efficiency
With the extended heating surface tubes the CFC-E boiler will provide fuel to water efficiency of up to 99% at low fire and 95% at high fire with 80 degrees F return water temperature.
Ease of Maintenance
The powder coated steel casing is designed for easy removal and re-assembly. As shown in Figure 1, the burner is hinged and is provided with hydraulic pistons for simple opening for service of the spark electrode, inspection of the burner cylinder, tubes and combustion chamber.
Figure 1. Fireside Access
Quality Construction
ASME Code construction ensures high quality design, safety, third party inspection, and reliability, and accordingly bears the ASME Section IV “H” stamp.
Premix Technology
The burner utilizes “Premix” technology to mix both gas fuel and combustion air prior to entering the burner canister, with air leading the fuel during burner firing transitions. Combined with the surface combustion burner and self-regulating gas valve-venturi fuel-air ratio control, this technology provides very low emission levels, exceptionally safe operation, and nearly 100% combustion efficiency.
Full Modulation
The variable speed combustion air blower with ECM technology provides modulated firing for precise
4
BOILER BOOK CFC-E FEATURES AND BENEFITS
linear load tracking, reduced on-off cycling, and reduced electrical consumption.
Figure 2. Premix Burner Technology
Designed For Heating Applications
The pressure vessel is designed for 125 psig MAWP (Maximum Allowable Working Pressure) and is constructed of durable ASTM Grade Steel and Stainless Steel materials. The true counter flow heat exchanger design equates to optimal heat transfer. The design also prevents hot spots, does not require a minimum flow for thermal shock protection, and does not require a minimum return water temperature. In fact, the design carries a 20-year thermal shock warranty.
Because of its design characteristics, the Model CFC-E is well suited for applications utilizing indoor/ outdoor reset controls, radiant floor heating, snow melt systems, ground source heat pump systems and systems that utilize variable speed circulating pumps. It may also be employed in standard hot water systems that require higher heated water at colder outdoor temperatures but then require lower temperatures during warmer heating days, realizing fuel efficiency savings over traditional hot water boilers.
While the design does not lend itself to the direct supply of potable water, a separate storage tank with an internal heat exchanger can be employed, as the onboard controls permit domestic water programming. Therefore, the Model CFC-E can service both hydronic heating and domestic water source heating.
Dual Return
Two return connections - high and low temperature - allow condensing performance with as little as 10% return water at condensing temperature.
SCAQMD Certified
The CFC-E is certified by the South Coast Air Quality Management District.
5
BOILER BOOK CFC-E PRODUCT OFFERING
PRODUCT OFFERING
Dimensions, ratings, and product information may change to meet current market requirements and product improvements. Therefore, use this information as a guide.
Standard Equipment
Equipment described below is for the standard boiler offering:
1. The Boiler A. Each boiler size is designed for a Maximum Allowable Working Pressure (MAWP) of 125 psig
(8.6 Bar), constructed in accordance with the ASME Code Section IV and bear the “H” stamp.
B. The insulated pressure vessel is mounted on a base and a powder coated steel casing is
provided.
C. A drain valve connection is provided at the front bottom for field piping of a boiler drain valve,
which can be furnished as an option.
2. Boiler Trim and Controls
The following items are furnished:
Probe Type Low Water Cutoff control, manual reset.
High Water Temperature Cutoff, manual reset.
NTC (negative temp. coefficient) sensor for hot water supply temperature.
NTC sensor for hot water return temperature.
ASME Safety Relief Valve set @ 125 psig. (8.6 Bar) (Optional SRV set points available.)
Combination Temperature/Pressure Gauge.
3. Burner Control A. The Falcon
controller is an integrated burner management and modulation control with a color
touch-screen display/operator interface. Its functions include the following:
• Two (2) heating loops with PID load control.
• Burner sequencing with safe start check, pre-purge, direct spark ignition, and post purge.
• Electronic ignition.
• Flame Supervision.
• Safety shutdown with time-stamped display of lockout condition.
• Variable speed control of the combustion fan.
• Supervision of low and high gas pressure, air proving, stack back pressure, high limit, and low water.
• First-out annunciator.
• Real-time data trending.
• (3) pump/auxiliary relay outputs.
• Modbus communication capability.
• Outdoor temperature reset.
• Remote firing rate or setpoint control
• Setback/time-of-day setpoint
• Lead/Lag for up to 8 boilers
6
BOILER BOOK CFC-E PRODUCT OFFERING
Figure 3. ClearFire CE Control Panel
4. Forced Draft Burner A. The burner is a “Pre-mix” design consisting of a unitized venturi, single body dual safety gas
valve, blower, and burner head. Consistent fuel-air ratio is maintained with a self-regulating
gas valve-venturi system which automatically compensates for changes in air density. B. Full modulation is accomplished with a variable speed fan for 5:1 turndown ratio. C. For near flameless combustion, the burner utilizes a Fecralloy-metal fiber head.
D. Noise level at maximum firing is less than 70 dBA regardless of boiler size.
E. Operating on Natural Gas, NOx emissions will be less than 20 PPM regardless of boiler size.
F. As an option, the burner is capable of direct vent combustion.
G. Ignition of the main flame is via direct spark, utilizing high voltage electrodes and a UV
scanner for flame supervision.
H. To ensure adequate combustion air is present prior to ignition, and to ensure the fan is
operating, a combustion air proving switch is furnished.
I. A High Air Pressure Switch is provided to ensure burner lockout if excessive back pressure
due to a blocked stack occurs.
J. For ease of maintenance and inspection, the burner is furnished with hydraulic rods and easy
opening lockdown nuts, which permit the burner to swing up. This provides full access to the
burner and electrodes, as well, to the tube sheet and tubes.
K. Supports direct vent combustion air.
5. Burner Gas Train
The standard gas train is equipped in accordance with UL certification and complies with ASME CSD-1. Each burner gas train includes:
Low Gas Pressure Interlock, manual reset.
7
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
High Gas Pressure Interlock, manual reset.
ASME CSD-1 Test Cocks.
Downstream manual ball type shutoff valve.
Single body dual safety shutoff gas valve.
Optional Equipment
For option details, contact the local authorized Cleaver-Brooks representative. In summary, here are some of the options that can be provided with the boiler:
A. Reusable air filter. B. Condensate neutralization tank assembly - consists of neutralizing media, filter, and PVC condensate holding
tank with integral drain trap. C. Outside air intake for direct vent combustion. D. Outdoor temperature sensor for indoor/outdoor control. E. Header temperature sensor for multiple boiler Lead/Lag operation. F. Auxiliary Low Water Control (shipped loose) for field piping by others into the system piping. G. Alarm Horn for safety shutdown. H. Relays for output signal for burner on, fuel valve open. I. Stack Thermometer. J. Stack temperature limit-sensor. K. Auto air vent. L. Boiler drain valve. M. Adjustable feet. N. Seismic anchoring brackets. O. Protocol translator for communications
DIMENSIONS AND RATINGS
For layout purposes, the overall dimensions for the Model CFC-E are shown in Table 1 (US Dimensions) and Table 2 (Metric Dimensions) including the various pipe connection sizes for supply and return water, drain, and vent. The performance ratings for the boiler are shown in Table 3.
Altitude
See Table 4 for input capacity ratings at various altitude levels.
