If the information in this manual is not followed exactly,
a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
!
WARNING
DANGER
Improper installation, adjustment, service, or maintenance can cause equipment damage, personal injury,
or death. Refer to the Operation and Maintenance
manual provided with the boiler. Installation and service must be performed by a qualified Cleaver-Brooks
service provider.
— WHAT TO DO IF YOU SMELL GAS
•Do not try to light any appliance.
•Do not touch any electrical switch; do not use
any phone in your building.
•Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
•If you cannot reach your gas supplier, call the
fire department.
— Installation and service must be performed by
a qualified Cleaver-Brooks, service agency or the
gas supplier.
!
WARNING
DANGER
To minimize the possibility of serious personal injury,
fire or damage to the equipment, never violate the following safety rules.
— Always keep the area around the boiler free of combustible materials, gasoline, and other flammable liquids and vapors
— Never cover the boiler, lean anything against it,
stand on it, or in any way block the flow of fresh air to
the boiler.
Notice
Where required by the authority having jurisdiction, the
installation must conform to the Standard for Controls
and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1.
!
WARNING
DANGER
The boiler and its individual shutoff valve must be
disconnected from the gas supply piping system
during any pressure testing of that system at test
pressures in excess of 1/2 psi (3.5 kPa).
!
WARNING
DANGER
Be sure the fuel supply which the boiler was designed
to operate on is the same type as specified on the boiler
name plate.
!
WARNING
DANGER
Should overheating occur or the gas supply valve fail to
shut off, do not turn off or disconnect the electrical sup-
ply to the boiler. Instead turn off the gas supply at a location external to the boiler.
!
WARNING
DANGER
Do not use this boiler if any part has been under
water. Immediately call your Cleaver-Brooks service representative to inspect the boiler and to replace any part of the control system and any gas
control which has been under water.
Notice
This manual must be maintained in legible condition and kept adjacent to the boiler or in a safe
place for future reference. Contact your local
Cleaver-Brooks representative if additional manuals are required.
!
WARNING
DANGER
The installation must conform to the requirements
of the authority having jurisdiction or, in the absence of such requirements, to UL 795 Commercial-Industrial Gas Heating Equipment and/or the
National Fuel Gas Code, ANSI Z223.1
ii
CLEAVER-BROOKS
Model CBT
TubelessVertical Boiler
Operation, Service, and Parts Manual
Cleaver-Brooks 2019
Manual Part No. 750-382
04/2019
iii
!
WARNING
DANGER
DO NOT OPERATE, SERVICE, OR REPAIR THIS EQUIPMENT UNLESS YOU FULLY UNDERSTAND ALL APPLICABLE SECTIONS OF THIS MANUAL.
DO NOT ALLOW OTHERS TO OPERATE, SERVICE, OR REPAIR THIS EQUIPMENT UNLESS THEY FULLY UNDERSTAND ALL APPLICABLE SECTIONS OF THIS MANUAL.
FAILURE TO FOLLOW ALL APPLICABLE WARNINGS AND INSTRUCTIONS MAY RESULT IN SEVERE PERSONAL
INJURY OR DEATH.
Cleaver-Brooks equipment is designed and engineered to give long life and excellent service on the job. The electrical
and mechanical devices supplied as part of the unit were chosen because of their known ability to perform; however,
proper operating techniques and maintenance procedures must be followed at all times. Although these components afford a high degree of protection and safety, operation of equipment is not to be considered free from all dangers and
hazards inherent in handling and firing of fuel.
Any “automatic” features included in the design do not relieve the attendant of any responsibility. Such features merely
eliminate certain repetitive chores, providing more time for the proper upkeep of equipment.
It is solely the operator’s responsibility to properly operate and maintain the equipment. No amount of written instructions
can replace intelligent thinking and reasoning and this manual is not intended to relieve the operating personnel of the
responsibility for proper operation. On the other hand, a thorough understanding of this manual is required before attempting to operate, maintain, service, or repair this equipment.
Because of state, local, or other applicable codes, there are a variety of electric controls and safety devices which vary
considerably from one boiler to another. This manual contains information designed to show how a basic burner operates.
Operating controls will normally function for long periods of time and we have found that some operators become lax in
their daily or monthly testing, assuming that normal operation will continue indefinitely. Malfunctions of controls lead to
uneconomical operation and damage and, in most cases, these conditions can be traced directly to carelessness and
deficiencies in testing and maintenance.
It is recommended that a boiler room log or record be maintained. Recording of daily, weekly, monthly and yearly maintenance activities and recording of any unusual operation will serve as a valuable guide to any necessary investigation.
Most instances of major boiler damage are the result of operation with low water. We cannot emphasize too strongly the
need for the operator to periodically check his low water controls and to follow good maintenance and testing practices.
Cross-connecting piping to low water devices must be internally inspected periodically to guard against any stoppages
which could obstruct the free flow of water to the low water devices. Float bowls of these controls must be inspected
frequently to check for the presence of foreign substances that would impede float ball movement.
The waterside condition of the pressure vessel is of extreme importance. Waterside surfaces should be inspected frequently to check for the presence of any mud, sludge, scale or corrosion.
It is essential to obtain the services of a qualified water treating company or a water consultant to recommend the proper
boiler water treating practices.
The operation of this equipment by the owner and his or her operating personnel must comply with all requirements or
regulations of his insurance company and/or other authority having jurisdiction. In the event of any conflict or inconsistency between such requirements and the warnings or instructions contained herein, please contact Cleaver-Brooks before proceeding.
Lifting and moving the boiler 2-2
Water treatment 2-2
Boiler room 2-4
Gas piping 2-5
Boiler water-side connections 2-10
Electrical connections 2-11
Wiring diagrams 2-12
CHAPTER 3 FLUE AND COMBUSTION AIR VENTING 3-1
Venting connections — general 3-2
Flue venting 3-2
Vent terminal location 3-2
Horizontal through-wall venting, inside air (Category III) 3-5
Horizontal through-wall direct venting 3-6
Horizontal through-wall flue vent termination 3-7
Vertical venting, inside combustion air (Category III) central heating 3-8
Vertical venting, direct vent combustion air (Category III) 3-9
Flue and combustion air duct design using direct vent combustion 3-9
CHAPTER 4 COMMISSIONING 4-1
Full modulation boilers 4-2
On/off boilers 4-25
Boil-out of a new unit 4-25
Post start-up checkout procedure 4-26
Falcon control functions and customer interface 4-27
The Cleaver-Brooks Model CBT is a two-pass vertical tubeless steam boiler with
side-mounted burner.
The CBT features thick pressure vessel plates designed to provide long life.
Full modulation and on/off options are available. On full modulation units, an
ECM variable speed combustion air blower modulates the burner to precisely
match steam production to demand for reduced fuel usage and cycling. The
side-mount burner arrangement allows for a larger steam space to deliver exceptionally dry steam quality while allowing easy access for service and maintenance. The Falcon control keeps the boiler and burner consistently operating at
peak efficiency.
On/off burners use the CB780 burner management control.
The CBT is available in 10, 15, 20, 25, and 30 HP sizes. Features include:
• Natural gas and propane fuels
• 15 psig or 150 psig design pressure
FIGURE 1-1. CBT-M boiler
• Up to 84% efficiency and high turndown with the PID modulating premix
burner.
• Low emissions: less than 20 ppm NOx (full mod, natural gas only)
• Robust pressure vessel, designed to provide long life; 5 year pressure vessel warranty
• Standard integrated control with user-friendly interface for peak operation and efficiency
Introduction
Quality construction
ASME construction ensures high quality design, safety, and reliability.
UL listed
The Model CBT and CBT-M are UL listed for both the US and Canada.
Premix technology
The Model CBT-M Boiler utilizes “Premix” technology to mix both fuel and combustion air prior to entering the
firing chamber. This technology provides clean, efficient combustion with very low emission levels.
1.1 — Pressure vessel
The boilers are constructed in accordance with the ASME Boiler Construction Code, Section I for high pressure
steam boilers and Section IV for low pressure steam boilers. High pressure steam boilers are stamped with the
ASME “S” symbol. Low pressure steam boilers are stamped with the ASME “H” symbol. The ASME data plate
can be found on the lower portion of the vessel on the front or left side (see Figure 1-2).
The CBT is a vertically oriented 2-pass tubeless pressure vessel design with a water-backed furnace. The first
fireside pass utilizes radiant heat transfer and the second pass uses convection. The second pass flue passageways incorporate extended heating surfaces designed using computational fluid dynamics (CFD) modeling.
The large steam chest volume ensures exceptional dry quality steam at both high and low operating pressures.
1-2
750-382
CBT
Pressure vessel
The pressure vessel is fully insulated with minimal use of refractory to significantly reduce radiation and convection losses. Refractory is limited to the burner dry oven and a bottom furnace target plate.
FIGURE 1-2. ASME data
(1)
FIGURE 1-2. CBT heat flow
(2)
(3)
Gases of combustion flow downward
through the furnace (1), then upward
through the 2nd pass (2) before exiting
the flue (3).
750-382
CBT
1-3
1.2 — Burner
1.2.1 — Full modulation (CBT-M)
Full modulation units use a premix burner with a self-regulating gas valve-venturi system, ECM variable regulating gas
valve, variable speed blower, and Fecralloy metal fiber
burner canister.
• Full modulation is provided using the integral variable
speed combustion air fan and Falcon control.
• The low temperature, surface combustion burner flame
provides low emissions and optimum combustion efficiency.
• Direct spark ignition with UV flame detection.
• At maximum firing rate, the sound level of the burner is
less than 70 dBA, measured in front of the boiler at a distance of 3 feet. At reduced firing rates, sound levels are
even lower.
• Provision is made for optional direct vent combustion air
connection.
• Combustion Air Proving Switch standard.
• Combustion air filter is standard.
Introduction
FIGURE 1-3. Full modulation burner
1.2.2 — On-off firing (CBT)
Gas is introduced into the combustion zone from a circular manifold
through multiple ports in the manifold. Burner firing is regulated by a
main gas regulator operating steam pressure control. Burner includes
microprocessor-based flame supervision control.
• Direct spark ignition with flame rod.
• Provision is made for optional direct vent combustion air connec-
tion.
• Combustion Air Proving Switch standard.
• Combustion air filter is standard.
FIGURE 1-4. On/off burner
1-4
750-382
CBT
Gas train
1.3 — Gas train
The gas train assembly is provided in accordance with UL/cUL certification and is ASME CSD-1 compliant. The
gas train assembly is factory assembled and wired.
F
VENTURI
C
E
OPTIONAL:
GAS PRESSURE REGULATOR
G
M
D
D
A
B
FULL MODULATION (CBT-M)
FIGURE 1-5. Gas train
Full modulation gas train components:
A. Single body, dual safety shutoff gas valve with integral trim regulator
B. Low Gas Pressure Switch
C. High Gas Pressure Switch
D. (2) Manual Shutoff Valves
E. Test Cocks
F. Venturi
G. Gas supply regulator (optional)
H
I
J
ON/OFF (CBT)
K
L
M
On/off gas train components:
H. Regulator
I. Low Gas Pressure Switch
J. Gas Solenoid Safety Shutoff Valve
K. Gas Diaphragm Safety Shutoff Valve
L. High Gas Pressure Switch
M. (2) Manual Shutoff Valves
750-382
CBT
1-5
1.4 — Controls
CONTROLS ABBREVIATIONS:
ALWCO - Auxiliary Low Water Cutoff
HLC - High Limit Control
HWA - High Water Alarm
OLC - Operating Limit Control
LWCO - Low Water Cutoff
1.4.1 — Full modulation controls
Introduction
(Optional)
(Optional)
FIGURE 1-6. Control panel, full modulation
(Optional)
The CB Falcon steam boiler control is an integrated burner management and modulation control with a color
touch-screen display/operator interface.
The controller is capable of the following functions:
Burner sequencing with safe start check, pre-purge, direct spark ignition, and post purge.
•
• Electronic ignition.
• Flame Supervision.
• Safety shutdown with time-stamped display of lockout condition.
• PID modulating steam pressure set point control.
• Supervision of low and high gas pressure, air proving, stack back pressure, high limit, and low water.
• First-out annunciator.
• Real-time data trending.
• (3) pump/auxiliary relay outputs.
• Modbus communication capability.
1-6
750-382
CBT
Controls
• Outdoor temperature reset.
• Remote firing rate or setpoint control
• Setback/time-of-day setpoint
• Built-in Lead-Lag control for multiple boiler systems
• Warm standby-minimum temperature control
1.4.2 — On-off controls
The Burner Control provides burner sequencing control and flame supervision.
A switch/light panel provides functionality similar to full modulation units: indicator lights for demand, fuel valve
open, alarm, low water, and (optional) high water; panel switches for power on/off and ALWCO reset.
BURNER
CONTROL
IGNITION
TRANSFORMER
LIGHT/BUTTON
PANEL
ALWCO
CONTROLLER
H.W.A. OPTION
LWCO CONTROLLER
PUMP CONTROL
TERMINAL STRIP
FIGURE 1-7. Control panel, on/off boilers
AIR PRESSURE
SWITCH
750-382
CBT
1-7
1.4.3 — Water level and limit controls, all boilers
The pressure transmitter provides an analog steam
pressure signal to the controller for modulated firing
(full modulation units) or on/off operation.
ALWCO probe
holder
Introduction
Manual valve
The high limit control (HLC) provides safety shutdown
when steam pressure exceeds the maximum operating
range of the boiler. It includes a manual reset switch
and adjustable set point.
The operating control (OLC) is set below the maximum
pressure setting of the HLC. This control is auto reset
and includes adjustable set point
Standard water level controls comprise an automatic
reset primary low water cutoff (LWCO) and a manual
reset auxiliary low water cutoff (ALWCO). A manual
reset LWCO is available where required by code.
Four individual conductance probes are mounted
within the LWCO water column to indicate levels for
low water, pump on, pump off, and high water alarm
(optional). The solid-state level control boards reside in
the boiler control enclosure.
A panel mounted ALWCO reset/test switch is provided.
The water column blowdown should be piped to a
boiler blowdown system. Please refer to service and
maintenance section for blowdown procedures.
Steam pressure gauge
HLC
Pressure transmitter
(modulating burner
only)
FIGURE 1-8. Low water and limit controls
LWCO/pump control
Gauge glass
Gauge glass
blowdown valve
OLC
WC blowdown valve
1-8
750-382
CBT
Component/connection locations
1.5 — Component/connection locations
Refer to Chapter 3 for recommended vent sizes and lengths.
AIR
INLET
SURFACE BLOWOFF PIPING
PRESSURE RELIEF VALVE
GAUGE GLASS
LEVEL CONTROL
GAS
TRAIN
AUX. LOW WATER CUTOFF
STACK
OUTLET
FEEDWATER PIPING
BLOWDOWN PIPING
(OPTIONAL)
FIGURE 1-9. Boiler components/connections, CBT-M
CONTROL
PANEL
BURNER
CABINET
ALWCO
SURFACE
BLOWOFF
PIPING
GAS TRAIN
LWCO
STACK OUTLET
BURNER
SIGHT GLASS
FEEDWATER PIPING
AIR INLET
BOTTOM BLOWDOWN (OPTIONAL)
FIGURE 1-10. Boiler components/connections, CBT
750-382
CBT
1-9
Introduction
1.6 — Optional equipment
Certain options are available for the Model CBT Boiler; normally these will have been specified at the time of
order entry. In addition, some options may have been provided (by others) that are not part of Cleaver-Brooks
scope of supply. In either case, the Cleaver-Brooks authorized representative should be consulted regarding
specific project requirements.
Model CBT optional features:
• Gas pressure regulator (>1/2 psig supply)
• Gas pressure relief valve (>1 psig supply)
• Minimum Temperature/Warm Standby
• Direct vent kit combustion air adapter
• Chemical feed system
• Surface blow-off conductivity control
• Feedwater system (includes tank, pump, and control) - shipped separately
• Feedwater valves
• Blowdown valves
• Steam header valves
• High water alarm
• Time clock for setback control
• Stack temperature limit control
• Stack thermometer
• Alarm horn
• Lead-Lag steam pressure header transmitter
• Feedwater sets and condensate receivers
• Blowdown separators and tanks
• Economizers
• Complete steam skid or field-installed solutions
• Factory mounted valves
• Communications gateway
• Boiler Monitor (remote connectivity)
1-10
750-382
CBT
CHAPTER 2Installation
Lifting and Moving the Boiler 2-2
Water Treatment 2-2
Boiler Room 2-4
Gas Piping 2-5
Boiler Waterside Connections 2-10
Electrical Connections 2-11
Wiring Diagrams 2-12
Warning
!
