Cleaver-Brooks CB780, CB784 Operation And Maintenance Manual

$25.00
Cleaver-Brooks
CB780/CB784
Operation and Maintenance Manual
750-166
DIVISION OF AQUA-CHEM, INC.
TO: Owners, Operators and/or Maintenance Personnel
It is the responsibility of the owner to train and advise not only his or her personnel, but the contractors' personnel who are servicing, repairing, or operating the equipment, in all safety aspects.
Cleaver-Brooks equipment is designed and engineered to give long life and excellent service on the job. The electrical and mechanical devices supplied as part of the unit were chosen because of their known ability to perform; however, proper operating techniques and maintenance procedures must be followed at all times. Although these components afford a high degree of protection and safety, operation of equipment is not to be considered free from all dangers and hazards inherent in handling and firing of fuel.
"Automatic" features included in the design do not relieve the attendant of any responsibility. Such features merely free him of certain repetitive chores and give him more time to devote to the proper upkeep of equipment.
It is solely the operator's responsibility to properly operate and maintain the equipment. No amount of written instructions can replace intelligent thinking and reasoning, and this manual is not intended to relieve operating personnel of the responsibility for proper operation.
Operating controls will normally function for long periods of time. Do not become lax in daily or monthly testing, assuming that normal operation will continue indefinitely. Malfunctions of controls lead to uneconomical operation and damage and, in most cases, these conditions can be traced directly to carelessness and deficiencies in testing and maintenance.
Operation of this equipment by the owner and his operating personnel must comply with all requirements or regulations of his insurance company and/or other authority having jurisdiction. In the event of any conflict or inconsistency between such requirements and the warnings or instructions contain herein, please contact Cleaver-Brooks before proceeding.
Cleaver-Brooks
CB780/CB784
Operation and Maintenance Manual
© Aqua-Chem, Inc., 1995
Please direct purchase orders for replacement manuals to your local
Cleaver-Brooks authorized representative
Manual Part Number 750-166 6/95 Rev 10/95
Printed in U.S.A.
CONTENTS
Section 1 – Installation and Operating Instructions Section 2 – System Annunciation Diagnostics and Troubleshooting
Section 1 - CB780/CB784
Installation and Operating Instructions
The Cleaver-Brooks CB780/CB784 is a microprocessor based integrated burner control for automatically fired gas, oil, or combination fuel single burner applications. The CB780 consists of a Relay Module and Keyboard Display Module. The CB784 consists of the Relay Module only. The Keyboard Display Module is optional with the CB784. Sub­base, Amplifier, and Purge Card are r e quired to complete the system. Options include Personal Computer Interface, Control Bus, Remote Display Mounting, First-Out Expanded Annun­ciator and Combustion System Managment software.
The CB780/CB784 is programmed to provide a level of safety, functional capability and features beyond the capacity of conventional controls.
Functions provided by the CB780/CB784 include auto­matic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting
.
Safety features:
—Interlock check. —Closed loop logic test. —Dynamic Auto-Check. —Dynamic input check. —Dynamic safety relay test. —Dynamic self-check logic. —Expanded safe-start check. —High Fire Purge Switch test. —Internal hardware status monitoring. —Low Fire Start Switch test. —Tamper resistant timing and logic.
Access for external electrical voltage checks.
Application flexibility.
Communication interface capability.
Dependable, long-term operation provided by microcom-
puter technology.
First-out annunciation and system diagnostics provided by
a 2 row by 20 column Vacuum Fluorescent Display (VFD) located on the Keyboard Display Module.
First-out expanded annunciation with 26 Light Emitting
Diodes (LEDs) for limits and interlocks (optional).
Five sequence information Light Emitting Diodes (LEDs).
Five function Run/Test Switch.
Interchangeable plug-in flame amplifiers.
Local or remote annunciation of operation and fault
information.
Nonvolatile memory for retaining history files and sequenc-
ing status after loss of power.
Remote reset (optional).
Report generation (optional).
Burner controller data:
—Sequence status. —Sequence time. —Hold status. —Lockout/alarm status.
—Flame signal strength. —Expanded annunciator status. —Total cycles of operation. —Total hours of operation. —Fault history of six most recent faults:
• Cycles of operation at time of fault.
• Expanded annunciator data at time of fault.
• Fault message and code.
• Hours of operation at time of fault.
• Sequence status at time of fault.
• Sequence time at time of fault.
—Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time.
• Manufacturing code.
• On/Off status of all digital inputs and outputs.
• Selected prepurge time.
• Software revision and version of CB780/CB784 and Keyboard Display Module.
• Status of configuration jumpers.
• Status of Run/Test Switch.
CONTENTS
Specifications ............................................................... 2
Principle Technical Features ...................................... 6
Safety Provisions ......................................................... 7
Installation ................................................................... 9
Wiring ........................................................................ 11
Assembly .................................................................... 15
Operation ................................................................... 18
Static Checkout .......................................................... 25
Checkout .................................................................... 27
Troubleshooting ......................................................... 34
750-166 1-1
CB780/CB784 SPECIFICATIONS
Specif ications
ELECTRICAL RATINGS, see Table 1:
Voltage and Frequency: 120 Vac (+10/-15%), 50 or
60 Hz (+/- 10%)5.
Keyboard Display Module: 13 Vdc peak full wave
rectified (+20/-15%).
Power Dissipation:
CB780/CB784: 10W maximum.
Display Module: 3W maximum. Maximum Total Connected Load: 2000 VA. Fusing: Total Connected Load: 20A maximum, type
FRN or equivalent.
TABLE 1—TERMINAL RATINGS.
Terminal No. Description Ratings
G Flame Sensor Ground
Earth G Earth Ground
1
1
L2(N) Line Voltage Common
3 Alarm 120 Vac, 1A pilot duty. 4 Line Voltage Supply (L1) 120 Vac (+10/-15%), 50 or 60 Hz (±10%).
2,5
5 Burner Motor 120 Vac, 9.8AFL, 58.8ALR (inrush). 6 Burner Controller and Limits 120 Vac, 1 mA. 7 Lockout/Running Interlock 120 Vac, 9A. 8 Pilot Valve/Ignition 120 Vac, 4.5A ignition and 50VA pilot duty. 9 Main Fuel Valve 120 Vac, 2A pilot duty.
10 Ignition 120 Vac, 4.5A Ignition.
4
3
3
F(11) Flame Sensor 60 to 220 Vac, current limited.
12 Firing Rate High Fire 120 Vac, 75 VA pilot duty. 13 Firing Rate Common 120 Vac, 75 VA pilot duty. 14 Firing Rate Low Fire 120 Vac, 75 VA pilot duty. 15 Firing Rate Modulate 120 Vac, 75 VA pilot duty. 16 Unused 17 Unused 18 Low Fire Switch Input 120 Vac, 1 mA. 19 High Fire Switch Input 120 Vac, 1 mA. 20 Preignition Interlock Input 120 Vac, 1 mA. 21 Interrupted/Pilot Valve/First Stage Oil Valve 120 Vac, 2A pilot duty. 22 Shutter 120 Vac, 0.5A.
1
The CB780/CB784 must have an earth ground providing a connection between the subbase and the control panel or the equipment. The earth ground wire must be capable of conducting the current to blow the 20A fuse (or breaker) in event of an internal short circuit. The CB780/CB784 needs a low impedance ground connection to the equipment frame which, in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection must be made by minimum length conductors having maximum surface areas. Wide straps or brackets are preferred rather than leadwires. Be careful to ensure that mechanically tightened joints along the ground path, such as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coatings and are protected against mating surface corrosion.
2
2000 VA maximum connected load to CB780/CB784 Assembly.
3
Can also be 120 Vac, 1A pilot duty.
4
Can also be 65 VA pilot duty with motorized valve, 1150 VA inrush, 460 VA open, 250 VA hold.
5
Operating frequency chosen by CB780/CB784 selection.
1-2 750-166
CB780/CB784
SPECIFICATIONS
ENVIRONMENTAL RATINGS:
Ambient Temperature:
Operating: -40°F to 140°F.
WEIGHT:
CB780/CB784: 1 pound 10 ounces, unpacked. Keyboard Display Module: 4 ounces, unpacked.
Storage: -40°F to 150°F. Humidity: 85% RH continuous, noncondensing. Vibration: 0.5G environment.
DIMENSIONS: Refer to Figs. 1 and -2.
IMPORTANT: Flame Detection System available for use
with CB780/CB784. To select your Plug-in Flame Signal Amplifier and matching Flame Detector, see Table 2.
TABLE 2—FLAME DETECTION SYSTEMS (FIGS. 3, 4, 5).
Plug-In Flame Amplifiers Applicable Flame Detectors
Flame
Failure
Part
Type Color Self-Checking
Number
Infrared Red No 833-2722 3 sec. Gas, oil,
Dynamic AMPLI-
Dynamic Auto-Check
CHECK™
833-2723
Response
Time Fuel Type
coal
c
Gas, oil, coal
Infrared (Lead Sulfide)
Infrared (Lead Sulfide)
Part
Number
817-1742
817-1742
Ultraviolet Purple No 833-2724 Gas, oil Ultraviolet 817-1743 Ultraviolet
Self-Check
Green Dynamic Self-
Check
833-2741
b
Gas, oil, coal
Ultraviolet (Purple
817-1121
Peeper)
a
The 817-1743 Flame Detector should be used only on burners that cycle on-off at least once every twenty-four hours. Appliances with burners that remain on for twenty-four hours continuously or longer should use the 817-1121 Flame Detector with the 833-2741 Amplifier as the ultraviolet flame detection system.
b
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during burner operation and shuts down the burner if the detection system fails.
c
Circuitry tests the flame signal amplifier 12 times a minute during burner operation and shuts down the burner if the amplifier fails.
a
Firing
Rate
2
Energy
Saving
No FM/IRI
Approval
Code
Modulating
TABLE 3—SEQUENCE TIMING FOR NORMAL OPERATION.
Flame
Establishing
Period
Device Initiate Standby Purge Pilot Main Run
CB 780/ CB 784
* STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which purge card is selected.
1
The MFEP will be determined by which terminal is used, see Figs. 7 and 18.
2
The operating sequence of the CB780 and CB784 Relay Modules are identical. The only difference between the Relay
10 sec * ** 4 or
10 sec
10 or 15 sec
* 15 sec Preignition,
1
Post
Purge Interlock
Timing Circuits Circuit Prepurge Bodies
Lockout, High and Low Fire
4-wire modulating
Modules is that the Keyboard Display Module is standard with the CB780 and optional with the CB784.
APPROVAL BODIES:
Underwriters Laboratories Inc. listed, File No. MP268,
Guide No. MCCZ. Canadian Standards Association certified, LR9S329-3.
Factory Mutual approved, Report No. JI1V9A0.AF. IRI acceptable. Federal Communications Commission, Part 15, Class B—
Emissions.
750-166 1-3
CCB780/CB784 SPECIFICATIONS
MOUNTING: 833-2725 for panel mount. REQUIRED COMPONENTS:
CB780: 120 Vac/60 Hz, 833-2718. CB780: 120 Vac/50 Hz, 833-2719. CB784: 120 Vac/60 Hz, 833-2720. CB784: 120 Vac/ 50 Hz, 833-2721 Plug-in Flame Signal Amplifier, see Table 2. Plug-in Purge Timer Cards: selectable:
833-2730 30 sec. 833-2731 60 sec. 833-2732 90 sec. 833-2733 2-1/2 min.
ACCESSORIES:
Optional:
Control Bus—part no. 833-2729. Provides
communication and remote reset capabilities on CB784; remote display capabilities on CB780
and CB784. CB783 Expanded Annunciator—part no. 833-2726. Keyboard Display Module—part no. 833-2727.
(Standard on CB780; optional on CB784.) Remote Mounting Kit for the Keyboard Display,
NEMA 4—part no. 833-2740. Tester—part no. 626-5050.
NOTE: The CB780 and CB784 are identical except for the
Keyboard Display Module which is standard with the CB780 and optional with the CB784.
Fig. 1—Mounting dimensions of CB780/CB784 Relay Module and 833-2725 Subbase, in inches (mm)
BURNER CONTROL
SCROLL MODE
SAVE
5
(127)
POWER PILOT FLAME MAIN ALARM
RESET
5 (127)
1
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
M7399
1-4 750-166
CB780/CB784
,
,
SPECIFICATIONS
Fig. 2—Mounting dimensions of Keyboard Display Module, in inches (mm).
BURNER CONTROL
2-3/4 (69)
15/ 32 (12)
1-15/16 (49)
29/32 (23)
SCROLL MODE
19/32 (15)
5/32 (4)
4-27/32 (123)
1-1/4 (32)
7/16 (11)
2-5/16 (58)
3-7/8 (99)
SAVE
4-3/32 (104)
1-1/32 (26)
13/ 32 (11)
5/32 (4)
1/2 (13)
5/16 (8)
2-1/32 (52)
5/15 (8)
29/32 (23)
M7405
Fig. 4—Ultraviolet detector.
4 (102)
3-1/2 (89)
COLLAR WITH 1/2-14 NPSM INTERNAL THREADS
817-1743
Fig. 5—Infrared detector.
2-3/4
(70)
2 LEADS IN A 48 INCH [1.2 METER] FLEXIBLE CONDUIT
BUSHING WITH MAGNIFYING LENS
COLLAR, 3/4-14 NPSM INTERNAL THREADS
817-1742
1-1/4
(32)
APERTURE
6 FOOT (1.83 METER) LEADWIRES (2)
1-1/16
(27)
HEAT BLOCKCELL MOUNT
1-5/8 (41)
1-1/16 (27)
1-1/4
3/4-14 NPSM
3/4-14 NPSM INTERNAL THREADS
M7419
(32)
M1982A
833-2727
(Standard with CB780, optional with CB784)
Fig. 3—Ultraviolet Self-Check detector.
3-3/4
(95)
7-7/32
(183)
1/2–14 NPSM
LEADWIRES
MOUNTING FLANGE
817-1121
5-1/8 (130)
3-7/16
(87)
FACEPLATE
3/4–14 NPT
5-1/4 (133)
M1962A
750-166 1-5
CB780/CB784 PRINCIPAL TECHNICAL FEATURES
Principal T echnical Features
The CB780/CB784 provides all customary flame safe­guard functions while providing significant advancements in the areas of safety, annunciation and system diagnostics.
SAFETY SHUTDOWN (LOCKOUT) OCCURS IF:
1. INITIATE Period a. Purge card is not installed or removed. b. Purge card is bad. c. Configuration jumpers were changed (after
200 hours). d. AC line power errors, see Operation. e. Four minute INITIATE period is exceeded.
2. STANDBY Period a. Flame signal is present after 40 seconds. b. Preignition Interlock is open an accumulative time
of 30 seconds.
c. Interlock check feature is enabled and the Inter-
lock String (including the airflow switch) is closed for 120 seconds with controller closed.
d. Ignition/pilot valve/intermittent pilot valve termi-
nal is energized. e. Main valve terminal is energized. f. Internal system fault. g. Purge card is not installed or removed. h. Purge card is bad.
3. PREPURGE Period a. Preignition Interlock opens anytime during
PREPURGE.
b. Flame signal detected after first ten seconds during
PREPURGE.
c. High Fire Switch fails to close within four minutes,
fifteen seconds after firing rate motor is commanded to drive to high fire position at start of PREPURGE.
d. Low Fire Switch fails to close within four minutes,
fifteen seconds after firing rate motor is commanded
to drive to low fire position at end of PREPURGE. e. Lockout Interlock does not close within 10 seconds. f. Lockout Interlock opens during PREPURGE. g. Ignition/pilot valve/intermittent pilot valve termi-
nal is energized. h. Main valve terminal is energized.
i. Internal system fault. j. Purge card is removed. k. Purge card is bad.
4. PILOT FLAME ESTABLISHING Period (PFEP) a. Low Fire Switch opens. b. Lockout Interlock opens. c. Ignition/pilot valve/intermittent pilot valve terminal
is not energized.
d. Early Spark Termination terminal is energized af-
ter five seconds. e. No flame is present at end of PFEP. f. Internal system fault. g. Purge card is removed. h. Purge card is bad.
5. MAIN FLAME ESTABLISHING Period (MFEP) a. Low Fire Switch opens. b. Lockout Interlock opens. c. Ignition/pilot valve/intermittent pilot valve termi-
nal is not energized. d. Main valve terminal is not energized. e. No flame is present at end of MFEP. f. Internal system fault. g. Purge card is not installed or removed. h. Purge card is bad.
6. RUN Period a. No flame is present. b. Lockout Interlock opens. c. Main valve terminal is not energized. d. Internal system fault. e. Purge card is not installed or removed. f. Purge card is bad.
7. POSTPURGE Period a. Preignition Interlock does not close within five sec-
onds or opens after five-second time period.
b. Ignition/pilot valve/intermittent pilot valve termi-
nal is energized. c. Main valve terminal is energized. d. Internal system fault. e. Purge card is removed. f. Purge card is bad.
1-6 750-166
CB780/CB784
SAFETY PROVISIONS
Safety Pro visions
INTERNAL HARDWARE STATUS MONITORING
The CB780/CB784 checks the purge card for correct parity to prevent purge timing shifts and circuitry failures. It also analyzes the integrity of the configuration jumpers and internal hardware. The POWER LED blinks every four seconds, signifying an internal hardware check.
CLOSED LOOP LOGIC TEST
The test verifies the integrity of all safety critical loads, terminals 8, 9, 10 and 21. If the loads are not energized properly; i.e., the main valve terminal is powered during PREPURGE, the CB780/CB784 will lockout on safety shut­down. The CB780/CB784 must react to input changes but avoid the occurrence of nuisance shutdown events. Signal conditioning is applied to line voltage inputs to verify proper operation in the presence of normal electrical line noise such as transient high voltage spikes or short periods of line dropout. Signal conditioning is tolerant of synchronous noise (line noise events that occur at the same time during each line cycle).
DYNAMIC AUTO-CHECK
Dynamic Auto-Check circuitry tests the flame signal amplifier during burner operation and shuts down the CB780/ CB784 if the flame amplifier fails.
DYNAMIC FLAME AMPLIFIER AND SHUTTER CHECK
Self-checking circuitry tests all electronic components in the flame detection system and amplifier 10 to 12 times per minute and shuts down the CB780/CB784 if the detection system fails.
DYNAMIC INPUT CHECK
All system input circuits are examined to verify that the CB780/CB784 is capable of recognizing the true status of external controls, limits and interlocks. If any input fails this test, a safety shutdown occurs and the fault is annunciated.
DYNAMIC SAFETY RELAY TEST
Checks the ability of the dynamic safety relay contacts to open and close. It also verifies that the safety critical loads, terminals 8, 9, 10 and 21, can be de-energized, as required, by the Dynamic Self-Check logic.
DYNAMIC SELF-CHECK SAFETY CIRCUIT
The microcomputer tests itself and related hardware while at the same time the safety relay system tests the micro­computer operation. If a microcomputer or safety relay failure occurs and does not allow proper execution of the self-check routine, safety shutdown will occur and all safety critical loads will be de-energized.
