CleaverBrooks CFC-E, CFC-E 500, CFC-E 750, CFC-E 1500, CFC-E 1000 Series Manual

...
CFC-E
ClearFire Condensing Boiler
Boiler Book 02/2018
BOILER BOOK CFC-E
FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
PRODUCT OFFERING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ENGINEERING DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fireside Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Premix Burner Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
ClearFire CE Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Model CFC-E Dimensional Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Efficiencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
Waterside Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-20
High Fire Speed Settings vs. % Glycol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Maximum Firing Rate vs. % Glycol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Condensate Piped Direct to Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Neutralization Capsule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Combo Trap/Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Treatment Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Condensate Piping for Multiple Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Tank Detail, Multiple Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Gas Piping Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Gas Header Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Model CFC-E Minimum Room Clearance Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
CFC-E Seismic Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Two Opening Outside Wall Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Two Opening Ducted Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
One Opening Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Two Opening Engineered Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Boiler Air Inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Horizontal through-wall venting using inside air for combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Horizontal flue through-wall with direct vent combustion intake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Inside Air - Vertical Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Vertical Stack with Direct Vent Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
CFC-E Rear Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
CB Falcon Pinout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Primary/Secondary Piping Schematic, Single Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Primary/Secondary Piping Schematic, Two Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Primary/Secondary Piping Schematic, Three Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Primary Variable Flow Piping Schematic, Single Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Primary Variable Flow Piping Schematic, Two Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Primary Variable Flow Piping Schematic, Three Boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Primary Variable Flow Piping Schematic, Single Boiler with Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Primary Variable Flow Piping Schematic, Single Boiler with Heat Exchanger and Dual Return . . . . . . . . . . . . . . . . . . . . . . 59
Table of Contents
List of Figures
List of Tables
U.S. Standard Dimensions Model CFC-E Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions (Metric) Model CFC-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Model CFC-E Boiler Ratings (Sea Level to 2000 Feet) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Altitude Correction for Input Capacity at Various Altitude Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CFC-E Efficiencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Emissions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Noise level (dBA) measured 3 feet in front of boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14
2
BOILER BOOK CFC-E
Model CFC-E Minimum Over Pressure Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Safety Relief Valve Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Model CFC-E Water Chemistry Requirements in accordance with ABMA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Glycol Minimum Flow Recommendations for ClearFire Model CFC-E Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Condensate piping for multiple boilers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Model CFC-E Minimum and Maximum Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Model CFC-E Minimum Required Gas Pressure Altitude Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Stack Sizing Using Outside Air for Combustion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Operating Conditions - Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Operating Conditions - Display/Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
CB Falcon burner sequence (Central Heat) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3
BOILER BOOK CFC-E FEATURES AND BENEFITS
FEATURES AND BENEFITS
Compact Firetube Design
The Model CFC-E boiler is a high mass, vertical down fired robust firetube boiler. The internal extended-heating surface tubes provide very high levels of performance in a compact space. The large water volume makes the CFC-E ideal for variable flow primary pumping systems.
Large Water Volume
The large water volume makes the CFC-E ideal for variable flow primary pumping systems.
Advanced Technology
Tubes, tube sheets, and combustion chamber are constructed from UNS S32101 duplex stainless steel. Tubes feature AluFer tube inserts for optimal heat transfer.
Advanced Fireside Construction
The extended heating surface design provides the ideal solution for the demands of a condensing boiler and helps to recover virtually all the latent heat of the flue gas. Each tube consists of an outer stainless steel tube (waterside) and the AluFer extended heating surface profile on the flue gas side.
High Efficiency
With the extended heating surface tubes the CFC-E boiler will provide fuel to water efficiency of up to 99% at low fire and 95% at high fire with 80 degrees F return water temperature.
Ease of Maintenance
The powder coated steel casing is designed for easy removal and re-assembly. As shown in Figure 1, the burner is hinged and is provided with hydraulic pistons for simple opening for service of the spark electrode, inspection of the burner cylinder, tubes and combustion chamber.
Figure 1. Fireside Access
Quality Construction
ASME Code construction ensures high quality design, safety, third party inspection, and reliability, and accordingly bears the ASME Section IV “H” stamp.
Premix Technology
The burner utilizes “Premix” technology to mix both gas fuel and combustion air prior to entering the burner canister, with air leading the fuel during burner firing transitions. Combined with the surface combustion burner and self-regulating gas valve-venturi fuel-air ratio control, this technology provides very low emission levels, exceptionally safe operation, and nearly 100% combustion efficiency.