Provisions for combustion and ventilation air must
be in accordance with UL 795, CommercialIndustrial Gas Heating Equipment, cUL, or
applicable provisions of the local building codes.
Failure to follow this warning could result in
personal injury or death
Warning
!
If an external electrical source is utilized, the boiler,
when installed, must be electrically bonded to
ground in accordance with the requirements of the
authority having jurisdiction or, in the absence of
such requirements, with the National Electrical
Code and/or UL 795, Commercial-Industrial Gas
Heating Equipment.
Caution
!
The boiler must be installed such that the gas
ignition system components are protected from
water (dripping, spraying, rain, etc.) during
appliance operation and service. Failure to follow
this warning could result in equipment failure.
750-382
CBT
2-1
Installation
2.1 — Lifting and Moving the Boiler
60° min.
FIGURE 2-1. Lifting boiler
The boiler should be lifted by the base using a suitable fork lift, or by the top using the lifting lugs provided. For
fork truck lifting, ensure the forks extend through the length of the base.
Note: The boiler should not be moved by pushing, prying, or pulling on any part of the casing.
The boiler must be installed on a non-combustible floor. If the floor is not level, piers or a raised pad slightly larger
in length and width than the boiler base dimensions will make boiler installation and leveling easier.
The boiler must be installed so that all components remain accessible for inspection, cleaning, or maintenance.
Field-installed piping and electrical connections must be arranged so as to avoid interfering with removal of the
casing panels or with the burner door.
Caution
!
In order to avoid damage to the unit, lifting or moving the boiler should only be done
by experienced personnel suitably equipped for moving heavy equipment.
Caution
!
The boiler must not be installed on combustible flooring.
2.2 — Water Treatment
Properly treated boiler water will help maximize the effectiveness and lifespan of the pressure vessel. Contact your
local Cleaver-Brooks representative or water management consultant for complete information on how to prevent
damage resulting from inadequate water treatment.
See Table 2-1 for CBT water quality guidelines.
2-2
750-382
CBT
Water Treatment
Important
!
The CBT boiler requires soft water. Failure to observe this requirement can lead to dangerous
operating conditions, and may result in damage to the boiler. If necessary, your Cleaver-Brooks representative
can provide additional information regarding your water softening requirements.
The objectives of water treatment in general are to:
1. Prevent hard scale and soft sludge deposits that inhibit heat transfer and that could lead to overheated metal
and costly downtime and repairs.
2. Eliminate corrosive gases in the supply or boiler water.
To accomplish these objectives, the boiler requires proper water treatment before and after introduction of water
into the unit. The selection of pretreatment processes depends upon the water source, its chemical characteristics,
the amount of makeup water needed, system operation practices, etc.
Because of the variables involved, no single boiler compound can be considered a cure-all; nor is it advisable to
experiment with homemade treating methods. A sound treatment program should include a weekly analysis of the
water in the system.
Warning
!
Inadequate or improper water treatment will shorten the life of the
boiler and could result in a hazardous condition.
The internal or waterside surfaces of the pressure vessel should be inspected at regular intervals for evidence of
corrosion, pitting, contamination, or accumulations of foreign matter. If any of these conditions are detected,
contact your local Cleaver-Brooks authorized representative for advice on corrective action. It is recommended that
a properly sized water meter be installed in the raw water makeup line to accurately determine the amount of raw
water admitted to the boiler.
Surface blow-off is available for steam boilers. This option allows removal of surface water impurities through a
blowdown line located at the normal operating water level of the boiler. If allowed to accumulate, surface
impurities may impede steam release and could cause foaming, leading to priming and carryover in the steam
lines.
Corrosion and sludge deposits in old systems must be removed prior to installation of a new boiler.
750-382
CBT
2-3
Installation
2.3 — Boiler Room
The boiler room must comply with all building codes and regulations. An adequate supply of combustion air and
sufficient ventilation are required for safe operation. If the optional direct vent combustion air kit is not used,
ventilation must be provided to meet applicable regulations for air supply.
TABLE 2- 2. Boiler room ambient conditions
Relative humidity< 85% non-condensing
Ambient temperature range0
Storage temperature range-40
Combustion air temperature0
Clean combustion air is required for optimum efficiency and boiler operation (minimum combustion air 10 cfm
per boiler horsepower). Dust and airborne contaminants will adversely effect burner performance. See Chapter 3,
Stack and Intake Venting, for more information.
If conditions dictate, a serviceable filter must be placed at the burner inlet to eliminate airborne contamination to
the burner. If a direct vent air intake is used, the intake and flue venting should be terminated so as to prevent
rain, snow, dust, or debris from entering the intake piping.
Observe proper clearances above and around boiler - see Figure 2-2.
o
C to 50 oC / 32oF to 122oF
o
C to 60 oC / -40oF to 140oF
o
C to 50 oC / 32oF to 122oF
18”
18”
18”18”
IN FRONT OF
36”
ELECTRICAL
CONTROL PANEL
FIGURE 2-2. Recommended Clearances
CLEARANCE
ABOVE BOILER = 18”
2-4
750-382
CBT
Gas Piping
STEAM OUTLET
WATER COLUMN
GAS
INLET
COMBUSTION AIR INLET
DRAIN
GAUGE
GLASS
DRAIN
SAFETY RELIEF VALVE
STACK OUTLET
CONDENSATE
DRAIN
SURFACE BLOWOFF
FIGURE 2-3. CBT connections
FEEDWATER
BOTTOM
BLOWDOWN
GAS INLET
ON/OFF UNITS
2.4 — Gas Piping
Gas pressure requirements - For proper and safe operation, each Model CBT boiler requires a stable gas pressure
input. The minimum inlet supply pressure must be as noted in Table 2-3. Pressure should be measured when the
burner is firing using a manometer at the upstream test port connection on the main gas valve. For a multiple
unit installation, gas pressure should be set for a single unit first, then the remaining units should be staged on to
ensure that gas pressure droop is not more than 1" w.c. and never below the required pressure. Fluctuating gas
pressure readings could be indicative of a faulty supply regulator or improper gas train size to the boiler.
TABLE 2- 3. Model CBT gas pressure requirements
CBT Size
(HP)
Min (“WC)Max (“WC)*Min (“WC)Max (“WC)*
Natural GasLP Gas
107.01411.014
157.01411.014
207.01411.014
257.01411.014
308.01411.014
*Maximum without upstream regulator
A manually operated shut-off valve is provided as standard on the CBT boiler. If dirt particles are present in the
gas supply, it may be necessary to install an approved gas filter. Please inquire with the local gas supply company.
The boiler shall be installed such that the gas ignition system components are protected from water (dripping,
spraying, etc.) during appliance operation and service.
A sediment trap must be provided upstream of the gas controls.
750-382
CBT
2-5
Installation
If building supply gas pressure is greater than 1 psig (27.8” WC), an upstream regulator with overpressure protection and proper gas venting will be required and must be piped to a safe point of discharge. For multiple boiller installations, a dedicated gas pressure regulator is required for each boiler to ensure consistent gas pressure
at the boiler.
Drip legs are required on any vertical piping at the gas supply to each boiler so that any dirt, weld slag, or debris
can deposit in the drip leg rather than into the boiler gas train. The bottom of the drip leg should be removable
without disassembling any gas piping. The connected piping to the boiler should be supported from pipe supports and not supported by the boiler gas train or the bottom of the drip leg.
All gas piping and components to the boiler gas train connection must comply with NFPA 54, local codes, and
utility requirements as a minimum. Only gas approved fittings, valves, or pipe should be used. Standard industry
practice for gas piping is normally Schedule 40 black iron pipe and fittings.
Before starting the unit(s) all piping must be cleaned to prevent the entrance of debris into the boiler gas train.
Piping should be tested as noted in NFPA 54, with the boiler isolated during tests.
After initial startup, the inlet screen to the gas valve should be checked and cleaned for any debris buildup.
Gas Supply Pipe Sizing - For proper operation of a single unit or a multiple unit installation, we recommend that
the gas piping be sized to allow no more than 0.3" w.c. pressure drop from the source (gas header or utility
meter) to the final unit location. Higher supply pressure systems may allow for a greater pressure drop. In ALL
cases, minimum supply pressures must be met for proper operation of the boiler(s). The gas supplier (utility)
should be consulted to confirm that sufficient volume and normal pressure are provided to the building at the
discharge side of the gas meter or supply pipe.
For installations of new boilers into an existing building, gas pressure should be measured with a manometer to
ensure sufficient pressure is available. A survey of all connected “gas using devices” should be made. If appliances other than the boiler or boilers are connected to the gas supply line, then a determination must be made of
how much flow volume will be demanded at one time and the pressure drop requirement when all appliances
are firing.
The total length of gas piping and all fittings must be considered when sizing the gas piping. Total equivalent
length should be calculated from the utility meter or source to the final unit connection. As a minimum guideline,
gas piping Tables 2-4 and 2-5 should be used. The data in these tables is from the NFPA 54 source book, 2006
edition.
To verify the input of each device that is connected to the gas piping, obtain the btu/hr input and divide this input
by the calorific value of the gas that will be utilized. For instance, a 40 HP unit with 1,613,253 btu/hr input
divided by a gas calorific value of 1060 will result in a flow of 1,522 CFH (cubic ft/hr). The single boiler is
approximately 20 feet from the gas supply header source. And with a measured gas supply pressure of 10" w.c.
we find from Table 2-4 that a supply pipe size of 2" should be used as a minimum.
2-6
750-382
CBT
Gas Piping
Table 2-4. Gas line capacity - Schedule 40 metallic pipe
Nominal
Actual I.D.
Length in feet
10
20
30
40
50
60
70
80
90
100
125
150
175
200
**Fuel: Natural Gas
**Inlet Pressure: Less than 2.0 psi
**Pressure Drop: 0.30" w.c.
**Specific Gravity: 0.60
1"1-1/4"1-1/2"2"2-1/2"3"4"
1.0491.380"1.610"2.067"2.469"3.068"4.026"
**Maximum Capacity in Cubic Feet of Gas per Hour (CFH)
Table 2-5. Gas line capacity - Schedule 40 metallic pipe
Pipe Size
Nominal1"1-1/4"1-1/2"2"2-1/2"3"4"
Actual I.D.1.049"1.380"1.610"2.067"2.469"3.068"4.026"
Length in feet**Maximum Capacity in Cubic Feet of Gas per Hour (CFH)
10
20
30
40
50
60
70
80
90
100
125
150
175
200
**Fuel: Natural Gas
**Inlet Pressure: Less than 2.0 psi
**Pressure Drop: 0.50" w.c.
**Specific Gravity: 0.60
6781,3902,0904,0206,40011,30023,100
4669571,4302,7604,4007,78015,900
3747681,1502,2203,5306,25012,700
3206579851,9003,0205,35010,900
2845838731,6802,6804,7409,600
2575287911,5202,4304,2908,760
2374867281,4002,2303,9508,050
2204526771,3002,0803,6707,490
2074246351,2201,9503,4507,030
1954006001,1601,8403,2606,640
1733555321,0201,6302,8905,890
1573224829281,4802,6105,330
1442964438541,3602,4104,910
1342754127941,2702,2404,560
750-382
CBT
2-7
Installation
Gas header - For multiple unit installations, a single common gas header is recommended with individual
takeoffs for each boiler (See Figure 2-4). Boiler gas manifold piping should be sized based on volume
requirements and lengths between each boiler and the fuel main header. Tables 2-6 through 2-10 indicate the
proper sizing for multiple units of equal size, placed on the factory standard center with the indicated take off
size. For installations with a mixed sized use, determine the flow of each unit and total the input. With the total
input, find length of run from the source and determine what size header will be needed for the flow of all units
firing. Pipe sizes are based on Table 2-4 with boiler gas line take-off at 20 feet from the header. If pipe runs are
greater or if gas pressure is different, refer to Tables 2-4 and 2-5 for pipe sizing. Main fuel supply header should
be sized for <4" w.c. pressure drop with all equipment operating at 100% capacity.
FROM METER
HEADER PIPE
MANUAL SHUTOFF
GAS STRAINER
REGULATOR
SEE NOTE 1
RELIEF VALVE
SEE NOTE 5
DRIP LEG
MANUAL
SHUTOFF
OPTIONAL
FIGURE 2-4. Typical gas piping - Example 1
NOTES:
1. Step-down regulator required
if supply pressure >1/2 psig.
2. Refer to local fuel gas codes when
applicable.
3. Header to be sized for room
capacity.
4. Provision required for measuring
gas supply pressure at boiler.
5. Relief valve required if gas supply
pressure >1 psig.
2-8
750-382
CBT
Gas Piping
MANUAL SHUTOFF
VALVE
REGULATOR (OPTIONAL)
STRAINER
MANUAL SHUTOFF
VALVE
GAS HEADER - SIZE FOR BOILER ROOM
CAPACITY AND TO MINIMIZE PRESSURE LOSS
BY INSTALLER
FIGURE 2-5. Typical gas piping - Example 2
Pipe sizing for multiple unit manifolds
TABLE 2- 6. CBT 10 HP boilers
# of
Units
Pipe Size
To Boiler
Header
Pipe Size
TABLE 2- 8. CBT 20 HP boilers
# of
Units
Pipe Size
To Boiler
Header
Pipe Size
12 3 4
1-1/4”1-1/4”1-1/4”1-1/4”
1-1/2”1-1/2”2”2”
12 3 4
1-1/2”1-1/2”1-1/2”1-1/2”
1-1/2”2”2-1/2”2-1/2”
DRIP LEG REQUIRED FOR ANY VERTICAL RUN OF PIPING
TABLE 2- 7. CBT 15 HP boilers
# of
Units
Pipe Size
To Boiler
Header
Pipe Size
TABLE 2- 9. CBT 25 HP boilers
# of
Units
Pipe Size
To Boiler
Header
Pipe Size
12 3 4
1-1/4”1-1/4”1-1/4”1-1/4”
1-1/2”2”2”2-1/2”
1234
1-1/2”1-1/2”1-1/2”1-1/2”
1-1/2”2"2-1/2”3"
TABLE 2- 10. CBT 30 HP boilers
# of
Units
Pipe Size
To Boiler
Header
Pipe Size
12 3 4
2”2”2”2”
2”2-1/2”3”3”
750-382
CBT
2-9
Installation
2.5 — Boiler Waterside Connections
Notice
Before filling boiler, check that all waterside
openings/fittings are plugged and all inspection
covers are secured
A pressure relief valve (safety valve), provided with the boiler, must be installed in the mounting provided. Use
pipe sealing compound and a flat sided wrench when securing the safety relief valve. Do not use a pipe wrench
and do not over tighten the relief valve. The safety valve must be mounted in a vertical position so that discharge
piping and code-required drains can be properly piped to prevent buildup of back pressure and accumulation of
foreign material around the valve seat area. Apply only a moderate amount of pipe compound to male threads and
avoid over-tightening, which can distort the seats. Use only flat-jawed wrenches on the flats provided.
Connection to the main steam header is made at the nozzle projecting upward from the boiler shell. ASME code
requires a suitable stop valve to be installed between the boiler and main steam header if multiple boilers are tied
to the header. This valve should be as close as possible to the boiler to facilitate venting and pressure testing. A
suitably rated gate valve is recommended for this purpose.
Feedwater is introduced through the piping assembly installed on the side of the boiler vessel. A stop valve and
check valve are optional equipment.
The feedwater supply should provide sufficient pressure to meet minimum flow requirements.
Cleaver-Brooks offers bottom blowdown piping and valves for CBT boilers. Optional surface blowoff is also
available.
A qualified boiler and piping installer should make all boiler waterside connections.
Only properly certified personnel such as the safety valve
manufacturer’s certified representative can adjust or repair the
boiler safety valves. Failure to follow this warning could result in
serious personal injury or death.
SURFACE BLOWOFF
FEEDWATER
STEAM
OUTLET
SAFETY VALVE
FIGURE 2-6. Waterside connections (boiler top view)
BOTTOM
BLOWDOWN
2-10
750-382
CBT
Electrical Connections
r
2.6 — Electrical Connections
A qualified electrician or service technician must make the electrical connections to the boiler; all local electrical
and building codes must be adhered to.