EXPANDED SAFE-START CHECK
The conventional safe-start check, which prevents burner start-up if flame is indicated at start-up, is expanded to include a flame signal check during STANDBY, a preigni­tion interlock check, an interlock check, and a safety critical load check.
HIGH FIRE PURGE AND LOW FIRE START SWITCH TESTS
High Fire Purge Switch Test examines the Purge Posi­tion Interlock Switch at the moment the firing rate motor is commanded to the high fire position. If the switch is by­passed, welded or otherwise closed prematurely, the system will automatically add 30 seconds to allow additional drive time for the firing rate motor to reach or near the open position before starting the purge timing; otherwise, purge timing starts when the High Fire Switch is closed. This switch will also cause a hold (four minutes, fifteen seconds) condition when the switch is open before purge or opens during purge. The CB780/CB784 will lockout and annunci­ate an alarm if the switch fails to close within the hold time period.
Low Fire Start Switch Test examines the Low Fire Start Switch at the moment PREPURGE is completed. If the switch is bypassed, welded or otherwise prematurely closed, the system automatically adds 30 seconds to allow the firing rate motor additional time to reach or near the low fire start position before ignition trials; otherwise, ignition trials start after the Low Fire Switch closes. The test also is used to prove that the firing rate motor is at low fire position throughout the ignition trial period. This switch will also cause a hold (four minutes, fifteen seconds) condition if the switch opens after purging is complete. The CB780/CB784 will lockout and annunciate an alarm if the switch fails to close within the hold time period.
750-166 1-7
CB780/CB784 SAFETY PROVISIONS
MANDATORY PURGE
If lockout occurs after the initiation of ignition trials, (or at anytime during a sequence when the fuel valves may have been energized), a mandatory POSTPURGE period is imposed.
OFF CYCLE (STANDBY OR PREPURGE) FLAME SIGNAL CHECK
The flame detection subsystem (flame detector and am­plifier) is monitored during STANDBY. If a flame simulat­ing condition or an actual flame exists, a system hold occurs and start-up is prevented. If the flame signal exists at any time after the first 40 seconds of STANDBY, a safety shut­down will occur and be annunciated. A shutter-check ampli­fier and self-checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY. If a flame exists, a safety shut­down occurs. An Auto-Check Amplifier is energized con­tinually through STANDBY and PREPURGE to detect any possibility of a runaway detector or a flame. If either situa­tion happens, a safety shutdown occurs. A standard amplifier is energized continually through STANDBY and PREPURGE. If either situation happens, a safety shutdown occurs.
PREIGNITION OUTPUT CIRCUIT CHECK
At the end of PREPURGE, the Dynamic Safety Relay operation is checked. Also, all safety critical loads, terminals 8, 9, 10 and 21 are checked to verify the terminals are not powered. If the Dynamic Safety Relay operation is faulty, or if any of the safety critical loads are powered, safety shut­down occurs and is annunciated.
TAMPER RESISTANT TIMING AND LOGIC
Safety and logic timings are inaccessible and cannot be altered or defeated.
VERIFIED SPARK TERMINATION
The ignition terminal is monitored to verify early spark termination (five seconds ignition and pilot and five seconds pilot only).
FIRST-OUT ANNUNCIATION AND SELF-DIAGNOSTICS
Sequence Status Lights (LEDs) provide positive visual indication of the program sequence: POWER, PILOT, FLAME, MAIN and ALARM. The green POWER LED blinks every four seconds to signify the CB780/CB784 hardware is running correctly.
Multi-function Keyboard Display Module (standard with CB780, optional with CB784) shows elapsed time during PREPURGE, PILOT IGN, MAIN IGN, and POSTPURGE. As an additional troubleshooting aid, it provides sequence timing, diagnostic information, historical information and expanded annunciator information when a safety shutdown or hold or normal operation occurs.
First-out Annunciation reports the cause of a safety shut­down or identifies the cause of a failure to start or continue the burner control sequence with an English text and num­bered code via the Keyboard Display Module. It monitors all field input circuits, including the Flame Signal Amplifier and Firing Rate Position Switches. The system distinguishes 118 modes of failure and detects and annunciates difficult­to-find intermittent failures.
Self-Diagnostics adds to the First-out Annunciation by allowing the CB780/CB784 to distinguish between field (external device) and internal (system related) problems. Faults associated within the flame detection subsystem, CB780/CB784 or plug-in Purge Card, are isolated and re­ported by the Keyboard Display Module. See the Diagnos­tics and Troubleshooting section of the CB780/CB784 Op­eration and Maintenance Manual, Manual Number 750-166.
INTERLOCK REQUIREMENTS
The following interlock inputs are provided:
Low Fire Interlock
This interlock verifies the firing rate motor is in the low fire position before and during ignition trials.
High Fire Interlock
This interlock verifies the firing rate motor is in the high fire position prior to and during PREPURGE.
Lockout Interlock
This interlock (ILK) input signifies a Lockout Interlock. If the Lockout Interlock is open for more than ten seconds into PREPURGE, the CB780/CB784 will lockout. After entering PREPURGE, if the Lockout Interlock opens during the first ten seconds, the purge timer will be reset. This provides a continuous PURGE to occur without interruption before the Pilot Flame Establishing Period. If a Lockout Interlock opens anytime after ten seconds into PURGE, during the Ignition Trials or Run, it causes a lockout.
A typical Lockout Interlock string contains an airflow switch (see Fig. 7). The Interlock Check is a site configur­able option (see Table 7). If this feature is enabled, the CB780/CB784 will lockout after 120 seconds whenever control terminal 6 is energized, and the Lockout Interlock string (including airflow switch) is closed during STANDBY.
Preignition Interlock
The Preignition Interlock input is typically connected to proof-of-closure switches for fuel valve(s). The Preignition Interlock must be energized throughout PREPURGE. If the Preignition Interlock opens during STANDBY, it causes a hold (30 seconds). The CB780/CB784 will lockout if the interlock does not close within 30 seconds during STANDBY. If the Preignition Interlock opens during PREPURGE, it will lockout. If the Preignition Interlock is open after five sec­onds into POSTPURGE, the CB780/CB784 will lockout. The Preignition Interlock is ignored during the ignition trials state and during RUN.
1-8 750-166
WARNING
FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH.
To prevent possible hazardous burner operation, verification of safety requirememts must be per- formed each time a control is installed on a burner.
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked on the product to make sure the product is suitable for the application.
3. Installer must be a trained, experienced, flame safe­guard service technician.
4. After installation is complete, check out the product operation as provided in these instructions.
CA UTION
1. Disconnect the power supply before beginning installation to prevent electrical shock, equip- ment and control damage. More than one power supply disconnect may be involved.
2. Wiring connections for the CB780/CB784 are unique; therefore, refer to Figs. 6, 7, 8 o r 9 or the correct Specifications for proper subbase wiring.
3. Wiring must comply with all applicable codes, ordinances and regulations.
4. Wiring, where required, must comply with NEC Class 1 (Line Voltage) wiring.
5. Loads connected to the CB780/CB784 must not exceed those listed on the CB780/CB784 label or the Specifications, see Table 1.
6. Limits and interlocks must be rated to simulta- neously carry and break current to the ignition transformer, pilot valve, and main fuel valve(s).
7. All external timers must be listed or component recognized by authorities who have jurisdiction for the specific purpose for which they are used.
IMPORTANT:
1. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safe­guard control and the main fuel valve(s).
2. Two Flame Detectors can be connected in parallel with the exception of Infrared Flame Detector (817-1742).
CB780/CB784
INSTALLATION
Installation
3. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause interfer­ence to radio communications. It has been tested and found to comply with the limits for a Class B comput­ing device of Part 15 of FCC rules which are designed to provide reasonable protection against such inter­ference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference; in which case, the users at their own expense may be required to take whatever mea­sures are required to correct this interference.
4. This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
HUMIDITY
Install the CB780/CB784 where the relative humidity never reaches the saturation point. The CB780/CB784 is designed to operate in a maximum 85% RH continuous, noncondensing, moisture environment. Condensing mois­ture may cause a safety shutdown.
VIBRATION
Do not install the CB780/CB784 where it could be sub­jected to vibration in excess of 0.5G continuous maximum vibration.
WEATHER
The CB780/CB784 is not designed to be weather tight. If installed outdoors, the CB780/CB784 must be protected by an approved weather-tight enclosure.
MOUNTING WIRING SUBBASE
NOTE: For installation dimensions, see Fig. 1.
1. Mount the subbase in any position except horizontally with the bifurcated contacts pointing down. The standard vertical position is recommended. Any other position de­creases the maximum ambient temperature rating.
2. The 833-2725 Wiring Subbase can be mounted di­rectly in the control cabinet. Be sure to allow adequate clear­ance for servicing, installation, access or removal of the CB780/CB784, Expanded Annunciator, Keyboard Dis­play Module, flame amplifier, flame amplifier signal voltage probes, Run/Test Switch, electrical signal voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a template to mark the four screw locations. Drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws.
750-166 1-9
CB780/CB784 INSTALLATION
Fig. 6—Internal block diagram of the CB780/CB784 (see Figs.7,8,9, or 10 for detailed wiring instructions).
4
RESET PUSHBUTTON
STATUS LEDs
RUN/TEST SWITCH
CONFIGURATION JUMPERS
MICROCOMPUTER
SAFETY RELAY CIRCUIT
RELAY DRIVE CIRCUIT
L1 (HOT) L2
1
120 Vac
2K 3K 4K 5K
6K 7K 8K 9K
1K
POWER SUPPLY
PLUG-IN PURGE TIMER CARD
FLAME SIGNAL
PLUG-IN FLAME AMPLIFIER
TEST
L2
TEST JACK
F
G
22
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
CONTROL POWER
20
PRE-IGNITION INTERLOCK
LIMITS CONTROLLER
6K1
3K1
KEYBOARD
DDL
DISPLAY MODULE
RS485
DDL COMMUNICATIONS
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
1
2
LOCKOUT INTERLOCK
6
LOW FIRE SWITCH
18
HIGH FIRE SWITCH
19
REMOTE
3
RESET
1K1 2K1 5K1
7
4K1
7K1
2K2
HIGH FIRE
8K1
COMMON
8K2
MODULATE
9K2
LOW FIRE
2
9K1
12
13
15
14
2 REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
10
8
21
9
5
3
INDICATES FEEDBACK SENSING TO RELAY STATUS FEEDBACK AND LINE VOLT INPUTS
FIELD WIRING INTERNAL WIRING
IGNITION
PILOT
PILOT/V2
MAIN VALVE
BLOWER
ALARM
M7420
1-10 750-166
CB780/CB784
Wiring
WIRING
1. a. For proper subbase wiring, refer to Fig. 7. b. For proper remote wiring of the Keyboard Dis-
play Module, refer to Fig. 8, 9 or 10 or to the Specifications for the Keyboard Display Module, Communication Interface Base Unit or Control Bus.
2. Disconnect the power supply from the main discon-
nect before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be involved.
3. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where required, must comply with NEC, Class 1 (Line Voltage) wiring.
4. Recommended wire size and type: a. All Line Voltage terminals use no. 14 or 16 cop-
per conductor (90°C or higher) 600 volt insula­tion wire (wire size must be coordinated with fuse protection). For high temperature installations, use wire selected for a temperature rating above the maximum operating temperature. All leadwires should be moisture resistant.
b. Keyboard Display Module—For communica-
tions purposes, use an unshielded 22 AWG 2-wire twisted cable and one wire for ground if the leadwire run and noise conditions permit; how­ever, some installations may need up to five wires, three for communications and two for remote reset (in either a single cable or separate cables for com­munications or remote reset) or use Belden 8771 shielded cable or equivalent. The Keyboard Dis­play Module, Control Bus (for remote mounting or communications) or Communication Interface ControlBus Module must be wired in a daisy chain configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connectors, for connec­tions over 100 feet, see Fig. 8, 9 and 10.
c. Control Bus—For communications purposes,
use an unshielded 22 AWG 2-wire twisted cable if the leadwire run and noise conditions permit; however, some installations may need up to five wires, three for communications and two for re­mote reset (in either a single cable or separate cables) or use a Belden 8771 shielded cable or equivalent. The Keyboard Display Module, Con­trol Bus (for remote mounting or communications) or Communication Interface ControlBus Module must be wired in a daisy chain configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of inter­connection of all the devices listed above is not
important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resis­tor termination across terminals 1 and 2 of electri­cal connectors, for connections over 100 feet, see Fig. 8, 9 and 10.
d. Remote Reset*—Use no. 22 AWG or greater
twisted pair wire, insulated for low voltage; see Fig. 8, 9 and 10.
e. Communication Interface ControlBus Module—
For communications purposes, use an unshielded 22 AWG 2-wire twisted cable if the leadwire run and noise conditions permit or use a Belden 8771 shielded cable or equivalent. The Keyboard Display Module, Control Bus (for remote mount­ing or communications) or Communication Inter­face ControlBus Module must be wired in a daisy chain configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connec­tors, for connections over 100 feet, see Fig. 8, 9 and 10.
f. Use the recommended wire size for the 13 Vdc
full wave rectified transformer power input of no. 18 AWG wire insulated for voltages and tem­peratures encountered in the application. Sug­gested wire types include TTW(60C), THW(75C) and THHN(90C).
5. Recommended grounding practices: a. The earth ground provides for a connection be-
tween the subbase and the control panel of the equip­ment. The earth ground wire must be capable of conducting the current to blow the 20A fuse (or breaker) in event of an internal short circuit. The CB780/CB784 needs a low impedance ground connection to the equipment frame which, in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection must be made with minimum length conductors that have a maximum surface area. Wide straps or brackets are preferred rather than leadwires. Be careful to ensure that mechanically tightened joints along the ground path, such as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coatings and are protected against corrosion on mating surfaces.
b. Keyboard Display Module,
Comm
unication Interface ControlBus Module—
Control Bus, or
750-166 1-11
*Note: Remote Reset must be mounted within sight of the boiler control panel.
CB780/CB784 WIRING
The shield, if used, should be connected to the signal ground terminal 3(c) provided as part of the CB780/CB784 device ControlBus connection. Connect the shield at both ends to earth ground.
c. CB780/CB784—Each CB780/CB784 will have
an earth ground terminal that must be grounded to the metal control panel with wire as short as prac­tical. Each ground wire must be capable of carrying a fault current equal to the rating of the protec­tive fuse (20A). A number 14 copper conductor is adequate, but wide straps or brackets are pre­ferred rather than leadwires.
6. Recommended wire routing: a. Flame detector leadwires:
1. Do not run high voltage ignition transformer wires in the same conduit with the flame detec­tion wiring.
2. Do not route scanner wires in conduit with line voltage circuits.
3. Enclose scanner wires without armor cable in metal cable or conduit.
4. Follow directions in flame detector Instructions.
b. Control Bus:
1. Do not run high voltage ignition transformer wires in the same conduit or close proximity with the Control Bus wiring.
2. Do not route Control Bus wires in conduit with line voltage circuits.
c. Keyboard Display Module (VFD): Because the
VFD is powered from a low voltage, energy lim­ited source, it can be mounted outside of a control panel if it is protected from mechanical damage.
d. Remote Reset:
1. Do not run high voltage ignition transformer wires in the same conduit with the Remote Reset wiring.
2. Do not route Remote Reset wires in conduit with line voltage circuits.
NOTE: A 13 Vdc power supply must be used any time more
than one Keyboard Display Module is used.
7. Maximum wire lengths: a. CB780/CB784 leadwires—The maximum length
of leadwire is 300 feet to terminal inputs (Control, Preignition Interlock, Running/Lockout Interlock, High Fire Switch and Low Fire Switch).
b. Flame Detector leadwires—The maximum flame
sensor leadwire length is limited by the flame signal strength.
c. Remote Reset leadwires—The maximum length
of wire is 1000 feet to a Remote Reset pushbutton.
d. Control Bus—The maximum Control Bus cable
length depends on the number of system modules connected, the noise conditions and the cable used. The maximum length of all interconnecting wire is 1000 feet.
8. Make sure loads do not exceed the terminal ratings.
Refer to the label on the CB780/CB784 or to the ratings in Specifications; see Table 1.
9. Check the power supply circuit. The voltage and fre-
quency tolerance must match those of the CB780/CB784. A separate power supply circuit may be required for the CB780/CB784. Add the required disconnect means and overload protection.
10. Check all wiring circuits and complete the Static Checkout, see Table 8, before installing the CB780/CB784 on the subbase.
11. Install all electrical connectors.
12. Restore power to the panel.
1-12 750-166
FIG. 7—WIRING CB780/CB784
833-2725
G
12
HIGH FIRE
SERIES 90 FIRING RATE MOTOR
B
SERIES 90 CONTROLLER
B
CB780/CB784
WIRING
13
14
15
16
17
18
19
20
21
22
COMMON
LOW FIRE
MODULATE
LOW FIRE START SWITCH
HIGH FIRE PURGE SWITCH
PREIGNITION INTERLOCK
15 SEC. INTERRUPTED PILOT VALVE
MASTER SWITCH
R
W
L1 (HOT)
L2
R
W
1
120V ALARM
BURNER MOTOR (BLOWER)
BURNER CONTROLLER/LIMITS
LOCKOUT INTERLOCKS (INC. AIR FLOW SWITCH)
10 SEC. INTERRUPTED PILOT/IGNITION
MAIN FUEL VALVE(S)
5 SECOND IGNITION (EARLY SPARK)t
(EARLY SPARK
(TERMINATION)
TERMINATION)
817-1742 INFRARED (LEAD SULFIDE) FLAME DETECTOR
L2
10
3
(L1)
4
5
6
7
8
9
F
OR
WHITE
817-1743 ULTRAVIOLET FLAME DETECTOR
OR
YELLOW
1 2
817-1121 ULTRAVIOLET FLAME DETECTOR
120V, 60 Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. DO NOT WIRE TO ANY UNUSED TERMINALS.
BLUE
BLUE
WHITE WHITE BLACK BLACK
FOR DIRECT SPARK IGNITION (OIL OR GAS)
IGNITION
10
TRANSFORMER
8
2ND STAGE
9
FUEL VALVE
L2 L1
L2
(OPTIONAL)
2
L2
M7408
750-166 1-13
CB780/CB784
L1 (HOT)
L2
1
1
120 OHM RESISTOR
1
120 OHM RESISTOR
A
B
A
B
C (GND)
+13 VDC
RESET
C (GND)
+13 VDC
RESET
1
23
4
5
1
23
4
5
MOMENTARY PUSH BUTTON SWITCH
833-2727 KEYBOARD DISPLAY MODULE (MOUNTED ON CB 780/CB 784)
13 VDC POWER SUPPLY
833-2727 REMOTE KEYBOARD DISPLAY MODULE
THREE WIRE SHIELDED CABLE MAY BE REQUIRED. TWO 120 OHM TERMINATING RESISTORS ARE REQUIRED FOR CONNECTIONS OVER 100 FEET. CABLE SHIELD MUST BE TERMINATED TO EARTH GROUND AT BOTH ENDS. IF SHIELDED CABLE IS NOT USED, TWISTED PAIR WIRE MUST BE USED.