Full Modulation
The variable speed combustion air blower with ECM technology provides modulated firing for precise
4
BOILER BOOK CFC-E FEATURES AND BENEFITS
linear load tracking, reduced on-off cycling, and reduced electrical consumption.
Figure 2. Premix Burner Technology
Designed For Heating Applications
The pressure vessel is designed for 125 psig MAWP (Maximum Allowable Working Pressure) and is constructed of durable ASTM Grade Steel and Stainless Steel materials. The true counter flow heat exchanger design equates to optimal heat transfer. The design also prevents hot spots, does not require a minimum flow for thermal shock protection, and does not require a minimum return water temperature. In fact, the design carries a 20-year thermal shock warranty.
Because of its design characteristics, the Model CFC-E is well suited for applications utilizing indoor/ outdoor reset controls, radiant floor heating, snow melt systems, ground source heat pump systems and systems that utilize variable speed circulating pumps. It may also be employed in standard hot water systems that require higher heated water at colder outdoor temperatures but then require lower temperatures during warmer heating days, realizing fuel efficiency savings over traditional hot water boilers.
While the design does not lend itself to the direct supply of potable water, a separate storage tank with an internal heat exchanger can be employed, as the onboard controls permit domestic water programming. Therefore, the Model CFC-E can service both hydronic heating and domestic water source heating.
Dual Return
Two return connections - high and low temperature - allow condensing performance with as little as 10% return water at condensing temperature.
SCAQMD Certified
The CFC-E is certified by the South Coast Air Quality Management District.
5
BOILER BOOK CFC-E PRODUCT OFFERING
PRODUCT OFFERING
Dimensions, ratings, and product information may change to meet current market requirements and product improvements. Therefore, use this information as a guide.
Standard Equipment
Equipment described below is for the standard boiler offering:
1. The Boiler A. Each boiler size is designed for a Maximum Allowable Working Pressure (MAWP) of 125 psig
(8.6 Bar), constructed in accordance with the ASME Code Section IV and bear the “H” stamp.
B. The insulated pressure vessel is mounted on a base and a powder coated steel casing is
provided.
C. A drain valve connection is provided at the front bottom for field piping of a boiler drain valve,
which can be furnished as an option.
2. Boiler Trim and Controls
The following items are furnished:
Probe Type Low Water Cutoff control, manual reset.
High Water Temperature Cutoff, manual reset.
NTC (negative temp. coefficient) sensor for hot water supply temperature.
NTC sensor for hot water return temperature.
ASME Safety Relief Valve set @ 125 psig. (8.6 Bar) (Optional SRV set points available.)
Combination Temperature/Pressure Gauge.
3. Burner Control A. The Falcon
controller is an integrated burner management and modulation control with a color
touch-screen display/operator interface. Its functions include the following:
• Two (2) heating loops with PID load control.
• Burner sequencing with safe start check, pre-purge, direct spark ignition, and post purge.
• Electronic ignition.
• Flame Supervision.
• Safety shutdown with time-stamped display of lockout condition.
• Variable speed control of the combustion fan.
• Supervision of low and high gas pressure, air proving, stack back pressure, high limit, and low water.
• First-out annunciator.
• Real-time data trending.
• (3) pump/auxiliary relay outputs.
• Modbus communication capability.
• Outdoor temperature reset.
• Remote firing rate or setpoint control
• Setback/time-of-day setpoint
• Lead/Lag for up to 8 boilers
6
BOILER BOOK CFC-E PRODUCT OFFERING
Figure 3. ClearFire CE Control Panel
4. Forced Draft Burner A. The burner is a “Pre-mix” design consisting of a unitized venturi, single body dual safety gas
valve, blower, and burner head. Consistent fuel-air ratio is maintained with a self-regulating
gas valve-venturi system which automatically compensates for changes in air density. B. Full modulation is accomplished with a variable speed fan for 5:1 turndown ratio. C. For near flameless combustion, the burner utilizes a Fecralloy-metal fiber head.
D. Noise level at maximum firing is less than 70 dBA regardless of boiler size.
E. Operating on Natural Gas, NOx emissions will be less than 20 PPM regardless of boiler size.
F. As an option, the burner is capable of direct vent combustion.
G. Ignition of the main flame is via direct spark, utilizing high voltage electrodes and a UV
scanner for flame supervision.