Main power and any remote wiring should be brought to the left side of the control panel and terminated at the
appropriate terminals provided.
- Connect UV Scanner to threaded connection on dry oven
1
- Connect spark cables to dual electrode and ignition transforme
2
- Plug AC power harness into blower
3
- Plug DC blower control harness plug into blower
4
- Connect incoming AC power per wiring diagram
5
- Connect optional heat request inputs per wiring diagram
6
- Connect pump controls per wiring diagram
7
Caution: The blower signal wiring must be isolated from the blower power wiring and the high voltage ignition
cables.
750-382
CBT
FIGURE 2-7. CBT wiring and cable connections
2-11
Installation
2.7 — Wiring Diagrams
Note: Wiring diagrams shown are for example only. Installations may vary. Refer to the Cleaver-Brooks wiring
diagram provided with the boiler for information specific to your installation.
Basic wiring diagram - full modulation
2-12
750-382
CBT
Wiring Diagrams
Basic wiring diagram - on/off boiler
750-382
CBT
2-13
Installation
2-14
750-382
CBT
CHAPTER 3Flue and Combustion Air
Venting
Venting connections - general 3-2
Flue venting 3-2
Vent terminal location 3-2
Horizontal through-wall venting, inside air (Category III) 3-5
Horizontal through-wall direct venting 3-6
Horizontal through-wall flue vent termination 3-7
Vertical venting, inside combustion air (Category III) central heating 3-8
Vertical venting direct vent combustion air (Category III) 3-9
Flue and combustion air duct design using direct vent combustion 3-9
750-382
CBT
3-1
Flue and Combustion Air Venting
3.1 — Venting connections - general
Proper installation of flue gas exhaust venting is critical for the efficient and safe operation of the boiler.
Definition of Appliance Categories
Boilers are divided into four categories based on the pressure and temperature produced in the exhaust
stack and the likelihood of condensate production in the vent.
• Category I - A boiler which operates with a non-positive vent static pressure and with a vent gas temperature
that avoids excessive condensate production in the vent.
• Category II - A boiler which operates with a non-positive vent static pressure and with a vent gas temperature
that may cause excessive condensate production in the vent.
• Category III - A boiler which operates with a positive vent pressure and with a vent gas temperature that avoids
excessive condensate production in the vent.
• Category IV - A boiler which operates with a positive vent pressure and with a vent gas temperature that may
cause excessive condensate production in the vent.
The Model CBT will in most applications be considered a Category III boiler. In certain applications, such as
with a condensing economizer, Category II or IV venting criteria may apply.
For additional information on boiler categorization, see latest edition standard of National Fuel Gas Code or in
Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment,
or applicable provisions of local building codes.
Contact the manufacturer of the vent material if there is any
question about the boiler categorization and suitability of a
vent material for application on a Category III vent system.
Using improper venting materials can result in personal
injury, death or property damage.
During winter months check the flue termination and make sure no blockage occurs from build up of ice or
snow. Condensate can freeze on a flue termination. Frozen condensation at the flue termination can result in a
blocked flue condition.
3.2 — Flue venting
The flue should be supported to maintain proper clearances from combustible materials.
Use insulated vent pipe spacers where the venting passes through combustible roofs and walls.
Cleaver-Brooks recommends the use of flue venting systems that are certified to UL 103 or ULC C-959.
Flue systems constructed of stainless steel are recommended. Please note: Type B vent is NOT appropriate
for Category II, III, or IV boiler systems.
3.3 — Vent terminal location
Give special attention to the location of the vent termination to avoid possibility of property damage or
personal injury.
1.Combustion gases can form a white vapor plume in the winter. The plume could obstruct a window view if
the termination is installed in close proximity to windows.
2.Prevailing winds could cause freezing of condensate and water/ice buildup on building, plants or roof.
3-2
750-382
CBT
Vent terminal location
3.The bottom of the vent terminal and the air intake shall be located at least 24 inches above grade, including
normal snow line.
4.Un-insulated single-wall metal vent pipe shall not be used outside in cold climates for venting combustion
gas.
5.Through-the-wall vents for Category II and IV appliances and non-categorized condensing appliances shall
not terminate over public walkways or over an area where condensate or vapor could create a nuisance or
hazard or could be detrimental to the operation of other equipment. Where local experience indicates that
condensate is a problem with Category III appliances, this provision shall also apply.
6.Locate and guard vent termination to prevent accidental contact by people and pets.
7.DO NOT terminate vent in window well, alcove, stairwell or other recessed area, unless previously approved
by local authority.
8.DO NOT terminate above any door, window, or gravity air intake. Condensate can freeze causing ice
formations.
9.Locate or guard vent to prevent condensate from damaging exterior finishes. Use a 2' x 2' rust resistant sheet
metal backing plate against brick or masonry surfaces.
10. Minimize exposed flue venting outside of building in extreme cold climates. In winter conditions condensate
could freeze and block the flue pipe or termination.
11. Ensure combustion air intake(s) are a sufficient distant away from any exhaust terminations to avoid drawing
in flue gases or other contaminants.
U.S. installations- Refer to latest edition of the National Fuel Gas Code.
Vent termination requirements are as follows:
1.Vent must terminate at least four (4) feet below, four (4) feet horizontally, or one (1) foot above any door,
window or gravity air inlet to the building.
2.The vent must not be less than seven (7) feet above grade when located adjacent to public walkways.
3.Terminate vent at least three (3) feet above any forced air inlet located within ten (10) feet.
4.Vent must terminate at least four (4) feet horizontally, and in no case above or below unless four (4) feet
horizontal distance is maintained, from electric meters, gas meters, regulators, and relief equipment.
5.Terminate vent at least six (6) feet away from adjacent walls.
6.DO NOT terminate vent closer than five (5) feet below roof overhang.
Canada installations- Refer to the latest edition of CAN/CGA-B149.1 and B149.2
A vent shall not terminate:
1.Directly above a paved sidewalk or driveway which is located between two single family dwellings and serves
both dwellings.
2.Less than 7 ft. (2.13m) above a paved sidewalk or paved driveway located on public property.
3.Within 6 ft. (1.8m) of a mechanical air supply inlet to any building.
4.Above a meter/regulator assembly within 3 ft. (900mm) horizontally of the vertical center-line of the regulator.
5.Within 6 ft. (1.8m) if any gas service regulator vent outlet.
6.Less than 1 ft. (300mm) above grade level.
7.Within 3 ft. (1m) of a window or door which can be opened in any building, any non-mechanical air supply
inlet to any building to the combustion air inlet of any other appliance.
8.Underneath a verandah, porch or deck, unless:
A. The verandah, porch or deck is fully open on a minimum of two sides beneath the floor.
B. the distance between the top of the vent termination and the underside of the verandah, porch or deck is
greater than 1 ft. (30cm)
Note: For direct vent installations where the air is piped in from outside, a protective screen on the air inlet
termination elbow must be used to act as an inlet screen.
750-382
CBT
3-3
Flue and Combustion Air Venting
Examine the venting system at least once a year. Check all joints and vent pipe connections for tightness,
corrosion or deterioration.
3.3.1 — Venting installation tips
Where to support piping:
• Horizontal runs- at least every five (5) feet.
• Vertical runs - use braces under or near elbows
Observe the following to avoid personal injury or property damage:
• To cut nonmetallic vent pipe, use a fine-toothed hacksaw (34 teeth per inch).
• Do not use nonmetallic vent pipe or fittings that are cracked or damaged.
• Do not use nonmetallic vent fittings if they are cut or altered.
• Do not drill holes, or use screws or rivets, in nonmetallic vent pipe or fittings.
Refer also to the vent manufacturer’s installation instructions.
During winter months check the flue termination and make sure no blockage occurs from build up of ice or
snow. Condensate can freeze on a flue termination. Frozen condensation at the flue termination can result in a
blocked flue condition.
3-4
FIGURE 3-1. Vent Terminations
750-382
CBT
Horizontal through-wall venting, inside air (Category III)
3.4 — Horizontal through-wall venting, inside air (Category III)
For boilers connected to gas vents or chimneys, vent installations shall be in accordance with Part 7, Venting of Equipment,
of the latest edition of National Fuel Gas Code, or in Canada, the
latest edition of CAN/CGA-B 149.1 and.2 Installation Code for
Gas Burning Appliances and Equipment, or applicable provisions of local building codes.
These installations utilize the boiler-mounted blower to vent the
combustion products to the outside. Combustion air is taken
from inside the room and the vent is installed horizontally
through the wall to the outside. Adequate combustion and ventilation air must be supplied to the boiler room in accordance with
the National Fuel Gas Code or, in Canada, the latest edition of
CAN/CGA-B 149.1 and.2 Installation Code for Gas Burning
Appliances and Equipment.
The direct vent intake should be considered in the overall length
calculation of the venting system.
FIGURE 3-2. Horizontal venting through-wall
using inside air for combustion
The vent must be installed to prevent the flue gas leakage. Care must be taken during assembly to insure that all
joints are sealed properly and are airtight.
The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is recommended that:
1.The flue venting be installed with a slight downward slope of at least 1/8” per foot of horizontal run to the
vent terminal.
2.The flue venting be insulated through the length of the horizontal run.
For appliances installed in extreme cold climate, it is recommended that:
1.The flue venting be installed with a slight upward slope of at least 1/8” per foot of horizontal run to the vent
terminal. In this case, an approved condensate trap must be installed per applicable codes.
2.The flue venting be insulated through the length of the horizontal run.
750-382
CBT
3-5
Flue and Combustion Air Venting
FIGURE 3-3. Horizontal through-wall direct venting system, Category
III installation
3.5 — Horizontal through-wall direct venting
These installations utilize the boiler mounted blower to draw combustion air from outside and vent combustion
gases to the outside.
Combustion air venting can be constructed of steel, stainless steel, PVC, CPVC, or material as deemed appropriate for the application and per local codes. The direct vent air intake should be considered in the overall length
calculation of the venting system.
Care must be taken during assembly that all joints are sealed properly and are airtight for both the combustion
air intake and the exhaust flue piping system.
The flue venting must be installed to prevent the potential accumulation of condensate in the stack pipes. It is
recommended that:
1.Vent be installed with a slight downward slope of at least 1/8” per foot of horizontal run to the stack terminal.
2.The flue venting is to be insulated through the length of the horizontal run.
For appliances installed in extreme cold climate, it is recommended that:
3-6
750-382
CBT
Horizontal through-wall flue vent termination
1.The flue venting be installed with a slight upward slope of at least 1/8” per foot of horizontal run to the vent
terminal. In this case, an approved condensate trap must be installed per applicable codes.
2.The flue venting is to be insulated through the length of the horizontal run.
Multiple direct flue terminations MUST NOT be installed with a combustion air inlet
directly above a flue termination. This vertical spacing would allow the flue products
from the flue termination to be pulled into the combustion air intake installed above.
This type of installation can cause non warrantable problems with components and
poor operation of the unit due to the recirculation of flue products.
The flue terminations MUST be mounted on the exterior of the building. The flue termination should not be
installed in a well or below grade. The flue termination must be installed at least one (I) foot above ground level
and above normal snow levels.
Combustion air supplied from outdoors must be free of particulate and chemical contaminants. To avoid a
restricted combustion air or blocked flue condition, keep all air intakes and flue terminations clear of snow, ice,
leaves, debris, etc.
750-382
CBT
3-7
Flue and Combustion Air Venting
3.7 — Vertical venting, inside combustion air (Category III) central heating
Flue Vent Termination
(velocity cone type)
24”
Minimum
If 10’-0”
or less
24”
Minimum
FIGURE 3-4. Vertical stack with inside combustion air
These installations utilize the boiler mounted blower to vent the combustion products to the outside. Combustion
air is taken from inside the room and the vent is installed vertically through the roof to the outside. Adequate
combustion and ventilation air must be supplied to the boiler room in accordance with the National Fuel Gas
Code or, in Canada, the latest edition of CAN/CGA-B 149.1 AND.2. Installation Code for Gas Burning Appliances
and Equipment.
To prevent condensation accumulation in extended horizontal runs:
• It is required to install the horizontal portion of the flue venting with a slight downward slope of at least 1/8”
per foot of horizontal run.
• An approved condensate trap must be installed per applicable codes.
3-8
750-382
CBT
Vertical venting direct vent combustion air (Category III)
3.8 — Vertical venting direct vent combustion air (Category III)
Flue Vent Termination
(velocity cone type)
24” Minimum
Air Intake
(w/Screen)
36”
Minimum
12” Minimum
FIGURE 3-5. Vertical stack with direct vent combustion air
These installations utilize the boiler mounted blower to draw combustion air from outside and vent combustion
products to the outside. A positive pressure venting system is required.
To prevent condensation accumulation in extended horizontal runs, it is required to install the horizontal portion
of the flue venting with a slight upward slope of at least 1/8” per foot of horizontal run; a drain with condensate
trap must be installed per applicable codes.
Combustion air venting can be constructed of steel, stainless steel, PVC, CPVC, or material as deemed appropriate for the application and per local codes.
3.9 — Flue and combustion air duct design using direct vent combustion air
Boiler Size HP Stack Connection - Flue
diameter (in)**
1064160
1564140
2064120
256
3086120
*Each additional 90 deg. elbow equals 5 equivalent feet of ductwork. Subtract from the maximum length accordingly. Increasing
the diameter of the air intake will reduce the pressure drop and thereby allow longer total vent lengths. Maximum allowable pressure
drop in combustion air intake duct is 0.25” w.c.
**The maximum allowable draft tolerance in the flue venting is +/- 0.25” w.c. as measured at the boiler's flue outlet.
Combustion Air Duct
diameter (in)
4100
6140
Maximum Air Intake
Length (ft)*
750-382
CBT
3-9
Flue and Combustion Air Venting
3-10
750-382
CBT
CHAPTER 4Commissioning
Operating conditions 4-2
Full modulation boilers 4-2
Operating conditions 4-2
Filling boiler 4-2
Control setpoints 4-2
Water level controls 4-2
CB Falcon setup 4-4
CB Falcon display/operator interface 4-5
Lockouts, Holds, and Alerts 4-9
Controller configuration 4-10
Program module 4-17
Burner sequence 4-17
Fan speed settings 4-18
Initial startup procedure 4-18
Gas train and piping 4-18
Power-up 4-19
Operation check: gas valve, gas pressure switches, and combustion air proving switch 4-20
LWCO and ALWCO Check 4-21
Low and high fire adjustments 4-22
Modulation OFF point 4-22
Setting Combustion 4-22
Limit Controls Check 4-24
On/off boilers 4-25
Ignition adjustment 4-25
Gas Adjustments 4-25
Electrical interference test 4-25
Boil-out of a new unit 4-25
Post start-up checkout procedure 4-26
Falcon control functions and customer interface 4-27
750-382
CBT
Warning
!
The boiler and its gas connection must be leak tested
before placing the boiler in operation.
4-1
Commissioning
4.1 — Full modulation boilers
4.1.1 — Operating conditions
• The installation site should be as free as possible from vibration, dust, and corrosive media
• The controllers should be located as far as possible from sources of electromagnetic fields, such as frequency
converters or high-voltage ignition transformers
• Control panel must be connected to earth ground.
Boiler room ambient conditions
Relative humidity
Ambient temperature range0
Storage temperature range-20
Combustion air temperature0
NOTE: When using direct vent combustion in cold climates, special care must be taken to observe combustion air
temperature limits. Failure to follow this precaution may lead to equipment damage or unsafe operation.
< 85% non-condensing
o
C to 50 oC / 32oF to 122oF
o
C to 60 oC / -4oF to 140oF
o
C to 50 oC / 32oF to 122oF
4.1.2 — Filling boiler
Open the vent valve and fill the boiler slowly to allow entrapped air to escape. Do not close the vent valve until
water is visible in the gauge glass. Check to ensure that no leaks appear at any pipe connections and correct if
water leaks are noticed.
4.1.3 — Control setpoints
Preliminary settings of the burner/boiler safety controls are necessary for the initial starting of the boiler. After
the burner has been properly set, minor adjustments to these controls may be necessary for the particular
installation. For initial starting, set the following controls accordingly:
1. Combustion Air Proving Switch - Set the dial @ minimum.
2. Low Gas Pressure Switch - Set the dial @ minimum.
3. High Gas Pressure Switch - Set the dial @ maximum.
Depress all manual reset buttons for all controls prior to starting.