8
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
OPTIONAL ADJUSTABLE FEET ALLOW FOR
1.56” TO 3.88” ADDITIONAL HEIGHT
Figure 4. Model CFC-E Dimensional Views
9
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
Table 1. U.S. Standard Dimensions Model CFC-E Boiler
ITEM DIMENSIONS (inches) 500 750 1000 1500 2000
A Overall Height 78.0 78.0 78.0 79.9 79.9 B Overall Width 34.9 34.9 34.9 35.8 35.8 C Overall Depth 49.4 49.4 49.4 56 56 D Width Less Casing 32.1 32.1 32.1 33.0 33.0 E Gas Connection to Floor 70.3 70.3 70.3 73.9 73.9 F Side of Casing to Gas Connection 3.7 3.7 3.7 7.1 7.1 G Side of Casing to Air Inlet 10.8 10.8 10.8 10.8 10.8 H Top of Casing to Air Inlet 7.7 7.7 7.7 7.1 7.1 J Floor to Condensate Drain 6.3 6.3 6.3 6.3 6.3 K Floor to Bottom of Casing 11.0 11.0 11.0 11.0 11.0
L Side of Base to Flue Outlet (Centered) 7.4 7.4 7.4 8.5 8.5 M Side of Base to Flue Outlet (Offset) 6.4 6.4 6.4 7.5 7.5 N Rear of Base to Flue Outlet 6.5 6.5 6.5 7.5 7.5
P Casing Depth 36.3 36.3 36.3 42.4 42.4
Q Casing Height 67.0 67.0 67.0 68.9 68.9
R Floor to Lower Return Connection 16.8 16.8 16.8 16.8 16.8
S Floor to Upper Return Connection 31.8 31.8 31.8 31.8 31.8
T Floor to Supply Connection 59.5 59.5 59.5 59.5 59.5 U Floor to Air vent Connection 66.3 66.3 66.3 66.3 66.3
V Air Vent Line Projection From Rear of Casing 3.2 3.2 3.2 3.3 3.3
CONNECTIONS
W Water Low Temp. Return, Class150 RF Flange 2-1/2" 2-1/2" 2-1/2" 4" 4"
X Water High Temp. Return, Class150 RF Flange 2-1/2" 2-1/2" 2-1/2" 4" 4"
Y Water Outlet, Class150 RF Flange 2-1/2" 2-1/2" 2-1/2" 4" 4"
Z Air Vent, NPT 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2"
AA Vessel Drain, NPT 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2" BB Flue Gas Outlet
CC Combustion Air - Nominal 6" 6" 6" 8" 8" DD Gas, NPT 1" 1" 1" 1-1/2" 1-1/2" EE Condensate Drain, NPT 1" 1" 1" 1" 1" FF Electrical Opening, Left or Right 1.6" 1.6" 1.6" 1.6" 1.6" GG Safety Relief Valve Vessel Connection, NPT 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4"
HH Safety Relief Valve
KK Water Outlet Coupling, NPT 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4"
(Standard) - Nominal 6" 6" 8" 8" 8" (Option) - Nominal 8" 8" 6" 10" 10"
30 psig Inlet x Outlet, NPT 1" x 1-1/4" 1" x 1-1/4" 1" x 1-1/4" 1" x 1-1/4" 1-1/4" x 1-1/2" 50 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 1" x 1-1/4" 60 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 1" x 1-1/4" 75 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 80 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 100 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 125 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1"
JJ Flue Coupling, NPT 3/4" 3/4" 3/4" 3/4" 3/4"
FORK POCKETS (inches)
LL Pocket Height 3.9 3.9 3.9 3.9 3.9
MM Pocket Width 11.8 11.8 11.8 11.8 11.8
NN Overall Pocket Width 27.6 27.6 27.6 27.6 27.6
WEIGHTS
Dry Weight (lb) 1298 1298 1396 1861 2041 Shipping Weight (lb) 1413 1413 1511 1986 2166 Operating Weight (lb) 2065 2065 2113 2778 2858 Water Volume (gallon) 92 92 86 110 98
CLEARANCES
Top 14" Side 3" Rear 20" Front 36"
Notes:
Boiler rear must be accessible for servicing.
Side clearance to wall or between boilers.
Side clearance typical each side.
10
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
Table 2. Dimensions (Metric) Model CFC-E
ITEM DIMENSIONS (mm) 500 750 1000 1500 2000
A Overall Height 1982 1982 1982 2028 2028 B Overall Width 886 886 886 908 908 C Overall Depth 1255 1255 1255 1422 1422 D Width Less Casing 816 816 816 838 838 E Gas Connection to Floor 1786 1786 1786 1877 1877 F Side of Casing to Gas Connection 95 95 95 180 180 G Side of Casing to Air Inlet 275 275 275 273 273 H Top of Casing to Air Inlet 196 196 196 180 180
J Floor to Condensate Drain 160 160 160 160 160 K Floor to Bottom of Casing 279 279 279 279 279 L Side of Base to Flue Outlet 189 189 189 217 217
M Side of Base to Flue Outlet (Offset) 164 164 164 192 192 N Rear of Base to Flue Outlet 165 165 165 190 190
P Casing Depth 921 921 921 1077 1077 Q Casing Height 1703 1703 1703 1749 1749 R Floor to Lower Return Connection 428 428 428 428 428 S Floor to Upper Return Connection 808 808 808 808 808 T Floor to Supply Connection 1511 1511 1511 1511 1511
U Floor to Air vent Connection 1683 1683 1683 1683 1683
V Air Vent Line Projection From Rear of Casing 81 81 81 84 84
FORK POCKETS (mm)
LL Pocket Height 100 100 100 100 100
MM Pocket Width 300 300 300 300 300
NN Overall Pocket Width 700 700 700 700 700
WEIGHTS
Dry Weight (kg) 589 589 633 844 926 Shipping Weight (kg) 641 641 686 901 983 Operating Weight (kg) 939 939 969 1260 1280 Water Volume (liter) 350 350 324 416 370
CLEARANCES (mm)
Top 356 Side 76 Rear 508 Front 914
Notes:
Boiler rear must be accessible for servicing.
Side clearance to wall or between boilers.
Side clearance typical each side.
11
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
Table 3. Model CFC-E Boiler Ratings (Sea Level to 2000 Feet)
Boiler Size
Description Units 500 750 1000 1500 2000
Input Max.
Natural Gas Propane Natural Gas Propane
Output at 120/80 F [49/27 C] 100% Firing
Output at 180/140 F [82/60 C] 100% Firing
MAWP
MAWT
Maximum Operating Setpoint
Water Content
Btu/Hr 500,000 750,000 1,000,000 1,500,000 2,000,000
KCal/Hr 126,000 189,000 252,000 378,000 504,000
Ft3/Hr Ft3/Hr M3/Hr M3/Hr
Btu/Hr 470,000 705,000 940,000 1,410,000 1,880,000
KCal/Hr 118,440 177,660 236,880 355,320 473,760
BHP 14 21 28 42 56
KW 138 207 275 413 551
Btu/Hr 440,000 660,000 880,000 1,320,000 1,760,000
KCal/Hr 110,880 166,320 221,760 332,640 443,520
BHP 13 20 26 39 53
KW 129 193 258 387 516
psi 125 125 125 125 125
Bar 8.6 8.6 8.6 8.6 8.6
°F 210 210 210 210 210 °C 99 99 99 99 99
°F 194 194 194 194 194 °C 90 90 90 90 90
Gallons 92 92 86 110 98
Liters 350 350 324 416 370
500 750 1000 1500 2000 200 300 400 600 800
14 21 28 42 57
5.7 8.5 11 17 23
Weight w/o Water
Standby Heat Loss
ECM Blower Motor Size Operating Voltage, Blower Control Circuit Max Current Draw, Blower Max Current Draw Cont. Circuit Max Over Current Protection
Condensate Quantity Firing Nat. Gas & operating @ 120/80 F.
Flue Gas Mass Flow @ 100% Firing
Pounds 1,298 1,298 1,396 1,861 2,041
Kg 589 589 633 844 926
Btu/Hr 1000 1500 2000 3000 4000
Watts 293 440 586 879 1172
Watts 335 335 335 1,700 1,700 Volts/Ph/Hz 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 Volts/Ph/Hz 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60
Amperes 4 4 4 13.5 13.5 Amperes 1.5 1.5 1.5 2 2 Amperes 20 20 20 20 20
Gal/Hr 3.5 5 7 10 13.5
lb/hr 557 835 1,113 1,670 2,226 kg/hr 252 379 505 758 1010
12
BOILER BOOK CFC-E PERFORMANCE DATA
Table 4. Altitude Correction for Input Capacity at Various Altitude Levels
Natural Gas MBTU/h at various altitudes
700' ASL 2000' 4000' 6000' 8000' 10000'
CFC-E 2000
CFC-E 1500
CFC-E 1000
CFC-E 750
CFC-E 500
** Ratings assume 35% excess air, 80F combustion air. Blower speed adjustments should be made to match performance and local conditions accordingly. For minimum gas supply pressures see Table 14. Altitude corrections for supply pressure should be made per Table 15 Natural gas heating value of 1000 BTU/SCF assumed.
2000 2000 1883 1747 1619 1552 1500 1500 1500 1500 1500 1472 1000 1000 945 877 813 779
750 750 750 707 655 628 500 500 473 438 406 389
LP Gas MBTU/h at various altitudes
700' ASL 2000' 4000' 6000' 8000' 10000'
CFC-E 2000
CFC-E 1500
CFC-E 1000
CFC-E 750
CFC-E 500
** Ratings assume 40% excess air, 80F combustion air. Blower speed adjustments should be made to match performance and local conditions accordingly. For minimum gas supply pressures see Table 14. Altitude corrections for supply pressure should be made per Table 15\ LP (propane) gas heating value of 2500 BTU/SCF assumed.