H. To ensure adequate combustion air is present prior to ignition, and to ensure the fan is
operating, a combustion air proving switch is furnished.
I. A High Air Pressure Switch is provided to ensure burner lockout if excessive back pressure
due to a blocked stack occurs.
J. For ease of maintenance and inspection, the burner is furnished with hydraulic rods and easy
opening lockdown nuts, which permit the burner to swing up. This provides full access to the
burner and electrodes, as well, to the tube sheet and tubes.
K. Supports direct vent combustion air.
5. Burner Gas Train
The standard gas train is equipped in accordance with UL certification and complies with ASME CSD-1. Each burner gas train includes:
Low Gas Pressure Interlock, manual reset.
7
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
High Gas Pressure Interlock, manual reset.
ASME CSD-1 Test Cocks.
Downstream manual ball type shutoff valve.
Single body dual safety shutoff gas valve.
Optional Equipment
For option details, contact the local authorized Cleaver-Brooks representative. In summary, here are some of the options that can be provided with the boiler:
A. Reusable air filter. B. Condensate neutralization tank assembly - consists of neutralizing media, filter, and PVC condensate holding
tank with integral drain trap. C. Outside air intake for direct vent combustion. D. Outdoor temperature sensor for indoor/outdoor control. E. Header temperature sensor for multiple boiler Lead/Lag operation. F. Auxiliary Low Water Control (shipped loose) for field piping by others into the system piping. G. Alarm Horn for safety shutdown. H. Relays for output signal for burner on, fuel valve open. I. Stack Thermometer. J. Stack temperature limit-sensor. K. Auto air vent. L. Boiler drain valve. M. Adjustable feet. N. Seismic anchoring brackets. O. Protocol translator for communications
DIMENSIONS AND RATINGS
For layout purposes, the overall dimensions for the Model CFC-E are shown in Table 1 (US Dimensions) and Table 2 (Metric Dimensions) including the various pipe connection sizes for supply and return water, drain, and vent. The performance ratings for the boiler are shown in Table 3.
Altitude
See Table 4 for input capacity ratings at various altitude levels.
8
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
OPTIONAL ADJUSTABLE FEET ALLOW FOR
1.56” TO 3.88” ADDITIONAL HEIGHT
Figure 4. Model CFC-E Dimensional Views
9
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
Table 1. U.S. Standard Dimensions Model CFC-E Boiler
ITEM DIMENSIONS (inches) 500 750 1000 1500 2000
A Overall Height 78.0 78.0 78.0 79.9 79.9 B Overall Width 34.9 34.9 34.9 35.8 35.8 C Overall Depth 49.4 49.4 49.4 56 56 D Width Less Casing 32.1 32.1 32.1 33.0 33.0 E Gas Connection to Floor 70.3 70.3 70.3 73.9 73.9 F Side of Casing to Gas Connection 3.7 3.7 3.7 7.1 7.1 G Side of Casing to Air Inlet 10.8 10.8 10.8 10.8 10.8 H Top of Casing to Air Inlet 7.7 7.7 7.7 7.1 7.1 J Floor to Condensate Drain 6.3 6.3 6.3 6.3 6.3 K Floor to Bottom of Casing 11.0 11.0 11.0 11.0 11.0
L Side of Base to Flue Outlet (Centered) 7.4 7.4 7.4 8.5 8.5 M Side of Base to Flue Outlet (Offset) 6.4 6.4 6.4 7.5 7.5 N Rear of Base to Flue Outlet 6.5 6.5 6.5 7.5 7.5
P Casing Depth 36.3 36.3 36.3 42.4 42.4
Q Casing Height 67.0 67.0 67.0 68.9 68.9
R Floor to Lower Return Connection 16.8 16.8 16.8 16.8 16.8
S Floor to Upper Return Connection 31.8 31.8 31.8 31.8 31.8
T Floor to Supply Connection 59.5 59.5 59.5 59.5 59.5 U Floor to Air vent Connection 66.3 66.3 66.3 66.3 66.3
V Air Vent Line Projection From Rear of Casing 3.2 3.2 3.2 3.3 3.3
CONNECTIONS