M7409
WIRING
Fig. 8—Wiring the Keyboard Display Module with Communication Interface ControlBus Module.
833-2727 KEYBOARD DISPLAY MODULE (MOUNTED ON CB 780/CB 784)
MOMENTARY PUSH BUTTON
A
1
120 OHM RESISTOR
120 OHM RESISTOR
1
A
THREE WIRE SHIELDED CABLE MAY BE REQUIRED. TWO 120
1
OHM TERMINATING RESISTORS ARE REQUIRED FOR CONNECTIONS OVER 100 FEET (30 METERS). CABLE SHIELD MUST BE TERMINATED TO EARTH GROUND AT BOTH ENDS. IF SHIELDED CABLE IS NOT USED, TWISTED PAIR WIRE MUST BE USED.
2 REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
B
C (GND)
23
1
1
23
B
C
RESET
+13 VDC
4
5
833-2734 COMMUNICATIONS INTERFACE CONTROLBUS MODULE
SWITCH
2
M7406
Fig. 9—Wiring multiple Keyboard Display Modules.
2
2 REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
Fig. 10—Wiring the Control Bus with remote Keyboard Display Module.
833-2729 DATA CONTROLBUS MODULE™ (MOUNTED ON CB 780/CB 784)
833-2729 CONTROL BOX (MOUNTED ON CB780/CB784)
1-14 750-166
MOMENTARY PUSH BUTTON
A
1
120 OHM RESISTOR
120 OHM RESISTOR
1
A
833-2727 REMOTE KEYBOARD DISPLAY MODULE
THREE WIRE SHIELDED CABLE MAY BE REQUIRED. TWO 120
1
OHM TERMINATING RESISTORS ARE REQUIRED FOR CONNECTIONS OVER 100 FEET. CABLE SHIELD MUST BE TERMINATED TO EARTH GROUND AT BOTH ENDS. IF SHIELDED CABLE IS NOT USED, TWISTED PAIR WIRE MUST BE USED.
WHEN CONNECTING THE KEYBOARD DISPLAY MODULE DATA
2
CONTROL BUS, OR REMOTE RESET MODULE
CONTROLBUS MODULE™, OR REMOTE RESET MODULE EXTERNAL FROM THE CONTROL CABINET, APPROPRIATE MEASURES MUST BE TAKEN TO MEET EN60730 SAFETY LOW VOLTAGE REQURIEMENTS (SEE APPROVALS).
3 REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
B
C (GND)
23
2
1
1
23
B
C (GND)
+13 VDC
4
4
+13 VDC
RESET
5
5
RESET
SWITCH
M7407
3
MOUNTING CB780/CB784
NOTE: For installation dimensions, see Fig. 1.
RELAY MODULE MOUNTING
1. Mount the CB780/CB784 vertically, see Fig. 11, or mount horizontally with the knife blade terminals pointing downward. The CB780/CB784 must be in an electrical enclosure.
2. Select the location in the electrical enclosure. Be sure to allow adequate clearance for servicing, installation and removal of the CB780/CB784, Keyboard Display Module, flame amplifier, flame amplifier signal voltage probes, elec­trical signal voltage probes, and electrical connections.
a. Allow an additional two inches below the CB780/CB784
for the flame amplifier mounting.
d. Allow an optional three-inch minimum to both sides
of the CB780/CB784 for electrical signal voltage probes.
3. Make sure no subbase wiring is projecting beyond the terminal blocks. Tuck wiring in against the back of the sub­base so it does not interfere with the knife blade terminals or bifurcated contacts.
CB780/CB784
ASSEMBLY
Assembly
Fig. 11—Electrical panel installation.
IMPORTANT: The CB780/CB784 must be installed with a
plug-in motion rather than a hinge action.
4. Mount the CB780/CB784 by aligning the four L shaped corner guides and knife blade terminals with the bifurcated contacts on the wiring subbase and tightening the two screws securely without deforming the plastic.
INSTALLING THE PURGE CARD
1. Remove the Keyboard Display Module or Control Bus, see Fig. 13 or 14.
2. Remove the current Purge Card from the CB780/CB784 by pulling the plastic support cover upward .
3. Make sure that the Purge Card selected has the desired timing.
4. Insert Purge Card into the opening of the CB780/CB784 compartment, see Fig. 12.
5. Reinstall the Keyboard Display Module or Control Bus onto the CB780/CB784 and restore power to the device.
6. Run the burner system through at least one complete cycle to verify the system is operating as desired.
IMPORTANT: The CB780 will not function properly with-
out one of the following mounted correctly: Keyboard Display Module, or Control Bus .
MOUNTING KEYBOARD DISPLAY MODULE (VFD)
1. Align the two interlocking ears of the Keyboard Dis­play Module with the two mating slots on the CB780/CB784; see Fig. 13.
2. Insert the two interlocking ears into the two mating slots and with a hinge action push on the lower corners of the Keyboard Display Module to secure it to the CB780/CB784.
3. Verify the Keyboard Display Module is firmly in place.
MOUNTING CONTROL BUS
1. Align the two interlocking ears with the two mating slots on the CB780/CB784; see Fig. 14.
2. Insert the two interlocking ears into the two mating slots and push on the lower corners of the Control Bus to secure it to the CB780/CB784.
3. Be sure the Control Bus is firmly in place.
750-166 1-15
CB780/CB784 ASSEMBLY
Fig. 12—Purge Card installation.
MODULE (VFD)
1. The Keyboard Display Module (VFD) can be mounted either on the face of a panel door or on other remote locations; see Fig. 15.
2. When mounting the Keyboard Display Module on the face of a door panel, closely follow these instructions:
a. Select the location on the door panel for flush mount-
ing. Pay attention to the insertion dimension of the two Keyboard Display Module screws, two interlocking ears and the two plug-in connectors to allow for sufficient clearance, 1/4 inch minimum inward from the surface of the door panel.
b. Use the Keyboard Display Module as a template; see
Fig. 28. Mark the two screw locations, two interlock­ing ear locations and two plug-in connector locations. Drill the pilot holes for the mounting screws. Provide for two holes on the door panel for the interlocking ears and plug-in connector holes.
c. Mount the Keyboard Display Module securing the
two no. 4 screws.
Fig. 13—Keyboard Display Module mounting.
Fig. 14—Control Bus mounting.
REMOTE MOUNTING OF KEYBOARD DISPLAY
INSTALLING PLUG-IN FLAME SIGNAL AMPLIFIER
1. Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be involved.
2. Align the amplifier circuit board edge connector with the keyed receptacle on the CB780/CB784. Verify the am­plifier nameplate faces away from the Relay Module, see Fig. 16.
3. Push in the amplifier until the circuit board is fully inserted into the receptacle and then push the amplifier toward the CB780/CB784 retaining clasp.
4. Verify the amplifier is firmly in place.
5. Perform all required checkout tests.
INSTALLING THE FLAME DETECTOR
NOTE: Table 2 lists the flame detection systems available
for use with the CB780/CB784. Make sure the correct combination of amplifier and flame detector(s) is used.
Proper flame detector installation is the basis of a safe and reliable flame safeguard installation. Refer to the instruc­tions packed with the flame detector and the equipment manufacturer instructions; see Fig. 17.
Keep the flame signal leadwires as short as possible from the flame detector to the wiring subbase. Capacitance in­creases with leadwire length, reducing the signal strength. The maximum permissible leadwire length depends on the type of flame detector, leadwire and conduit. The ultimate limiting factor in the flame detector leadwire is the flame signal; see Table 9.
1-16 750-166
CB780/CB784
ASSEMBLY
Display Module.
Fig. 16—Flame signal amplifier mounting.
Fig.17—Flame detector wiring.Fig. 15—Remote mounting of Keyboard
INFRARED (817-1742)
F
3
G
ULTRAVIOLET (817-1743)
BLUE
F
1
WHITE
G
SOLID STATE SELF-CHECKING ULTRAVIOLET (817-1121)
BLUE
F
YELLOW
2
G
WHITE
22
WHITE
L2
BLACK
L1
BLACK
L2
FLAME DETECTOR LEADS ARE COLOR CODED. THE BLUE LEAD
1
MUST BE CONNECTED TO THE F TERMINAL AND THE WHITE MUST BE CONNECTED TO THE G TERMINAL. THE UV SENSING TUBE IS POLARITY SENSITIVE. REVERSING THE LEADS EVEN MOMENTARILY CAN DAMAGE OR DESTROY THE UV TUBE.
2
FLAME DETECTOR LEADS ARE COLOR CODED. THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE YELLOW MUST BE CONNECTED TO THE G TERMINAL. THE UV SENSING TUBE IS POLARITY SENSITIVE. REVERSING THE LEADS EVEN MOMENTARILY CAN DAMAGE OR DESTROY THE UV TUBE.
3
1 BROWN WIRE AND 1 WHITE WIRE FROM THE 817-1742, CONNECT TO THE CB 780/CB 784 WIRING SUBBASE, COLOR NOT IMPORTANT. KEEP WIRES AS SHORT AS POSSIBLE AND TWIST THEM.
M7410
750-166 1-17
CB780/CB784
MAIN IGN 00:15 Flame Signal 2.7V
OPERATION
Operation
SEQUENCE OF OPERATION
The CB780/CB784 has the following operating sequence,
see Fig. 18 and Table 4.
INITIATE
The CB780/CB784 enters the INITIATE sequence when the Relay Module is powered. The CB780/CB784 can also enter the INITIATE sequence if the Relay Module verifies voltage fluctuations of +10/-15% or frequency fluctuations of +/-10% during any part of the operating sequence. The INITIATE sequence lasts for ten seconds unless the voltage or frequency tolerances are not met. When the tolerances are not met, a hold condition will be initiated and will be displayed on the VFD for at least five seconds. When the tolerances are met, the INITIATE sequence will restart. If the condition is not corrected and the hold condition exists for four minutes, the CB780/CB784 will lockout. Causes for hold conditions in the INITIATE sequence:
a. AC line dropout is detected.
b. AC line frequency error caused by using a 60 Hz device
on a 50 Hz line, or vice versa.
c. AC line noise that can prevent a sufficient reading of
the line voltage inputs. d. Brownouts caused by a low line voltage. The INITIATE sequence
also delays the burner motor starter from being energized
INITIATE 00:10 Diagnostic Info
and de-energized from an intermittent AC line input or control input.
STANDBY
The CB780/CB784 is
ready to start an operating
STANDBY Total Cycles 132
sequence when the operat­ing control determines a call for heat is present. The burner switch, limits, operating control and all microcomputer moni­tored circuits must be in the correct state for the CB780/ CB784 to continue into the PREPURGE sequence.
NORMAL START-UP PREPURGE
The CB780/CB784 pro-
PURGE 00:30 Total Hours 396
vides a PREPURGE timing selectable from 30 seconds to 2-1/2 minutes with power applied and the CB780/CB784 operating control indicating a call for heat:
a. Running Interlocks, Preignition Interlocks, Burner
Switch, Run/Test Switch, Lockout Interlocks and all
microcomputer monitored circuits must be in the cor-
rect operating state. b. The blower motor output, terminal 5, is powered to
start the PREPURGE sequence. The firing rate motor
is driven to the high fire position. The PREPURGE
timing does not begin until the Lockout Interlock
String and High Fire Switch are both closed. c. The Preignition Interlock input must remain closed
throughout PREPURGE; otherwise, safety shutdown
occurs.
d. The Lockout Interlock or Running Interlock inputs
(interlock circuit including Airflow Switch) must close by ten seconds into PREPURGE; otherwise, a safety shutdown occurs.
e. After the firing rate motor reaches the PREPURGE
rate position and PREPURGE timing is completed, the firing rate motor will drive to the low fire position.
f. When the firing rate motor reaches low fire position,
the Low Fire Switch, terminal 18, input must be energized before entering the Ignition Trial state.
IGNITION TRIALS
a. Pilot Flame Establish-
ing Period (PFEP):
PILOT IGN 00:10 Fault History
1. With the firing rate motor at the low fire position: a. The pilot valve and the ignition transformer,
terminals 8, 10 and 21, are energized. The CB780/CB784 has a fifteen second interrupted pilot valve, terminal 21 and a ten second inter­rupted pilot valve/ignition, terminal 8.
b. During PFEP, the Low Fire Switch must remain
closed. If it opens, a safety shutdown occurs.
c. The Preignition Interlock input is ignored
throughout the Ignition Trial state.
2. Flame must be proven by the end of the four or ten second PFEP to allow the sequence to continue. If flame is not proven by the end of PFEP, a safety shutdown occurs.
3. With flame proven, the ignition, terminal 10, is de­energized for early spark termination.
b. Main Flame Establish-
ing Period (MFEP):
1. T h e CB780/CB784 has a selectable ten second or fifteen second MFEP. After the Ignition Trials, and with the pres­ence of flame, the main fuel valve, terminal 9, is powered. If a flameout occurs, the CB780/CB784 will lockout within 3 seconds.
RUN
1. A ten second stabilization period occurs at the begin-
ning of the RUN period.
2. The firing rate motor releases to modulation.
3. The CB780/CB784 is now in RUN and will remain in RUN until the controller input, terminal 6, opens, indicating that the demand is satisfied or a limit has opened.
POSTPURGE
The CB780/CB784 pro­vides a fifteen second POST-PURGE following
RUN Expanded Annun.
the completion of the RUN period. The blower motor output is powered to drive all products of combustion and any unburned fuel from the
1-18 750-166
CB780/CB784
OPERATION
combustion chamber. It also supplies combustion air to burn fuel being purged from the fuel line downstream of the fuel shutoff valve.
1. The main fuel valve and intermittent pilot valve, termi­nals 9 and 21, are de-energized and the firing rate motor is commanded to the low fire position to begin the POSTPURGE period.
Fig. 18—CB780/CB784 sequence.
PREPURGE
VFD DISPLAY
LED DISPLAY
BURNER
OPERATING CONTROLS AND INTERLOCKS
FLAME SIGNAL
FIRING RATE MOTOR
INITIATE
STANDBY
POWER
INTERLOCK CHECK
PREIGNITION INTERLOCK CLOSED
00
POWER
SAFE START CHECK
MOTOR OUTPUT SWITCHING
00 00 10 25 00 1520
DRIVE TO HIGH FIRE
5
TIMED PURGE
POWER
TO
POWER PILOT FLAME MAIN
BURNER/BLOWER MOTOR
LIMITS AND BURNER CONTROLLER CLOSED
LOCKOUT INTERLOCKS CLOSED
19
HIGH FIRE SW.
12
13
TO
MOTOR ACTION
2. The Preignition Interlock closes within the first five seconds of POSTPURGE.
3. After the fifteen second POSTPURGE period is com­pleted, the CB780/CB784 reenters STANDBY.
CB 780/CB 784
PREPURGE
00
DRIVE TO LOW FIRE
POWER PILOT FLAME MAIN
PFEP
4 OR 10 SEC
POWER PILOT FLAME MAIN
IGN.
10
10 SEC. IGN./PILOT
15 SEC. PILOT
4
LOW FIRE SW.
5 SEC.
20TO
MFEP
POWER PILOT
FLAME
MAIN
ALARMALARMALARMALARM
8
21
MAIN VALVE
L1
TO
6
18
5
TO
FLAME PROVING
14
13
TO
RUN POWER PILOT FLAME
MAIN
ALARM
5
6
7TO
13 15
TO
9
POST PURGE 00:12
Flame Signal 0.0V
Device RM7800L
POSTPURGE
13
POWER
TO
STANDBY
POWER
IC
PII
SSC
14
KEYBOARD DISPLAY MODULE (VFD)
The first line of the Vacuum Fluorescent Display (VFD) provides current status of the burner sequence (STANDBY, PURGE, PILOT IGN, MAIN IGN, RUN and POST­PURGE), timing information (PURGE, PILOT IGN, MAIN IGN and POSTPURGE) in minutes and seconds, hold infor­mation (PURGE HOLD: T19) and lockout information (Lockout, Fault Code, Message and Sequence); see Fig. 19. The extreme right side of the first line will either be blank or it will show a small arrow pointing to the second line followed by a two-letter code (DI-Diagnostic Information, Hn-Fault History Information, and EA-Expanded Annun­ciator). When the arrow and two-letter code are displayed, it indicates the second line is showing a selectable message submenu. The second line will display selectable or preemp­tive messages. A selectable message supplies information for flame strength, system status indication, system or self-diag­nostics and troubleshooting. A preemptive message will have parentheses around the message and supply a detailed mes­sage to support the sequence status information. A preemp­tive message can also be a lockout message. A preemptive
M7411
Fig. 19—Keyboard Display Module and sequence status LEDs (Table 4).
FIVE WIRE CONNECTOR FOR COMMUNICATIONS, REMOTE KEYBOARD DISPLAY AND REMOTE RESET
RUN/TEST SWITCH
SEQUENCE STATUS
SELECTABLE MESSAGE OR PREEMPTIVE MESSAGE
SEQUENCE STATUS LEDs
RESET PUSH BUTTON
FLAME SIMULATOR INPUT
* NOTE: REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
*
FLAME CURRENT TEST JACKS
DI = DIAGNOSTICS H1 = HISTORY EA = EXPANDED ANNUNCIATOR
CAPTIVE MOUNTING SCREW
PLUG-IN PURGE CARD
KEYBOARD DISPLAY MODULE
RELAY MODULE
FLAME AMPLIFIER
M7395
750-166 1-19
CB780/CB784 OPERATION
message will replace a selectable message to support the sequence status information. It will also replace a selectable message after 60 seconds if it or a lockout message is
TABLE 4—SEQUENCE STATUS DISPLAY INFORMATION (See Fig. 19).
NOTE: Normal sequences are in BOLD TYPE, while abnormal sequences are not in bold type.