4.1.4 — Water level controls
The LWCO/pump control and ALWCO control boards are located in the boiler control panel. The LWCO control
is connected to conductance probes mounted within the external water column. This column has 4 probes used
for the following functions: low water cut-off, pump on, pump off, and high water alarm (optional). The ALWCO
control is connected to a conductance probe(s) in a vessel-mounted probe head. The ALWCO includes a panel
mounted manual reset/test switch.
4-2
750-382
CBT
Full modulation boilers
750-382
CBT
FIGURE 4-1. CBT probe and WC levels
4-3
FIGURE 4-2. CB Falcon controller
Commissioning
4.1.5 — CB Falcon setup
The Model CBT boiler uses the CB Falcon boiler control system. Primary controller functions include:
• Flame supervision
• Burner sequencing
• PID Modulation control
• Operating Limit Control
Additional features include:
• User-friendly touchscreen interface
• Modbus communication capability
• Alarm/lockout messaging with history (last 15 messages)
• Annunciation
• Password protection of configurable parameters
• Time of Day (dual setpoint) control
• Remote reset
• (3) configurable pump relays
• Remote modulation/remote setpoint
4-4
750-382
CBT
Full modulation boilers
FIGURE 4-3. Controller status LEDs and reset button
Please review the tables within this Commissioning section to familiarize yourself with the functions and
parameters of the Controller. Also see Appendices A and B for details on control configuration and operation.
The Model CBT is factory tested. Nevertheless, all burner safety controls should be checked upon installation,
prior to initial firing. Failure to verify burner control functioning could result in severe bodily injury or death.
FIGURE 4-4. CB Falcon display/operator interface
4.1.6 — CB Falcon display/operator interface
The CB Falcon display/operator interface is mounted in the boiler control panel for convenient access to all
operating controls.
Note: CBT boilers will be equipped with the 833-05105 System Display. For more information see Appendix B.
750-382
CBT
4-5
Home page
Apply power to the boiler. The Home page will appear on the CB Falcon display.
FIGURE 4-5. Home Page
Commissioning
If the screen does not display properly when the unit is powered up:
• Verify that the controller is receiving power.
• Check the communication wiring between the controller and display; verify the following connections (also see
Figure 4-6):
Falcon Controller
(Terminal J3)
MB1 A (RED)Terminal 5
MB1 B (BLACK)Terminal 4
MB1 C (WHITE)Terminal 3
If the home screen appears, but without the Falcon icon:
1. Press <Setup>, then from the Setup screen press
Display
12 VDC
Common
RED BLK
CB Falcon
MB1MB2
WH
<Refresh>.
2. When the controller name shows up on the Setup screen,
press <Synchronize>. It will take a short time for the dis-
FIGURE 4-6. Falcon communications wiring
play to synchronize with the controller.
4-6
750-382
CBT
Full modulation boilers
Note: The “Home” icon at the upper left of the display screen always returns to the Home Page.
The “Back” icon at the upper right displays the previous screen.
The camera icon will take a snapshot of the currently displayed screen. Up to 16 snapshots can
be saved and loaded to a USB device.
Display setup
Starting from the Home screen, press <Setup> then <Display Setup> for the Display Setup menu.
The Display Setup menu accesses selections for adjusting and customizing the Falcon display and for basic settings of the COM1 and COM2 Modbus ports.
After making changes, press <Save> and cycle power to the controller.
Status page
Pressing the Falcon icon on the Home page takes the user to the Status page, which summarizes boiler status
and allows navigation to the configuration, operational, and diagnostic areas of the CB Falcon interface.
750-382
CBT
FIGURE 4-7. Display Setup Menu
4-7
Commissioning
FIGURE 4-8. Status page
The Demand display will show one of the following:
Burner enable off
Off (burner switch on but no demand)
Steam
Burner state shows the currently active step in the burner operating sequence.
The central portion of the display can be toggled between the following:
Pumps shows the status of the pump/auxiliary relay contacts
Modulation shows fan speed RPM settings for Demand, Limited, and Override rates
Setpoints shows the ON, Modulation, and OFF setpoints.
Note: Before clearing a lockout, first
i dentify a n d c o r r e c t t h e
condition that caused the
lockout.
The History banner is located near the bottom of the screen. Lockouts, Alerts, and Hold conditions will be
annunciated here. Pressing the banner allows access to the Lockout and Alert history logs. In the case of a
lockout alarm, the lockout can be cleared by navigating to the Lockout History and pressing <Clear Lockout>.
The steam pressure modulation setpoints can be changed from the Status page by pressing the current
displayed value. A numeric keypad will pop up, allowing entry of new values.
4-8
750-382
CBT
Full modulation boilers
FIGURE 4-9. Operation page
Operation page
From the Operation Page page the user can change setpoints, manually control the boiler’s firing rate, manually
turn pumps on, and view annunciation information. If a password is required to change any of the settings on
this page, the user can press the Login button to enter the password.
The burner is enabled from this page by turning the <Burner enable> screen button ON.
4.1.7 — Lockouts, Holds, and Alerts
The CB Falcon implements two kinds of faults: lockouts and alerts. The Falcon will also annunciate hold conditions which automatically clear when the condition is removed or satisfied.
Lists of fault codes and alerts can be found inAppendix A, CB Falcon Control.
LOCKOUT
• A lockout causes the boiler control to shutdown and requires manual or remote reset to clear the lockout.
• Always causes alarm contacts to close.
• Logged in lockout history in controller non-volatile memory.
ALERT
• Any fault condition that is not a lockout is an alert. Examples include boiler control abnormal conditions, faults
from non-safety functions, etc.
• Alerts never require manual intervention to reset them; they are for informational use only. Normal operation
continues.
• Alerts are logged in a 15-item volatile alert history sorted in chronological order. Only one instance of each alert
code occurs in the history, corresponding to the most recent occurrence of that alert.
HOLD
• A hold prevents the boiler from continuing until the hold condition is satisfied.
• Holds are not alarm conditions and are not logged in memory.
750-382
CBT
4-9
Commissioning
See also Chapter 5, Section E - Troubleshooting.
4.1.8 — Controller configuration
The CB Falcon controller should be factory configured for the specific CBT boiler model. Prior to starting the
boiler, verify that the factory default settings are correct for your application. Please refer to CB default settings,
Table 4-1, and make any changes at this time if needed.
The CB Falcon steam control parameter settings are organized into the following parameter groups:
CB Falcon factory parameter settings - Model CBT-M (Continued)
Range
start delay
overrun time
options 1
options 2
Burner cycle countRead Only0Cycles128
Burner run timeRead Only0Hours130
CH pump cycle countService0Cycles132
System pump cycle
count
Boiler pump cycle
count
Auxiliary 1 pump
cycle count
Auxiliary 2 pump
cycle count
Service0m 0smmm ss757
Service3m 0smmm ss758
ServiceInhibit for faults759
ServiceUse for Local
Service0Cycles136
Service0Cycles138
Service0Cycles140
Service0Cycles146
Default SettingMax.
Range
Demands (burner)
Parameter UnitsInstallation
Setting
Modbus
Register
(dec)
760
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciator 1
location
Annunciator1 short
name
Annunciator 1 long
name
Annunciator 2
location
Annunciator2 short
name
Annunciator 2 long
name
Annunciator 3
location
Annunciator3 short
name
Annunciator 3 long
name
Annunciator 4
location
Annunciator4 short
name
Annunciator 4 long
name
Annunciator 5
location
Annunciator5 short
name
Annunciator 5 long
name
Annunciator 6
location
Annunciator6 short
name
OEME:Other
annunciation
OEMA1307
OEMAIR SWITCH309
ServiceC:LCI circuit319
ServiceA2320
ServiceLOW WATER322
OEMD:Interlock circuit332
OEMA3333
OEMAUX LOW WATER335
OEMD:Interlock circuit345
OEMA4346
OEMHIGH LIMIT348
OEMD:Interlock circuit358
OEMA5359
OEMHIGH GAS
PRESSURE
OEMD:Interlock circuit371
OEMA6372
306
361
4-12
750-382
CBT
Full modulation boilers
TABLE 4- 1.
Parameter GroupParameter NameAccessMin.
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
Annunciation
Configuration
CB Falcon factory parameter settings - Model CBT-M (Continued)
Range
Annunciator 6 long
name
Annunciator 7
location
Annunciator7 short
name
Annunciator 7 long
name
Annunciator 8
location
Annunciator8 short
name
Annunciator 8 long
name
PII short nameOEMPII410
PII long nameOEMPre-Ignition ILK412
LCI short nameOEMLCI422
LCI long nameOEMLimit Circuit Input424
ILK short nameOEMILK434
ILK long nameOEMInterlock436
OEMLOW GAS
ServiceE:Other
ServiceA7385
ServiceAnnunciator7387
ServiceE:Other
ServiceA8398
ServiceAnnunciator8400
Default SettingMax.
Range
PRESSURE
annunciation
annunciation
Parameter UnitsInstallation
Setting
Modbus
Register
(dec)
374
384
397
Burner Control
Interlocks
Burner Control
Interlocks
Burner Control
Interlocks
Burner Control
Interlocks
Burner Control
Interlocks
Burner Control
Interlocks
Burner Control
Interlocks
Burner Control
Timings & Rates
Burner Control
Timings & Rates
Burner Control
Timings & Rates
Burner Control
Timings & Rates
Burner Control
Timings & Rates
Burner Control
Timings & Rates
Burner Control
Timings & Rates
Purge rate provingOEMFan speed229
Lightoff rate provingServiceFan speed except
Interlock open
response
Interrupted air switch
enable
LCI enableRead OnlyEnabled248
PII enableServiceDisabled249
ILK bounce detection
enable
Prepurge rateOEM3000rp
Postpurge rateService1000rp
Standby rateService0rpm0rpm3000rpmRPM207
Prepurge timeService0m 30s0m 30s15m 0smmm ss231
Run stabilization time Service0m 10s15m 0smmm ss235
Postpurge timeService0m 15s0m 15s15m 0smmm ss236
Forced recycle
interval time
Read OnlyLockout238
ServiceEnable IAS during
OEMEnabled253
m
m
OEM0h 0mmin254
during ignition
purge & ignition
4000rpm6500rpmRPM196
2000rpm6500rpmRPM198
230
246
Burner Control
Ignition
Pilot test holdServiceOff197
750-382
CBT
4-13
Commissioning
TABLE 4- 1.
Parameter GroupParameter NameAccessMin.
Burner Control
Ignition
Burner Control
Ignition
Burner Control
Ignition
Burner Control
Ignition
Burner Control Flame
Failure
Burner Control Flame
Failure
Burner Control Flame
Failure
Burner Control Flame
Failure
Burner Control Flame
Failure
System Configuration Burner EnableUserNo//Off203
System Configuration Flame sensor typeServiceUV power tube with
System Configuration Modulation outputOEMFan PWM192
System Configuration Temperature unitsServiceA:Fahrenheit178
System Configuration Antishort cycle timeService0m 0smmm ss179
System Configuration Alarm silence timeServicemmm ss
System Configuration Line frequencyServiceAuto detect 48
System Configuration Safety configuration
CB Falcon factory parameter settings - Model CBT-M (Continued)
Range
Lightoff rateService1000rp
Preignition timeService0m 0s15m 0smmm ss232
PFEPRead Only4 seconds233
Flame thresholdOEM0.50.8510ths (V or uA)250
Ignite failure response ServiceLockout239
Ignite failure retriesOEM1240
Ignite failure delayService0m 0smmm ss241
Run flame failure
response
Fan speed error
response
options
Read OnlyLockout243
OEMLockout255
OEMIgnore Flame rod
m
Default SettingMax.
Range
2000rpm3000rpmRPM197
spark interference
through 63 Hz
faults for UV config
Parameter UnitsInstallation
Setting
Modbus
Register
(dec)
228
630
631
Sensor Configuration S1 (J8-4) sensor type Service0-150 psi608
Sensor Configuration S2 (J8-6) sensor type ServiceUnconfigured609
Fan ConfigurationAbsolute max fan
Fan ConfigurationAbsolute min fan
Fan ConfigurationPWM frequencyOEMD:3000 Hz258
Fan ConfigurationPulses per revolution Read Only233259
Fan ConfigurationFan speed up rampService001000RPM/sec260
Fan ConfigurationFan slow down rampService001000RPM/sec261
Fan ConfigurationFan gain upService30262
Fan ConfigurationFan gain downService30263
Fan ConfigurationFan min duty cycleService100-100%264
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
speed
speed
Lead lag master
enable
Lead lag hysteresis
step time
Lead lag P gainService10552
Lead lag I gainService10553
OEM200065006500RPM256
OEM8009003000RPM257
ServiceNo Lead Lag master545
Service0m 0smmm ss551
4-14
750-382
CBT
Full modulation boilers
TABLE 4- 1.
Parameter GroupParameter NameAccessMin.
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
Lead Lag Master
Configuration
CB Falcon factory parameter settings - Model CBT-M (Continued)
Range
Lead lag D gainService0554
Lead lag operation
switch
Lead lag Steam
demand switch
Lead lag Steam
setpoint source
Lead lag modulation
sensor
Lead Lag Modbus
port
Base load commonService75%0 to 100%572
Lead selection
method
Lag selection methodServiceSequence order575
Lead lag add stage
method 1
Lead lag add stage
detection time 1
Lead lag add stage
rate offset
Lead lag add stage
interstage delay
Lead lag drop stage
method 1
Lead lag drop stage
detection time 1
Lead lag drop stage
rate offset
Lead lag drop stage
interstage delay
Lead rotation timeService120h 0mmin733
Force lead rotation
time
Lead lag pressure
setpoint
Lead lag pressure
TOD setpoint
Lead lag pressure on
hysteresis
Lead lag pressure off
hysteresis
Lead lag add stage
pressure error
threshold
Lead lag drop stage
pressure error
threshold
Lead lag 4 mA steam
pressure
Lead lag 20 mA
steam pressure
ServiceNo//Off555
ServiceSTAT terminal556
OEMLocal setpoint is
ServiceS2 (J8-6) Steam
OEMMB2569
ServiceSequence order574
ServiceFiring rate threshold
Service2m 0smmm ss716
Service0%-100% to 100%719
Service3m 0smmm ss722
ServiceFiring rate to drop
Service1m 0smmm ss725
Service-3%-100% to 100%728
Service3m 0smmm ss731
Service168h 0mmin734
User010135psig738
Service0psig739
Service0psig740
Service6psig741
Service3psig742
Service3psig743
Service00psig745
Service0135150psig746
Default SettingMax.
Range
used
sensor
to add stage
stage
Parameter UnitsInstallation
Setting
Modbus
Register
(dec)
557
558
714
723
Lead Lag Slave
Configuration
Lead lag slave enableServiceDisabled544
750-382
CBT
4-15
Commissioning
TABLE 4- 1.
Parameter GroupParameter NameAccessMin.
Lead Lag Slave
Configuration
Lead Lag Slave
Configuration
Lead Lag Slave
Configuration
Lead Lag Slave
Configuration
Lead Lag Slave
Configuration
Lead Lag Slave
Configuration
CB Falcon factory parameter settings - Model CBT-M (Continued)
Range
Slave modeServiceEqualize runtime564
Base load rateService3000rpmRPM566
Fan during off cycle
rate
Slave sequence orderService01 to 8568
Lead lag slave
demand to firing
delay
Modbus addressService11 to 8568
Service0rpm0rpm4000rpmRPM567
Service3m 0smmm ss570
Default SettingMax.
Range
Parameter UnitsInstallation
Changing parameter settings
To access the CB Falcon configuration menu, press <Configure> on the Status page.
From the Configuration menu (Figure 4-6), select the parameter group to be changed.
Setting
Modbus
Register
(dec)
FIGURE 4-10. Configuration menu
Some parameters require a password entry before allowing changes. The <Login> button will appear when any
password-protected parameter is displayed on the screen.
Press <Login> to display the alphanumeric keyboard. Enter password and press <OK>
Change parameter settings by selecting the parameter on the page. A dialog box appears with controls allowing
the user to change the selected value. Press <Clear> to clear the current value. Enter the new value and press
<OK> (press <Cancel> to leave the parameter unchanged).
4-16
750-382
CBT
Full modulation boilers
FIGURE 4-11. Parameter change dialog
Safety parameters
When configuring safety parameters an additional verification step is required to confirm the changes.
1. When a safety parameter is changed, the Safety Parameter Verification page will appear. Press <Begin> to continue.
2. The affected parameter group will be displayed, showing current parameter values and a prompt, “Are these parameters
set to proper values?”. Press <Yes> to continue.