W Water Low Temp. Return, Class150 RF Flange 2-1/2" 2-1/2" 2-1/2" 4" 4"
X Water High Temp. Return, Class150 RF Flange 2-1/2" 2-1/2" 2-1/2" 4" 4"
Y Water Outlet, Class150 RF Flange 2-1/2" 2-1/2" 2-1/2" 4" 4"
Z Air Vent, NPT 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2"
AA Vessel Drain, NPT 1-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2" BB Flue Gas Outlet
CC Combustion Air - Nominal 6" 6" 6" 8" 8" DD Gas, NPT 1" 1" 1" 1-1/2" 1-1/2" EE Condensate Drain, NPT 1" 1" 1" 1" 1" FF Electrical Opening, Left or Right 1.6" 1.6" 1.6" 1.6" 1.6" GG Safety Relief Valve Vessel Connection, NPT 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4"
HH Safety Relief Valve
KK Water Outlet Coupling, NPT 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4"
(Standard) - Nominal 6" 6" 8" 8" 8" (Option) - Nominal 8" 8" 6" 10" 10"
30 psig Inlet x Outlet, NPT 1" x 1-1/4" 1" x 1-1/4" 1" x 1-1/4" 1" x 1-1/4" 1-1/4" x 1-1/2" 50 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 1" x 1-1/4" 60 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 1" x 1-1/4" 75 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 80 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 100 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 125 psig Inlet x Outlet, NPT 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1" 3/4" x 1"
JJ Flue Coupling, NPT 3/4" 3/4" 3/4" 3/4" 3/4"
FORK POCKETS (inches)
LL Pocket Height 3.9 3.9 3.9 3.9 3.9
MM Pocket Width 11.8 11.8 11.8 11.8 11.8
NN Overall Pocket Width 27.6 27.6 27.6 27.6 27.6
WEIGHTS
Dry Weight (lb) 1298 1298 1396 1861 2041 Shipping Weight (lb) 1413 1413 1511 1986 2166 Operating Weight (lb) 2065 2065 2113 2778 2858 Water Volume (gallon) 92 92 86 110 98
CLEARANCES
Top 14" Side 3" Rear 20" Front 36"
Notes:
Boiler rear must be accessible for servicing.
Side clearance to wall or between boilers.
Side clearance typical each side.
10
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
Table 2. Dimensions (Metric) Model CFC-E
ITEM DIMENSIONS (mm) 500 750 1000 1500 2000
A Overall Height 1982 1982 1982 2028 2028 B Overall Width 886 886 886 908 908 C Overall Depth 1255 1255 1255 1422 1422 D Width Less Casing 816 816 816 838 838 E Gas Connection to Floor 1786 1786 1786 1877 1877 F Side of Casing to Gas Connection 95 95 95 180 180 G Side of Casing to Air Inlet 275 275 275 273 273 H Top of Casing to Air Inlet 196 196 196 180 180
J Floor to Condensate Drain 160 160 160 160 160 K Floor to Bottom of Casing 279 279 279 279 279 L Side of Base to Flue Outlet 189 189 189 217 217
M Side of Base to Flue Outlet (Offset) 164 164 164 192 192 N Rear of Base to Flue Outlet 165 165 165 190 190
P Casing Depth 921 921 921 1077 1077 Q Casing Height 1703 1703 1703 1749 1749 R Floor to Lower Return Connection 428 428 428 428 428 S Floor to Upper Return Connection 808 808 808 808 808 T Floor to Supply Connection 1511 1511 1511 1511 1511
U Floor to Air vent Connection 1683 1683 1683 1683 1683
V Air Vent Line Projection From Rear of Casing 81 81 81 84 84
FORK POCKETS (mm)
LL Pocket Height 100 100 100 100 100
MM Pocket Width 300 300 300 300 300
NN Overall Pocket Width 700 700 700 700 700
WEIGHTS
Dry Weight (kg) 589 589 633 844 926 Shipping Weight (kg) 641 641 686 901 983 Operating Weight (kg) 939 939 969 1260 1280 Water Volume (liter) 350 350 324 416 370
CLEARANCES (mm)
Top 356 Side 76 Rear 508 Front 914
Notes:
Boiler rear must be accessible for servicing.
Side clearance to wall or between boilers.
Side clearance typical each side.
11
BOILER BOOK CFC-E DIMENSIONS AND RATINGS
Table 3. Model CFC-E Boiler Ratings (Sea Level to 2000 Feet)
Boiler Size
Description Units 500 750 1000 1500 2000
Input Max.