Burner Sequence LEDs Energized
INITIATE minutes:seconds
POWER, PILOT, FLAME, MAIN AND ALARM
selectable—message INITIATE HOLD: AC
POWER, PILOT, FLAME, MAIN AND ALARM
(AC Freq/Noise) INITIATE HOLD: AC
POWER, PILOT, FLAME, MAIN AND ALARM
(AC Line Dropout) INITIATE HOLD: AC
POWER, PILOT, FLAME, MAIN AND ALARM
(AC Frequency) INITIATE HOLD: AC
POWER, PILOT, FLAME, MAIN AND ALARM
(Low Line Voltage)
STANDBY
POWER, PILOT, FLAME, MAIN AND ALARM
selectable —message STANDBY HOLD: REM
POWER, PILOT, FLAME, MAIN AND ALARM
(Remote Control) STANDBY HOLD: F/G
POWER, PILOT, FLAME, MAIN AND ALARM
(Flame Detected) STANDBY HOLD: T20
POWER, PILOT, FLAME, MAIN AND ALARM
(Preignition ILK) STANDBY HOLD: T7
POWER, PILOT, FLAME, MAIN AND ALARM
(Running ILK) STANDBY HOLD: T7
POWER, PILOT, FLAME, MAIN AND ALARM
(Lockout ILK)
PURGE HOLD: T19
POWER, PILOT, FLAME, MAIN AND ALARM
(High Fire Switch) PURGE DELAY: T19
POWER, PILOT, FLAME, MAIN AND ALARM
(High Fire Jumprd) PURGE HOLD: TEST
POWER, PILOT, FLAME, MAIN AND ALARM
(Run/Test Switch) PURGE DELAY: T18
POWER, PILOT, FLAME, MAIN AND ALARM
(Low Fire Jumprd) PURGE HOLD: F/G
POWER, PILOT, FLAME, MAIN AND ALARM
(Flame Detected)
PURGE HOLD: T18
POWER, PILOT, FLAME, MAIN AND ALARM
(Low Fire Switch)
PURGE minutes:seconds
POWER, PILOT, FLAME, MAIN AND ALARM
selectable—message PURGE HOLD: T7
POWER, PILOT, FLAME, MAIN AND ALARM
(Running ILK)
PILOT IGN minutes:seconds
POWER, PILOT, FLAME, MAIN AND ALARM
selectable—message PILOT HOLD: TEST
POWER, PILOT, FLAME, MAIN AND ALARM
(Run/Test Switch)
MAIN IGN minutes:seconds
POWER, PILOT, FLAME, MAIN AND ALARM
selectable—message
RUN
POWER, PILOT, FLAME, MAIN AND ALARM
selectable—message
RUN
POWER, PILOT, FLAME, MAIN AND ALARM
selectable—message RUN LOWFIRE: TEST
POWER, PILOT, FLAME, MAIN AND ALARM
(Run/Test Switch)
available. The CB780/CB784 LEDs provide positive visual indication of the program sequence: POWER, PILOT, FLAME, MAIN and ALARM.
(continued)
1-20 750-166
CB780/CB784
OPERATION
TABLE 4—SEQUENCE STATUS DISPLAY INFORMATION (See Fig. 19) (Continued).
NOTE: Normal sequences are in BOLD TYPE, while abnormal sequences are not in bold type.
Burner Sequence LEDs Energized
POSTPURGE minutes:seconds
POWER, PILOT, FLAME, MAIN AND ALARM
selectable—message Waiting for connection… POWER, PILOT, FLAME, MAIN AND ALARM RESET/ALARM TEST
POWER, PILOT, FLAME, MAIN AND ALARM
selectable—message
Additional sequence status information when an Expanded Annunciator is connected to the relay module, also see
Additioanl sequence status information when an Expanded Annunciator is connected to the relay module. Also see
CB 780/CB 784 System Annunciation Diagnostics and Troubleshooting, Bulletin Number CB-7803.
CB780/CB784 Operating and Maintenance Manual, Manual Number 750-166.
BURNER OFF: T6
POWER,PILOT, FLAME, MAIN AND ALARM
(Burner Switch) STANDBY HOLD: T6
POWER, PILOT, FLAME, MAIN AND ALARM
(Expanded Annunciator hold message) STANDBY HOLD: T6
POWER, PILOT, FLAME, MAIN AND ALARM
(Circuit Fault)
KEYBOARD FUNCTIONS
The keyboard contains four pushbuttons and each has separate functions (SCROLL-Down, SCROLL-Up, MODE and Change-Level). The MODE and Change-Level push­buttons, when pressed together, provide a SAVE function.
1. SCROLL Down-Up pushbuttons (), see Fig. 20.
The SCROLL Down-Up pushbuttons () are used to scroll through the selectable messages. The double-headed
Fig. 20—() SCROLL pushbutton function.
BURNER CONTROL
RUN Total Cycles 333
SCROLL
MODE
SAVE
arrow (), which is located in the lower left position of the second line of the display, represents the SCROLL Down­Up pushbuttons. The SCROLL Down-Up pushbuttons (↕) can be pressed to display selectable messages one at a time or held down to scroll through the selectable messages at a rate of two per second. When the last item of the selectable message is viewed, the display wraps around and displays the first selectable message again.
BURNER CONTROL
RUN Total Hours 1332
SCROLL
MODE
SAVE
M7401
2. Change-Level pushbutton (), see Fig. 21.
The Change-Level pushbutton is used to change between the first hierarchy of selectable messages to a subset of selectable messages. The Change-Level pushbutton can also be used to change from a subset message to a first level selectable message. The symbol (>) located on the second line in the lower right corner of the VFD represents a first level hierarchy of selectable messages. The symbol (<) located on the second line in the lower right corner of the VFD represents a subset of selectable messages.
750-166 1-21
3. MODE pushbutton, see Fig. 22.
The MODE pushbutton instantaneously switches the display from a second-line-selectable message to second- line-preempted message. The sixty second timeout function also can be used for this task. The MODE pushbutton will work only if there is a second-line-preempted message or lockout message.
CB780/CB784 OPERATION
Fig. 21 ()—Change-Level pushbutton function.
BURNER CONTROL
PILOT IGN 00:05
Fault History
SCROLL
MODE
Fig. 22—MODE pushbutton function.
BURNER CONTROL
LOCKOUT #17 MFEP Main Valve T9 Off
SCROLL
MODE
SAVE
SAVE
BURNER CONTROL
PILOT IGN 00:10 H1 Fault Cycle 174
SCROLL
MODE
BURNER CONTROL
LOCKOUT #17 MFEP
*Main Flame Fail*
SCROLL
MODE
SAVE
SAVE
M7402
The SAVE function enables users to identify the select­able message they want to view upon power restoration. The second line selectable message will be restored to the most recently saved selection when power returns. The SAVE function is performed by pressing and holding the MODE key and then pressing the Change-Level pushbutton (). The second line of the display will briefly note “…SAV­ING…” to confirm the key press.
SELECTABLE MESSAGES
VFD Second Line Display, Two-Level Hierarchy, see Table 5.
The display values are as follows:
n represents a numbered value. T represents the terminal number. x represents the suffix letter of the Relay Module.
M7403
Fig. 23—SAVE function.4. SAVE function; see Fig. 23.
BURNER CONTROL
PURGE 00:30 ... SAVING ...
SCROLL
MODE
SAVE
M7404
1-22 750-166
CB780/CB784
OPERATION
TABLE 5—SELECTABLE MESSAGES.
Selectable Message Display Value First Line
(Second Line) (Second Line) Message
Flame Signal n.nV
Total Cycles nnnnn
Total Hours nnnnn
Fault History
Fault Cycle nnnnn < H1Fault Hours nnnnn < H1Fault Code nnn < H1*fault —message*< H1sequence—message< H1(second-line-msg)< H1Fault Cycle nnnnn < H2Fault Hours nnnnn < H2Fault Code nnn < H2*fault —message*< H2sequence—message< H2(second-line-msg)< H2Fault Cycle nnnnn < H3Fault Hours nnnnn < H3Fault Code nnn < H3*fault —message*< H3sequence—message< H3(second-line-msg)< H3Fault Cycle nnnnn < H4Fault Hours nnnnn < H4Fault Code nnn < H4*fault —message*< H4sequence—message< H4(second-line-msg)< H4Fault Cycle nnnnn < H5Fault Hours nnnnn < H5Fault Code nnn < H5*fault —message*< H5sequence—message< H5(second-line-msg)< H5Fault Cycle nnnnn < H6Fault Hours nnnnn < H6Fault Code nnn < H6*fault —message*< H6sequence—message< H6(second-line-msg)< H6
Diagnostic Info
Device RM78nnx < DIDevice Suffix nnnn < DIRun/Test Sw. RUN or TEST < DIOperating Control (OperControl) T6 ON or OFF < DIInterlock T7 ON or OFF < DIPilot Valve T8 ON or OFF < DIMain Valve T9 ON or OFF < DIIgnition T10 ON or OFF < DILowFire Sw T18 ON or OFF < DIHighFireSw T19 ON or OFF < DIPreignition Interlock (PreIgn ILK) T20 ON or OFF < DIPilot Valve/First Stage OilValve (Valv/Start,V25) T21 ON or OFF < DIJumper 1 INTACT or CLIPPED < DIJumper 2 INTACT or CLIPPED < DIJumper 3 INTACT or CLIPPED < DIAmplifier Type (Amp Type) NORMAL or AMP-CHECK or SHUTTER DIFlame Response 0.8s or 3s < DIPurge Time mm:ss < DIManufacturing Code (Mfg Code) nnnn < DI
Software Revision (SW Rev.) nnnn/nnnn < DIExpanded Annun. (see Table 5)Remote Command NONE/HOLD/HF/LF
750-166 1-23
CB780/CB784 OPERATION
EXPANDED ANNUNCIATOR MESSAGES, SEE TABLE 6
The Expanded Annunciator (EA) may or may not be
connected because it is an optional device. If the EA is not connected, a display message of “(EA not connected)” will
shown, see Table 6 and the Diagnostic and Troubleshooting section of the CB780/CB784 Operation and Maintenance Manual, Manual No. 750-166, Tables 6 and 7 for fault codes. When accessing Expanded Annunciator Messages, follow the same operations as used with the Selectable Messages.
be shown. If the EA is connected, display messages will be
TABLE 6—EXPANDED ANNUNCIATOR MESSAGES.
Selectable Message Display Value First Line (Second Line) (Second Line) Message
Expanded Annun.Expanded Annunciator (EA not connected)<Current Status (CS:)Valve Closure (Valve Close) T4 ON or OFF< EABurner Switch (Burner Sw.) T5 ON or OFF< EAOperating Control (OperControl) T6 ON or OFF< EAAuxiliary Limit (Aux Limit 1) T7 ON or OFF< EAAuxiliary Limit (Aux Limit 2) T8 ON or OFF< EALow Water Cutoff (LWCO) T9 ON or OFF< EAHigh Limit (High Limit) T10 ON or OFF< EAAuxiliary Limit (AuxLimit 3) T11 ON or OFF< EAOil Selection Switch (Oil Select) T12 ON or OFF< EAHigh Oil Pressure Switch (Hi OilPres) T13 ON or OFF< EALow Oil Pressure Switch (LowOilPres) T14 ON or OFF< EAHigh Oil Temperature Switch (Hi OilTemp) T15 ON or OFF< EALow Oil Temperature Switch (LowOilTemp) T16 ON or OFF< EAAtomizing Switch (Atomize Sw) T19 ON or OFF< EAGas Selection Switch (Gas Select) T17 ON or OFF< EAHigh Gas Pressure Switch (Hi GasPres) T18 ON or OFF< EALow Gas Pressure Switch (LowGasPres) T19 ON or OFF< EAAirflow Switch (Airflow Sw) T20 ON or OFF< EAAuxiliary Interlock (Aux ILK 4) T21 ON or OFF< EAAuxiliary Interlock (Aux ILK 5) T22 ON or OFF< EAEA Fault Code nnn< EASoftware Revision (SW Rev.) nnnn< EA
a
Expanded Annunciator Diagnostic Current Status Messages can be reviewed in CB780/CB784 Operating and Maintenance
a
EA Message< ↓EA
Manual, Manual Number 750-166.
RUN/TEST SWITCH FUNCTIONS
The Run/Test Switch is located on the top side of the
CB780/CB784; see Fig. 19. The Run/Test Switch allows the burner sequence to be altered as follows:
1. In Prepurge Drive To High Fire Position, the Run/Test
Switch, when placed in the TEST position, will hold in PREPURGE with the firing rate motor in the High Fire position.
2. In the measured PREPURGE sequence, the Run/Test
Switch, when placed in the TEST position, will cause the PREPURGE timing to stop. The firing rate motor will be in the High Fire position.
3. In Prepurge Drive to Low Fire position, the Run/Test
Switch, when placed in the TEST position, will hold the burner sequence in PREPURGE with the firing rate motor in the Low Fire position.
4. In PFEP, the Run/Test Switch, when placed in the
TEST position, will stop the timer during the first eight seconds when a ten second PFEP is selected or during the first three seconds when a four second PFEP is selected, allowing pilot-turn-down test and other burner adjustments
1-24 750-166
to be made. This activates a fifteen second flameout timer that permits pilot flame adjustment without nuisance safety shutdowns. The Run/Test Switch will be ignored during PFEP for the CB780/CB784 if terminals 8 and 9 or 9 and 21 are jumpered.
5. During RUN, the Run/Test Switch, when placed in the TEST position, will drive the firing rate motor to the Low Fire position.
NOTE: When CB780/CB784 is switched to the TEST mode,
it will stop and hold at the next Run/Test Switch point in the operating sequence. Make sure that the Run/Test
Switch is in the RUN position before leaving the installa­tion.
SELECTABLE SITE-CONFIGURABLE JUMPERS
The CB780/CB784 has two site-configurable jumper options; see Fig. 24 and Table 7. The site-configurable jumpers should be clipped with side cutters and the resistors removed from the Relay Module.
TABLE 7—SITE CONFIGURABLE
JUMPER OPTIONS.
Jumper
Number Description Intact Clipped
JR1 Pilot Flame
Establishing Period (PFEP)
JR3 Start-up
Interlock Check
NOTE: For all standard installations, these jumpers
should be left intact, unless otherwise indicated on wiring diagram.
10 Seconds 4 Seconds
Disabled Enabled
CB780/CB784
OPERATION • STATIC CHECKOUT
Fig. 24—Selectable site-configurable jumpers.
SELECTABLE CONFIGURATION JUMPERS
RUN/TEST SWITCH
M7397
CA UTION
1. Use extreme care while testing the system. Line voltage is present on most terminal connections when power is on.
2. Open the master switch before installing or removing a jumper on the subbase.
3. Before continuing to the next test, be sure to remove test jumper(s) used in the previous test.
4. Replace all limits and interlocks that are not operating properly. Do not bypass limits and interlocks.
5. Close all manual fuel shutoff valve(s) before starting these tests.
After checking all wiring, perform this checkout before installing the CB780/CB784 on the subbase. These tests verify the Wiring Subbase is wired correctly, and the exter­nal controllers, limits, interlocks, actuators, valves, trans­formers, motors and other devices are operating properly.
NOTE: Do not perform a dielectric test with theCB780/CB784
installed. Internal surge protectors will break down and
conduct a current. This could cause the CB780/CB784 to
fail the dielectric test or possibly destroy the internal
lightning and high current protection.
Static Checkout
EQUIPMENT RECOMMENDED
1. Voltmeter (20 kohm/volt minimum sensitivity) set on
the 0-300 Vac scale.
2. Two jumper wires; no. 14 wire, insulated, 12 inches
[304.8 mm] long with insulated alligator clips at both ends.
GENERAL INSTRUCTIONS
1. Perform all applicable tests listed in Static Checkout,
Table 8, in the order listed.
2. Make sure all manual fuel shutoff valve(s) are closed.
3. Raise the setpoint of the operating controller to simu-
late a call for heat.
4. For each test, open the master switch and install the
jumper wire(s) between the subbase wiring terminals listed in the Test Jumpers column.
5. Close the master switch before observing operation.
6. Read the voltage between the subbase wiring termi-
nals listed in the Voltmeter column.
7. If there is no voltage or the operation is abnormal, check the circuits and external devices as described in the last column.
8. Check all wiring for correct connections, tight termi­nal screws, correct wire, and proper wiring techniques. Re­place all damaged or incorrectly sized wires.
9. Replace faulty controllers, limits, interlocks, actuators, valves, transformers, motors and other devices as required.
10. Ensure normal operation is obtained for each required
test before continuing the checkout.
11. After completing each test, be sure to remove the
test jumper(s).
750-166 1-25
CB780/CB784 STATIC CHECKOUT
Test
No.
Test
Jumpers
WARNING
Make sure all manual fuel shutoff valves are closed.
IMPORTANT: Low fuel pressure limits, if used, could be open. Bypass them with jumpers for the remaining Static
Tests (if required).
2 None 6-L2 Line voltage at terminal 6. 1. Limits.
3 None 20-L2 Line voltage at terminal 20. 1. Preignition interlocks. 4 4-5 7-L2 1. Burner motor (fan or blower) starts.
5 4-10 Ignition spark (if ignition transformer is
6 4-8 1. Ignition spark (if ignition transformer is
7 4-21 Same as test no. 6 for connections to terminal 8.
8 4-9 Automatic main fuel valve(s) open. If using
9 4-3 Alarm (if used) turns on. 1. Alarm.
10. 4-5 and 12-13
11 4-5 and
14-13
12 4-5 and
12-13
13 4-5 and
14-13
TABLE 8—STATIC CHECKOUT.
Volt-
meter Normal Operation
1None 4-L2 Line voltage at terminal 4. 1. Master switch.
2. Line voltage at terminal 7 within 10 seconds.
connected to terminal 10).
connected to terminal 8).
2. Automatic pilot valve opens (if con­nected to terminal 8).
NOTE: Refer to wiring diagram of system
being tested.
If using direct spark ignition, check the first stage fuel valve(s) instead of pilot valve.
direct spark ignition with intermittent pilot on terminal 21, check the optional second stage fuel valve, if used.
18-L2 Firing rate motor drives open; zero volts at
terminal 18 after motor starts driving open.
18-L2 Firing rate motor drives closed; line voltage at
terminal 18 after motor is in Low Fire position.
19-L2 Firing rate motor drives open; line voltage at
terminal 19 after motor is in High Fire position.
19-L2 Firing rate motor drives closed; zero volts at
terminal 19 after m otor starts driving closed.
If Operation is Abnormal, Check the
Items Listed Below
2. Power connected to the master switch.
3. Overload protection (fuse, circuit breaker, etc.) has not opened the power line.
2. Burner controller.
1. Burner motor circuit. a. Manual switch of burner motor. b. Burner motor power supply,
overload protection, and starter.
c. Burner motor.
2. Running or Lockout Interlocks (including Airflow Switch).
1. Watch for spark or listen for buzz. a. Ignition electrodes are clean. b. Ignition transformer is okay.
1. Watch for spark or listen for buzz. a. Ignition electrodes are clean. b. Ignition transformer is okay.
2. Listen for click or feel head of valve for activation. a. Actuator if used. b. Pilot valve.
Same as test no. 6. If using direct spark ignition, check the first stage fuel valve(s) isntead of the pilot valve.
1. Listen for and observe operation of the main fuel valve(s) and actuator(s).
2. Valve(s) and actuator(s).
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
1. Low Fire Start switch.
2. Firing rate motor and transformer.
1. High Fire Purge Switch.
2. Firing rate motor and transformer.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
1-26 750-166
(Continued)
CB780/CB784
STATIC CHECKOUT • CHECKOUT
TABLE 8—STATIC CHECKOUT (Continued).
Test
No.
IMPORTANT: Low fuel pressure limits, if used, could be open. Bypass them with jumpers for the remaining Static
14 15-13 1. Raise set point of Series 90 controller—
Final
Test
Jumpers
WARNING
Make sure all manual fuel shutoff valves are closed.