3. The screen will indicate RESET DEVICE NOW. Open the control panel and press the RESET button on the CB Falcon
controller (press and hold for 3 seconds).
RESET must be pressed within 30 seconds to save changes.
Note: When changing multiple safety parameters, the verification steps do not need to be completed immediately.
See Appendix for complete instructions on using the CB Falcon Display/Interface.
4.1.9 — Program module
CB Falcon parameter information (non-safety parameters only) can be uploaded/
downloaded using the optional Program Module. When the Program Module is
installed, its features are accessible from the Falcon Setup page. See Appendices
for instructions.
4.1.10 — Burner sequence
In addition to providing modulation control, the CB Falcon is responsible for flame
supervision and burner sequencing.
The CBT boiler uses direct spark ignition (no pilot) to light the main flame. Flame
FIGURE 4-12. Program module
sensing is accomplished using an ultraviolet (UV) flame detector.
Basic burner sequencing:
1. Heat request detected (Setpoint minus On Hysteresis); LCI limits and steam demand detected (terminals J6 3 and J8 3).
2. After a system Safe Start Check, the Blower (combustion air fan) is started
3. After the ILK input is energized - 10 sec. allowed for IAS input (combustion air proving) to energize - and the purge rate
proving fan RPM is achieved, prepurge time is started.
4. When 30 sec. purge time is complete, the fan RPM is changed to the lightoff speed.
5. As soon as the fan-rpm is equal to the light-off RPM, the Trial for Ignition or Pre-Ignition Time is started (depending on
configuration). If enabled, Pre-Ignition Time will energize the ignitor and check for flame prior to TFI.
6. Trial for Ignition (4 sec).
7. The ignitor and the gas valve are energized.
750-382
CBT
4-17
Commissioning
8. The ignitor is turned off at the end of the direct burner ignition period.
9. The fan is kept at the lightoff rate during the stabilization time.
10.Release to modulation.
11.At the end of the heat request the burner is switched off and the fan stays on until post purge is complete.
4.1.11 — Fan speed settings
The boiler firing rate is determined by the combustion air fan speed. Accordingly, fan speed settings may have
to be modified for the particular application, for high altitudes, or when using direct vent combustion. The table
below provides the default fan speed settings in typical applications for the various boiler sizes. To allow safe
modulation through the firing range, these parameters should be initially set to the recommended speeds.
Please contact your authorized Cleaver-Brooks representative for proper settings in high altitude and direct vent
combustion applications.
TABLE 4- 2. Fan Speed Settings RPM
Natural GasPropane
HPMax - High Fire Min - Low FireIgnitionHPMax - High Fire Min - Low FireIgnition
1056001300220010520011002200
1553001300220015490012002200
2053001300200020460011002000
2554001200200025500013002000
3060001100180030570012001800
4.1.12 — Initial startup procedure
Warning
!
Before initial startup, check for blockages in the flue venting or vent
terminations. Inspect the burner and furnace for any contamination
or blockages.
4.1.13 — Gas train and piping
The burner is equipped with a combination servo-regulated gas valve and venturi mixing unit. The gas valve
consists of a single body with dual solenoid shut off valves, filter screen, and a built-in constant pressure gas/
air servo controller. The blower speed is controlled by the CB Falcon with airflow directly proportional to the
speed of the fan. The airflow creates a drop in pressure due to the venturi effect. The modulating controller of
the valve actuator senses air pressure change and brings about a change in the gas flow proportional to the air
flow. The gas follows the airflow in a set ratio, so that fuel always matches the air as the burner firing rate
increases or decreases.
1. Check the gas delivery system to be sure it is properly piped and wired.
2. Review available gas pressure to assure it is compatible with the main
gas regulators upstream of the Model CBT gas train. Note: The
maximum rated inlet pressure to the CBT gas train is 1 psig (28" WC).
An upstream regulator and overpressure protection are required if
Note: To measure supply pressure
at the CBT gas valve, use the
test port on the valve inlet
flange. Do not use the leak
test cocks to measure gas
pressure.
building supply gas pressure is greater than 1 psig.
3. To bleed air from the supply pipe, open the manual gas shut off valve upstream of the burner gas train and
bleed air from the piping by loosening the union in the upstream piping or opening the inlet gas test cock.
4-18
750-382
CBT
Full modulation boilers
4. The burner and its gas connection must be leak tested before placing the boiler into operation.
5. Gas Pressure Regulator - Using the adjusting screw on the main gas regulator, adjust the inlet pressure to the
recommended levels in Table 4-3.
TABLE 4- 3. CBT Gas Pressure Requirements
CBT SizeNatural GasLP Gas
Min (“WC)Max (“WC)*Min (“WC)Max (“WC)*
107.01411.014
157.01411.014
207.01411.014
257.01411.014
308.01411.014
*Maximum pressure without the use of an upstream regulator.
FIGURE 4-13. Premix burner technology - full modulation
4.1.14 — Power-up
1. Ensure blower motor is properly wired for the available power supply.
2. Verify the voltage (control voltage is 115V-1Ph.-50/60Hz) to ensure it is within specifications.
3. To power the control and blower circuits, the CC-Blower switch to the “ON” position.
4. When the control and blower circuits are powered, commissioning may begin. Turn the Demand switch to
the “LOC” (Local) position. On the Operation page, the Demand status should indicate “Steam”. The boiler
will now start if the LCI and ILK circuits are satisfied and the steam pressure is below the current On point.
750-382
CBT
4-19
Commissioning
4.1.15 — Operation check: gas valve, gas pressure switches, and combustion air proving switch
Before initial firing of the burner, the gas valve, Low Gas Pressure Switch (LGPS), High Gas Pressure Switch
(HGPS), and Combustion Air Proving Switch (CAPS) should be checked for proper operation.
• Before proceeding, review Section 4.3 - Control setpoints for initial LGPS, HGPS, and CAPS settings.
Note: Close the downstream manual gas shut-off valve before checking pressure switches and CAPS.
While performing the following safety checks, use the CB Falcon Annunciation screen to monitor the status of
the circuits involved. Press <Annunciation> on the Operation page to access this screen.
FIGURE 4-14. Annunciation screen
LGPS
1. To check the Low Gas Pressure Switch, first close the upstream manual shutoff valve (both manual shutoff
valves should now be closed).
2. Start the burner and wait 10 seconds during purge for CAPS to be made.
3. Turn the LGPS setting to maximum.
4. Open the test cock to bleed the gas line.
5. The controller should lock out. The screen will indicate Lockout 67 ILK OFF.
6. Reset the controller and change the LGPS setting back to minimum to proceed.
CAPS (Interrupted Airflow Switch)
1. Initiate burner sequence.
2. During purge cycle, set Combustion Air Proving Switch to its maximum setting.
3. The CB Falcon should lock out on an airflow failure. The display will show Lockout 65 Interrupted Airflow
Switch OFF.
Note: If the CAPS fails to open even when set to maximum, test by disconnecting the low-pressure line to the
switch and initiating burner sequence. The switch should now break during the purge cycle. Reconnect low-pressure side after a successful CAPS check.
4. Following a successful CAPS check, dial the CAPS back to its minimum setting and reset the CB Falcon.
Note: The CAPS is ignored when the boiler is in “Run” state. A CAPS test must be performed during Purge or
Trial for Ignition.
HGPS and GAS VALVE
1. Open the upstream manual shutoff valve and wait a few moments for gas pressure to rise.
4-20
750-382
CBT
Full modulation boilers
2. Lower the switch setting to minimum.
3. Initiate burner sequence. During the main flame establishing period, verify gas valve LEDs energize, indicating
both safety shutoff valves open.
4. The CB Falcon should lock out on an interlock failure (Lockout 67).
5. Reset CB Falcon.
6. Open the downstream manual shutoff valve to clear the lockout condition.
7. Dial the HGPS back to its maximum setting and reset.
IGNITION FAILURE CHECK
7. Close the downstream shut off valve and attempt to start the burner. The Falcon should lock out, indicating
Lockout 109 Ignition Failure.
After making the above operation checks, re-open the downstream manual shut-off valve.
4.1.16 — LWCO and ALWCO Check
• Before testing low water controls, disconnect power to the feed pump.
LWCO
1. To verify proper LWCO operation, conduct a blowdown of the water
column (refer to Chapter 5, Section 5.3 - Water Column Blowdown).
2. During WC blowdown, the burner should shut off when low water level
is reached.
3. Upon shutdown, check the LWCO control board in the CBT electrical
panel. The LED indicator should be off, indicating that the LWCO has
switched off the control circuit.
ALWCO
FIGURE 4-15. LWCO test
1. To check the ALWCO, drain the boiler (refer to Chapter 5, Section 5.2 - Blowdown).
2. Observe the ALWCO control board in the CBT electrical panel. When the ALWCO level is reached, the LED
indicator should go out.
3. Close the blowdown valves, refill boiler and reset the ALWCO.
• After testing the low water controls, reconnect power to the feed pump.
750-382
CBT
4-21
Commissioning
4.1.17 — Low and high fire adjustments
All CBT boilers are factory tested firing natural gas at an altitude of 1000
ft ASL. Operating under different conditions may require re-adjustment of
the gas valve.
Adjustments are made using a TORX® T40 (low fire adjustment) and 3
mm hex wrench (main gas choke). The adjustment screws should initially
be set to half way through each setting’s range. The low fire adjustment
screw is accessed by removing the slotted cap on the gas regulator using
a blade screwdriver (see Figure 4-12). The high fire adjustment screw is
accessed by removing the blue plastic cap from the valve cover (see
Figure 4-13).
Turn the adjustment screw completely clockwise, counting the turns until
the screw will no longer turn. Then, turn the adjustment screw
counterclockwise half the number of turns counted when turning
FIGURE 4-16. Regulating adjusting
screw - low fire offset
clockwise.
NOTE:When adjusting low fire offset, clockwise adjustments increase gas flow, and counterclockwise
adjustments decrease gas flow.
When adjusting the main gas choke, clockwise adjustments decrease gas flow, and counterclockwise
adjustments increase gas flow.
Refer to Appendix A for further information on gas valve setup, operation, and
testing.
4.1.18 — Modulation OFF point
Prior to setting combustion, the steam pressure off hysteresis point should be
adjusted upward to avoid nuisance shutdowns while the burner is under
manual control. This parameter is located under Steam Configuration.
NOTE: Install the combustion analyzer probe as close as possible to the boiler
vent connection. Sampling too far from the boiler vent can produce false
readings due to air leakage diluting the flue gas.
FIGURE 4-17. Main gas choke -
high fire adjustment
4.1.19 — Setting Combustion
Note: A Combustion Analyzer is required to properly set-up the Model CBT burner. Do not attempt to fire and
adjust the burner without this equipment.
Note: Ensure boiler is filled with water prior to burner startup.
The burner does not have need of linkages for fuel/air adjustment, nor is a separate manual-auto switch
provided for burner positioning. All firing rate adjustments are accomplished via the CB Falcon Control. Setting
combustion will require manually modulating the burner via the CB Falcon from low fire to high fire to ensure
a consistent air/fuel ratio.
To enable the burner, go to the Operation screen and press the <Burner switch> button at the upper left. Theburner will not operate if this button is in the “OFF” state.
4-22
750-382
CBT
Full modulation boilers
Manual Modulation - use the procedure below to change the burner firing rate manually.
1. On the CB Falcon Operation screen, press
the Firing rate display.
2. A numeric keypad will appear,
showing the current firing rate
and operating mode.*
3. Under Firing rate control select Manual in Run.
4. Press <Clear> to clear the current RPM value.
5. Enter the desired RPM setting using the numeric keypad (refer to
Table 4-2, Fan Speed Settings, for upper and lower limits).
6. Press <OK>. The display will return to the Operation screen and the
burner will modulate to the chosen firing rate.
*Use Manual in Run for normal manual operation. In Manual in Run and Standby mode, the
burner will not operate. Use this mode to run the blower without firing the boiler.
750-382
CBT
4-23
To set combustion:
Commissioning
FIGURE 4-18. Operation screen
1. Check inlet gas pressure and reset low gas pressure switch.
2. At Operation screen set firing rate to low fire. Review burner sequence before proceeding.
3. Turn Demand switch to LOCAL.
4. Initiate burner firing sequence. The burner switch is accessed via the CB Falcon Operation page (Figure 4-
15). If the burner does not ignite, adjust choke counterclockwise slightly until you can see a slight yellow
flame at the burner during ignition. Clockwise adjustments to the low-fire offset screw may also be tried.
Check that gas pressure to gas valve inlet is sufficient to fire burner (see Table 4-3 for gas pressure
requirements).
5. After burner lights, maintain in low fire position. At low fire, using main choke on gas valve and a
combustion analyzer set O2 level within 3-8% O2.
6. Manually modulate the burner to high fire. Adjust the gas choke if necessary to obtain desired O2% (6.0% -
7.0%).
7. Modulate to low fire and fine tune offset screw to obtain desired O2% (6.0% - 7.0%).
Verify adjustments by modulating back and forth between low and high fire.
While setting combustion observe gas pressure at low fire and at high fire. Ensure pressure is within limits
shown in Table 4-3.
4.1.20 — Limit Controls Check
The operating (OLC) and high pressure limit (HLC) controls are externally mounted to the control panel. The
setting of the OLC should be slightly higher than the configured set point plus the hysteresis off value set in the
CB Falcon control. The setting of the HLC should be slightly higher than the OLC. For example:
CB Falcon set point = 100.0 psig, Hysteresis Off = 5.0 psi
OLC could be set to 110 psig, HLC set to 120 psig
Specific settings are determined by application and system control scheme.
4-24
750-382
CBT
On/off boilers
The OLC and HLC can be tested while the boiler is producing steam by adjusting the switch setting downward.
A lockout should result when the switch setting is at or just below the current steam pressure.
Readjust each switch (and reset HLC) after testing.
4.2 — On/off boilers
Follow steps 4.1.1 through 4.1.4 above to prepare for startup.
4.2.1 — Ignition adjustment
Normal setting is 0.5" W.C. when the burner is on. The flame must be sufficient to be proven by the flame detector and ignite the main flame.
Although it is possible to visually adjust the size of the minimum flame, the recommended method is to obtain a
proper DC volt or microamp reading of the flame signal. Refer to burner control instructions for optimal flame signal readings.
4.2.2 — Gas Adjustments
Low fire combustion analysis typically is 7% to 9% O2 and less than .04% CO (400 ppm). A high fire reading
typically is 3% to 4% O2 and less than .04% CO.
4.2.3 — Electrical interference test
Prior to putting the burner into service, conduct the following test to ascertain that main power will not cause the
flame relay to pull in.
1. Close the manual gas valves.
2. Start the burner, the flame relay should not pull in (be energized).
3. Upon completion of successful test, proceed with startup procedures.
4. Reconnect the power supply and proceed with startup procedures.
4.3 — Boil-out of a new unit
The inside of a new boiler may contain oil, grease, or other contaminants which, if not removed, could adversely
affect system performance. New units should be cleaned by boil-out before use.
Recommended boil-out procedure is as follows:
1. Determine boiler water capacity (see Table 4-4). Have sufficient cleaning material on hand to complete the
job.
2. When dissolving dry chemicals, slowly introduce the chemical into warm water in a suitable container. Stir
constantly until the chemical is completely dissolved.
3. An over-flow pipe should be attached to one of the top boiler openings and routed to a safe point of
discharge. A relief or safety valve tapping is normally used for this purpose.
4. Water relief valves and steam safety valves must be removed before adding the boilout solution to avoid
contaminating the valves. Use caution when removing and reinstalling these devices.
750-382
CBT
4-25
Commissioning
5. All valves in the piping leading to or from the system must be closed to prevent cleaning solution from
getting into the system.
6. Fill the boiler vessel with enough clean water to cover the furnace. Add the cleaning solution, then fill to the
top. The water used in the initial fill should be at ambient temperature.
7. Fire the boiler intermittently so as to hold solution just at the boiling point. Boil for at least five hours. Do not
produce steam pressure.
8. Allow a small amount of fresh water into the boiler. This will create a slight overflow that will carry off
surface impurities.
9. Continue the boil and overflow process until the water clears. Shut the burner down.
o
10. Let the boiler cool to 120
F or less.
11. Drain the boiler, remove hand-hole plates and wash the waterside surfaces thoroughly using a high pressure
hose.