2000 2000 2000 1867 1730 1659 1500 1500 1500 1500 1500 1500 1000 1000 1000 926 858 822
750 750 750 750 724 694 500 500 500 472 437 419
PERFORMANCE DATA
Efficiency
The Model CFC-E is a “full condensing” boiler realizing efficiency gain at variable operating conditions. It is designed to extract the latent heat of condensation over a greater range than other designs. The nominal point of condensation is approximately 132 its more efficient heat transfer design and lower stack temperature, is able to capture the latent heat of condensation over a broader range.
Fuel-to-water efficiency is relative to specific operating conditions. Operating efficiency will be greater in the “condensing” mode of operation as noted above, yet with its inherently greater heat transfer surfaces and superior premix burner, the ClearFire’s efficiency under “traditional” hot water conditions is also outstanding. Table 5 shows the guaranteed efficiencies at various operating conditions and firing rates for Natural Gas. It should be noted that the efficiency is exceptional at high fire and low fire versus other designs where high efficiency is realized only with low fire or minimal firing rates and low temperature returns.
ClearFire Efficiencies
The tables below list the operating efficiencies of each size Model CFC-E boiler, including radiation losses. As the Model CFC-E is a fully condensing boiler, maximum efficiency is obtained when operating within the condensing mode, utilizing the latent heat of condensation.
F (55.5 C). The ClearFire, due to
13
BOILER BOOK CFC-E PERFORMANCE DATA
Table 5. CFC-E Efficiencies
CFC-E 500 Efficiency
Return Water Temperature °F ( °C )
% Firing Rate
20% 99.0 97.8 96.1 92.4 90.4 88.9 88.1 50% 97.9 96.7 94.7 91.5 89.9 88.6 87.9 75% 97.2 95.7 93.6 90.8 89.4 88.4 87.7
100% 96.5 94.8 92.5 90.0 89.0 88.1 87.6
% Firing Rate
20% 98.5 97.4 95.6 92.1 90.3 88.8 88.0 50% 97.2 95.7 93.6 90.8 89.4 88.4 87.7 75% 96.1 94.3 92.0 89.7 88.7 88.0 87.5
100% 95.0 92.9 90.3 88.6 88.0 87.6 87.3
% Firing Rate
20% 99.0 98.8 97.0 93.3 90.7 88.9 88.0 50% 97.8 96.9 94.7 91.5 89.8 88.5 87.7 75% 96.9 95.4 92.7 90.0 89.0 88.2 87.5
100% 95.9 93.8 90.8 88.6 88.2 87.9 87.3
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
CFC-E 750 Efficiency
Return Water Temperature °F ( °C )
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
CFC-E 1000 Efficiency
Return Water Temperature °F ( °C )
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
CFC-E 1500 Efficiency
Return Water Temperature °F ( °C )
% Firing Rate
20% 98.5 97.6 95.2 91.8 90.1 88.8 88.0 50% 97.1 95.9 93.4 90.6 89.3 88.3 87.8 75% 96.0 94.4 91.9 89.6 88.6 87.9 87.5
100% 94.9 93.0 90.4 88.6 87.9 87.5 87.3
% Firing Rate
20% 98.0 97.1 94.5 91.4 90.0 88.9 88.0 50% 96.6 95.5 93.0 90.5 89.3 88.5 87.7 75% 95.5 94.1 91.7 89.6 88.8 88.2 87.5
100% 94.3 92.7 90.5 88.8 88.3 87.8 87.2
Conditions:
Natural Gas 40% Excess Air Relative Humidity = 50% ΔT = 40°F R & C Loss = 0.2% of rated capacity
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
CFC-E 2000 Efficiency
Return Water Temperature °F ( °C )
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
14
BOILER BOOK CFC-E PERFORMANCE DATA
Figure 5. Efficiency 500
CFC-E 500 Eciency Curve
100
99
98
97
96
95
94
93
Eĸciency (%)
92
91
90
89
88
87
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature (
40° F Temperature DiīerenƟal
°F)
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
Figure 6. Efficiency 750
CFC-E 750 Eciency Curve
100
99
98
97
96
95 94
93
92
Eciency (%)
91
90
89 88
87
86
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature ( °F)
40°F Temperature DiīerenƟal
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
15
BOILER BOOK CFC-E PERFORMANCE DATA
Figure 7. Efficiency 1000
CFC-E 1000 Eciency Curve
100
99
98
97
96
95 94
93
92
Eciency (%)
91
90
89 88
87
86
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature ( °F)
40°F Temperature DiīerenƟal
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
Figure 8. Efficiency 1500
CFC-E 1500 Eciency Curve
100
99
98
97
96
95 94
93
92
Eciency (%)
91
90
89 88
87
86
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature ( °F)
40°F Temperature DiīerenƟal
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
16
BOILER BOOK CFC-E PERFORMANCE DATA
Figure 9. Efficiency 2000
CFC-E 2000 Eciency Curve
99 98
97 96
95 94
93 92
91
Eciency (%)
90 89
88 87
86
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature ( °F)
40°F Temperature DiīerenƟal
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
Emissions
By means of the Pre-mix burner, the Clearfire boiler provides environmentally friendly emissions when firing natural gas; emission data are shown below.
Table 6. Emissions
POLLUTANT UNITS
CO
NOx
SOx
HC/VOC
PM
*ppm levels are given on a dry volume basis and corrected to 3% oxygen (15% excess air)
ppm* <20
lb/MMBTU <0.014
ppm* <20
lb/MMBTU <0.024
ppm* <1
lb/MMBTU <0.001
ppm* <4
lb/MMBTU <0.0016
ppm* -
lb/MMBTU <0.01
Noise Level
The Model CFC-E is extremely quiet at all operating levels, does not require any sound level modifications to provide ultra low noise levels, and is virtually vibration free. Thus, it is very suitable in applications that demand low noise levels.
Table 7.
CFC-E 500 43 56 61
CFC-E 750 41 51 60
CFC-E 1000 43 56 61
CFC-E 1500 46 56 66
CFC-E 2000 46 61 70
Noise level (dBA) measured 3 feet in front of boiler
20% Input 60% Input 100% Input
17
BOILER BOOK CFC-E ENGINEERING DATA
ENGINEERING DATA
Boiler Information
The Model CFC-E boiler is designed for service in any closed hydronic system. It can be put into operation as a single stand-alone unit with 5:1 turndown or in multiple units for larger turndown and capacity.
Clearfire boilers may be utilized in water heating systems with temperatures from 40 194
F (90 C); ideal for systems such as ground water source heat pump applications. Because the
Clearfire is a full condensing boiler, low water temperature (below the dewpoint) restrictions do not apply. In fact, the lower the return the better the fuel savings.
Variable temperature differentials can be designed to make use of changing outdoor conditions and thus, the Clearfire is not restricted to a nominal 20
F (10 C) differential. The boiler is designed to
withstand thermal stresses with supply and return temperature differences up to 100 without the use of a boiler-circulating pump, blend pump or minimum water flow.
Note: The Clearfire does not require a minimum flow or continuous flow through it during operation. However, the load
imposed on the boiler must be considered when sizing the system flow so that the flow does not exceed the capacity of the boiler or the demand.
Flow Rates and Pressure Drops
To maintain rated capacity of the boiler, recommended flow rates should not be exceeded as the flow will remove the heat beyond the capacity of the boiler.