Tests (if required).
Volt-
meter Normal Operation
firing rate motor should drive toward open.
2. Lower setpoint of Series 90 controller— firing rate motor should drive toward closed.
CAUTION
On completing these tests, open the master switch and remove all test jumpers from the subbase terminals. Also remove bypass jumpers from the low fuel pressure limits (if used).
If Operation is Abnormal, Check the
Items Listed Below
1. Series 90 Controller.
2. Firing rate motor and transformer.
Checkout
WARNING
Do not allow fuel to accumulate in the combus- tion chamber. If fuel is allowed to enter the chamber for longer than a few seconds without igniting, an explosive mixture could result. It is recommended that you limit the trial for pilot to ten seconds, and limit the attempt to light the main burner to two seconds from the time the fuel has reached the burner nozzle. In any case, do not exceed the nominal lightoff time specified by the equipment manufacturer; close the manual fuel shutoff valve(s) if the flame is not burning at the end of the specified time.
CA UTION
1. Use extreme care while testing the system. Line voltage is present on most terminal connections when power is on.
2. Open the master switch before removing or in- stalling the CB780/CB784 or Keyboard Dis- play Module connector.
3. Make sure all manual fuel shutoff valve(s) are closed before starting the initial lightoff check and the Pilot Turndown tests.
4. Do not put the system in service until you have satisfactorily completed all applicable tests in this section and any others required by the equipment manufacturer.
IMPORTANT:
1. If the system fails to perform properly, note the fault code, fault message, equipment status, and sequence time on the display. Refer to the Troubleshooting sec­tion of the CB780/CB784 Operation and Maintenance Manual, Manual Number 750-166.
2. Repeat ALL required Checkout tests after all adjust­ments are made. ALL tests must be satisfied with the flame detector(s) in its FINAL position.
EQUIPMENT RECOMMENDED
Volt-ohmmeter (20 kohm/volt minimum sensitivity) with:
• 0-300 Vac capability.
• 0-6000 ohm capability.
• 0-10 Vdc capability.
CHECKOUT SUMMARY
• Preliminary inspection—all installations.
• Flame signal measurement—all installations.
• Initial lightoff check for proved pilot—all installations using a pilot.
• Initial lightoff check for direct spark ignition of oil— all burners using DSI.
• Pilot turndown test—all installations using a pilot.
• Hot refractory saturation test—all installations using Infrared (lead sulfide) Flame Detectors.
• Hot refractory hold-in test—all installations.
• Ignition interference test—all installations using flame rods.
• Ignition spark pickup—all installations using Ultra­violet Flame Detectors.
• Response to other ultraviolet sources—all installa­tions using Ultraviolet Flame Detectors.
750-166 1-27
CB780/CB784 CHECKOUT
• Flame signal with hot combustion chamber—all installations.
• Safety shutdown tests—all installations.
See Figs. 1 and 2 for location of component parts and
Fig. 7 or wiring subbase specifications for terminal locations.
7. Power is connected to the system disconnect switch,
(master switch).
8. Lockout is reset (push in reset button) only if the Relay
Module is powered; see Figs. 1 and 2.
9. Run/Test Switch is in RUN position.
10. System is in the STANDBY condition. STANDBY
PRELIMINARY INSPECTION
Perform the following inspections to avoid common
message is viewable in the VFD.
11. All limits and interlocks are reset.
problems. Make certain that:
1. Wiring connections are correct and all terminal screws
are tight.
2. Flame detector(s) is clean, and installed and positioned
properly. Consult the applicable instructions.
3. Correct combination of amplifier and flame detec-
tor(s) is used. See Table 2 in the Specifications section.
4. Plug-in amplifier and purge card are securely in place.
5. Burner is completely installed and ready to fire; con-
sult equipment manufacturer instructions. Fuel lines are purged of air.
6. Combustion chamber and flues are clear of fuel and
fuel vapor.
FLAME SIGNAL MEASUREMENT (TABLE 9 AND FIG. 26)
Measure the flame signal at the appropriate times as defined in the following Checkout tests. Read the flame signal in volts dc at the flame amplifier test jacks + and (Com) or at the Keyboard Display Module.
1. Use 1M ohm/volt meter with a 0 to 10 Vdc capability.
2. Set the 1M ohm/volt meter to the 0 to 10 Vdc range.
3. Insert the positive (red) probe into the + jack of the flame amplifier. Insert the negative (black) probe into the (Com) jack of the flame amplifier; see Fig. 26.
4. Allow a few seconds for the meter reading to stabilize.
TABLE 9—FLAME SIGNAL.
Flame
Detector
817-1121 833-2741 817-1742 833-2722 or
Flame Signal
Amplifier
b
833-2723
c
Minimum Acceptable
Steady dc Voltage
a
Maximum Expected
1.25 Vdc 5.0 Vdc at Keyboard Display Module
or
dc Voltage
817-1743 833-2724 5.0 Vdc at 1M ohm/volt meter
a
This minimum or stronger signal should easily be obtained if the detector is correctly installed and positioned to properly sense the flame. This voltaged must be obtained before completing checkout.
b
The flame signal amplifier circuitry istested one-half second every five seconds during burner operation and shuts down the
burner if the amplifier fails (all installations).
c
This flame amplifier is Auto-Check type.
5. If using Auto-Check or shutter check amplifiers, read
Fig. 26—Flame signal measurement.
the average stable voltage, disregarding the peaks and val­leys caused by the self-checking operation.
6. The meter reading must be as specified in Table 8 after
all tests are completed and all adjustments made.
As an option, the flame signal can be checked by using the
Keyboard Display Module.
NEGATIVE (-) METER LEAD
POSITIVE (+) METER LEAD
ONE MEGOHM/VOLT METER
If the signal is unstable or less than the minimum accept-
able voltage, check flame detector installation and circuitry.
1. Check the supply voltages at terminals 4 (L1) and L2 (N). Make sure the master switch is closed, connections are correct, and the power supply is of the correct voltage, fre­quency and is sinusoidal.
2. Check the detector wiring for defects including:
• Incorrect connections.
• Wrong type of wire.
• Deteriorated wire.
• Open circuits.
M7383
• Short circuits.
• Leakage paths caused by moisture, soot or accu­mulated dirt.
1-28 750-166
CB780/CB784
CHECKOUT
3. For all optical detectors, clean the detector viewing
window and inside of the sight pipe as applicable.
4. With the burner running, check temperature at the de-
tector. If it exceeds the detector maximum rated temperature:
• Add a heat block to stop conducted heat traveling up the sight pipe.
• Add a shield or screen to reflect radiated heat.
• Add cooling (refer to sight pipe ventilation in the detector Instructions).
5. Make sure the flame adjustment is not too lean.
6. Make sure the detector is properly sighting the flame.
7. If necessary, resight or reposition the detector.
INITIAL LIGHTOFF CHECK FOR PROVED PILOT
Perform this check on all installations that use a pilot. It
should immediately follow the preliminary inspection. NOTE: Low fuel pressure limits, if used, could be open. If
so, bypass them with jumpers during this check.
1. Open the master switch.
2. Make sure that the manual main fuel shutoff valve(s) is closed. Open the manual pilot shutoff valve. If the pilot takeoff is downstream from the manual main fuel shutoff valve(s), very slightly open the manual main valve to supply pilot gas flow. Make sure the main fuel is shut off just up­stream from the burner inlet, or disconnect power from the automatic main fuel valve(s).
3. Close the master switch and start the system with a call for heat by raising the set point of the operating control­ler; see Fig. 19 or CB780/CB784 sequence. The program should start the ten second INITIATE sequence.
4. Let the sequence advance through PREPURGE. When the PILOT IGN status is displayed on the Keyboard Display Module, ignition spark should occur and the pilot should light. If the pilot ignites, the FLAME LED will be energized. Proceed to step 7.
5. If the pilot flame is not established in ten seconds, safety shutdown occurs. Let the sequence complete its cycle. Consult the equipment operating manual for further information.
6. Push the reset pushbutton, and let the system recycle once. If the pilot still does not ignite, make the following ignition/pilot adjustments:
a. Open master switch and remove the CB780/CB784
from the subbase.
b. On the subbase, temporarily jumper terminal 4 to
ignition terminals 8, 10 or 21; refer to the appropri­ate wiring diagram to determine the proper termi­nal. Disconnect the leadwire to the pilot valve if it is connected to the same terminal.
c. Close the master switch to energize only the igni-
tion transformer.
d. If the ignition spark is not strong and continuous,
open the master switch and adjust the ignition electrode spark gap setting to the manufacturer
recommendations. e. Make sure the ignition electrodes are clean. f. Close the master switch and observe the spark.
g. After a continuous spark is obtained, open the master
switch and add a jumper on the subbase from terminal 4 (L1) to the pilot terminal 8 or 21. Recon­nect the leadwire from the pilot valve if it was disconnected in step b.
h. Close the master switch to energize both the igni-
tion transformer and the pilot valve.
i. If the pilot does not ignite and if the ignition spark
is still continuous, adjust the pressure regulator until a pilot is established.
j. When the pilot ignites properly and stays ignited,
open the master switch and remove the jumper(s)
from terminals 4-8, 4-10 and 4-21 of the subbase. k. Check for adequate bleeding of the fuel line. l. Reinstall the CB780/CB784 on the subbase, close
the master switch, and then return to step 4.
7. When pilot ignites, measure the flame signal. If the pilot flame signal is unsteady or approaching the 1.25 Vdc minimum value, adjust the pilot flame size or detector sighting to provide a maximum and steady flame signal.
8. Recycle the system to recheck lightoff and pilot flame signal.
9. When the MAIN IGN period is displayed on the VFD, make sure the automatic main fuel valve is open; then smoothly open the manual main fuel shutoff valve(s) and watch for main burner flame ignition. When the main burner flame is established, proceed to step 15.
10. If the main burner flame is not established within
ten second s, close the manual main fuel shutoff valve(s).
11. Recycle the system to recheck the lightoff and pilot
flame signal.
12. Smoothly open the manual fuel shutoff valve(s) and try lightoff again. (The first reattempt may have been re­quired to purge the lines and bring sufficient fuel to the burner.)
13. If the main burner flame is not established within five seconds or the normal lightoff time specified by the equipment manufacturer, close the manual main fuel shutoff valves(s). Check all burner adjustments.
14. If the main burner flame is not established after two attempts:
a. Check for improper pilot size. b. Check for excess combustion air at low fire. c. Check for adequate low fire fuel flow. d. Check for proper gas supply pressure. e. Check for proper valve operation. f. Check for proper pilot flame positioning.
15. Repeat steps 10 through 14 to establish the main burner flame; then proceed to step 16.
16. With the sequence in RUN, make burner adjustments for flame stability and Btu input rating.
17. Shut down the system by opening the burner switch or by lowering the set point of the operating controller. Make sure the main flame goes out. There may be a delay due to gas trapped between the valve(s) and burner. Make sure all automatic fuel valve(s) close.
750-166 1-29
CB780/CB784 CHECKOUT
18. Restart the system by closing the burner switch and/or raising the set point of the operating controller. Observe that the pilot is established during PILOT IGN and the main burner flame is established during MAIN IGN within the normal lightoff time.
19. Measure the flame signal. Continue to check for the proper signal, see Table 9, through the RUN period. Check the signal at both High and Low Firing Rate positions and while modulating.
20. Run the burner through another sequence, observing the flame signal for:
a. Pilot flame alone (DSI). b. Pilot and main flame together. c. Main flame alone (unless monitoring an intermit-
tent pilot). Also observe the time it takes to light the main flame. Ignition of main flame should be smooth.
21. Make sure all readings are in the required ranges before proceeding.
22. Return the system to normal operation. NOTE: After completing these tests, open the master switch
and remove all test jumpers from the subbase terminals, limits/controls or switches.
INITIAL LIGHTOFF CHECK FOR DIRECT SPARK IGNITION
This check applies to gas and oil burners not using a pilot. It should immediately follow the preliminary inspection. Refer to the appropriate sample block diagram of field wiring for the ignition transformer and fuel valve(s) hookup.
NOTE: Low fuel pressure limits, if used, could be open. If so,
bypass them with jumpers during this check.
1. Open the master switch.
2. Complete the normal ready-to-fire checkout of the fuel supply and equipment as recommended by the equip­ment manufacturer.
3. Close all manual main fuel shutoff valve(s). Check that the automatic fuel valve(s) are closed. Make sure fuel is not entering the combustion chamber.
4. Close the master switch and start the system with a call for heat by raising the setpoint of the operating controller, see Fig.18 for CB780/CB784 sequencing. The program sequence should start the ten second INITIATE sequence.
5. Let the sequence advance through PREPURGE. Igni­tion spark should occur after PREPURGE period. Listen for the click of the first stage fuel solenoid valve(s).
6. Let the program sequence complete its cycle.
7. Open the manual fuel shutoff valve(s).
8. Push the reset button and recycle the program se­quence through PREPURGE.
9. When PILOT IGN status is displayed , watch that the first stage burner flame is established. If it is established, proceed to step 15.
10. If the first stage burner flame is not established within ten seconds, close the manual fuel shutoff valve(s), and open the master switch after POSTPURGE is completed.
11. Check all burner adjustments.
12. Wait about three minutes. Close the master switch, open the manual fuel shutoff valve(s), and try to lightoff the burner again. The first attempt may have been required to purge the lines and bring sufficient fuel to the burner.
13. If the first stage burner flame is not established within ten seconds, close the manual fuel shutoff valve(s), and open the master switch.
14. If necessary, repeat steps 11 through 13 to establish the first stage burner flame. Then proceed to step 15.
15. When the first stage burner flame is established, the sequence will advance to RUN. Make burner adjustments for flame stability and input rating. If a second stage is used, proceed to step 18.
16. Shut down the system by opening the burner switch or by lowering the set point of the operating controller. Make sure the burner flame goes out and all automatic fuel valve(s) close.
17. If used, remove the bypass jumpers from the low fuel pressure limit and subbase.
18. If a second stage is used, make sure the automatic sec­ond stage fuel valve(s) has opened. Check the lightoff as follows (otherwise proceed to step 19):
a. Open the manual second stage fuel valve(s). b. Restart the system by raising the set point of the
operating controller.
c. When the first stage burner flame is established,
watch for the automatic second stage fuel valve(s) to open. Observe that the second stage lights off properly.
d. Make burner adjustments for flame stability and
input rating.
e. Shut down the system by lowering the set point of
the operating controller. Make sure the burner flame goes out and all automatic fuel valve(s) close.
f. Proceed to step 19.
19. Restart the system by closing the burner switch and/or raising the set point of the operating controller. Observe that the burner flame is established during PILOT IGN, within the normal lightoff time specified by the equipment manufacturer.
20. Measure the flame signal. Continue to check for the proper signal, see Table 9, through the RUN period. Check the signal at both high and low firing rate positions and while modulating. Any pulsating or unsteady readings will require further attention.
21. Make sure all readings are in the required ranges before proceeding.
NOTE: Upon completing these tests, open the master
switch and remove all test jumpers from the subbase terminals, limits/controls or switches.
22. Return the system to normal operation.
PILOT TURNDOWN TEST (ALL INSTALLATIONS USING A PILOT)
Perform this check on all installations that use a pilot. The purpose of this test is to verify that the main burner can be lit by the smallest pilot flame that will hold in the flame
1-30 750-166
amplifier and energize the FLAME LED. Clean the flame detector(s) to make sure that it will detect the smallest acceptable pilot flame. If using Auto-Check or Self-Check­ing Amplifier and 1M ohm/volt meter, the flame signal will fluctuate every time the amplifier does a self-check or a shutter check.
CB780/CB784
CHECKOUT
Fig. 27—Flame-out timer lockout.
LOCKOUT #16 PFEP * Flame-out Timer*
NOTE: Low fuel pressure limits, if used, could be open. If
so, bypass them with jumpers during this test.
1. Open the master switch.
2. Close the manual main fuel shutoff valve(s).
3. Connect a manometer (or pressure gauge) to measure
pilot gas pressure during the turndown test.
4. Open the manual pilot shutoff valve(s).
5. Close the master switch and start the system with a call for heat. Raise the set point of the operating control­ler. The program sequence should start, and PREPURGE should begin.
6. When the PILOT IGN begins, set the Run/Test Switch to TEST position to stop the sequence. The FLAME LED will come on when the pilot ignites.
NOTE: If the sequence does not stop, reset the system and
make sure you set the Run/Test Switch to TEST within the first eight seconds of the PILOT IGN sequence.
IMPORTANT: You have eight seconds or three seconds,
depending on PFEP selected, to position the Run/Test Switch to the TEST position to stop the sequence after the start of the PILOT IGN period.
7. Turn the pilot pressure down very slowly, reading the manometer (or pressure gauge) as it drops. Stop instantly when the FLAME LED goes out. Note the pressure at the CB780/CB784 flame relay dropout point. The pilot is at the minimum turndown position. Immediately turn up the pilot pressure until the FLAME LED comes on again or the flame signal increases to 1.25 Vdc.
NOTE: If there is no flame for fifteen seconds with the
sequence stopped at this point, the CB780/CB784 will lockout and flash a lockout message; see Fig. 27.
8. Repeat step 7 to verify the pilot gas pressure reading at the exact point the FLAME LED light goes out.
9. Increase the pilot pressure immediately until the FLAME LED comes on, and then turn it down slowly to obtain a pressure reading just above the dropout point or until the flame signal increases to 1.25 Vdc.
Condition at the time of lockout . . .
PILOT HOLD: (Run/Test Sw)
M5001
10. Set the Run/Test Switch in the RUN position and let the sequence proceed. At ten seconds into the Ignition Trial period, make sure the automatic main fuel valve(s) open; then smoothly open the manual main fuel shutoff valve(s) (or any other manually opened safety shutoff valve(s), if used) and watch for main burner ignition. If the main burner flame is established, proceed to step 18.
NOTE: This step requires two people, one to open the
manual valve(s) and one to watch for ignition.
11. If the main burner flame is not established within ten seconds, close the manual main fuel shutoff valve(s) and open the master switch. If the lightoff was rough, the pilot flame size is too small.
12. Recycle the burner and stop the sequence in the PI­LOT IGN period by using the Run/Test Switch.
13. Increase the pilot flame size by increasing its fuel flow until a smooth main flame is accomplished.
14. Reposition the flame scanner sight tube or use orifices until the pilot flame signal voltage is in the range of 1.25 to
1.50 Vdc.
15. When the main burner lights reliably with the pilot at turndown, disconnect the manometer (or pressure gauge) and turn the pilot gas flow up to that recommended by the equipment manufacturer.
16. If used, remove the bypass jumpers from the sub­base terminals, limits/controls, or switches.
17. Run the system through another cycle to check for normal operation.
18. Return the system to normal operation.
750-166 1-31
CB780/CB784 CHECKOUT
HOT REFRACTORY SATURATION TEST (ALL INFRARED DETECTORS)
Test to make certain that radiation from hot refractory
does not mask the flickering radiation of the flame itself.