Natural Gas Propane Natural Gas Propane
Output at 120/80 F [49/27 C] 100% Firing
Output at 180/140 F [82/60 C] 100% Firing
MAWP
MAWT
Maximum Operating Setpoint
Water Content
Btu/Hr 500,000 750,000 1,000,000 1,500,000 2,000,000
KCal/Hr 126,000 189,000 252,000 378,000 504,000
Ft3/Hr Ft3/Hr M3/Hr M3/Hr
Btu/Hr 470,000 705,000 940,000 1,410,000 1,880,000
KCal/Hr 118,440 177,660 236,880 355,320 473,760
BHP 14 21 28 42 56
KW 138 207 275 413 551
Btu/Hr 440,000 660,000 880,000 1,320,000 1,760,000
KCal/Hr 110,880 166,320 221,760 332,640 443,520
BHP 13 20 26 39 53
KW 129 193 258 387 516
psi 125 125 125 125 125
Bar 8.6 8.6 8.6 8.6 8.6
°F 210 210 210 210 210 °C 99 99 99 99 99
°F 194 194 194 194 194 °C 90 90 90 90 90
Gallons 92 92 86 110 98
Liters 350 350 324 416 370
500 750 1000 1500 2000 200 300 400 600 800
14 21 28 42 57
5.7 8.5 11 17 23
Weight w/o Water
Standby Heat Loss
ECM Blower Motor Size Operating Voltage, Blower Control Circuit Max Current Draw, Blower Max Current Draw Cont. Circuit Max Over Current Protection
Condensate Quantity Firing Nat. Gas & operating @ 120/80 F.
Flue Gas Mass Flow @ 100% Firing
Pounds 1,298 1,298 1,396 1,861 2,041
Kg 589 589 633 844 926
Btu/Hr 1000 1500 2000 3000 4000
Watts 293 440 586 879 1172
Watts 335 335 335 1,700 1,700 Volts/Ph/Hz 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 Volts/Ph/Hz 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60
Amperes 4 4 4 13.5 13.5 Amperes 1.5 1.5 1.5 2 2 Amperes 20 20 20 20 20
Gal/Hr 3.5 5 7 10 13.5
lb/hr 557 835 1,113 1,670 2,226 kg/hr 252 379 505 758 1010
12
BOILER BOOK CFC-E PERFORMANCE DATA
Table 4. Altitude Correction for Input Capacity at Various Altitude Levels
Natural Gas MBTU/h at various altitudes
700' ASL 2000' 4000' 6000' 8000' 10000'
CFC-E 2000
CFC-E 1500
CFC-E 1000
CFC-E 750
CFC-E 500
** Ratings assume 35% excess air, 80F combustion air. Blower speed adjustments should be made to match performance and local conditions accordingly. For minimum gas supply pressures see Table 14. Altitude corrections for supply pressure should be made per Table 15 Natural gas heating value of 1000 BTU/SCF assumed.
2000 2000 1883 1747 1619 1552 1500 1500 1500 1500 1500 1472 1000 1000 945 877 813 779
750 750 750 707 655 628 500 500 473 438 406 389
LP Gas MBTU/h at various altitudes
700' ASL 2000' 4000' 6000' 8000' 10000'
CFC-E 2000
CFC-E 1500
CFC-E 1000
CFC-E 750
CFC-E 500
** Ratings assume 40% excess air, 80F combustion air. Blower speed adjustments should be made to match performance and local conditions accordingly. For minimum gas supply pressures see Table 14. Altitude corrections for supply pressure should be made per Table 15\ LP (propane) gas heating value of 2500 BTU/SCF assumed.
2000 2000 2000 1867 1730 1659 1500 1500 1500 1500 1500 1500 1000 1000 1000 926 858 822
750 750 750 750 724 694 500 500 500 472 437 419
PERFORMANCE DATA
Efficiency
The Model CFC-E is a “full condensing” boiler realizing efficiency gain at variable operating conditions. It is designed to extract the latent heat of condensation over a greater range than other designs. The nominal point of condensation is approximately 132 its more efficient heat transfer design and lower stack temperature, is able to capture the latent heat of condensation over a broader range.
Fuel-to-water efficiency is relative to specific operating conditions. Operating efficiency will be greater in the “condensing” mode of operation as noted above, yet with its inherently greater heat transfer surfaces and superior premix burner, the ClearFire’s efficiency under “traditional” hot water conditions is also outstanding. Table 5 shows the guaranteed efficiencies at various operating conditions and firing rates for Natural Gas. It should be noted that the efficiency is exceptional at high fire and low fire versus other designs where high efficiency is realized only with low fire or minimal firing rates and low temperature returns.