12. Inspect the surfaces. If they are not clean, repeat boil-out procedure.
13. After closing the handholes and reinstalling safety or relief valves, fill the boiler and fire it until the water is
heated to at least 180
TABLE 4- 4. Boiler water capacity
Boiler HP1015202530
Normal volume (gal)150#5555113113180
Flooded volume (gal)150#8080168203248
o
F to drive off any dissolved gases.
15#5757115115184
15#8282171206252
4.4 — Post start-up checkout procedure
1. Set high gas pressure switch to 50% higher than operating gas pressure at low fire. Set low gas pressure
switch to 50% lower than operating gas pressure at low fire.
2. Check the draft on the outlet stack on each boiler, compare to acceptable limits (-.25 to +.25“ W.C.) and
record in start up form. Operating outside of acceptable limits could result in light off and flame failure
problems.
3. Switch to automatic operation and monitor flue gas to ensure consistent excess air.
4. Reassemble all panels and covers that were removed and replace any plugs that were removed to check gas
pressure.
5. Verify gas pressures remain within limits shown in Table 4-3.
6. Provide instructions to owner and operators on operation, safety and maintenance of the equipment.
7. Provide instructions to owner and operators on proper water treatment guidelines and procedures.
4-26
750-382
CBT
Falcon control functions and customer interface
4.5 — Falcon control functions and customer interface
Following is a brief overview of the Falcon control features on steam boilers. Please refer to the Falcon Control
operating instructions in Appendix A for more detailed explanations.
• Set Point
• Time-of-Day (TOD) Set Point
• Hysteresis On and Hysteresis Off
• PID modulation control
• Remote Enable and Remote 4-20mA Input
• Remote Modulation
• Remote Set Point
• Configurable pump/auxiliary relay contacts
• Annunciator
• Diagnostics
• Lockout/Alarm History
• Trend Analysis
• Modbus communications
Set point, TOD set point, hysteresis on, hysteresis off, and PID load control
The set point is the value that the boiler’s PID load control attempts to maintain in order to meet the steam
demand. The modulating set point can be adjusted at the Operation page or under the Steam Configuration
parameter group. No password is required to change the set point. To change the set point at the Operation
page, press the set point value next to “Normal”. Clear the current value and enter the new value. Press <OK>
to establish the new set point.
The Time-of-Day (TOD), or setback, set point is an alternative set point that is enabled when a remote contact
connected to terminals J10-2 & J10-3 is closed (Refer to Figure 2-8 CBT Wiring Diagram). When the circuit is
open, the boiler control reverts back to the normal set point. The TOD set point can be adjusted at either the
Operation page or under the Steam Configuration parameter group. Service level password login is required to
change this parameter.
The hysteresis on and hysteresis off points can only be changed under the Steam Configuration parameter group
and require a login with the Service level password. Hysteresis on is the differential below the current set point
at which the boiler will restart following an off cycle. Hysteresis off is the differential above the current set point
at which the boiler will cycle off – effectively the boiler’s operating limit. These two parameters apply to both
the normal and TOD set points. To minimize the frequency of cycling the boiler on and off, the values of either,
or both, of these settings may be increased. Default settings for Hysteresis on and off are 0 and 3 psi,
respectively.
The PID (Proportional-Integral-Derivative) load control operates to generate the demand source’s modulation
rate. Under Steam configuration, the PID gain values can be adjusted to match the desired modulation
response. The default gain value settings of P=50, I=50 & D=0 have proven to work well with typical steam
boiler applications.
750-382
CBT
4-27
Commissioning
Remote enable and remote 4-20mA input
Remote enable and Remote 4-20mA input allow the boiler to be sequenced and/or controlled from a separate
boiler room controller or building management system. The 3-position Demand switch at the front of the control
panel determines whether the boiler is off, in local, or under remote control. When in the “LOC” (local) position,
the boiler operates on its own set point and ignores any remote signal connections. When in the “REM” (remote)
position, the boiler can be enabled and modulated by remote discrete and analog (4-20mA) inputs, respectively.
When in the “OFF” position, the boiler will not operate.
Refer to Figures 2-7 & 2-8, or your specific boiler wiring diagram, for remote enable and remote 4-20mA input
connections. For simple remote on-off sequencing, only terminals 24 and 25 (Falcon J8-1 & J8-3) need to be
connected to dry enable contacts at the remote controller. When terminal 25 (steam demand input) is
energized, the steam demand is enabled. The boiler operates on its local set point and PID modulating control
settings.
For remote modulation (firing rate) control, both the remote enable and remote 4-20mA input connections must
be made. The default setting for the 4-20mA remote input is “Modulation”. This setting should be verified under
the Falcon control’s Steam configuration group, “Steam 4-20mA remote control”. To avoid nuisance operating
limit shut downs of the boiler, the Falcon’s normal operating set point should be adjusted to a value that is
greater than the system header set point.
With steam demand present and completion of a successful trial for ignition sequence, the boiler will modulate
according to the 4-20mA input signal provided: 4mA = minimum modulation rate (low fire); 20mA =
maximum modulation rate (high fire). The boiler will continue to modulate until the steam demand is removed,
the operating limit is reached, LCI is opened (e.g. low water condition), or a Falcon lockout alarm occurs (e.g.
ILK opens on a High Limit trip).
To configure the boiler for remote set point control, navigate to the Falcon control’s Steam configuration group.
Change the setting of “Steam 4-20mA remote control” to “Set Point”. Next, the span of the 4-20mA needs to
be established. The steam set point determines the value for 20mA; “minimum steam pressure” determines
the value for 4mA.
Depending on the quality of the remote input signal, the modulation rate or operating set point may fluctuate
unnecessarily because of small changes in the measured current signal. Under the Modulation configuration
group, the “4-20mA input Hysteresis” setting may need to be adjusted to avoid undesired fluctuations in the
either the modulation rate or operating set point. The default setting is 0.1mA and can be increased to
essentially filter out small fluctuations of the input signal. It may take some trial and error to establish the
optimum input hysteresis setting for a particular system.
If at any time the remote 4-20mA input signal is disconnected, the Falcon control will indicate “OPEN” under
the 4-20mA input value at the operation screen. The boiler will then operate on its local set point and PID
modulation control. Once the 4-20mA signal is reestablished, the boiler will resume operation under remote
control.
4-28
750-382
CBT
CHAPTER 5Maintenance
General 5-2
Bottom blowdown 5-2
Water column blowdown 5-3
Fireside cleaning procedure/disassembly 5-5
Ignition electrode 5-7
UV scanner (full modulation only) 5-8
Waterside inspection/cleaning 5-10
Safety valve 5-11
Troubleshooting 5-11
Display diagnostics 5-27
Lay-up 5-27
750-382
CBT
5-1
Maintenance
5.1 — General
A well-planned maintenance program will help avoid unnecessary downtime or costly repairs, and will promote
safety and aid boiler inspectors. It is recommended that a boiler room log or record be maintained. Recording of
daily, weekly, monthly, and yearly maintenance activities will help to obtain economical and lengthy service from
the equipment.
Only trained and authorized personnel should be permitted to operate, adjust, or repair the boiler and related
equipment. The boiler room should be kept free of all material and equipment not necessary to the operation of
the boiler or heating system.
Be alert to unusual noises, improper gauge readings, leaks, etc. Any leaks - fuel, water, steam, exhaust gas should be repaired promptly and with attention to safety. Preventive measures, such as regularly checking the
tightness of connections, should be included in regular maintenance activities.
Insurance regulations and local laws normally require periodic inspection of the pressure vessel by an authorized
inspector. Inspections are usually, though not necessarily, scheduled for periods of normal boiler downtime, such
as an off season. This period can be used to accomplish maintenance, replacement, or repairs that cannot easily
be done at other times.
NOTE: To insure proper operation, use only Cleaver-Brooks parts for replacement.
While the inspection pertains primarily to the waterside and fireside surfaces of the pressure vessel, the inspection
period provides operators with an opportunity for a detailed check of all boiler components including piping,
valves, gaskets, refractory, etc. Comprehensive cleaning, spot painting, and replacement of expendable items
should be planned for and taken care of during this time.
Cleaver-Brooks recommends common replacement parts be on hand during inspection and maintenance. Please
refer to the Recommended Spare Parts List In the Parts section of this manual.
5.2 — Bottom blowdown
FIGURE 5-1. Bottom blowdown piping
Water treatment alone can never completely eliminate unwanted solids from boiler feedwater. In order to keep
these substances to a minimum, blowdown should be performed at regular intervals.
If both a quick-opening and a slow-opening valve are present, the quick-opening valve (the valve nearest the
boiler) is opened first and closed last, with blowdown controlled using the slow-opening or downstream valve.
Bottom blowdown should be done under a light load and with the water level at the normal operating level.
Blowdown should be piped to a blowdown separator.
5-2
750-382
CBT
Water column blowdown
Caution
!
• Never pump the quick-opening valve to blow down the boiler. Such action could cause water hammer and damage the
piping and valves. It could also cause personal injury.
• Never leave an open blowdown valve unattended.
• Remember the valve closest to the boiler must be opened first.
• Blowdown should be done at least once per shift. Depending on operations, more frequent blowdowns may be required.
Manual blowdown procedure
Blowdown is most effective when the boiler is under a light load, and when the water level is at the Normal Operating
Water Level.
Be sure the blowdown piping is in proper operating condition. Waste should be piped to a point of safe discharge. To blow
down the boiler:
1. Open the quick-opening valve (one closest to the boiler).
2. Open the slow-opening valve.
3. Blow down the boiler for the amount of time specified by your water treatment consultant by opening and
closing the slow-opening valve. A minimum of 10 seconds with the valve fully open is recommended.
4. Some boilers may require several short blowdown cycles to maintain the proper water level.
5. Close the slow-opening valve.
6. Close the quick-opening valve.
7. Open the slow-opening valve again to drain the line between the quick and slow-opening valves.
8. Close the slow-opening valve again and double check that the shutoff is tight after the valve has cooled.
It is generally recommended that bottom blowdown be performed at least once in every eight-hour period. Actual
frequency may vary depending on water conditions and boiler operating conditions. Consult the appropriate water
treatment personnel regarding blowdown scheduling.
5.3 — Water column blowdown
Free flow of water through the water column and gauge glass is essential to obtaining accurate boiler water level
indication and control. It is recommended that the water column and gauge glass be blown down every shift to
remove accumulated solids. Regular blowdown of the water column will help maintain the integrity of the water
level probes and will help to ensure trouble-free operation of the boiler. See Figure 5-2 for procedure.
750-382
CBT
5-3
Maintenance
Open
Open
Closed
2
1
1. Open Water Column blowdown valve (5 to
10 sec.) to discharge water from WC.
2. Close WC blowdown valve.
6
3
4
3. Close upper gauge glass isolation valve.
4. Open gauge glass blowdown valve to
discharge water from gauge glass.
5
7
8
5. Close lower gauge glass isolation valve.
6. Open upper gauge glass isolation valve.
7. Open lower gauge glass isolation valve
to discharge steam from gauge glass.
FIGURE 5-2. Water column and gauge glass blowdown
8. Close gauge glass blowdown
valve.
Periodic replacement of the water gauge glass should be part of a regular maintenance program. A broken or
discolored glass should be replaced at once.
Use a proper size rubber packing. Do not use loose packing, which could be forced below the glass and possibly
plug the valve opening.
5-4
750-382
CBT
Fireside cleaning procedure/disassembly
Close the valves when replacing the glass. Slip a packing nut, packing washer, and packing ring onto each end of
the glass. Insert one end of the glass into the upper gauge valve body far enough to allow the lower end to be
dropped into the lower body. Slide the packing nuts onto each valve and tighten.
It is recommended that the boiler is off and cool when the glass is replaced. However, if the glass is replaced while
the boiler is in service, open the blowdown valve and slowly bring the glass up to temperature by opening the
gauge valves slightly. After the glass is warmed up, close the blowdown valve and open the gauge valves
completely.
5.4 — Fireside cleaning procedure/disassembly
1. Locate the manual shutoff gas valve for the gas supply to the burner and turn it to the closed or shut position.
2. Disconnect all electrical power to the control panel at the primary switch box or breaker box supplying power
to the boiler.
4. Disconnect power and signal harnesses from blower.
5. Disconnect the ignition cables from the electrodes and unscrew the UV flame detector from its bracket.
6. If using room combustion air, remove air filter. Inspect and replace as necessary.
7. Disconnect the burner gas train from the gas supply piping.
8. Unscrew the nuts (4) securing the blower adapter plate to the dry oven assembly.
9. The blower motor and assembly can now be removed, providing access to the burner head and combustion
chamber. The following inspections can now be performed:
• Check ignition electrodes for deposits and proper gap. Clean or replace as required.
• Check the burner canister for any damage, burn marks, or perforations. Replace if damaged. If the canister is
in good condition, clean out any dirt or dust with a vacuum cleaner or low-pressure air hose.
• Inspect the dry oven/combustion chamber area for any damage or residue. If dirt or contaminants are found, it
is recommended that the fire side be washed with a high-pressure power washer.
If any adverse conditions are observed during operation or inspection, contact your authorized Cleaver-Brooks
service representative.
When inspection and servicing are completed, reassemble the burner in reverse order.
Ensure that all connections are tight and secure before reconnecting power or fuel supply. After turning the gas
supply on, reset the gas pressure switches.
NOTE: A gas valve leak test is recommended during fireside
inspection. See Appendix A for leak test procedure.
750-382
CBT
5-5
Maintenance
DRY OVEN
SIGHT
GLASS
BURNER CAN
GASKET
BURNER
BURNER CAN
GASKET
CANISTER
ADAPTER PLATE
ADAPTER PLATE GASKET
UV SCANNER
IGNITION
ELECTRODE
VENTURI
FIGURE 5-3. Burner assembly - full modulation
BLOWER UNIT
ELECTRODE
SPRING PIN
ORIFICE PLATE
LOCK WASHER
FLAME ROD
FIGURE 5-4. Burner assembly - on/off
STANDOFF
BAFFLE WELDMENT
LOCK WASHER
SCREW
5-6
750-382
CBT
Ignition electrode
5.5 — Ignition electrode
5.5.1 — Full modulation burners
Caution
!
The dimensions on the Ignition Electrode are not easily adjustable.
Bending the rods can cause damage to the insulating material. In addition, a bent
electrode will have a tendency to return to its original shape when heated. If the
electrode is out of specification, replacement is generally recommended.
The ignition electrode should be checked on an annual basis or as needed if ignition problems are encountered.
In order to verify spacing of electrode, center the burner cylinder within the dry oven. Then attach electrode to
the dry oven with the screws provided. Verify the dimensions shown in Figure 5-5.
Sight glass
Flame scanner
Ignition electrode
0.64 GAP
FIGURE 5-5. Igniter, full modulation burner
5.5.2 — On/off burners
The ignition transformer requires little attention other than making sure the ignition wire is firmly attached to the
transformer and the electrode. Be sure the wire insulation is in good condition and not grounded. Failure to keep
the ignition electrode clean and properly set can cause faulty operation. The electrode assembly is supported by
a socket in the diffuser and gas inlet tube. No adjustment is required except proper positioning of the electrode
wire.
750-382
CBT
5-7
COVER
FLAME ROD
Maintenance
0.25 - 0.125
ORIFICE PLATE
FLAME ROD
BAFFLE PLATE
ORIFICE PLATE
ELECTRODE
FIGURE 5-6. Ignition electrode and flame rod, on/off burners
BAFFLE PLATE
ELECTRODE
(TIP IS FLUSH WITH
FACE OF BAFFLE PLATE)
.16
ORIFICE PLATE
BAFFLE PLATE
ELECTRODE
5.6 — UV scanner (full modulation only)
Maintenance of the UV scanner consists of periodic inspection and cleaning. To inspect, unscrew the UV flame
detector from the bracket. Check to ensure that the flame viewing lens is clear and free of dust or debris. Wipe
with a clean rag if necessary.
To function properly, the scanner needs a clear line of sight to the burner canister. Welding slag or other debris,
an out-of-place gasket, or the boiler refractory dry oven can all potentially obstruct the scanner. To verify a line
of sight, unscrew the UV scanner from the mounting bracket and ensure that it is possible to sight through the
bracket to the burner can without obstruction (Figure 5-7).
Figure 5-8 shows the UV scanner wiring connections.