Start the burner and monitor the flame signal during the warmup period. A decrease in signal strength as the refrac­tory heats up indicates hot refractory saturation. If saturation is extreme, the flame signal will drop below 1.25 Vdc and the system will shut down as though a flame failure occurred.
If hot refractory saturation occurs, the condition must be corrected. Add an orifice plate in front of the cell to restrict the viewing area, lengthen the sight pipe or decrease the pipe size (diameter). Continue adjustments until hot refractory saturation is eliminated.
HOT REFRACTORY HOLD-IN TEST (ALL INFRARED DETECTORS)
Test to make certain hot refractory will not delay the flame detection system response to a flameout. This condi­tion can delay response to flame failure and also can prevent a system restart as long as hot refractory is detected.
Infrared (lead sulfide) detectors can respond to infrared rays emitted by a hot refractory, even when the refractory has visibly ceased to glow. Infrared radiation from a hot refrac­tory is steady, but radiation from a flame has a flickering characteristic. The infrared detection system responds only to flickering infrared radiation; it can reject a steady signal from hot refractory. The refractory steady signal can be made to fluctuate if it is reflected, bent or blocked by smoke or fuel mist within the combustion chamber. Be careful when ap­plying an infrared system to verify its response to flame only.
To check infrared (lead sulfide) detectors for hot refrac­tory hold-in, operate the burner until the refractory reaches its maximum temperature. If the installation has a multi-fuel burner, burn the heavier fuel that is most likely to reflect, bend or obscure the hot refractory steady infrared radiation. When the maximum refractory temperature is reached, close all manual fuel shutoff valve(s), or open the electrical circuits of all automatic fuel valve(s). Visually observe when the burner flame or FLAME LED goes out. If this takes more than three seconds, the infrared detector is sensing hot refractory. Immediately terminate the firing cycle. (Lower the set point to the operating controller, or set the Burner Switch to OFF. Do not open the master switch.)
NOTE: Some burners continue to purge oil lines between the
valve(s) and nozzle(s) even though the fuel valve(s) are
closed. Terminating the firing cycle (instead of opening
the master switch) will allow purging the combustion
chamber. This will reduce a buildup of fuel vapors in the
combustion chamber caused by oil line purging.
If the detector is sensing hot refractory, the condition must be corrected. Add an orifice plate in front of the cell to restrict the viewing area of the detector. If this does not correct the problem, resight the detector at a cooler, more distant part of the combustion chamber. While resighting the detector, be
aware that it must also properly sight the flame. For an infrared detector, try lengthening the sight pipe or decreasing the pipe size (diameter). For details, refer to the detector Instructions and the equipment Operating Manual. Continue adjustments until hot refractory hold-in is eliminated.
ULTRAVIOLET SENSOR, IGNITION SPARK RE­SPONSE TEST (ALL ULTRAVIOLET DETECTORS)
Test to make certain that the ignition spark is not actuating
the FLAME LED.
1. Close the pilot and main burner manual fuel shut-off
valve(s).
2. Start the burner and use the Run/Test Switch to stop
the sequence in the PILOT IGN period. Ignition spark should occur, but the flame signal should not be more than 0.5 Vdc.
3. If the flame signal is higher than 0.5 Vdc and the
FLAME LED does come on, consult the equipment operat­ing manual and resight the detector farther out from the spark, or away from possible reflection. It may be necessary to construct a barrier to block the ignition spark from the detector view. Continue adjustments until the flame signal due to ignition spark is less than 0.5 Vdc.
RESPONSE TO OTHER ULTRAVIOLET SOURCES
Some sources of artificial light, such as incandescent or fluorescent bulbs, mercury sodium vapor lamps and day­light, produce small amounts of ultraviolet radiation. Under certain conditions, an ultraviolet detector will respond to these sources as if it is sensing a flame. To check for proper detector operation, check the Flame Failure Response Time (FFRT) and conduct Safety Shutdown Tests under all oper­ating conditions.
FLAME SIGNAL WITH HOT COMBUSTION CHAMBER (ALL INSTALLATIONS)
With all initial start-up tests and burner adjustments com­pleted, operate the burner until the combustion chamber is at the maximum expected temperature. Observe the equipment manufacturer warm-up instructions. Recycle the burner un­der these hot conditions and measure the flame signal. Check the pilot alone, the main burner flame alone, and both together (unless monitoring only the main burner flame when using DSI). Check the signal at both High and Low Firing Rate positions and while modulating, if applicable.
Check the FFRT of the Flame Amplifier. Lower the set point of the operating controller and observe the time it takes for the burner flame to go out. This should be within 3 sec­onds maximum.
If the flame signal is too low or unsteady, check the flame detector temperature. Relocate the detector if the tempera­ture is too high. If necessary, realign the sighting to obtain the proper signal and response time. If the response time is still too slow, replace the Plug-in Flame Signal Amplifier. If the detector is relocated or resighted, or the amplifier is replaced, repeat all required Checkout tests.
1-32 750-166
CB780/CB784
CHECKOUT
SAFETY SHUTDOWN TESTS (ALL INSTALLATIONS)
Perform these tests at the end of Checkout, after all other tests have been completed. If used, the external alarm should turn on. Press the CB780/CB784 reset pushbutton to restart the system.
1. Opening a Preignition Interlock during STANDBY or
PREPURGE period.
a. *Preignition ILK* fault will be displayed on the
VFD. Fault code 10 or 33 will be displayed to denote the fault.
b. Safety shutdown will occur.
2. Opening a Lockout Interlock during PREPURGE,
PILOT IGN, MAIN IGN or RUN period.
a.*Lockout ILK* fault will be displayed on the VFD.
Fault code 11 or 12 or 21 or 29 will be displayed to denote the fault.
b. Safety shutdown will occur.
3. Detection of flame 40 seconds after entry to STAND­BY, fault code 9. Detection of flame ten seconds into Drive to Purge Rate or during measured PREPURGE time.
a. Simulate a flame to cause the flame signal voltage
level to be at least 1.25 Vdc for 40 seconds after entry to STANDBY and also simulate a flame signal for 10 seconds during PREPURGE.
b.*Flame Detected* fault will be displayed on the
VFD. Fault code 9 or 15 or 18 will be displayed to denote the fault.
c. Safety shutdown will occur.
4. Failure to ignite pilot.
a. Close pilot and main fuel manual shutoff valve(s). b. Depress the reset button. c. Start the system. d. The automatic pilot valve(s) should be energized
but the pilot cannot ignite.
e. *Pilot Flame Fail* fault will be displayed on the
VFD. Fault code 28 will be displayed four or ten seconds (depending on the jumper configuration selection for PFEP) after the pilot valve(s) is energized to denote the fault.
f. Safety shutdown will occur.
5. Failure to ignite main. a. Open the manual pilot valve(s); leave the main fuel
manual shutoff valve(s) closed. b. Depress the reset button. c. Start the system. d. The pilot should ignite and the flame signal should
be at least 1.25 Vdc but the main burner cannot light. e. The flame signal should drop below 1.25 Vdc with-
in 3 seconds after the interrupted pilot goes out. f. *Main Flame Ign.* fault will be displayed on the
VFD. Fault code 19 will be displayed to denote
the fault. g. Safety shutdown will occur.
6. Loss of flame during RUN. a. Open the main fuel manual shutoff valve(s) and open
manual pilot shutoff valve(s). b. Depress the reset button. c. Start the system. Start-up should be normal and the
main burner should light normally. d. After the sequence is in the normal RUN period for
at least ten seconds with the main burner firing,
close the manual main fuel shutoff valve(s) to extin-
guish the main burner flame. e. The flame signal should drop below 1.25 Vdc within
3 seconds after the main flame goes out. f. *Main Flame Fail* fault will be displayed on the
VFD. Fault code 17 will be displayed to denote
the fault. g. Safety shutdown will occur.
7. Opening a Preignition Interlock after the first five
seconds of POSTPURGE.
a. *Preignition ILK* fault will be displayed on the
VFD. Fault code 33 will be displayed to denote
the fault. b. Safety shutdown will occur.
IMPORTANT:
1. If the CB780/CB784 fails to shut down on any of these tests, take corrective action; refer to CB780/CB784 Troubleshooting and diagnostics manual and return to the beginning of all Checkout tests.
2. When all Checkout tests have been completed, reset all switches to original status.
750-166 1-33
CB780/CB784 TROUBLESHOOTING
Troubleshooting
CB780/CB784 SYSTEM DIAGNOSTICS
Troubleshooting control system equipment failures is
made easier with the CB780/CB784 self-diagnostics and first-out annunciation. In addition to an isolated spst alarm relay (audible annunciation), the CB780/CB784 provides visual annunciation by displaying a fault code and fault or hold message at the Keyboard Display Module 2 row by 20 column VFD. The CB780/CB784 provides118 diag­nostic messages for troubleshooting the system (see the CB780/CB784 Operating and Maintenance Manual, Manual Number 750-166).
Self-diagnostics of the CB780/CB784 enables it to detect and annunciate both external and internal system problems. Internal faults and external faults such as interlock failures, flame failures and false flame signals are annunciated by the CB780/CB784, which energizes the ALARM LED or visu­ally displayed at the Keyboard Display Module VFD.
The VFD displays a sequence status message indicating: STANDBY, PREPURGE, PILOT IGN, MAIN IGN, RUN and POSTPURGE. The selectable messages also provide visual indication of current status and historical status of the equipment such as: Flame Signal, Total Cycles, Total Hours, Fault History, Diagnostic Information and Expanded An­nunciator terminal status (if used). With this information, most problems can be diagnosed without extensive trial and error testing.
Table 4 provides the sequence and status hold messages. Table 10 provides a summary of all CB780/CB784 fault messages and fault codes. In addition, Diagnostic Informa­tion and History Data are available to assist in troubleshoot­ing the CB780/CB784, see Table 6.
The CB780/CB784 provides diagnostic information to aid the service mechanic in obtaining information when troubleshooting the system, see Tables 4, 5, 6 and 10. Informa­tion available in the Diagnostic Information includes Device Type, Device Suffix, Software Revision, Manufacturing Code, Flame Amplifier Type, Flame Failure Response Time, Selectable Jumper Configuration Status, Run/Test Switch Status and Terminal Status.
Diagnostic Information Index
The CB780/CB784 monitors input/output terminals and can display the status of the terminal at the VFD (example: Pilot Valve T8 ON<). See Table 5 for a complete terminal description and number. The display will show the actual status of the terminal. If voltage is detected at the terminal, ON is displayed, but if no voltage is detected at the terminal, OFF is displayed; see Table 5.
Historical Information Index
The CB780/CB784 has nonvolitile memory that allows the Relay Module to retain Historical Information for the six most recent lockouts. Each of the six lockout files retains the cycle when the fault occurred, the hour of operation when the fault occurred, a fault code, a fault message and burner status when the fault occurred; see Table 4.
IMPORTANT: The CB780 will not operate without a Key-
board Display Module or a Control Bus installed.
SERVICE NOTE: If the Keyboard Display Module VFD
is scrambled, remove and reinstall the Keyboard Display
Module, and reset the CB780/CB784 Relay Module. SERVICE NOTE: Reset CB780/CB784 by pressing the
reset pushbutton on the CB780/CB784, or pressing a
remote reset pushbutton wired through the Keyboard
Display Module or Control Bus. A power-up reset will
cause an electrical reset of the CB780/CB784, but will not
reset a lockout condition. SERVICE NOTE: Use the access slots on the sides of the
Wiring Subbase to check the terminal voltage of the
CB780/CB784. SERVICE NOTE: Maximum ambient operating tempera-
ture of an 817-1121 flame sensor, Series 1 through 6 will
be reduced to 125°F because of the duty cycle operation
of the CB780/CB784 Relay Module.
1-34 750-166
TABLE 10—HOLD AND FAULT MESSAGE SUMMARY.
Fault Number Annunciation Message
Fault 1 *No Purge Card* Fault 2 *AC Frequen/Noise* Fault 3 *AC Line Dropout* Fault 4 *AC Frequency* Fault 5 *Low Line Voltage* Fault 6 *Purge Card Error* Fault 7 *Flame Amplifier* Fault 8 *Flame Amp/Shutr* Fault 9 *Flame Detected* Fault 10 *Preignition ILK* Fault 11 *Running ILK On* Fault 12 *Lockout ILK On* Fault 14 *High Fire Sw.* Fault 15 *Flame Detected* Fault 16 *Flame-Out Timer* Fault 17 *Main Flame Fail* Fault 18 *Flame Detected* Fault 19 *Main Flame Ign.* Fault 20 *Low Fire Sw. Off* Fault 21 *Running ILK* Fault 24 *Call Service* Fault 25 *Call Service* Fault 28 *Pilot Flame Fail* Fault 29 *Lockout ILK* Fault 33 *Preignition ILK* Fault 35 - 40 *Call Service* Fault 41 *Main Valve On* Fault 42 *Pilot Valve On* Fault 43 *Ignition On* Fault 44 *Pilot Valve 2 On* Fault 45 *Low Fire Sw. Off* Fault 46 *Flame Amp Type* Fault 47 *Jumpers Changed* Fault 50 *Jumpers Wrong* Fault 51 *Flame Too Strong* Fault 52 - 70 *Call Service* Fault 71 - 75 *Device Specific* Fault 76 - 93 *Accessory Fault* Fault 94 - 108 *Call Service* Fault 109 *Call Service* Fault 110 - 127 *Call Service*
CB780/CB784
TROUBLESHOOTING
750-166 1-35
,
CB780/CB784 TROUBLESHOOTING
Fig. 28—Flush mounting of a Keyboard Display Module template.
1/8 DIA. (2)
M5082A
Section 2 - CB780/CB784
System Annunciation
Diagnostics and T roubleshooting
FIVE WIRE CONNECTOR FOR COMMUNICATIONS, REMOTE KEYBOARD DISPLAY AND REMOTE RESET
RUN/TEST SWITCH
SEQUENCE STATUS
SELECTABLE MESSAGE OR PREEMPTIVE MESSAGE
SEQUENCE STATUS LEDs
RESET PUSHBUTTON
FLAME SIMULATOR INPUT
CB780/CB784 SYSTEM DIAGNOSTICS
Troubleshooting control system equipment failures is
made easier with the CB780/CB784 self-diagnostics and first-out annunciation. In addition to an isolated spst alarm relay (for audible annunciation), the CB780/CB784 pro­vides visual annunciation by displaying a fault code and fault or hold message at the Keyboard Display Module (standard on CB780, optional on CB784) 2 row by 20 column Vacuum Fluorescent Display (VFD). The CB780/CB784 provides 127 different diagnostic messages for troubleshooting the system.
Self-diagnostics of the CB780/CB784 enables it to detect and annunciate both external and internal system problems. Internal faults and external faults (e.g., interlock failures, flame failures, and false flame signals) are annunciated by the CB780/CB784, through the Device ALARM LED Alarm output, and can be visually displayed at the Keyboard Dis­play Module (KDM).
The KDM displays a sequence status message indicat­ing: STANDBY, SAFE START CHECK, PREPURGE, PILOT IGN, MAIN IGN, RUN and POSTPURGE. The selectable messages also provide visual indication of current status and historical status of the equipment such as: Flame Signal, Total Cycles, Total Hours, Fault History, Diagnostic Information and Expanded Annunciator terminal status (if used). With this information, most problems can be diag­nosed without extensive trial and error testing.
DI = DIAGNOSTICS
*
H1 = HISTORY EA = EXPANDED ANNUNCIATOR
CAPTIVE MOUNTING SCREW
PLUG-IN PURGE CARD
KEYBOARD DISPLAY MODULE
RELAY MODULE
FLAME AMPLIFIER
FLAME CURRENT TEST JACKS
M7395
Table 1 provides the sequence and status hold messages. Table 6 provides a summary of all CB780/CB784 fault messages and fault codes. In addition, Diagnostic Informa­tion and History Data are available to assist in troubleshoot­ing the CB780/CB784, see Table 2.
The CB780/CB784 provides diagnostic information to aid the service mechanic in obtaining information when troubleshooting the system, see Tables 1, 2, 3 and 4. Infor­mation available in the Diagnostic Information includes Device Type, Device Suffix, Software Revision, Manufac­turing Code, Purge Time, Flame Amplifier Type, Flame Failure Response Time, Selectable Jumper Configuration Status, Run/Test Switch Status and Terminal Status.
Diagnostic Information Index
The CB780/CB784 monitors input/output terminals and can display the status of the terminal at the KDM (example: Pilot Valve T8 1 (one), see Table 3. A complete terminal description and terminal number are provided. The display shows the actual status of the terminal. If voltage is detected at the terminal, 1 (one) is displayed; but if no voltage is detected at the terminal, 0 is displayed; see Table 3.
*NOTE: Remote Reset must be mounted within sight of the boiler control panel.
750-166 2-1
Historical Information Index
The CB780/CB784 retains historical information for the six most recent lockouts. Each of the six lockout records retain the cycle when the fault occurred, the hour of opera­tion when the fault occurred, a fault code, a fault message and burner status when the fault occurred; see Table 2.
SERVICE NOTE: Reset the CB780/CB784 by pressing
the reset button on the CB780/CB784, or pressing a re­mote reset pushbutton wired through the Keyboard Dis­play Module or Control Bus. A power-up reset causes an electrical reset of the CB780/CB784 but does not reset a lockout condition.
SERVICE NOTE: The CB780 Relay Module will not
operate without a Keyboard Display Module or Control
SERVICE NOTE: Use the access slots on the sides of the
833-2725 wiring subbase to check terminal voltage. Bus installed. (These devices are optional with CB784 control.)
SERVICE NOTE: Maximum ambient operating tempera-
ture of the 817-1121 UV self-check scanner, Series 1
SERVICE NOTE: If the Keyboard Display Module KDM
is scrambled, remove and remount the Keyboard Dis-
through 6, is reduced to 125°F because of the duty cycle
operation of the CB780/CB784 Relay Module. play Module, and reset the CB780/CB784 Relay Mod­ule.
SERVICE NOTE: Configuration jumpers must be selected
prior to 200 hours of operation. If configuration jumpers
are changed after 200 hours, lockout 110 occurs.
TABLE 1—SEQUENCE AND STATUS HOLD MESSAGES FOR ALL CB780/CB784 CONTROLS.
NOTE: Normal sequences are in BOLD type, while abnormal sequences are not in bold type.
Sequence Burner Control Status
INITIATE mm:ss The KDM indicates the burner status, INITIATE, which is a stabilization period for the
CB 780/CB 784 to check for any fluctuations in ac line voltage on POWER UP or control/recycle limit contact bounce during normal operation. The timing of the INITIATE period is ten seconds before entering STANDBY.
INITIATE HOLD: AC (ac Frequency/Noise)
The KDM indicates the burner status, INITIATE, and that it is waiting for excess line noise to clear up. The burner sequence will not advance into STANDBY until the excess line noise, which prevents sufficient reading of the line voltage inputs ceases or a line frequency error is corrected (perhaps caused by using a 60 Hz device on a 50 Hz line, or vice versa).