ClearFire Efficiencies
The tables below list the operating efficiencies of each size Model CFC-E boiler, including radiation losses. As the Model CFC-E is a fully condensing boiler, maximum efficiency is obtained when operating within the condensing mode, utilizing the latent heat of condensation.
F (55.5 C). The ClearFire, due to
13
BOILER BOOK CFC-E PERFORMANCE DATA
Table 5. CFC-E Efficiencies
CFC-E 500 Efficiency
Return Water Temperature °F ( °C )
% Firing Rate
20% 99.0 97.8 96.1 92.4 90.4 88.9 88.1 50% 97.9 96.7 94.7 91.5 89.9 88.6 87.9 75% 97.2 95.7 93.6 90.8 89.4 88.4 87.7
100% 96.5 94.8 92.5 90.0 89.0 88.1 87.6
% Firing Rate
20% 98.5 97.4 95.6 92.1 90.3 88.8 88.0 50% 97.2 95.7 93.6 90.8 89.4 88.4 87.7 75% 96.1 94.3 92.0 89.7 88.7 88.0 87.5
100% 95.0 92.9 90.3 88.6 88.0 87.6 87.3
% Firing Rate
20% 99.0 98.8 97.0 93.3 90.7 88.9 88.0 50% 97.8 96.9 94.7 91.5 89.8 88.5 87.7 75% 96.9 95.4 92.7 90.0 89.0 88.2 87.5
100% 95.9 93.8 90.8 88.6 88.2 87.9 87.3
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
CFC-E 750 Efficiency
Return Water Temperature °F ( °C )
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
CFC-E 1000 Efficiency
Return Water Temperature °F ( °C )
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
CFC-E 1500 Efficiency
Return Water Temperature °F ( °C )
% Firing Rate
20% 98.5 97.6 95.2 91.8 90.1 88.8 88.0 50% 97.1 95.9 93.4 90.6 89.3 88.3 87.8 75% 96.0 94.4 91.9 89.6 88.6 87.9 87.5
100% 94.9 93.0 90.4 88.6 87.9 87.5 87.3
% Firing Rate
20% 98.0 97.1 94.5 91.4 90.0 88.9 88.0 50% 96.6 95.5 93.0 90.5 89.3 88.5 87.7 75% 95.5 94.1 91.7 89.6 88.8 88.2 87.5
100% 94.3 92.7 90.5 88.8 88.3 87.8 87.2
Conditions:
Natural Gas 40% Excess Air Relative Humidity = 50% ΔT = 40°F R & C Loss = 0.2% of rated capacity
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
CFC-E 2000 Efficiency
Return Water Temperature °F ( °C )
68 80 100 120 130 140 160
(20) (27) (38) (49) (55) (60) (72)
14
BOILER BOOK CFC-E PERFORMANCE DATA
Figure 5. Efficiency 500
CFC-E 500 Eciency Curve
100
99
98
97
96
95
94
93
Eĸciency (%)
92
91
90
89
88
87
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature (
40° F Temperature DiīerenƟal
°F)
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
Figure 6. Efficiency 750
CFC-E 750 Eciency Curve
100
99
98
97
96
95 94
93
92
Eciency (%)
91
90
89 88
87
86
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature ( °F)
40°F Temperature DiīerenƟal
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
15
BOILER BOOK CFC-E PERFORMANCE DATA
Figure 7. Efficiency 1000
CFC-E 1000 Eciency Curve
100
99
98
97
96
95 94
93
92
Eciency (%)
91
90
89 88
87
86
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature ( °F)
40°F Temperature DiīerenƟal
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
Figure 8. Efficiency 1500
CFC-E 1500 Eciency Curve
100
99
98
97
96
95 94
93
92
Eciency (%)
91
90
89 88
87
86
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature ( °F)
40°F Temperature DiīerenƟal
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
16
BOILER BOOK CFC-E PERFORMANCE DATA
Figure 9. Efficiency 2000
CFC-E 2000 Eciency Curve
99 98
97 96
95 94
93 92
91
Eciency (%)
90 89
88 87
86
60 70 80 90 100 110 120 130 140 150 160 170
Return Water Temperature ( °F)
40°F Temperature DiīerenƟal
20% Firing Rate
50% Firing Rate
75% Firing Rate
100% Firing Rate
Emissions
By means of the Pre-mix burner, the Clearfire boiler provides environmentally friendly emissions when firing natural gas; emission data are shown below.