5-8
750-382
CBT
UV scanner (full modulation only)
FIGURE 5-7. UV Scanner
832-2326
FIGURE 5-8. Scanner Wiring
750-382
CBT
5-9
Maintenance
5.7 — Waterside inspection/cleaning
Waterside inspection frequency may depend upon the local jurisdiction and
inspector but it is recommended that a waterside inspection take place 2-3
months after initial startup.
C-B further recommends to semiannually remove all handhole covers and
thoroughly clean the water side cavity and bottom of the boiler.
To inspect the boiler on the waterside, first shut off the electric power to the
burner. Close all waterside stop and shutoff valves, including the steam stop valve
or valves. Close the manual gas shutoff valve. After allowing the boiler to cool,
open the bottom blowdown valve, crack the manual bleed valve (Figure 5-9), and
drain the boiler. While the boiler is draining, note the condition of the water.
When the water has drained from the boiler, remove the handhole covers and
examine the waterside surfaces. Use a good flashlight and, where necessary, a
swivel mirror with an extension. Discuss any scale, sludge or other buildup on the surfaces with the water
treatment company or technician.
FIGURE 5-9. Manual bleed valve
FIGURE 5-10. Inspection port (handhole) locations
On the water column piping, remove the plugs, remove all probes, and inspect. Clean as necessary, being sure
to remove any debris or blockages.
Important
!
Clean probes are essential to proper boiler operation. Always
ensure that probes remain free of debris and buildup.
If a waterside sludge buildup is noticed, flush the waterside and drain. Again, consult with the water treatment
company or technician on cleaning. After inspection, install new gaskets, close the handholes, replace probes,
tighten plugs, and allow water to fill the boiler while keeping the bleed valve open. Close valve before placing
boiler back into operation.
5-10
750-382
CBT
Safety valve
5.8 — Safety valve
The safety valve is an important safety device and deserves attention accordingly. Follow the recommendations of
your boiler inspector regarding valve inspection and testing. The frequency of testing, either by use of the lifting
lever or by raising the steam pressure, should be based on the recommendation of your boiler inspector and/or the
valve manufacturer, and should be in accordance with Sections VI and VII of the ASME Boiler and Pressure Vessel
Code.
FIGURE 5-11. Safety valve
Avoid excessive operation of the safety valve; a valve that is opened too frequently can develop leaks. Safety valves
should be operated only often enough to assure that they are in good working order. When a pop test is required,
raise the operating pressure to the set pressure of the valve, allowing it to open and reseat as it would in normal
service.
Do not hand operate the valve with less than 75% of the stamped set pressure on the underside of the disc. When
hand operating, be sure to hold the valve in an open position long enough to purge accumulated foreign material
from the seat area and then allow the valve to snap shut.
5.9 — Troubleshooting
The Falcon lockout and alert histories (full modulation units) contain information which can help in determining
the cause of problems. To view the lockout/alert history, first press the alarm banner, then press the appropriate
button in the pop-up window.
View
history
750-382
CBT
Alarm
banner
5-11
Maintenance
The alert (or lockout) list will appear, showing date and time for each item. Pressing an individual item in the list
will display additional information. Diagnostic information available for lockouts includes annunciator status,
states of system inputs, and steam pressure at time of lockout.
The Falcon display touch-screen interface is a valuable tool to help identify and resolve conditions that prevent
normal and safe operation of the boiler. The focus of this section is to help the boiler operator utilize the Falcon
display interface to evaluate and correct conditions that can cause nuisance shutdowns and contribute to unsafe
operation of the boiler.
There are 3 levels of “alarm” conditions utilized by the Falcon controller: Lockout, Hold, and Alert. Lockouts and
Holds indicate interruptions in boiler operation, whether occurring as part of the normal operating sequence or
due to an abnormal condition. Lockouts always require a manual reset to resume operation, while Holds will
automatically resume when the hold condition is removed or satisfied. Alerts indicate conditions or events
which, while not preventing normal boiler operation, may be of interest in evaluating boiler operating conditions.
Alerts require no operator acknowledgment and are for informational purposes only.
A Lockout will result in boiler shut down and always requires a manual reset of the Falcon controller. In certain
cases, a lockout may also require a manual reset of a safety control interlock device connected to the Falcon.
These include the auxiliary low water cut-off, high limit control, and gas pressure limit controls. Typically, a
safety interlock can only be reset when the condition that caused the lockout has been corrected (i.e. water level
returns to normal allowing the auxiliary low water cut-off to be reset).
Lockouts, Holds, and Alerts will often provide clues to the cause of the interruption or abnormal condition that
generated the message. However, sometimes these messages can be misleading and may not point directly to
the actual cause of the condition. A careful reading of this chapter, the rest of the manual, and the boiler specific
wiring diagram will help in resolving boiler interruptions and abnormal conditions.
The key to diagnosing recurring nuisance interruptions is to identify the underlying cause of the condition that led
to the interruption. Once the underlying cause is identified a permanent solution can implemented. Too often,
safety controls are reset without proper analysis of the operating condition that caused the boiler operation interruption. If not adequately addressed, the interruptions tend to be repeated with increasing frequency resulting in
down time and increased maintenance. Merely resetting a safety control device does not resolve the cause of the
condition that led to the lockout!
The following chart takes a methodical approach to diagnosing abnormal boiler operating conditions. This
approach begins with the “Problem” as identified by the operator. The 2nd column indicates displayed messages
(“Display Message”) by the Falcon display interface that will generally provide clues to the cause of the problem.
The 3rd column lists “Possible Causes” and/or related “Symptoms” associated with the “Problem” and “Displayed Message”. The 4th column recommends a “Diagnostic Check” that should be investigated for a potential
cause or system. The last column provides recommendation for “Corrective Measures” to resolve the problem
and return to normal operation.
This chart includes the most common conditions and resolutions for successful ClearFire boiler operation. It does
not include all possible lockouts and alerts. The Falcon controller appendix has a comprehensive list of lockouts,
holds, and alerts. The boiler operator can use this format and method to diagnose other conditions that may not
be included here.
5-12
750-382
CBT
Troubleshooting
TABLE 5- 1. CBT troubleshooting
ProblemDisplay MessagePossible Cause/Symp-
tom
Boiler will not start -no lockout or alarm
present
A. Hold 63 LCI OffA.1. Touch Screen
“Demand” status is in
OFF position
A.2. Auxiliary device
(e.g. OLC) is interrupting LCI circuit.
A.3. Start interlock
proving switch is not
closed (when using
start interlock)
A.4. Jumper is not
wired between start
interlock (typically terminals 13 & 14) terminals in LCI circuit -- no
start interlock connected
A.5. Loose wiring in
Falcon LCI circuit (line
18 on wiring diagram)
B. Hold 63 Low WaterB.1. Low water condi-
tion -- water level is
low in sight glass
Diagnostic CheckCorrective Measures
Check demand state
on Falcon boiler Status
screen
Check state of Operating Limit Control in LCI
circuit.
Check start interlock
device (e.g. air damper
switch) wired in ClearFire's LCI circuit
Check for jumper
between start interlock
terminals in control
panel -- refer to WD.
Check for 115VAC
power along LCI circuit up to Falcon controller terminal J6-3
Check that Feed Water
(FW) pump is running
and water is flowing to
boiler
Correct problem with
start interlock device
and/or wiring connections (e.g. ensure air
damper is open and
damper prove switch is
functioning properly)
Jumper start interlock
terminals if not using a
start interlock.
Secure wiring to appropriate terminal connection(s)
If FW pump is not running, see Possible
Cause B.2. FW pump
not running; if FW
pump is running, see
Possible Cause B.3.
FW pump is running
750-382
CBT
Check water level in
the feed tank
Check water flow to
boiler
If water level is low in
feed tank, check tank
make-up valve/piping
and fix problem
Open boiler feedwater
valve(s). Check/adjust
pump pressure relief
valve (if present).
Remove any unnecessary restrictions.
5-13
Maintenance
ProblemDisplay MessagePossible Cause/Symp-
tom
B.2. Feed Water (FW)
pump is not running,
water level is low
Diagnostic CheckCorrective Measures
Check blowdown valve
positions.
Check for power to FW
pump
Open boiler control
panel and check pump
relay LED ("H/L
RELAY") on the Warrick LLCO/Level control board
Manually enable pump
starter to "bump" pump
motor.
All blowdown valves
should be closed
during operation,
except during active
blowdown procedures. Close any blowdown valves that may
be open.
If no power present -connect power/replace
fuses as needed
If LED is off, see Possible Cause B.4. Water
Level Probe connections; if LED is on,
check pump control
wiring from boiler to
pump contactor/starter.
If pump motor does not
operate, repair or
replace pump and/or
motor.
B.3. Feed Water (FW)
pump is running, but
boiler water level is low
B.4. Water Level Probe
connections
Check water flow to
boiler
Listen for FW pump
cavitation noise and
check feed tank temperature
Check blowdown valve
positions.
Check pump seals and/
or impeller
For 3 phase power only
-- check pump rotation
Check Warrick board
connections in boiler
control panel
Open valves, remove
restrictions
If FW temperature is
greater than 180F,
check steam traps.
Service steam traps as
needed.
All blowdown valves
should be closed,
except during active
blowdown procedures. Close any blowdown valves that may
have been left open.
Service/replace FW
pump as needed.
If incorrect pump rotation, swap 2 of the 3
incoming 3-phase
power wire connections to pump starter/
contactor
Secure any loose connections
5-14
750-382
CBT
Troubleshooting
ProblemDisplay MessagePossible Cause/Symp-
tom
Diagnostic CheckCorrective Measures
Inspect high-temp
wire-to-probe connections in boiler water
column connection box
(Warrick)
Tighten jam nuts on
any loose probe connections.
If slight corrosion present, remove terminal
connection, clean
crimp-on ring terminal, re-crimp, and
replace with copper
flat washer between
ring terminal and jam
nut, tightening jam nut
to secure ring terminal.
Apply dielectric grease
to terminal connections.
If severe corrosion
present, cut-off crimpon ring terminal, strip
wire end, crimp-on
new high temperature,
SS ring terminal, reattach with copper flat
washer between ring
terminal and jam nut.
Apply dielectric grease
to terminal connections.
750-382
CBT
B.5. Dirty water level
probes
Check Warrick board
"dirty probe" LED. If off,
remove associated
probe wire from Warrick DF board and
check continuity
between probe and
panel ground.
If all connections
secure and clean, see
Possible Cause B.5.
Dirty water level
probes
If no continuity, remove
probe. Visually inspect
and clean or replace.
Secure all wiring connections and coat wire
terminal ring connection in probe head with
dielectric grease.
Check feed water treatment/softening. Perform water softening
and chemical treatment as necessary.
5-15
Maintenance
ProblemDisplay MessagePossible Cause/Symp-
tom
Boiler will not start -active lockout/alarm
C. Demand: Steam
Burner state: Standby
(normal)
D. Hold 100 Pressure
sensor fault
E. Hold 131 Fan
movement during
standby
F. Lockout 67 ILK OFF
AUX LOW WATER
C.1. Steam pressure is
greater than Falcon ON
point (SP - ON hysteresis)
Reset Falcon controller.
Check steam pressure
reading on Falcon display.
Check draft presure at
boiler flue outlet (+/-
0.25" w.c. allowed)
Check if blower is turning when not on (e.g.
high negative draft can
force blower to turn)
Check Auxiliary Low
Water Cut-off (ALWCO)
control LED located on
Warrick Single Function board (smaller circuit board) located
inside control panel.
Change steam Set
Point, On hysteresis,
and Off hysteresis
parameters to desired
settings.
If closed, carefully
open steam stop valve
to allow steam to flow
to the process. Also,
carefully blowdown
boiler to relieve steam
pressure.
If loose, open, or
shorted transmitter circuit, secure wiring connections
Replace steam pressure transmitter
Resolve draft condition (e.g. adjust stack
damper) to near neutral (0" w.c.)
Resolve draft condition (e.g. adjust stack
damper) to near neutral (0" w.c.)
If ALWCO control
board LED is off, reset
ALWCO switch. Clear
Falcon lockout and
restart.
5-16
750-382
CBT
Troubleshooting
ProblemDisplay MessagePossible Cause/Symp-
tom
Diagnostic CheckCorrective Measures
Check Auxiliary Low
Water Cut-off (ALWCO)
control LED inside control panel. Also observe
primary LWCO control
“LLCO” LED located on
Dual Function (DF-16,
larger circuit board)
located inside control
panel.
Check ALWCO board
wiring and probe connections
If LED remains off after
reset and LWCO
“LLCO” LED is ON,
perform water column
and boiler bottom
blowdown. Primary
LWCO (“LLCO” LED)
should go OFF during
blowdown. IF “LLCO”
LED REMAINS ON,
DISCONNECT POWER
TO FEED PUMP AND
CLOSE FEED WATER
VALVE IMMEDIATELY.
POTENTIAL LOW
WATER CONDITION
PRESENT AND MUST
BE RESOLVED!
Secure any loose connections. If corrosion
present, remove corrosion and/or replace terminal connection.
G. Lockout 67 ILK OFF
HIGH LIMIT
F.2. Low water condition -- water level is
low in the sight glass -see B. Hold 63 LCI Off
LOW WATER Display
Message, Possible
Causes, Checks, and
Corrective Measures
G.1. Steam pressure
exceeded High Limit
Control (HLC) set
point.
Observe steam pressure gauge reading and
compare to HLC setting (outside the control panel) and Falcon
OFF point.
Check position of
steam stop valve.
Observe steam pressure gauge reading.
Adjust HLC setting to
setting higher than
OLC setting and Falcon
OFF point. Reset HLC
after pressure drops
below setting. Clear
Falcon lockout and
restart.
If stop valve closed,
wait for pressure to
drop enough so steam
stop valve can be
opened safely. Reset
HLC after pressure
drops below setting.
Clear Falcon lockout
and restart.
750-382
CBT
5-17
Maintenance
ProblemDisplay MessagePossible Cause/Symp-
tom
H. Lockout 67 ILK OFF
LOW GAS PRESSURE
I. Lockout 67 ILK OFF
HIGH GAS PRESSURE
J. Lockout 65 Interrupted Airflow Switch
OFF
H.1. Insufficient gas
supply pressure or gas
valve closed
I.1. Manual gas shutoff valve (between gas
safety shut-off and
venturi) closed causing gas pressure spike.
J.1. Combustion Air
Proving Switch (CAPS)
is not closing when
blower starts during
purge
Diagnostic CheckCorrective Measures
Check gas supply pressure at boiler gas valve
inlet during trial for
ignition (refer to boiler
O&M commissioning
section for minimum
pressure required).
Check Low Gas Pressure Switch (LGPS)
setting -- should be
50% of gas supply
pressure required.
Check position of manual gas shut-off valve.
Check HGPS setting -setting should be
~150% of gas supply
pressure to boiler.
Check air switch
(CAPS) setting; on Falcon Annunciation
screen check "Interrupted Air Sw" status
during purge
Check air switch
(CAPS) pressure tubing
connections for tightness -- one is at blower
outlet, other is at
blower/venturi inlet
Check air switch
(CAPS) wiring connections -- white wire
should be connected to
COM and black wire to
NO terminal.
If all previous tests
pass and "Interrupted
Air Sw" status during
purge does not indicate
ON:
Confirm gas shut-off
valve is open. Increase
gas supply to boiler
room and/or boiler by
increasing pressure out
of regulator. Reset
LGPS. Clear lockout on
Falcon and restart.
Confirm gas shut-off
valve is open. Increase
gas supply to boiler
room and/or boiler by
increasing pressure out
of regulator. Reset
LGPS. Clear lockout on
Falcon and restart.
Open manual shut-off
valve between gas
safety shut-off valve
and venturi. Reset
High Gas Pressure
Switch (HGPS). Clear
Falcon lockout and
restart.
Adjust switch to appropriate setting. Reset
HGPS. Clear Falcon
lockout and restart.
Set CAPS to minimum
set point. Clear lockout and restart.
If loose, tighten pressure connections. Clear
lockout and restart.
If wrong or not secure,
correct and secure connections. Clear lockout
and restart.
Replace air switch
(CAPS)
5-18
750-382
CBT
Troubleshooting
ProblemDisplay MessagePossible Cause/Symp-
tom
J.2. Combustion Air
Blower does not run or
does not run to purge
speed (4000 RPM)
Observe Firing rate and
Fan speed on Falcon
status screen -- they
should closely agree
and read approximately 4000 RPM
during purge.