INITIATE HOLD: AC (ac Line Dropout)
The KDM indicates the burner status, INITIATE, and that ac line power has momentarily dropped out. The burner sequence will not advance into STANDBY until the ac line voltage has stabilized throughout the INITIATE period.
INITIATE HOLD: AC (ac Frequency)
The KDM indicates the burner status, INITIATE, and that line frequency is faster than the expected value. The burner sequence will not advance into STANDBY until the line frequency returns to the proper value (perhaps caused by using a 50 Hz device on a 60 Hz line).
INITIATE HOLD: AC (Low Line Voltage)
The KDM indicates the burner status, INITIATE, and that low line voltage has occurred. The burner sequence will not advance into STANDBY until the line voltage is at a sufficient level for proper operating parameters.
STANDBY The KDM indicates the burner status, STANDBY. The burner can be placed in
STANDBY by opening the burner switch or if the operating controller indicates setpoint has been satisfied. A demand could be present for burner operation, but the burner sequence will not advance from STANDBY to PURGE until the recycle limits close. If an Expanded Annunciator is connected, the display messages will be enhanced.
STANDBY HOLD: F/G (Flame Detected)
The KDM indicates the burner status, STANDBY, and that a flame is detected. A demand is present for burner operation. The burner sequence will not advanced to prepurge because a flame is detected as being present. The sequence will not advance to prepurge until the flame signal clears. If the flame signal does not clear within 40 seconds the CB 780/CB 784 will lockout.
STANDBY HOLD: T20 (Preignition Interlock)
The KDM indicates the burner status, STANDBY, and that the Preignition Interlock is not closed. If a demand is present for burner operation, the burner sequence will not advance to PREPURGE until the Preignition Interlock proves closed. If this time exceeds a 30 second hold, the CB 780/CB 784 will lockout.
(Continued)
2-2 750-166
TABLE 1—SEQUENCE AND STATUS HOLD MESSAGES FOR ALL CB780/CB784 CONTROLS (Continued).
Sequence Burner Control Status
STANDBY HOLD: T7 (Lockout Interlock)
The KDM indicates the burner status, STANDBY, and that the Lockout Interlock is closed. If a demand is present for burner operation, the burner sequence will not advance to PREPURGE until the Lockout Interlocks prove open. If this time exceeds the 120 second hold, the CB 780/CB 784 will lockout.
PURGE HOLD: T19 (High Fire Switch)
The KDM indicates the burner status, PURGE, and that the High Fire Switch is not closed. The firing rate motor is driving to its PURGE rate position. If this time exceeds two minutes and 15 seconds, the CB 780/CB 784 will lockout.
PURGE DELAY: T19 (High Fire Jumpered)
The KDM indicates the burner status, PURGE, and that the High Fire Switch is jumpered. The High Fire Switch is bypassed, welded or otherwise prematurely closed. The system will automatically add 30 seconds to allow the firing rate motor additional drive time to reach or near the open damper position before starting the PURGE sequence.
PURGE mm:ss The KDM indicates the burner status, PURGE, which is the period of time before the
ignition period when the blower motor is running. The timing of the PURGE period is selectable. PREPURGE is counted in minutes and seconds.
PURGE HOLD:TEST (Run/Test Switch)
The KDM displays the burner status, PURGE, and that the Run/Test Switch is in the TEST position. The sequence will not continue until the Run/Test switch is placed in the RUN position.
PURGE HOLD:T18 (Low Fire Jumpered)
The KDM displays the burner status, PURGE, and that the Low Fire Switch is jumpered. The Low Fire Switch is bypassed, welded or otherwise prematurely closed. The system will automatically add 30 seconds to allow the firing rate motor additional drive time to reach or near the closed damper position before starting the ignition sequence.
PURGE HOLD: F/G (Flame Detected)
The KDM indicates the burner status, PURGE, and that a flame is detected. The burner sequence will not advance through PREPURGE because a flame is detected as being present. The sequence will hold waiting for the flame signal to clear. If the time exceeds 30 seconds, the CB 780/CB 784 will lockout.
PURGE HOLD: T18 (Low Fire Switch)
The KDM indicates the burner status, PURGE, and that the Low Fire Switch is not closed. The firing rate motor is driving to its low fire position in preparation for ignition trials. If this time exceeds two minutes and 15 seconds, the CB 780/CB 784 will lockout.
PILOT IGN mm:ss The KDM indicates the burner status, PILOT IGN, and the timing of the PILOT IGN
trial begins, in seconds. During this period of time, the CB 780/CB 784 permits the pilot valve to be open and the pilot flame to be established.
PILOT HOLD: TEST (Run/Test Switch)
The KDM indicates the burner status, PILOT IGN, and that the Run/Test Switch is in the TEST position. The sequence will not continue until the Run/Test switch is placed in the RUN position.
MAIN IGN mm:ss The KDM indicates the burner status, MAIN IGN, and the timing of the MAIN IGN trial
begins, in seconds. During this period of time, the CB 780/CB 784 permits the main valve to be open and the main flame to be established.
RUN The KDM indicates the burner status, RUN, which is the period of time after the ignition
trials and before the operating controller setpoint is reached. During this time the burner is firing under the control of the firing rate controller.
RUN LOWFIRE:TEST (Run/Test Switch)
The KDM indicates the burner status, RUN, and that the Run/Test Switch is in the TEST position. The firing rate motor will drive to the low fire position. Normal modulation or operation will not resume until the Run/Test Switch is placed in the RUN position.
POSTPURGE mm:ss The KDM indicates the burner status, POSTPURGE, which is the period of time after the
RUN period during which the blower motor continues to run. The timing of the POSTPURGE period is 15 seconds.
Waiting for connection… The display has power but is waiting to receive a signal from the CB 780/CB 784 to
continue operation.
(Continued)
750-166 2-3
TABLE 1—SEQUENCE AND STATUS HOLD MESSAGES FOR ALL CB780/CB784 CONTROLS (Continued).
Sequence Burner Control Status
RESET/ALARM TEST The KDM indicates the burner status, RESET/ALARM TEST. This display indicates
that the reset button is pressed. If it is held for more than four seconds, the alarm output is energized. The alarm output will be deenergized when the reset button is released.
ADDITIONAL SEQUENCE STATUS INFORMATION IF AN EXPANDED ANNUNCIATOR IS
CONNECTED TO THE RELAY MODULE.
BURNER OFF: T6 (Burner Switch)
The KDM indicates the Burner Switch is not closed. The burner sequence will not advance to PREPURGE until the Burner Switch closes.
STANDBY The KDM indicates the burner status, STANDBY, and the Operating Control is not
closed. The burner sequence will not advance to PREPURGE until the Operating Control closes.
STANDBY HOLD: T6 (EA Hold Message)
The KDM indicates the burner status, STANDBY, and a limit is not closed. The burner sequence will not advance to PREPURGE until one or all limits close downstream from the Operating Control.
STANDBY HOLD: T6 (Circuit Fault)
The KDM indicates the burner status, STANDBY, and the control input is not closed. The burner sequence will not advance to PREPURGE until the control input closes.
TABLE 2—ACCESSING HISTORICAL AND DIAGNOSTIC SELECTABLE MESSAGES.
Step Operation Press Display Comments
1. Press scroll key to access Diagnostic Information
() STANDBY
Diagnostic Info>
Use the down/up scroll keys to access the selectable message. The second line will display Diagnostic Information.
2. Press change level key to access Diagnostic
() STANDBY
Diagnostic Info>
Use the change key to access the Diagnostic Information.
Information
3. Continue display of Diagnostic Information.
() STANDBY⁄DI
Device RM7800<
Push the () scroll key to scroll to the next Diagnostic message.
4. Continue through remaining Diagnostic Information display following step 3 as required.
5. Press change level key to return to the first level of Diagnostic Information
() STANDBY
Diagnostic Info>
Another display can be selected or discontinue accessing Diagnostic
Information review. data prompt or to other selectable messages.
NOTE: Historical Files may be selected similarly.
2-4 750-166
TABLE 3—SELECTABLE MESSAGES (see CB780/CB784 Relay Module, Manual Part Number 750-166).
Selectable
Message/Display Description
Flame Signal Flame signal strength. 0 - 5.0 Vdc Flame
Total Cycles Total number of equipment
operating cycles
Possible States/Range
(Terminals) Comments
Flame relay pull-in and drop-
Amp (+ and - (Com))
out value 1.25 Vdc.
0 - 99,999 cycles Cycle counter will be updated
each time the main valve is energized.
Total Hours Total number of equipment
operating hours.
0 - 99,999 hours Hour counter will be updated
each time the main valve output is energized for 60 minutes.
Fault History> (six most recent faults)
First level prompt for history information. Has subset level.
Fault Cycle ÂH1 Cycle when the fault
0 - 99,999 cycles
occurred.
Fault Hours ÂH1H1Run hour when the fault
0 - 99,999 hours
occurred.
Fault Code ÂH1 Number that identifies the
0 - 999
reason for the lockout.
*Fault Message* ÂH1 Indicates lockout cause. Sequence Message ÂH1 Indicates where the lockout
occurred in the sequence.
(Second Line Message)
ÂH1
Second Line Message explains any further information available from the CB 780/CB 784 or may be blank if there is not a preemptive second line. H2…H6 etc.
Diagnostic Information> First level prompts for
history information. Has
subset level. Device Device type number. RM7800x or RM7840x Device Suffix Device suffix number. nnnn Run/Test Sw Position of Run/Test
switch.
RUN or TEST Indicates if CB 780/CB 784 is
in RUN or TEST mode.
OperControl T6 Operating Control Input. 1 or 0 Indicates if input is on or off,
energized or de-energized.
Interlock T7 Running/Lockout Interlock. 1 or 0 Indicates if input is on or off,
energized or de-energized.
Pilot Valve T8 Pilot Valve. 1 or 0 Indicates if output terminal is
on or off, energized or de-energized.
Main Valve T9 Main Fuel Valve. 1 or 0 Indicates if output terminal is
on or off, energized or de-energized.
Ignition T10 Ignition. 1 or 0 Indicates if output terminal is
on or off, energized or de-energized.
(Continued)
750-166 2-5
TABLE 3—SELECTABLE MESSAGES (Continued).
Selectable
Message/Display Description
Possible States/Range
(Terminals) Comments
LowFire Sw T18 Low Fire Switch. 1 or 0 Indicates if input is on or off,
energized or deenergized.
HighFire Sw T19 High Fire Switch. 1 or 0 Indicates if input is on or off,
energized or deenergized.
PreIgn ILK T20 Preignition Interlock. 1 or 0 Indicates if input is on or off,
energized or deenergized.
Valv/Start T21 Interrupted/Intermittent
Pilot Valve. First stage oil
1 or 0 Indicates if output is on or off,
energized or deenergized.
valve or start input. Jumper 1 Pilot Flame Establishing
Period (PFEP).
INTACT/CLIPPED Display shows state of PFEP
jumper. If jumper is intact, the CB 780/CB 784 will have a 10 second PFEP. If jumper is clipped, the CB 780/CB 784
will have a 4 second PFEP. Jumper 2 NOT USED JUMPER 3 Interlock Check (IC). INTACT Disabled/
CLIPPED Enabled
Display shows state of Start-
Up Interlock Check (IC)
jumper. If jumper is clipped,
CB 780/CB 784 IC check is
enabled. If jumper is intact,
IC is disabled. Amp Type Defines type of amplifier
installed.
NORMAL/AMP­CHECK/SHUTTER
Display shows type of flame
detection system installed (i.e.,
as NORMAL/Standard, AMP-
CHECK/AMPLI-CHECK™,
and SHUTTER/Dynamic Self-
Checking). Flame Response Amplifier Flame Failure
3 seconds Response Time (FFRT) in seconds.
Purge Time Timing value of purge card. mm:ss 30 seconds to 2-1/2 minutes Mfg Code Manufacturing code is five
nnnnn digit code representing date code.
SW Rev Software revision and
version code for Keyboard Display Module and CB 780/CB 784.
nnnn/nnnn First four digits represent the
software revision of the Keyboard Display Module. Second four digits represent the software revision of the relay module.
Expanded Annunciator First level prompt for
See Table 5. Expanded Annunciator information and has subset level (Table 5).
Remote Command Status of firing rate
command from remote
NONE/HOLD HF/LF
controller.
2-6 750-166
LOCKOUT MESSAGES (TABLE 4)
When the CB780/CB784 is locked out, it displays a repeating cycle of messages (in English text); see Table 4. In addition to the lockout messages, Table 4 provides the system failure and recommended troubleshooting. There are four states in the cycle:
1. STATE 1, see Fig. 1: First state message display lasts six seconds. First line displays the word LOCKOUT fol­lowed by the fault code number, and possibly a lower case letter if an Expanded Annunciator is connected. The status of the Relay Module at the time of lockout is shown on the right side of the first line as either INITIATE, STANDBY, PURGE, PFEP, MFEP, RUN or POSTPRG. The lockout reason corresponding to the fault code number is displayed on the second line, highlighted by asterisks on each side. If the lockout reason is being enhanced due to the presence of an Expanded Annunciator, a lower case letter follows the fault code number. This letter corresponds to the first-out code supplied by the Expanded Annunciator.
2. STATE 2, see Fig. 2: Display of the second state message lasts two seconds.
3. STATE 3, see Fig. 3: Display of the third state mes­sage lasts three seconds. It is a replica of the burner status as it existed at the time of lockout. The second line will be blank if the burner status at the time of lockout did not include a pre-emptive message (in parentheses) for the second line.
4. STATE 4: In the fourth state, both lines are blanked for one-half second, then sequence to the first state.
Fig. 2—Lockout message state 2.
BURNER CONTROL
Condition at the time of lockout ...
SCROLL
MODE
SAVE
Fig. 1—Lockout message state 1.
BURNER CONTROL
LOCKOUT #23p PURGE *Airflow Sw.*
SCROLL
MODE
SAVE
M7416
Fig. 3—Lockout message state 3.
BURNER CONTROL
PURGE HOLD: T7 (Airflow Sw.)
SCROLL
MODE
SAVE
M7415
M7414
750-166 2-7
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING.
Fault Code System Failure Recommended Troubleshooting
Fault 01 *No Purge Card*
Fault 02 *AC Frequen/Noise*
Fault 03 *AC Line Dropout*
Fault 04 *AC Frequency*
Fault 05 *Low Line Voltage*
Fault 06 *Purge Card Error*
Fault 07 *Flame Amplifier*
No card is plugged into the purge card slot.
1. Assure the purge card is seated properly.
2. Inspect the purge card and the connector on the relay module for damage or contaminants.
3. Reset and sequence the CB 780/CB 784.
4. If fault code reappears, replace the purge card.
5. Reset and sequence the CB 780/CB 784.
6. If fault persists, replace the relay module.
Excess noise or device running on slow AC.
1. Check the relay module and display module connections.
2. Reset and sequence the CB 780/CB 784.
3. Check the CB 780/CB 784 power supply to assure that both frequency and voltage meet specifications.
4. Check the backup power supply as appropriate.
AC Line dropout detected. 1. Check the relay module and display module
connections.
2. Reset and sequence the CB 780/CB 784.
3. Check the CB 780/CB 784 power supply to assure that both frequency and voltage meet specifications.
4. Check the backup power supply as appropriate.
Device running on fast AC. 1. Check the relay module and display module
connections.
2. Reset and sequence the CB 780/CB 784.
3. Check the CB 780/CB 784 power supply to assure that both frequency and voltage meet specifications.
4. Check the backup power supply as appropriate.
Low AC line detected. 1. Check the relay module and display module
connections.
2. Reset and sequence the CB 780/CB 784.
3. Check the CB 780/CB 784 power supply to assure that both frequency and voltage meet specifications.
4. Check the backup power supply as appropriate.
The purge card timing has changed from the original configuration.
1. Assure that the purge card is seated properly.
2. Inspect the purge card and the connector on the relay module for any damage or contaminants.
3. Reset and sequence the CB 780/CB 784.
4. If fault code reappears, replace the purge card.
5. Reset and sequence the CB 780/CB 784.
6. If code persists, replace relay module.
Flame not sensed when checked for a nonself-check version.
1. Check wiring; correct any errors.
2. Assure that the flame detector and flame amplifier are compatible.
3. Remove the flame amplifier and inspect its connections. Reseat the amplifier.
4. Reset and sequence the CB 780/CB 784.
5. If the code reappears, replace the flame amplifier and/or the flame detector.
6. If fault persists, replace the relay module.
(Continued)
2-8 750-166
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING (Continued).
Fault Code System Failure Recommended Troubleshooting
Fault 08 *Flame Amp/Shutr*
Fault 09 *Flame Detected*
Fault 10 *Preignition ILK*
Fault 12 *Lockout ILK On*
Flame sensed when checked for shutter-check or ampli-check versions.
Flame sensed when shutter open and no flame is expected during Standby.
Preignition interlock fault during Standby.
Lockout Interlock powered at improper point in sequence.
1. Check wiring; correct any errors.
2. Assure that the flame detector and flame amplifier are compatible.
3. Remove the flame amplifier and inspect its connections. Reseat the amplifier.
4. Reset and sequence the CB 780/CB 784.
5. If the code reappears, replace the flame amplifier and/or the flame detector.
6. If fault persists, replace the relay module.
1. Check that flame is not present in the combustion chamber; correct any errors.
2. Check wiring; correct any errors.
3. Remove the flame amplifier and inspect its connections. Reseat the amplifier.
4. Reset and sequence the CB 780/CB 784.
5. If the code reappears, replace the flame amplifier and/or the flame detector.
6. If fault persists, replace the relay module.
1. Check wiring; correct any errors.
2. Check Preignition Interlock switches to assure proper functioning.
3. Check fuel valve operation.
4. Reset and sequence the CB 780/CB 784; monitor the Preignition interlock status.
5. If code persists, replace the relay module.
1. Check wiring to assure that the Lockout Interlocks are connected properly between terminals 6 and 7. Correct any errors.
2. Reset and sequence the CB 780/CB 784.
3. If the fault persists, measure the voltage between terminals 6 and G (ground), then terminal 7 and G (ground). If there is 120 Vac at terminal 6 when the controller is off, the Controller switch may be bad or is jumpered.
4. If steps 1 through 3 are correct and there is 120 Vac at terminal 7 while the controller is closed and the fault persists, check for a welded or jumpered Running Interlock, Lockout Interlock or Airflow switch. Correct any errors.
5. If steps 1 through 4 are correct and the fault persists, replace the relay module.
750-166 2-9
(Continued)
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING (Continued).
Fault Code System Failure Recommended Troubleshooting
Fault 14 *High Fire Sw.*
Fault 15 *Flame Detected*
Fault 16 *Flame-Out Timer*
Fault 17 *Main Flame Fail*
High fire interlock switch failure to close during prepurge.
Flame sensed when shutter open and no flame is expected.
Integrated no-flame time exceeded the limit during Pilot Flame Establishing Period.