F (4.4 C) to
F (55 C),
Table 8. Flow Rates
CFC-E Flow Rates
Temperature Differential (°F)
10 20 30 40 50 60 70 80 90 100 110 120 Size Flow Rate GPM 500 94 47 31 24 19 16 13 12 10 9 9 8 750 141 71 47 35 28 24 20 18 16 14 13 12
1000 188 94 63 47 38 31 27 24 21 19 17 16 1500 283 141 94 71 57 47 40 35 31 28 26 24 2000 377 188 126 94 75 63 54 47 42 38 34 31
Recommended flow rates relative to temperature drop so as not to exceed boiler output. Based on 94% nominal effficiency and maximum firing capacity Based on water only
CFC-E Flow Rates [metric]
Temperature Differential (°C)
6 1117222833394450566167
Size 500 21.4 10.7 7.1 5.3 4.3 3.6 3.1 2.7 2.4 2.1 1.9 1.8
750 32.1 16.0 10.7 8.0 6.4 5.3 4.6 4.0 3.6 3.2 2.9 2.7
1000 42.8 21.4 14.3 10.7 8.6 7.1 6.1 5.3 4.8 4.3 3.9 3.6 1500 64.1 32.1 21.4 16.0 12.8 10.7 9.2 8.0 7.1 6.4 5.8 5.3 2000 85.5 42.8 28.5 21.4 17.1 14.3 12.2 10.7 9.5 8.6 7.8 7.1
Recommended flow rates relative to temperature drop so as not to exceed boiler output. Based on 94% nominal efficiency and maximum firing capacity Based on water only
Flow Rate m
3
/hr
18
BOILER BOOK CFC-E ENGINEERING DATA
Figure 10. Waterside Pressure Drop CFC-E 500
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Pressure (psi)
0.5
0.4
0.3
0.2
0.1
0.0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
Flow Rate (gpm)
Figure 11. Waterside Pressure Drop CFC-E 750
19
BOILER BOOK CFC-E ENGINEERING DATA
Figure 12. Waterside Pressure Drop CFC-E 1000
Figure 13. Waterside Pressure Drop CFC-E 1500
20
BOILER BOOK CFC-E ENGINEERING DATA
Figure 14. Waterside Pressure Drop CFC-E 2000
System Operating Parameters
To prevent water flashing to steam within the boiler or system, hot water boilers must operate with proper over-pressure. System over-pressure requirements are shown in Table 9.
Maximum Allowable Working Temperature (MAWT) is 210°F (99°C). Maximum operating set point is 194°F (90°C) Maximum Allowable Working Pressure is 125 PSIG (963 KPA) Practical operating pressure limit is 112 PSIG (874 KPA)
While proper overpressure is required, a means to relieve excess pressure at or beyond the design pressure of the boiler must be provided. As boiler water is heated, expansion occurs. And this expansion must be accounted for either with an expansion tank (air filled) or with a bladder type tank. These devices permit the water pressure to expand outside of the boiler and not impact the pressure vessel or pressure relieving device. But, in accordance with Code, each boiler is equipped with an ASME approved safety relieving device should pressure build-up occur (See Table 10).
Air Venting
The elimination of entrained air is required. It is recommended that each unit be piped to an expansion tank. If this is not possible, then an auto air vent should be provided on the vent connection of the boiler. The caveat in using an auto vent is that free oxygen can be introduced to the vessel as the boiler cools, or in some instances the vent can become plugged.
Table 9. Model CFC-E Minimum Over Pressure Requirements
Outlet Water Temperature Minimum System Pressure
(°F) (°C) PSIG Bar
80-180 27-82 12 0.83 181-185 83-85 15 1.03 186-195 86-91 18 1.24
21
BOILER BOOK CFC-E ENGINEERING DATA
Table 10. Safety Relief Valve Information
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH) CFC-E 500 3/4” 1" 3364 CFC-E 750 3/4” 1" 3364 CFC-E 1000 3/4” 1" 3364 CFC-E 1500 3/4” 1" 3364 CFC-E 2000 3/4” 1" 3364
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH) CFC-E 500 3/4” 1" 2756 CFC-E 750 3/4” 1" 2756 CFC-E 1000 3/4” 1" 2756 CFC-E 1500 3/4” 1" 2756 CFC-E 2000 3/4” 1" 2756
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH) CFC-E 500 3/4” 1" 2270 CFC-E 750 3/4” 1" 2270 CFC-E 1000 3/4” 1" 2270 CFC-E 1500 3/4” 1" 2270 CFC-E 2000 3/4” 1" 2270
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH) CFC-E 500 3/4” 1" 2148 CFC-E 750 3/4” 1" 2148 CFC-E 1000 3/4” 1" 2148 CFC-E 1500 3/4” 1" 2148 CFC-E 2000 3/4” 1" 2148
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH) CFC-E 500 3/4” 1" 1785 CFC-E 750 3/4” 1" 1785 CFC-E 1000 3/4” 1" 1785 CFC-E 1500 3/4” 1" 1785 CFC-E 2000 1" 1-1/4" 2789
Model Inlet (NPT) Outlet (NPT) Valve Capacity (MBH) CFC-E 500 3/4” 1" 1540 CFC-E 750 3/4” 1" 1540 CFC-E 1000 3/4” 1" 1540 CFC-E 1500 3/4” 1" 1540 CFC-E 2000 1" 1-1/4" 2407
@125 psig
@100 psig
@80 psig
@75 psig
@60 psig
@50 psig
22
BOILER BOOK CFC-E ENGINEERING DATA
Water Treatment
Even though hot water systems are “closed”, some amount of make-up water (up to 10%) will be introduced. This more often than not happens from seal leaks of pumps, or other minimal leaks from valves etc., that go unnoticed. Therefore, proper water chemistry of a hot water boiler is necessary for good operation and longevity, particularly to ensure that free oxygen is removed to prevent waterside corrosion.
Table 11. Model CFC-E Water Chemistry Requirements in accordance with ABMA
Parameter Limit
Glycol 50%
pH 8.3 - 10.5 Nitrates 50 ppm Sulfates 50 ppm
Chloride < 250 ppm
Oxygen < 0.1 ppm
Specific Conductivity
Total Hardness < 10 ppm
< 3500 mmho/cm
Glycol Application Guidelines
The Model CFC-E boiler may be operated with a solution of glycol and water. Where glycols are added, the system must first be cleaned and flushed. Correct glycol selection and regular monitoring of the in-use concentration and its stability is essential to ensure adequate, long-term freeze protection, including protection from the effects of glycol-derived corrosion resulting from glycol degradation.
Typically, ethylene glycol is used for freeze protection, but other alternatives exist, such as propylene glycol. Glycol reduces the water-side heat capacity (lower specific heat than 100% water) and can reduce the effective heat transfer to the system. Because of this, design flow rates and pump selections should be sized with this in mind.
Generally, corrosion inhibitors are added to glycol systems. However, all glycols tend to oxidize over time in the presence of oxygen, and when heated, form aldehydes, acids, and other oxidation products. Whenever inadequate levels of water treatment buffers and corrosion inhibitors are used, the resulting water glycol mixture pH may be reduced to below 7.0 (frequently reaching 5) and acid corrosion results. Thus, when pH levels drop below 7.0 due to glycol degradation the only alternative is to drain, flush, repassivate, and refill with a new inhibited glycol solution.
The following recommendations should be adhered to in applying ClearFire model CFC-E boilers to hydronic systems using glycol:
1) Maximum allowable antifreeze proportion (volume%): 50% antifreeze (glycol) 50% water
2) The glycol concentration determines the maximum allowable firing rate and output of the boiler(s). Please refer to the firing rate limitation and corresponding high fire speed settings vs. glycol% in the charts below.
3) Maximum allowable boiler outlet/supply temperature: 185 deg F (85 deg C).
4) Minimum water circulation through the boiler:
a) The minimum water circulation must be defined in such a way that the temperature difference between
the boiler outlet/supply and inlet/return is a maximum of 40 deg F (22 deg C), defined as DT (Delta T). A DT Limit algorithm should be enabled in the boiler controller.
23
BOILER BOOK CFC-E ENGINEERING DATA
b) Independent from the hydraulics of the heating system, constant water circulation through each boiler is
required while the boiler is operating (requires a dedicated boiler pump if in a primary/secondary loop arrangement). Refer to table below for minimum boiler circulation rates.
5) Minimum over-pressure at the boiler: For outlet temperatures up to the maximum of 185 deg F (85 deg C), a minimum operating pressure of 30 psig (2.1 bar) is required.
6) pH level should be maintained between 8.3 and 10.5
7) It is recommended to maintain continuous circulation in glycol systems. Where this is impractical (e.g. multiple boiler systems), a periodic pump exercise routine should be implemented to ensure proper mixture of glycol and to avoid degradation that naturally occurs with glycol mixtures. This can be as simple as opening a boiler isolation valve once a day or turning on a boiler circulating pump.
Table 12. Glycol Minimum Flow Recommendations for ClearFire Model CFC-E Boiler
(Minimum required boiler circulation rate (gpm) at maximum firing rate.)