Open control panel
door. With volt meter,
check for 115 VAC on
both sides of blower
fuse and at control
panel blower terminal
(T1 on newer boilers;
T46 on older models).
Check that blower
cable/harnesses are
secure on both ends:
3-conductor power
cable to blower power
circuit and 4-conductor
signal cable to Falcon
J2 plug. If either is
found loose and subsequently secured, clear
lockout and restart.
If Fan speed does not
match Firing rate, see
next step.
If no power after
blower fuse, replace
blower fuse. Refer to
boiler wiring diagram
for correct fuse size
and type for the boiler.
Clear lockout and
restart.
If no power before
blower fuse, reset circuit breaker. Clear
lockout and restart.
750-382
CBT
K. Lockout 66 Interrupted Airflow Switch
ON
K.1. High negative
draft condition
With 115VAC power
connected to blower,
temporarily disconnect
4-conductor blower
signal cable from
blower or Falcon J2
plug. Blower should
run at full speed.
Check draft presure at
boiler flue outlet (+/-
0.25" w.c. allowed)
If measured voltage is
greater than 10V but
less than 104V, check
incoming power, neutral, and ground connections to boiler.
Resolve power wiring
as necessary.
If 115VAC power confirmed at blower connection and blower
does not run, contact
factory and/or replace
blower assembly.
Resolve draft condition (e.g. adjust stack
damper) to near neutral (0" w.c.)
5-19
Maintenance
ProblemDisplay MessagePossible Cause/Symp-
tom
K.2. Blower running
when boiler is off
K.3. Combustion Air
Proving switch (CAPS)
failure
Light-off problemsL. Lockout 109 Igni-
tion Failure
L.1. Gas supply - is
pressure too low at
boiler gas valve inlet
during trial for ignition
(refer to manual's commissioning section for
minimum gas supply
pressure requirement
and recommended gas
line sizing)
Diagnostic CheckCorrective Measures
Check if blower is turning when not on.
Check Firing rate and
Fan speed on Falcon
status screen
At Operation screen,
check Modulation Firing rate setting
Check switch connections and proper function of air switch.
Check for flame signal
on boiler status screen
(DC Volts)
Resolve draft condition (e.g. adjust stack
damper) to near neutral (0" w.c.)
If Firing rate indicates
0 or low RPM and Fan
speed is at a high
RPM, inspect/secure
blower signal cable
connections at both
ends. A disconnected
blower signal cable will
result in the blower
running at full speed.
If set to "Manual in
Run & Standby", set to
"Automatic" or "Manual in Run"
Correct/secure connections. Clear lockout
and restart. If CAPS
not functioning,
replace air switch.
Increase gas supply
pressure to boiler room
Increase gas supply
pipe size
5-20
L.2. Manual gas valve
located between gas
valve and venturi
closed
L.3. Gas safety shut-off
valve not opening
Check position of manual shut-off valves
Check gas valve indicator LED's during trial
for ignition
Adjust setting of boiler
gas regulator
Clear Lockout and try
again
Open Manual Gas
Valve
If LED(s) not energizing, secure gas valve
wiring connections.
Refer to boiler wiring
diagram. Ensure DIN
connector is secured to
gas valve.
750-382
CBT
Troubleshooting
ProblemDisplay MessagePossible Cause/Symp-
tom
L.4. Gas supply restriction -- improperly sized
high pressure regulator,
gas pipe size to small,
too many elbows, high
lockup pressure, no
gas pressure relief (>1
psig supply pressure),
insufficient gas volume supply to boiler
room,…
L.5. Multiple appliances sharing an insufficiently sized gas
supply header
L.6. Ignitor weak or not
sparking - check
burner sight port for
visual spark indication
during trial for ignition
Diagnostic CheckCorrective Measures
Monitor gas supply
pressure at boiler gas
valve inlet during trial
for ignition and modulation -- note gas pressure at low fire and
high fire rates.
Note gas supply pressure when all appliances are firing at
rated capacity.
Check for flame signal
on boiler status screen
(DC Volts) during trial
for ignition.
Check for wiring to
ignition transformer;
check ground of transformer
If significant fluctations
in gas pressure (e.g. 5"
to 10" of droop) are
observed, identify gas
supply restriction and
correct condition(s).
If gas supply pressure
drops below minimum
requirement, correct
gas supply header pipe
sizing.
Check ignition cables
for secure connection
to sparking electrodes replace if connection is
loose or if insulation is
brittle and/or charred
Secure wiring and
ground connection to
ignition transformer
Check dual sparking
electrodes condition,
gap, and condition of
insulators
750-382
CBT
Replace ignition cables
Clear Lockout and try
again
Check for power
between terminals 2 &
4 in control panel
during trial for ignition.
L.7. Combustion Air
restriction - dirty/
clogged air filter
L.8. Blocked air intakeCheck for flame signalinspect air intake/
L.9. Blocked flue/
exhaust
Check for flame signalinspect/clean air filter
Check for flame signalinspect flue/remove
If power present,
replace ignition transformer; if no, check
wiring from Falcon
control to ignition
transformer and
secure.
Clear Lockout and try
again
remove blockage
blockage
5-21
Maintenance
ProblemDisplay MessagePossible Cause/Symp-
tom
L.10. Burner canister
clogged
L.11. No or poor flame
signal (less than 1
VDC) -- UV flame sensing
Diagnostic CheckCorrective Measures
Check for flame signalinspect burner/clean
surface. Replace
burner canister if
clogged or damaged.
Clear Lockout and try
again
Check for flame signal; Visually check for
ignition in burner sight
port
Remove UV scanner
for inspection.
Shut-off gas supply;
remove UV scanner
from burner mount,
with match or lighter,
place flame in front of
UV scanner -- observe
displayed flame signal
on boiler status screen
If flame observed,
inspect UV scanner;
remove and clean as
necessary and reinstall.
Inspect scanner
mounting tube for clear
line-of-sight to burner
canister - remove any
blockages that would
inhibit scanner viewing.
If no flame signal,
replace UV scanner
with new one. If yes,
remount UV scanner at
burner. Open gas shutoff valve.
Clear Lockout and try
again
M. Lockout 107 Flame
lost early run
L.12. No or poor flame
signal (less than 1
VDC) -- flame rod sensing
M.1. Refer to L. Lockout 109 Possible
Causes and Corrective
Measures
M.2. Poor combustion
tuning
Check for flame signal; Visually check for
ignition in burner sight
port
With combustion analyzer, compare O2 levels at HF and LF with
manual recommedations.
If condition persists,
contact factory
If flame is observed,
remove flame rod,
inspect, clean and reinstall. Replace as necessary based on usage
and environmental
conditions.
Retune combustion
settings as necessary.
5-22
750-382
CBT
Troubleshooting
ProblemDisplay MessagePossible Cause/Symp-
tom
M.3. Flame Rod (Ionization Electrode)
grounding itself
N. Lockout 122 Lightoff rate proving failed
N.1. Blower speed signal cable is too close to
ignition cables
N.2. Blower speed
control not functioning
properly
Diagnostic CheckCorrective Measures
Check flame signal and
inspect flame rod position.
Observe RPM on display during trial for
ignition
On display screen,
compare Fan speed to
Firing rate command.
Check that blower signal cable is securely
connected at both ends
-- Falcon control J2
socket and blower
speed control signal
socket.
Increase the gap
between the flame rod
tip to the burner canister surface. Replace
flame rod if damaged.
Route blower signal
cable at least 12" away
from ignition cables.
Clear Lockout and try
again
If blower/fan speed
does not respond to
Firing rate command,
perform the following
Diagnostic Checks.
If Fan speed is slow to
respond to Firing rate
command, adjust the
Fan gain up and down
parameters in Fan Configuration group for
better response.
Secure blower signal
cable connections.
750-382
CBT
Check blower AC
power fuse and connections.
With boiler demand is
off, temporarily disconnect blower signal
cable. With AC power
connected, blower
should go to max
speed.
If AC power not present replace fuse.
If AC power low, check
blower wiring circuit
for proper connections. Check ground to
boiler control panel.
If blower does not
respond, recheck
blower AC power circuit. If AC power is
OK, replace blower.
Clear Lockout and try
again
If condition persists,
contact factory
5-23
Maintenance
ProblemDisplay MessagePossible Cause/Symp-
tom
O. Lockout 173 Pilot
relay feedback error
P. Lockout 174 Safety
relay feedback error
Flame FailureQ. Lockout 108 Flame
failure in Run
O.1. Loose wire or neutral in fuel valve circuit
P.1. High ambient temperature inside control
panel.
P.2. Falcon "pump"
relay output assigned
task, but not used
P.3. External electrical
noise (e.g. ignition
sparking) near Falcon
control circuit
P.4. Faulty safety interlock control (e.g.
ALWCO, HLC, HGPS,
LGPS);
Q.1. Refer to Lockout
109 & 107 Possible
Causes and Corrective
Measures -- except for
Ignitor not sparking
Q.2. Poor combustion
tuning
Diagnostic CheckCorrective Measures
Check fuel valve wiring from control panel
to gas valve connection
DIN connector. With
power disconnected,
perform continuity
check of each wire
from control panel terminal to fuel valve DIN
connector. Refer to
boiler wiring diagram.
Measure temperature
in boiler room and
inside control panel.
Refer to boiler wiring
diagram for Falcon
"pump" relay connections. Access Falcon
Pump Configuration
menu.
Check that all electrical
noise sources (e.g.
ignition cables) are
kept away from the
Falcon controller and
connected control circuit wiring.
Check function of each
safety interlock switch
in ILK circuit.
Check Lockout History
for boiler state/status
and cycle run time
when lockout occurred.
With combustion analyzer, compare O2 levels at HF and LF with
manual recommedations.
Correct/secure any
loose wire connections
in fuel valve circuit.
Ensure DIN connector
is secured to gas valve.
If room is greater than
120F, ventilate room
with cooler make-up
air. If control panel is
greater than 140F,
ventilate control panel.
Set all pump control
block assignments that
are not being used to
“None”.
Separate and secure all
control wiring from
electrical noise generators such as ignition
transformer and
cables.
Secure wiring connections or replace faulty
safety interlock control
device.
If condition persists,
contact factory
If feasible, identify
potential adverse operating conditions at
time of lockout (e.g.
low fire or high fire?)
and remedy.
Retune combustion
settings as necessary.
5-24
750-382
CBT
Troubleshooting
ProblemDisplay MessagePossible Cause/Symp-
tom
Q.3. Low fire (Minimum modulation
speed) too low
False FlameR. Hold/Lockout 105
Flame out of sequence
R.1. Gas valve stuck
open
R.2. Electrical noise
from ignition cables
and/or transformer
R.3. Failed UV scannerCheck flame signal on
Diagnostic CheckCorrective Measures
Observe if Lockout
occurs at lower firing
rate. Compare Minimum modulation
parameter setting to
Manual commissioning recommendation.
Check flame signal on
display and visually
check for flame
through burner sight
port
Check gas valve output - control panel terminal 3.
Check routing of flame
signal cable/wiring so
that it is at least 12"
away from high voltage
source.
display and visually
check for flame
through burner sight
port
Increase Minimum
modulation speed by
100-300 RPM as
needed.
Clear Lockout and try
again
If condition persists,
contact factory
If flame observed
through sight port,
CLOSE manual gas
shut-off valve! Check
status of Safety ShutOff gas valve (SSOV) -replace gas valve if it
failed to close.
If energized, check/
correct wiring.
Reroute flame signal
cable/wiring away from
high voltage igntion
sources.
Clear Lockout and try
again
If no flame, clear Lockout and observe controller status
If condition persists,
replace UV scanner
Steam pressure drops
too much when boiler
is off
S. Demand: Steam
Burner state: Standby
(normal)
750-382
CBT
S.1. Steam On point is
too low
Check On point setting
on status screen
If UV scanner replacement does not resolve
Lockout 105, contact
factory.
Set Steam On hysteresis parameter to 0
(zero)
5-25
Maintenance
ProblemDisplay MessagePossible Cause/Symp-
tom
S.2. Anti-short cycle
time is too long
Boiler cycles on and off
too frequently
TABLE 5- 2. Common abbreviations
WDWiring Diagram
ILKSafety InterLock circuit (always require a manual reset)
LCILimit Control Input circuit (resets automatically)
LEDLight Emitting Diode (common on solid state controls, such as LWCO)
AC or VACAlternating Current (electrical power) or Voltage AC
DC or VDCDirect Current (electrical power) or Voltage DC
RPMRevolutions Per Minute (combustion air fan speed or firing rate)
DINelectrical connector type defined by German standards association
UVUltra-Violet (flame scanner type)
T. Demand: Steam
Burner state: Standby
(normal)
T.1. Steam Off hysteresis setting is too low
T.2. PID gains are too
aggressive, or too high
Diagnostic CheckCorrective Measures
Check anti-short cycle
time
Check Steam Off point
on boiler status screen
Check P (proportional)
and I (integral) gain
settings.
Reduce ant-short cycle
time parameter; set to
0 to disable this function. Anti-short cycle is
located in the "Steam
Configuration" parameter group.
Increase the Steam Off
point hysteresis parameter setting to allow
boiler to modulate longer before shutting off.
Reduce the gain values
for both P and I gain.
Observer control of
boiler to meet steam
pressure set point.
5-26
750-382
CBT
Display diagnostics
5.10 — Display diagnostics
The CB Falcon display/interface provides diagnostic features under the Setup menu. To access display diagnostics,
beginning on the Home screen, press <Setup>, then <Display Diagnostics>
If the touch screen is not working properly, it may require re-calibration. Go to Display Diagnostics as above and
press <Calibrate Screen>. Follow the on-screen instructions.
Date and time
The Setup menu also allows access to system Date and Time settings. Press <Setup>, <Display Setup>, <Set
Date/Time>.
5.11 — Lay-up
If the boiler will be out of use for an extended period, precautions must be taken to protect fireside and waterside
surfaces from deterioration due to corrosion.
At the start of lay-up, thoroughly clean the fireside by removing any soot or other products of combustion from the
fireside surfaces. After brushing all surfaces clean, sweep away or vacuum any residue. The fireside may be
flushed with water; however, all surfaces should be completely dried before lay-up.
Dry lay-up
Dry lay-up is generally used when the boiler will be out of service for a lengthy time period, or where the boiler
might be subject to freezing temperatures. The boiler must be thoroughly dried before dry storage, as any moisture
could cause corrosion. Both fireside and waterside surfaces must be cleaned of all scale, deposits, soot, etc. A
desiccant such as quick lime or silica gel should be placed in suitable containers inside the boiler vessel.
Wet lay-up
Wet storage is generally used when a boiler may be needed on short notice or in cases where dry storage is not
practical. Before wet storage the vessel should be drained, thoroughly cleaned, and refilled to overflowing with
treated water. If deaerated water is not available, the unit should be fired to boil the water for a short period of time.
Whichever method of lay-up is used, a periodic re-check of fireside and waterside conditions is recommended
during lay-up.
750-382
CBT
5-27
Maintenance
5-28
750-382
CBT
CHAPTER 6Parts
Recommended spare parts list 6-2
Safety valves 6-3
Control panel 6-4
Burner assembly 6-6
Water Column 6-12
Feedwater piping 6-13
Gas train 6-14
Direct vent kits 6-15
750-382
CBT
6-1
6.1 — Recommended spare parts list
PART NUMBER
DESCRIPTION10-15 HP20-25 HP30 HP
Falcon controller, steam833-03578
Falcon Display833-05105
Power Supply, 12VDC832-02179
Gasket, Adapter Plate To Blower380-01037
Gasket, Burner Canister (2)380-01136380-00902380-01169
Burner Canister380-01134380-00900380-01170
Ignition Cable (2)826-00156
Pressure Gauge, 0-300 PSI850-00122
Gasket, Electrode380-01032
Scanner Assembly, UV 817-01743
Electrode, Ignition380-01174380-01172
Gasket, Venturi800-00098
Burner Sight Glass851-06429
Gasket, Handhole (3)853-00934
Valve Set, Gauge Glass825-00281825-00132
Gauge Glass, Pyrex, Tubular851-00199
Protector Set, Gauge Glass912-00085
Probes, LWCO, Pump On/Off, HWA817-03728
Probe, ALWCO067-00873
Fuse, Blower832-01881
Fuse, Control Circuit, 5A832-01811
Fuse, DC Power Supply, 1A832-02045
Fuse, 24VAC Secondary, 2A832-02051
Ignition Transformer832-02451
Safety Relief Valvesee table next page