Main flame failure during Run after flame was established and on for at least 10 seconds.
1. Check wiring; correct any errors.
2. Reset and sequence the CB 780/CB 784.
3. Use either the manual motor potentiometer to drive the motor to the High Fire position or use the Run/Test switch option (if available) sequence to Prepurge Drive to High Fire and place in the TEST position. Adjust the High Fire switch while in this state to assure that it is closing properly.
4. Measure the voltage between terminal 18 and G (ground) while in the Prepurge Drive to High Fire state. 120 Vac should be present. If not, the switch adjustment is incorrect and/or the switch is defective and should be replaced.
5. Reset and sequence the CB 780/CB 784. If 120 Vac was present between the High Fire switch and terminal 18, and the fault still persists, replace the relay module.
1. Check that flame is not present in the combustion chamber; correct any errors.
2. Assure that the flame amplifier and flame detector are compatible.
3. Check wiring and correct any errors.
4. Remove the flame amplifier and inspect its connectors. Reseat the flame amplifier.
5. Reset and sequence the CB 780/CB 784.
6. If the code reappears, replace the flame amplifier and/or the flame detector.
7. If fault persists, replace the relay module.
1. Measure the flame signal. If one exists, does it meet specifications? Make appropriate burner adjustments.
2. Assure that the flame amplifier and the flame detector are compatible.
3. Replace the flame amplifier and/or the flame detector, if necessary.
4. If the fault persists, replace the relay module.
1. Inspect the main fuel valve(s) and its connection(s).
2. Verify that the fuel pressure is sufficient enough to supply fuel to the combustion chamber. Inspect the connections to the fuel pressure switches. Assure tproper functioning.
3. Inspect the Airflow Switch and assure that it is functioning properly.
4. Check the flame detector sighting position; reset and cycle. Measure flame signal strength. Does it meet specifications? If not, refer to the flame detector and/or flame amplifier checkout procedures in the installation instructions.
(Continued)
2-10 750-166
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING (Continued).
Fault Code System Failure Recommended Troubleshooting
Fault 18 *Flame Detected*
Fault 19 *Main Flame Ign.*
Fault 20 *Low Fire Sw. Off*
Fault 22 *Lockout ILK*
Flame sensed when shutter open and no flame is expected during Prepurge.
Flame was lost during MFEP or the first 10 seconds of the Run state.
Low fire interlock switch failure to close during Prepurge.
Lockout Interlock fault during Prepurge.
1. Check that flame is not present in the combustion chamber. Correct any errors.
2. Assure that the flame amplifier and flame detector are compatible.
3. Check wiring; correct any errors.
4. Remove the flame amplifier and inspect the connectors. Reseat the flame amplifier.
5. Reset and sequence the CB 780/CB 784.
6. If the code reappears, replace the flame amplifier and/or the flame detector.
7. If the fault persists, replace the relay module.
1. Inspect the main fuel valve(s) and connections.
2. Verify that the fuel pressure is sufficient to supply fuel to the combustion chamber. Inspect the connections to the fuel pressure switches to assure proper functioning.
3. Inspect the Airflow Switch to assure proper functioning.
4. Check the flame detector sighting position; reset and cycle. Measure flame signal strength. Does it meet specifications? If not, refer to the flame detector and/or flame amplifier checkout procedures in the installation instructions.
1. Check wiring; correct any errors.
2. Reset and sequence the CB 780/CB 784.
3. Use either the manual motor potentiometer to drive the motor to the Low Fire position, or use the Run/Test switch option (if available) sequence to Prepurge Drive to Low Fire and place in the TEST position. Adjust the Low Fire switch while in this state to assure that it is closing properly.
4. While in the Prepurge Drive to Low Fire state, measure the voltage between terminal 19 and G (ground). 120 Vac should be present. If not, the switch adjustment is incorrect and/or the switch is defective and should be replaced.
5. Reset and sequence the CB 780/CB 784. If 120 Vac was present between the Low Fire switch and terminal 19 and the fault still persists, replace the relay module.
1. Check wiring; correct any errors.
2. Inspect the fan; assure that there is no blockage of the air intake and that it is supplying air.
3. Assure that the Lockout Interlock switches are functioning properly and that the contacts are free from contaminants.
4. Reset and sequence the CB 780/CB 784 to Prepurge (place the Run/Test switch into the TEST position, if available). Measure the voltage between terminal 7 and G (ground). 120 Vac should be present.
5. If steps 1 through 4 are correct and the fault persists, replace the relay module.
(Continued)
750-166 2-11
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING (Continued).
Fault Code System Failure Recommended Troubleshooting
Fault 24 *Call Service*
Fault 25 *Call Service*
Fault 28 *Pilot Flame Fail*
Fault 29 *Lockout ILK*
Fault 31 *Low Fire Sw. Off*
The Flame Interlock (relay module) was on when it should
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
have been off. The Flame Interlock (relay
module) was off when it should
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
be on. Pilot flame failure. 1. Check pilot valve wiring and operation. Correct
any errors.
2. Check fuel supply.
3. Check pilot pressure and repeat pilot turndown test.
4. Check ignition transformer electrode, flame detector, flame detector sighting, and flame amplifier.
5. If steps 1 through 4 are correct and the fault persists, replace the relay module.
Lockout Interlock fault. 1. Check wiring; correct any errors.
2. Inspect the fan; assure that there is no blockage of the air intake and that it is supplying air.
3. Assure that the Lockout Interlock switches are functioning properly and that the contacts are free from contaminants.
4. Reset and sequence the CB 780/CB 784 to Prepurge (place the Run/Test Switch into the TEST position, if available). Measure the voltage between terminal 7 and G (ground). 120 Vac should be present.
5. If steps 1 through 4 are correct and the fault persists, replace the relay module.
Low Fire Interlock switch failure to close during Run.
1. Check wiring; correct any errors.
2. Reset and sequence the CB 780/CB 784.
3. Use either the manual motor position to drive the motor to the LOW FIRE position, or use the Run/ Test switch option (if available) sequence to Run Drive to Low Fire and place in the TEST position. Adjust the Low Fire switch while in this state to assure that it is closing properly.
4. While in Run Drive to Low Fire state, measure the voltage between terminal 19 and G (ground). 120 Vac should be present. If not, the switch adjustment is incorrect and/or the switch is defective and needs replacement.
5. Reset and sequence the CB 780/CB 784. If 120 Vac was present between the Low Fire switch and terminal 19 and the fault still persists, replace the relay module.
(Continued)
2-12 750-166
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING (Continued).
Fault Code System Failure Recommended Troubleshooting
Fault 33 *Preignition ILK*
Fault 35 *Call Service*
Fault 36 *Call Service*
Fault 37 *Call Service*
Fault 38 *Call Service*
Fault 39 *Call Service*
Fault 40 *Call Service*
Fault 41 *Main Valve On*
Fault 42 *Pilot Valve On*
Fault 43 *Ignition On*
Preignition Interlock fault. 1. Check wiring; correct any errors.
2. Inspect the Preignition Interlock switches and assure proper funcitoning.
3. Check fuel valve operation. Valve must close within five seconds.
4. Reset and sequence the CB 780/CB 784. During Standby or Prepurge, measure the voltage between terminal 20 and G (ground). 120 Vac should be present. If not, the Preignition Interlock switches may be defective and need replacement.
5. If the fault persists, replace the relay module.
Safety relay was off when it should be on or fuse has blown.
Main valve terminal was off when it should be on.
Pilot (ignition) valve terminal was off when it should be on.
Ignition terminal was off when it should be on.
V2S valve terminal was off when it should be on.
Safety relay was on when it should be off.
Main valve terminal was on when it should be off.
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
1. Warning! Remove system power; turn off fuel supply.
2. Check wiring to terminal 9; correct any errors.
3. Inspect the Main Fuel Valve(s) and connections. Assure that switches are functioning correctly and are not jumpered or welded.
4. Reset and sequence the CB 780/CB 784.
5. If the fault persists, replace the relay module.
Pilot (ignition) valve terminal was on when it should be off.
1. Warning! Remove system power; turn off fuel supply.
2. Check wiring to terminal 8; correct any errors.
3. Inspect the Pilot Fuel Valve(s) and connections. Assure that switch is functioning correctly and is not jumpered or welded.
4. Reset and sequence the CB 780/CB 784.
5. If the fault persists, replace the relay module.
Ignition terminal was on when it should be off.
1. Warning! Remove system power; turn off fuel supply.
2. Check wiring to terminal 10; correct any errors.
3. Inspect the Ignition terminal and connections. Assure that switch is functioning correctly and is not jumpered or welded.
4. Reset and sequence the CB 780/CB 784.
5. If the fault persists, replace the relay module.
(Continued)
750-166 2-13
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING (Continued).
Fault Code System Failure Recommended Troubleshooting
Fault 44 *Pilot Valve 2 On*
Fault 45 *Low Fire Sw. Off*
Fault 47 *Jumpers Changed*
Fault 50 *Jumpers Wrong*
Fault 51 *Flame Too Strong*
Fault 52 *Internal Fault*
V2S valve terminal, used as a pilot, was on when it should be off.
Low fire interlock switch failure to close or stay closed.
The configuration jumpers differ from the sample taken at startup.
The sequence logic detected a combination of jumpers that is illegal for the sequence (e.g., if it was correct to clip jumper 1 or jumper 2, but not both, this fault would be used if both were clipped).
Flame signal value is too high to be valid.
Pilot Valve 2 terminal was off when it should be on.
1. Warning! Remove system power; turn off fuel supply.
2. Check wiring to terminal 21; correct any errors.
3. Inspect the Pilot Fuel Valve 2 and connections. Assure that switch is functioning correctly and is not jumpered or welded.
4. Reset and sequence the CB 780/CB 784.
5. If the fault persists, replace the relay module.
1. Check wiring; correct any errors.
2. Reset and sequence the CB 780/CB 784.
3. Use either the manual motor position to drive the motor to the LOW FIRE position, or use the Run/Test switch option, if available. Sequence to the LOW FIRE position and place the switch in the TEST position. Adjust the Low Fire switch while in this state to assure that it is closing properly.
4. While in the Drive to Low Fire state, measure the voltage between terminals 19 and G (ground). 120 Vac should be present. If not, the switch adjustment is incorrect and/or the switch is defective and should be replaced.
5. If steps 1 through 4 are correct and the fault still persists, replace the relay module.
1. Inspect the jumper connections. Assure that clipped jumpers were completely removed.
2. Reset and sequence the CB 780/CB 784.
3. If fault persists, replace the relay module.
1. Inspect jumpers and consult the instruction and installation guide for compatible jumper configurations. Assure clipped jumpers are completely removed.
2. Reset and sequence the CB 780/CB 784.
3. If fault persists, replace the relay module.
1. Assure that flame detector and flame amplifier are compatible.
2. Remove the flame amplifier and inspect its connectors. Reset the flame amplifier.
3. Reset and sequence the CB 780/CB 784.
4. Check the flame detector sighting position, reset and cycle. Measure flame strength. Does it meet specifications? If not, refer to flame detector and/or flame amplifier checkout procedures in installation instructions.
5. If the code reappears, replace the flame amplifier and/or the flame detector.
6. If fault persists, replace the relay module.
1. Inspect Pilot terminal 21 and connections. Assure that Pilot is functioning properly.
2. Reset and sequence the CB 780/CB 784.
3. If fault persists, replace the relay module.
(Continued)
2-14 750-166
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING (Continued).
Fault Code System Failure Recommended Troubleshooting
Fault 67 *AC Phase*
Fault 105 *Call Service*
Fault 106 *Call Service*
Fault 107 *Call Service*
Fault 109 *Call Service*
Fault 110 *Call Service*
Fault 111 *Call Service*
Fault 112 *Call Service*
Fault 113 *Call Service*
Fault 114 *Call Service*
Fault 117 *Call Service*
Fault 118 *Call Service*
L1 and L2 miswired/exchanged. 1. Check L1 and L2 for proper line phasing.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault reappears, remove power from the device, reapply power, reset and sequence the CB 780/CB 784.
3. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault reappears, remove power from the device, reapply power, reset and sequence the CB 780/CB 784.
3. If fault persists, replace the relay module.
Relay Module flame signal cross-check failure.
1. Reset and sequence the CB 780/CB 784.
2. If fault reappears, remove power from the device, reapply power, reset and sequence the CB 780/CB 784.
3. If fault persists, replace the relay module.
Negative cycle test failed; earth ground absent or line voltage phasing improper.
1. Assure that a good earth ground connection exists at the installation site and that all earth ground connections are complete and correct.
2. Assure that the CB 780/CB 784 and all loads operate at the same line voltage phase.
3. Reset and sequence the CB 780/CB 784.
4. If fault persists, replace the relay module.
Configuration jumpers differ from stored values.
1. Inspect the jumper connections. Assure they match the original selection and clipped jumpers were completely removed.
2. Reset and sequence the CB 780/CB 784.
3. If fault persists, replace the relay module.
4. Configuration jumpers must be selected prior to 200 hours of operation. If configuration jumpers are changed after 200 hours of operation, lockout 110 occurs.
Relay Module configuration jumper test failure.
1. Inspect the jumper connections. Assure they match the original selection and clipped jumpers have been completely removed.
2. Reset and sequence the CB 780/CB 784.
3. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
(Continued)
750-166 2-15
TABLE 4—FAULT MESSAGE AND RECOMMENDED TROUBLESHOOTING (Continued).
Fault Code System Failure Recommended Troubleshooting
Fault 119 *Call Service*
Fault 120 *Call Service*
Fault 121 *Call Service*
Fault 122 *Call Service*
Fault 123 *Call Service*
Fault 125 *Call Service*
Fault 126 *Call Service*
Fault 127 *Call Service*
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Relay Module self-test failure. 1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
Safety relay feedback circuit was in an improper state.
1. Reset and sequence the CB 780/CB 784.
2. If fault persists, replace the relay module.
2-16 750-166
TABLE 5—CB783 EXPANDED ANNUNCIATOR HOLD CODES.
Annunciation Message Symbol System Holds
BURNER OFF: T6
EA Burner switch is open.
(Burner Switch) STANDBY HOLD: T6
EA Auxiliary limit #1 is open.
(Aux. Limit #1) STANDBY HOLD: T6
EA Auxiliary limit #2 is open.
(Aux. Limit #2) STANDBY HOLD: T6
EA Open low water cutoff.
(LWCO) STANDBY HOLD: T6
EA High limit (pressure or temperature) exceeded.
(High Limit) STANDBY HOLD: T6
EA Auxiliary limit #3 is open.
(Aux. Limit #3) STANDBY HOLD: T6
EA No fuel selected.
(FuelSelect Off) STANDBY HOLD: T6
EA Both fuels selected.
(BothFuelSelect) STANDBY HOLD: T6
EA Oil pressure is above high oil pressure limit.
(High Oil Pres.) STANDBY HOLD: T6
EA Oil pressure is below low oil pressure limit.
(Low Oil Pres.) STANDBY HOLD: T6
EA Oil temperature is above high oil temperature limit.
(High Oil Temp.) STANDBY HOLD: T6
EA Oil temperature is below low oil temperature limit.
(Low Oil Temp.) STANDBY HOLD: T6
EA Atomizing switch is open.
(Atomizing Sw.) STANDBY HOLD: T6
EA Gas pressure is above high gas pressure limit.
(High Gas Pres.) STANDBY HOLD: T6
EA Gas pressure is below low gas pressure limit.
(Low Gas Pres.) STANDBY HOLD: T6
EA Control input is not energized.
(Circuit Fault)
750-166 2-17
TABLE 6—CB783 EXPANDED ANNUNCIATOR FAULT CODES.
Annunciation Message Symbol System Faults
LOCKOUT nna
EA Auxiliary limit #1 is open.
*Aux. Limit #1* LOCKOUT nnb
EA Auxiliary limit #2 is open.
*Aux. Limit #2* LOCKOUT nnc
EA Open low water cutoff.
*LWCO* LOCKOUT nnd
EA High limit (pressure or temperature) is exceeded.
*High Limit* LOCKOUT nne
EA Auxiliary limit #3 is open.
*Aux. Limit #3* LOCKOUT nnf
EA No fuel is selected.
*FuelSelect Off* LOCKOUT nng
EA Both fuels are selected.
*BothFuelSelect* LOCKOUT nnh
EA Oil pressure is above high oil pressure limit.
*High Oil Pres.* LOCKOUT nni
EA Oil pressure is below low oil pressure limit.
*Low Oil Pres.* LOCKOUT nnj
EA Oil temperature is above high oil temperature limit.
*High Oil Temp.* LOCKOUT nnk
EA Oil temperature is below low oil temperature limit.
*Low Oil Temp.* LOCKOUT nnm
EA Atomizing switch failed to close.
*Atomizing Sw.* LOCKOUT nnn
EA Gas pressure is above high gas pressure limit.
*High Gas Pres.* LOCKOUT nno
EA Gas pressure is below low gas pressure limit.
*Low Gas Pres.* LOCKOUT nnp
EA The airflow switch is open when it should be closed or vice versa.
*Airflow Switch* LOCKOUT nnq
EA Auxiliary interlock #3 is open.
*Aux. ILK #4* LOCKOUT nnr
EA Auxiliary interlock #4 is open.
*Aux. ILK #5* LOCKOUT nns
EA Other Auxiliary Interlocks are open.
*Other ILKs* LOCKOUT nny
EA Preignition Interlock or other valve closure switch is open.
*Valve Closure* LOCKOUT nnz
EA Other Preignition Interlocks are open.
*Other PIIs*
2-18 750-166
CB783 EXPANDED ANNUNCIATOR DIAGNOS­TIC CURRENT STATUS MESSAGES (TABLE 7)
These messages are used to provide information from the CB783 Expanded Annunciator to the Keyboard Display Module in the EA Diagnostic section under Current Status; see Table 7. This information explains the first limit or interlock in the system that is de-energized.
TABLE 7—CB783 EXPANDED ANNUNCIATOR
DIAGNOSTIC CURRENT STATUS MESSAGES.
Display Description
Burner Sw. Burner Switch Oper. Control Operating Control Aux. Limit #1 Auxiliary Limit #1 Aux. Limit #2 Auxiliary Limit #2 LWCO Low Water Cutoff High Limit High Temperature or High
Pressure Limit Aux. Limit #3 Auxiliary Limit #3 FuelSelectOff Fuel Select Off BothFuelSelect Both Fuels Selected High Oil Pres. High Oil Pressure Low Oil Pres. Low Oil Pressure High Oil Temp. High Oil Temperature Low Oil Temp. Low Oil Temperature Atomizing Sw. Atomizing Switch High Gas Pres. High Gas Pressure Low Gas Pres. Low Gas Pressure Airflow Sw. Airflow Switch Aux. ILK #4 Auxiliary Interlock #4 Aux. ILK #5 Auxiliary Interlock #5 All switches on
750-166 2-19
NOTES
2-20 750-166
T ecnnology Proven Worldwide
Loading...