System T (˚F) Model-Size CFC-E 500 95 47 32 24 CFC-E 750 142 71 47 36 CFC-E 1000 190 95 63 47 CFC-E 1500 285 142 95 71 CFC-E 2000 380 190 127 95
T = 10˚ T = 20˚ T = 30˚ T = 40˚
Notes/Limitations:
1. Maximum firing rate determined by ClearFire CFC-E Glycol Firing Rate Limitation chart (below). Maximum high fire blower speed set according to chart.
2. Glycol concentration of 25%-50%. Minimum required system operating pressure is 30 psig.
3. Maximum system operating temperature of 180 ˚F. Maximum T of 40˚.
4. Circulation rates correlate with boiler output based on 92% nominal efficiency.
5. Standard altitude (<1000' ASL). Contact Cleaver-Brooks for high altitude applications.
6. Pumps should be sized based on system design T and minimum required flow rates.
7. At minimum firing rate, the minimum circulation rate should correspond to the boiler's turndown.
24
BOILER BOOK CFC-E ENGINEERING DATA
Figure 15. High Fire Speed Settings vs. % Glycol
CFC-E High Fire Blower Speed Seƫng vs. % Glycol
6200
6100
6000
5900
5800
5700
5600
5500
5400
5300
5200
5100
5000
4900
4800
4700
Hi gh Fi re Bl ower Speed (r pm)
4600
4500
4400
4300
4200
4100
4000
20% 25% 30% 35% 40% 45% 50% 55%
Gl ycol Content
CFC- E 750
CFC-E 500/1000
CFC-E 1500
CFC-E 2000
Figure 16. Maximum Firing Rate vs. % Glycol
25
BOILER BOOK CFC-E ENGINEERING DATA
Condensation
The CFC-E uses one of several condensate removal options, depending on the application:
(1) Condensate direct to drain - The condensate is piped directly to a drain through the piping and water trap supplied during installation (see Figure 17).
• Piping is to be a minimum of 3/4” NPT.
• Maximum discharge pipe height from floor to be 9”.
• Condensate water trap (5”) required.
Figure 17. Condensate Piped Direct to Drain
(2) Neutralization Capsule - A compact, corrosion resistant capsule is piped to the condensate drain downstream of the water trap. Capsule is filled with a replaceable neutralizing agent.
The neutralization media will require periodic replacement, to be determined by pH analysis of condensate. If condensate is too acidic (pH is below acceptable value) the neutralization media should be replaced.
Capsule is limited to individual boilers 1000 MBH and smaller.
FROM
BOILER
TO
DRAIN
Figure 18. Neutralization Capsule
26
BOILER BOOK CFC-E ENGINEERING DATA
(3) Combo trap/treatment tank - The condensate is held in a condensate tank under the boiler. The condensate is neutralized as it passes through the granular bed. The neutralized condensate is then piped to the drain.
The combo tank features an integral water trap and float makeup valve.
• To install the system, assemble the tank and neutralization granulate per Figure 19. Two bags of neutralization
media are sufficient to fill the tank.
• Install the condensate tank cover and slide the complete assembly under the boiler
Pipe to the appropriate drain.
Drain trap
Condensate in
Float valve for makeup water
Neutralization tank
To drain
Neutralization media
Figure 19. Combo Trap/Tank
The neutralization media will require periodic replacement, to be determined by pH analysis of condensate. If condensate is too acidic (pH is below acceptable value) the neutralization media should be replaced.
The neutralizing media should be gently agitated periodically to ensure even distribution and to avoid channeling of the condensate.
(4) Treatment tank - The condensate is held in a condensate tank(s) under or near the boiler. The condensate is neutralized as it passes through a bed of granular material. The neutralized condensate is then piped to the drain.
• To install the system, assemble the tank and fittings per instructions supplied with tank. Neutralization media
are already installed in tank.
• Install the condensate tank cover and connect tank to boiler condensate discharge.
Pipe to an appropriate drain.
27
BOILER BOOK CFC-E ENGINEERING DATA
FROM
BOILER
TO DRAIN
1" FNPT
outlet
1" FNPT
inlet
Figure 20. Treatment Tank
Condensate Piping for Multiple Boilers
Table 13. Condensate piping for multiple boilers
CFC-E Model
2000 2,000,000 13.5 4
1500 1,500,000 10 4
1000 1,000,000 7 4
750 750,000 5 4
500 500,000 3.5 4
BTU/hr Max.
Condensation
GPH
Max. Boilers
per Tank
The number of condensate treatment tanks required for multiple boiler installations depends on the total amount of condensate produced by the system. As a general rule, CB recommends a maximum of 4 boilers per tank, with total BTU per tank not to exceed 8,000,000.
See figures below for suggested piping. When using the combo tank, supply make-up water at the connection shown. An internal float in the tank activates the make-up water valve.
28
BOILER BOOK CFC-E ENGINEERING DATA
Total boiler capacity per condensate tank should not exceed 8,000,000 BTU/hr
Figure 21. Condensate Piping for Multiple Boilers
Figure 22. Tank Detail, Multiple Boilers
Gas Fuel Connections
The local Gas Company should be consulted for the requirements for installation and inspection of gas supply piping. Installation of gas supply piping and venting must be in accordance with all applicable engineering guidelines and regulatory codes. All connections made to the boiler must be arranged so that all components are accessible for inspection, cleaning, and maintenance.
A drip leg should be installed in the supply line before the connection to the boiler. The drip leg should be at least as large as the gas piping connection on the boiler. See Figure 23 and Figure 24 for piping suggestions.
29
BOILER BOOK CFC-E ENGINEERING DATA
Relief Valve (NOTE 5)
Same or larger tha n boiler ga s c onnect ion size
R egulator (NOTE 1)
Manual Shutoff
Strainer
Manual Shutoff
Drip leg required for any vertical run of piping
Gas header - size for boiler room capa c ity and to minimize pres s ure los s
= opt ional or by other s
Figure 23. Gas Piping Schematic
Consideration of volume and pressure requirements must be given when selecting gas supply piping. Connections to the burner gas train must include a union so that the burner may be opened for
inspection and maintenance.
A. Gas supply connection is at the rear of the boiler near the top. To permit burner opening, gas
piping must not traverse the top of the boiler.
B. Table 14 shows the gas pressure required at the inlet of the gas line. Note: a pressure
regulator is not furnished and if gas pressure exceeds 14" W.C. a pressure regulator is required.
C. Table 15 shows the correction factors for gas pressure at elevations at 2000 feet and higher
above sea level.
30
BOILER BOOK CFC-E ENGINEERING DATA
Met er
Header Pipe
Gas Strainer
Manual S hut Off
Re g u l a t o r See Note 1
Re l i e f Valve See Note 5
NOTES:
Ga s He ader Piping, Typical
1. Dedicated gas press ure regulator recommended for each boiler.
2. Refer to local fuel gas codes when applicable.
3. Header to be sized for room capacity.
4. Provision require d for mea s uring ga s s upply press ure a t boiler.
5. Relief valve re quired if gas supply pres s ure > 1 ps ig.
Figure 24. Gas Header Piping
Table 14. Model CFC-E Minimum and Maximum Gas Pressure
Minimum pressure required at gas train
Boiler Model
connection (inches Water Column)
Natural Gas LP Gas UL cUL/CSA 500 7” 11” 750 7” 11”
1000 7” 11” 1500 7” 11” 2000 7” 11”
Max. pressure
(without step-down
regulator)
14” WC
(1/2 psig)
Maximum gas train pressure rating*
1 psig 1/2 psig
*Overpressure protection required when room supply gas pressure is greater than maximum gas train pressure rating.
31
BOILER BOOK CFC-E ENGINEERING DATA
Table 15. Model CFC-E Minimum Required Gas Pressure Altitude Correction
Altitude in Feet Correction Factor Altitude in Feet Correction Factor
1000 1.04 6000 1.25
2000 1.07 7000 1.3
3000 1.11 8000 1.35
4000 1.16 9000 1.4
5000 1.21
To obtain minimum required inlet pressure, select altitude of installation and multiply the pressure shown in Table 13 by the correction factor corresponding to the altitude listed above.
Boiler Room Information
The boiler must be installed on a level non-combustible surface. If the surface is not level, piers or a raised pad, slightly larger than the length and width of the boiler base dimensions, will make boiler leveling possible. Installing the boiler on a raised pad or piers will make boiler drain connections more accessible and will keep water from splashing onto the boiler whenever the boiler room floor is washed.