Table 6. Emissions
POLLUTANT UNITS
CO
NOx
SOx
HC/VOC
PM
*ppm levels are given on a dry volume basis and corrected to 3% oxygen (15% excess air)
ppm* <20
lb/MMBTU <0.014
ppm* <20
lb/MMBTU <0.024
ppm* <1
lb/MMBTU <0.001
ppm* <4
lb/MMBTU <0.0016
ppm* -
lb/MMBTU <0.01
Noise Level
The Model CFC-E is extremely quiet at all operating levels, does not require any sound level modifications to provide ultra low noise levels, and is virtually vibration free. Thus, it is very suitable in applications that demand low noise levels.
Table 7.
CFC-E 500 43 56 61
CFC-E 750 41 51 60
CFC-E 1000 43 56 61
CFC-E 1500 46 56 66
CFC-E 2000 46 61 70
Noise level (dBA) measured 3 feet in front of boiler
20% Input 60% Input 100% Input
17
BOILER BOOK CFC-E ENGINEERING DATA
ENGINEERING DATA
Boiler Information
The Model CFC-E boiler is designed for service in any closed hydronic system. It can be put into operation as a single stand-alone unit with 5:1 turndown or in multiple units for larger turndown and capacity.
Clearfire boilers may be utilized in water heating systems with temperatures from 40 194
F (90 C); ideal for systems such as ground water source heat pump applications. Because the
Clearfire is a full condensing boiler, low water temperature (below the dewpoint) restrictions do not apply. In fact, the lower the return the better the fuel savings.
Variable temperature differentials can be designed to make use of changing outdoor conditions and thus, the Clearfire is not restricted to a nominal 20
F (10 C) differential. The boiler is designed to
withstand thermal stresses with supply and return temperature differences up to 100 without the use of a boiler-circulating pump, blend pump or minimum water flow.
Note: The Clearfire does not require a minimum flow or continuous flow through it during operation. However, the load
imposed on the boiler must be considered when sizing the system flow so that the flow does not exceed the capacity of the boiler or the demand.
Flow Rates and Pressure Drops
To maintain rated capacity of the boiler, recommended flow rates should not be exceeded as the flow will remove the heat beyond the capacity of the boiler.
F (4.4 C) to
F (55 C),
Table 8. Flow Rates
CFC-E Flow Rates
Temperature Differential (°F)
10 20 30 40 50 60 70 80 90 100 110 120 Size Flow Rate GPM 500 94 47 31 24 19 16 13 12 10 9 9 8 750 141 71 47 35 28 24 20 18 16 14 13 12
1000 188 94 63 47 38 31 27 24 21 19 17 16 1500 283 141 94 71 57 47 40 35 31 28 26 24 2000 377 188 126 94 75 63 54 47 42 38 34 31
Recommended flow rates relative to temperature drop so as not to exceed boiler output. Based on 94% nominal effficiency and maximum firing capacity Based on water only
CFC-E Flow Rates [metric]
Temperature Differential (°C)
6 1117222833394450566167
Size 500 21.4 10.7 7.1 5.3 4.3 3.6 3.1 2.7 2.4 2.1 1.9 1.8
750 32.1 16.0 10.7 8.0 6.4 5.3 4.6 4.0 3.6 3.2 2.9 2.7
1000 42.8 21.4 14.3 10.7 8.6 7.1 6.1 5.3 4.8 4.3 3.9 3.6 1500 64.1 32.1 21.4 16.0 12.8 10.7 9.2 8.0 7.1 6.4 5.8 5.3 2000 85.5 42.8 28.5 21.4 17.1 14.3 12.2 10.7 9.5 8.6 7.8 7.1
Recommended flow rates relative to temperature drop so as not to exceed boiler output. Based on 94% nominal efficiency and maximum firing capacity Based on water only
Flow Rate m
3
/hr
18
BOILER BOOK CFC-E ENGINEERING DATA
Figure 10. Waterside Pressure Drop CFC-E 500
1.2
1.1
1.0
0.9
0.8
0.7
0.6
Pressure (psi)
0.5
0.4
0.3
0.2
0.1
0.0 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95
Flow Rate (gpm)
Figure 11. Waterside Pressure Drop CFC-E 750
19
Loading...
+ 42 hidden pages