Note: The pad or piers must be of sufficient load bearing strength to safely support the operating weight of the boiler and
any additional equipment installed with it. Approximate operating weights are shown in Dimensions and Ratings.
Leveling
Once the boiler is placed, it must be leveled side to side and front to back using the supply and return nozzles for horizontal and vertical positions. If shims are required to level the boiler, the weight of the boiler must be evenly distributed at all points of support. The optional adjustable feet may also be used for leveling.
Clearances
The boiler must be installed so that all components remain accessible; ensure no overhead obstructions so the burner may be opened. Refer to Figure 25.
Hot Water Piping
Dedicated boiler circulation pumps are not required with the Model CFC-E boiler. As its design is such that no minimum flow is required, variable speed or on/off pumps may be employed in the piping scheme.
32
BOILER BOOK CFC-E ENGINEERING DATA
Figure 25. Model CFC-E Minimum Room Clearance Dimensions
Seismic Legs
Seismic mounting details shown below.
2”
2”
DETAIL A
7/16" HOLE
"A"
"C"
Q
DIM.
"A" "B" 47.4" 47.4" "C"
750 1000 1500
34.35" 34.35" 35.25" 35.25"
A
2000
54" 54"
17.625"17.625"17.175”17.175”
33
FRONT VIEW
"B"
PLAN VIEW
Figure 26. CFC-E Seismic Mounting
BOILER BOOK CFC-E ENGINEERING DATA
Boiler Room Combustion and Ventilation Air
The boiler(s) must be supplied with adequate quantities of uncontaminated air to support proper combustion and equipment ventilation. Air shall be free of chlorides, halogens, fluorocarbons, construction dust or other contaminants that are detrimental to the burner/boiler. If these contaminants are present, we recommend the use of direct vent combustion provided the outside air source is uncontaminated.
Combustion air can be supplied by means of conventional venting, where combustion air is drawn from the area immediately surrounding the boiler (boiler room must be positive pressure), or with direct vent (direct vent combustion) where air is drawn directly from the outside. All installations must comply with local Codes and with NFPA 54 (the National Fuel Gas Code - NFGC) for the U.S. and for Canada, CAN/CGA B 149.1 and B 149.2.
Note: A boiler room exhaust fan is not recommended as this type of device can cause a negative pressure in the boiler room
if using a conventional air intake.
In accordance with NFPA54, the required volume of indoor air shall be determined in accordance with the “Standard Method” or “Known Air Infiltration Rate Method. Where the air infiltration rate is known to be less than 0.40 Air Changes per Hour, the Known Air Infiltration Rate Method shall be used. (See Section 8.3 in the NFPA54 Handbook for additional information.)
Combustion Air Supply - Unconfined Spaces (For U.S. Installations Only)
A. All Air From Inside the Building - If additional combustion air is drawn from inside the
building (the mechanical equipment room does not receive air from outside via louvers or vent openings and the boiler is not equipped with direct vent combustion) and the boiler is located in a unconfined space, use the following guidelines:
1. The mechanical equipment room must be provided with two permanent openings linked directly with additional room (s) of sufficient volume so that the combined volume of all spaces meet the criteria for an unconfined space. Note: An “unconfined space” is defined as a space whose volume is more than 50 cubic feet per 1,000 Btu per hour of aggregate input rating of all appliances installed in that space.
2. Each opening must have a minimum free area of one square inch per 1,000 Btu per hour of the total input rating of all gas utilizing equipment in the mechanical room.
3. One opening must terminate within twelve inches of the top, and one opening must terminate within twelve inches of the bottom of the room.
4. Refer to the NFGC, Section 8.3 for additional information.
34
BOILER BOOK CFC-E ENGINEERING DATA
Figure 27. Two Opening Outside Wall Method
B. All Air From Outdoors - If all combustion air will be received from outside the building (the
mechanical room equipment is linked with the outdoors), the following methods can be used:
1. Two Opening Method (Figure 27) - The mechanical equipment room must be provided with two permanent openings, one terminating within twelve inches from the top, and one opening terminating within twelve inches of the bottom of the room.
2. The openings must be linked directly or by ducts with the outdoors.
3. Each opening must have a minimum free area of one square inch per 4,000 Btu per hour of total input rating of all equipment in the room, when the opening is directly linked to the outdoors or through vertical ducts.
4. The minimum free area required for horizontal ducts is one square inch per 2,000 Btu per hour of total input rating of all the equipment in the room.
35
BOILER BOOK CFC-E ENGINEERING DATA
Figure 28. Two Opening Ducted Method
C. One Opening Method (Figure 29) - One permanent opening, commencing within 12 inches
of the top of the enclosure, shall be provided.
1. The equipment shall have clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance.
2. The opening shall directly communicate with the outdoors and shall have a minimum free area of 1 square inch per 3000 BTU's per hour of the total input rating of all equipment located in the enclosure, and not less than the sum of the areas of all vent connectors in the confined space.
3. Refer to the NFGC, Section 8.3 for additional information.
36
BOILER BOOK CFC-E ENGINEERING DATA
Figure 29. One Opening Method
Unconfined Space/Engineered Design
When determining boiler room air requirements for unconfined space, the size of the room, airflow, and velocity of air must be reviewed as follows:
1. Size (area) and location of air supply openings in the boiler room. A. Two permanent air supply openings in the outer walls of the boiler room are recommended.
Locate one at each end of the boiler room, preferably below a height of 7 feet. This allows air to sweep the length of the boiler. See Figure 30.
B. Air supply openings can be louvered for weather protection, but they should not be covered
with fine mesh wire, as this type of covering has poor air flow qualities and is subject to clogging with dirt and dust.
C. A vent fan in the boiler room is not recommended, as it could create a slight vacuum under
certain conditions and cause variations in the quantity of combustion air. This can result in unsafe burner performance.
D. Under no condition should the total area of the air supply openings be less than one square
foot.
37
BOILER BOOK CFC-E ENGINEERING DATA
Figure 30. Two Opening Engineered Method
E. Size the openings by using the formula:
Area in square feet = cfm/fpm Where cfm = cubic feet per minute of air Where fpm = feet per minute of air
2. Amount of Air Required (cfm). A. Combustion Air = 0.25 cfm per kBtuh.
B. Ventilation Air = 0.05 cfm per kBtuh.
C. Total air = 0.3 cfm per kBtuh (up to 1000 feet elevation. Add 3% more per 1000 feet of
added elevation).
3. Acceptable air velocity in the Boiler Room (fpm). A. From floor to 7 feet high = 250 fpm.
B. Above 7 feet above floor = 500 fpm.
Example: Determine the area of the boiler room air supply openings for (2) Clearfire 1800 boilers at 750 feet elevation. The air openings to be 5 feet above floor level.
Air required: 1800 x 2 = 3600 kBtuh. From 2C above, 3600 x 0.3 = 1,080 cfm.
Air Velocity: Up to 7 feet = 250 fpm from 3 above.
Area required: Area = cfm/fpm = 1,080/250 = 4.32 square feet total.
Area/Opening: 4.32/2 = 2.16 sq-ft/opening (2 required).
Consult local codes, which may supersede these requirements.
38
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
Boiler Air Inlet
The boiler ships with both an air inlet screen and a direct vent collar (see illustration below). If room air will be used for combustion, install the air inlet screen; the collar may be discarded. If direct venting will be used, install the vent collar; the screen may be discarded.
Mounting hardware is provided with the boiler. When using direct vent combustion:
1. Provide for adequate ventilation of the boiler room or mechanical equipment room.
2. In cold climates, and to mitigate potential freeze-up of the intake pipe, it is highly recommended
that a motorized sealed damper be used to prevent the circulation of cold air through the boiler during non-operating hours.
Figure 31. Boiler Air Inlet
STACK/BREECHING SIZE CRITERIA
General
Boilers are divided into four categories based on the pressure and temperature produced in the exhaust stack and the likelihood of condensate production in the vent.
• Category I. A boiler which operates with a non-positive vent static pressure and with a vent gas temperature that avoids excessive condensate production in the vent.
• Category II. A boiler which operates with a non-positive vent static pressure and with a vent gas temperature that may cause excessive condensate production in the vent.
• Category III. A boiler which operates with a positive vent pressure and with a vent gas temperature that avoids excessive condensate production in the vent.
• Category IV. A boiler which operates with a positive vent pressure and with a vent gas temperature that may cause excessive condensate production in the vent.
Depending on the application, the Model CFC-E may be considered Category II, III, or IV. The specifying engineer should dictate flue venting as appropriate to the installation.
In some cases, PVC/CPVC material meeting ULC Type BH Class IIB specifications may be used. Use of PVC/CPVC depends on operating conditions, specific vent suppliers, and any local codes having jurisdiction. Refer to vent manufacturer’s specifications for applicability.
Proper installation of flue gas exhaust venting is critical to efficient and safe operation of the Clearfire Boiler. The vent should be supported to maintain proper clearances from combustible materials. Use insulated vent pipe spacers where the vent passes through combustible roofs and walls.
39
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
The design of the stack and breeching must provide the required draft at each boiler flue gas connection; proper draft is critical to burner performance.
Although constant pressure at the flue gas outlet is not required, it is necessary to size the breeching and stack to limit flue gas pressure variation. Consideration of the draft must be given whenever direct vent combustion is utilized and lengthy runs of breeching are employed. Please note: The allowable pressure range for design of the stack, breeching and if used, direct vent combustion pipe, is negative 0.25" W.C. (- 62 Pa) to positive 0.25" W.C. (+62 Pa) for proper combustion and light offs.
Whenever two or more boilers are connected to a common breeching/stack, a draft control system may be required to ensure proper draft.
Vent Termination
To avoid the possibility of property damage or personal injury, special attention to the location of the vent termination must be considered.
1. Combustion gases can form a white vapor plume in the winter. The plume could obstruct a window view if the termination is installed in close proximity to windows.
2. Prevailing winds could cause freezing of Condensate and water/ice buildup on building, plants, or roof.
3. The bottom of the vent termination and the air intake shall be located at least 12 inches above grade, including the normal snow line.
4. Non-insulated single-wall metal vent pipe shall not be used outside in cold climates for venting combustion gases.
5. Through the wall vents for Category II and Category IV appliances shall not terminate over public walkways or over an area where Condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of other equipment.
6. To prevent accidental contact by people or pets, the vent termination shall be guarded.
7. DO NOT terminate vent in window well, alcove, stairwell or other recessed area, unless approved by local authority.
8. DO NOT terminate above any door, window, or gravity air intake as Condensate can freeze causing ice formation.
9. Locate or guard vent to prevent Condensate from damaging exterior finishes. Use a 2' x 2' rust resistant sheet metal backing plate against brick or masonry surfaces.
10. Multiple direct stack installations require four feet clearance between the stack caps, center to center.
40
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
U.S. Installations
Refer to the latest edition of the National Fuel Gas Code/NFPA 54. Vent termination requirements are:
1. Vent must terminate at least four feet below and four feet horizontally or one foot above any door, window or gravity air inlet to the building.
2. The vent must be at least seven feet above grade when located adjacent to public walkways.
3. Terminate vent at least three feet above any forced air inlet located within ten feet.
4. Vent must terminate at least four feet horizontally, and in no case above or below unless four feet horizontal distance is maintained, from electric meters, gas meters, regulators, and relief equipment.
5. Terminate vent at least six feet from adjacent walls.
6. DO NOT terminate vent closer than five feet below roof overhang.
Canadian Installations
Refer to the latest edition of CAN/CSA-B149.1 and B149.2. Vent shall not terminate:
1. Directly above a paved sidewalk or driveway which is located between two single-family dwellings and serves both dwellings.
2. Less than 7 feet (2.31m) above a paved sidewalk or paved driveway located on public property.
3. Within 6 feet (1.8m) of a mechanical air supply inlet to any building.
4. Above a meter/regulator assembly with 3 feet (900mm) horizontally of the vertical centerline of the regulator.
5. Within 6 feet (1.8m) of any gas service regulator vent outlet.
6. Less than 1 foot (300mm) above grade level.
7. Within 3 feet (1m) of a window or door which can be opened in any building, any non­mechanical air supply inlet to any building or to the combustion air inlet of any other appliance.
8. Underneath a veranda, porch, or deck unless:
A. The veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
B. The distance between the top of the vent termination and the underside of the veranda, porch,
or deck is greater than one foot (300mm).
Horizontal Through the Wall Venting
Venting configurations using inside air for combustion (See Figure 32)
These installations utilize the boiler-mounted blower to vent the combustion products to the outside. Combustion air is obtained from inside the room and the exhaust vent is installed horizontally through the wall to the exterior of the building. Adequate combustion and ventilation air must be supplied to the boiler room in accordance with the NFGC/NFPA 54 for the U.S. and in Canada, the latest edition of CAN/CSA-B149.1 and.2 Installation Code for Gas Burning Appliances and Equipment.
41
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
Figure 32. Horizontal through-wall venting using inside air for combustion
The vent must be installed to prevent the potential accumulation of stack condensate in the horizontal run of vent pipe. Therefore, it is recommended that:
1. The vent shall be installed with a slight downward slope of not more than 1/4” per foot of horizontal run to the vent termination.
2. The vent must be insulated through the length of the horizontal run.
Note: For installations in cold/freezing climates, it is recommended that:
1. The vent shall be installed with a slight upward slope of not more than 1/4" per foot of horizontal run to the vent termination. In this case, an approved Condensate trap must be installed per applicable codes.
2. The vent must be insulated through the length of horizontal run.
The stack vent cap MUST be mounted on the exterior of the building. The stack vent cap cannot be installed in a well or below grade. The stack vent cap must be installed at least two feet above ground level and above normal snow levels.
The stainless steel direct vent cap must be furnished in accordance with AGA/CGA requirements.
Refer to table for the recommended sizes of horizontal vent pipe.
42
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
Horizontal Through the Wall Stack Venting
Dire c t Vent C o mb u stion. S ee Fig u re 3 3 .
Figure 33. Horizontal flue through-wall with direct vent combustion intake
These installations utilize the boiler-mounted blower to take combustion air from the outside and vent combustion by-products to the outside.
The direct vent combustion air vent cap is not considered in the overall length of the venting system. The stack vent must be installed to prevent the potential accumulation of Condensate in the stack
pipes. It is recommended that:
1. The vent shall be installed with a slight downward slope of not more than 1/4” per foot of horizontal run to the stack termination.
2. The stack vent is to be insulated through the length of the horizontal run.
Note: For installations in freezing climates, it is recommended that:
1. The vent shall be installed with a slight upward slope of not more than 1/4” per foot of horizontal run to the vent termination. In this case, an approved Condensate trap must be installed per applicable codes.
2. The stack vent is to be insulated through the length of the horizontal run.
43
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
Note: For Horizontal Stack Vent Termination:
1. The stack vent cap must be mounted on the exterior of the building. The stack vent cap cannot be installed in a well or below grade. The stack vent cap must be installed at least one foot above ground level and above normal snow levels.
2. Multiple stack vent caps should be installed in the same horizontal plane with three feet clearance from side of one stack cap to the side of the adjacent vent cap.
3. Combustion air supplied from the outside must be free of particulate and chemical contaminants. To avoid a blocked flue condition, keep all the vent caps clear of snow, ice, leaves, debris, etc.
Note: Multiple direct stack vent caps must not be installed with one combustion air inlet directly above a stack vent cap.
This vertical spacing would allow the flue products from the stack vent to be pulled into the combustion air intake installed above. This type of installation can cause non-warrantable problems with components and poor operation of the unit due to the recirculation of flue products.
Table 15. STACK SIZING USING OUTSIDE AIR FOR COMBUSTION (DIRECT VENT)
Boiler Combustion Air Duct
(Inches Diameter)
CFC-E 500 6 125 SCFM 6 standard 100
CFC-E 750 6 188 SCFM 6 standard 100
CFC-E 1000 6 250 SCFM 8 standard 100
CFC-E 1500 8 375 SCFM 8 standard 100
CFC-E 2000 8 500 SCFM 8 standard 100
Combustion Air SCFM
Required
Flue Connection/Duct
(Inches Diameter)
8 optional 120
8 optional 120
6 optional 50
10 optional 120
10 optional 120
Max. Length* (Equivalent
Feet)
Each additional 90° elbow equals 5 equivalent feet of ductwork. Flue terminations may add 5-10 feet to the equivalent length and should also be included in the equivalent length calculation.
Draft tolerance at boiler flue connection during operation is +/-0.25” W.C.; Use +/-0.10” when designing venting system. *Maximum vent length assumes horizontal run and sidewall terminations. Larger diameter venting, vertical flue runs, and vertical
flue termination may allow for longer vent lengths than indicated here, provided the engineered draft calculations are within the allowable operational tolerance of +/-0.25” W.C.
44
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
Vertical Venting Inside Combustion Air
S e e Fig ure 34 .
Figure 34. Inside Air - Vertical Vent
As noted in Paragraph A above, these installations use air from within the boiler room for combustion. The same recommendations apply as noted in Paragraph A above.
45
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
Vertical Venting Direct Vent Combustion
S e e Fig ure 35 .
WITH PARAPET WALL
Figure 35. Vertical Stack with Direct Vent Combustion Air
As noted in Paragraph B above, these installations use air from outside the building for combustion. The same recommendations apply as noted in B and also, the recommendations on flue vent sizing.
46
BOILER BOOK CFC-E STACK/BREECHING SIZE CRITERIA
Boiler Rear Connections
ELECTRICAL RACEWAY
COMBUSTION
AIR INLET
ELECTRICAL RACEWAY
HIGH TEMPERATURE RETURN
LOW TEMPERATURE RETURN
Figure 36. CFC-E Rear Connections
47
BOILER BOOK CFC-E CB FALCON CONTROLLER
CB FALCON CONTROLLER
1. Control Description - The CB Falcon hydronic control is an integrated burner management and modulation control with a touch-screen display/operator interface.
2. Functionality - The controller is capable of the following functions:
• Flame supervision
• Burner sequencing
• Heating/modulation control
• Hot water system pump control
• High Limit temperature control
• Thermowell-mounted NTC temperature sensors to provide measured process variable signals to the controller.
• User-friendly touchscreen interface
• Modbus communication capability
• Alarm/lockout messaging with history (last 15 messages)
• Annunciation
• Outdoor reset
• Central Heating and Domestic Hot Water loop control
• Password protection of configurable parameters
• High Stack Temperature limit
• Remote reset
• Lead/Lag sequencing
• (3) configurable pump relays
• Remote modulation/remote setpoint
• Frost protection
• Time of Day (dual setpoint) control
• Three levels of access to control configuration:
•End-user
•Installer/Service Engineer (password protected)
•OEM Manufacturer (password protected)
Table 16. Operating Conditions - Controller
Operating -4 F to 150 F (-20 C to 66 C)
Temperature Range
Humidity 85% max. relative humidity, non-condensing
Storage -40 F to 150 F (-40 C to 66 C)
Table 17. Operating Conditions - Display/Interface
Operating 32 F to 122 F (0 C to 50 C)
Temperature Range
Humidity 85% max. relative humidity
Storage -40 F to 150 F (-40 C to 66 C)
48
BOILER BOOK CFC-E CB FALCON CONTROLLER
Table 18. CB Falcon burner sequence (Central Heat)
1. Heat request detected (CH demand)
2. CH pump switched on
3. Safe Start Check, dynamic ILK input test (if enabled), blower switched on
4. If ILK input and CAPS switch closed and purge rate fan speed achieved, begin 15 second prepurge
5. When purge complete, blower RPM changed to lightoff speed
6. Trial for Ignition - 4 seconds
7. Ignition and gas valve switched on
8. Ignition turned off at the end of direct ignition period; 5 sec. stabilization time*
9. Release to modulation (Run)
10. At the end of CH heat request, burner is switched off and blower stays on for 15 sec. post purge period. Boiler enters standby mode.
3. Main Voltage Connection - 115V/single phase/60Hz
4. Local/Remote demand switch
5. Combustion Air Proving Switch - This input is used for proving airflow sufficient for proper combustion throughout the burner run sequence.
6. High Air Pressure Switch - prevents boiler operation in the event of high stack back pressure (blocked flue or condensate drain).
7. Gas Pressure Switch - Gas pressure switches for low gas pressure and high gas pressure prevent the burner from being activated if either is open. Each switch is a physical manual reset device, requiring physical depression of the reset button if either switch is not closed prior to burner start or during burner operation.
8. NTC (Negative Temperature Coefficient) Thermistor Inputs (10k @ 25
o
C)
A.Flow Temperature (Outlet water temperature) B.Return Temperature (Inlet water temperature) C.Optional Domestic Water Temperature D.Optional Outdoor Temperature E.Optional Stack Temperature F.Optional Header Temperature
9. System Configuration - CB Falcon configuration is arranged into the following functional groups:
49
System Identication and Accesss
CH - Central Heat
Outdoor Reset
DHW - Domestic Hot Water
DHW Storage
DHW Plate
Warm Weather Shutdown
Demand Priority
Modulation Conguration
Pump Conguration
Statistics Conguration
High Limit
Stack Limit
Delta T Limits
T-Rise Limit
Heat Exchanger High Limit
Anti-condensation
Frost Protection Conguration
Annunciation Conguration
Burner Control Interlocks
BOILER BOOK CFC-E CB FALCON CONTROLLER
10. CB Falcon Access - There are three levels of access to the CB Falcon controller:
End User Level - read or view parameters; change setpoints. No password required.
Installer/Service Level - read all parameters; enables changing of most parameters. This access level is used to configure the CB Falcon for a particular installation, and is password­protected.
OEM Level - read/change all parameters; for factory configuration of boiler-specific parameters. Password-protected and restricted to CB or factory authorized service personnel.
For additional information regarding service and setup of the burner controller, refer to CFC-E manual 750-263 or to the CB Falcon manual 750-265.
Figure 37. CB Falcon Pinout
FAN POWER (25 VDC) FAN GND PWM OUT TACHOMETER
4
EGND
L2 FOR 120VAC OR 24VAC RETURN (OPTOS)
L1
P
PUMP A
P
PUMP B
P
PUMP C
EX. IGNITION
MAIN VALVE
INTERLOCK
ALARM
LCI ANNUN 1/IAS
ANNUN 2
ANNUN 3 ANNUN 4
ANNUN 5
ANNUN 6
12
11
10
9
8
7
{
J4
6
5
{
4
3
{
2
1
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
7
6
5
4
3
2
1
J5
J6
J7
CB FALCON HYDRONIC CONTROL
POWER
FLAME
ALARM
RESET
J1
LOCAL
MODBUS
A B C
1
5
2
3
6
J3
GLOBAL
ENVIRACOM
MODBUS
D R C
A B C
J2J1
PIM
3
4
2
1
STRENGTH
FLAME
1
2
3
4
5
6
J8
7
8
9
10
11
12
1
2
3
4
J9
5
6
7
1
2
3
+
4
J10
J11
+
5
6
7
8
1
2
3
4
FUTURE
5
6
7
24 VAC
24 VAC RTN
INLET TEMP
INLET TEMP RTN
HEADER TEMP
HEADER TEMP RTN
OUTLET TEMP A
OUTLET TEMP RTN
OUTLET TEMP B
OUTDOOR TEMP
OUTDOOR TEMP RTN
DHW TEMP A
DHW TEMP RTN
DHW TEMP B
STACK TEMP A
STACK TEMP RTN
STACK TEMP B
REMOTE RESET
TOD
4 TO 20 MA
0 - 10 VDC
MA /VDC RTN
AUX. (REMOTE) INPUT
SYSTEM DISPLAY
I
V
50
MULTIPLE
APPLIANCE
CONTROLLER
BUILDING
AUTOMATION
SYSTEM
LOCAL DISPLAY
GLOBALMODBUS
LOCALMODBUS
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
EXAMPLE SYSTEM SCHEMATICS
Typical piping arrangements using the CFC-E are shown in the figures that follow.
Note: These diagrams are generic and are not intended for use in a specific design without consultation with your local
Cleaver-Brooks sales representative
51
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
Figure 38. Primary/Secondary, Single Boiler
52
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
Figure 39. Primary/Secondary, Two Boilers
53
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
Figure 40. Primary/Secondary, Three Boilers
54
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
Figure 41. Primary Variable Flow, Single Boiler
55
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
Figure 42. Primary Variable Flow, Two Boilers
56
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
Figure 43. Primary Variable Flow, Three Boilers
57
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
Figure 44. Primary Variable Flow, Single Boiler with Heat Exchanger
58
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
Figure 45. Primary Variable Flow, Single Boiler with Heat Exchanger and Dual Return
59
BOILER BOOK CFC-E EXAMPLE SYSTEM SCHEMATICS
60
BOILER BOOK CFC-E
e-mail: info@cleaverbrooks.com
Web Address: http://www.cleaverbrooks.com
Loading...