Cleaver-Brooks CB780, CB784 Operation And Maintenance Manual

$25.00
Cleaver-Brooks
CB780/CB784
Operation and Maintenance Manual
750-166
DIVISION OF AQUA-CHEM, INC.
TO: Owners, Operators and/or Maintenance Personnel
It is the responsibility of the owner to train and advise not only his or her personnel, but the contractors' personnel who are servicing, repairing, or operating the equipment, in all safety aspects.
Cleaver-Brooks equipment is designed and engineered to give long life and excellent service on the job. The electrical and mechanical devices supplied as part of the unit were chosen because of their known ability to perform; however, proper operating techniques and maintenance procedures must be followed at all times. Although these components afford a high degree of protection and safety, operation of equipment is not to be considered free from all dangers and hazards inherent in handling and firing of fuel.
"Automatic" features included in the design do not relieve the attendant of any responsibility. Such features merely free him of certain repetitive chores and give him more time to devote to the proper upkeep of equipment.
It is solely the operator's responsibility to properly operate and maintain the equipment. No amount of written instructions can replace intelligent thinking and reasoning, and this manual is not intended to relieve operating personnel of the responsibility for proper operation.
Operating controls will normally function for long periods of time. Do not become lax in daily or monthly testing, assuming that normal operation will continue indefinitely. Malfunctions of controls lead to uneconomical operation and damage and, in most cases, these conditions can be traced directly to carelessness and deficiencies in testing and maintenance.
Operation of this equipment by the owner and his operating personnel must comply with all requirements or regulations of his insurance company and/or other authority having jurisdiction. In the event of any conflict or inconsistency between such requirements and the warnings or instructions contain herein, please contact Cleaver-Brooks before proceeding.
Cleaver-Brooks
CB780/CB784
Operation and Maintenance Manual
© Aqua-Chem, Inc., 1995
Please direct purchase orders for replacement manuals to your local
Cleaver-Brooks authorized representative
Manual Part Number 750-166 6/95 Rev 10/95
Printed in U.S.A.
CONTENTS
Section 1 – Installation and Operating Instructions Section 2 – System Annunciation Diagnostics and Troubleshooting
Section 1 - CB780/CB784
Installation and Operating Instructions
The Cleaver-Brooks CB780/CB784 is a microprocessor based integrated burner control for automatically fired gas, oil, or combination fuel single burner applications. The CB780 consists of a Relay Module and Keyboard Display Module. The CB784 consists of the Relay Module only. The Keyboard Display Module is optional with the CB784. Sub­base, Amplifier, and Purge Card are r e quired to complete the system. Options include Personal Computer Interface, Control Bus, Remote Display Mounting, First-Out Expanded Annun­ciator and Combustion System Managment software.
The CB780/CB784 is programmed to provide a level of safety, functional capability and features beyond the capacity of conventional controls.
Functions provided by the CB780/CB784 include auto­matic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting
.
Safety features:
—Interlock check. —Closed loop logic test. —Dynamic Auto-Check. —Dynamic input check. —Dynamic safety relay test. —Dynamic self-check logic. —Expanded safe-start check. —High Fire Purge Switch test. —Internal hardware status monitoring. —Low Fire Start Switch test. —Tamper resistant timing and logic.
Access for external electrical voltage checks.
Application flexibility.
Communication interface capability.
Dependable, long-term operation provided by microcom-
puter technology.
First-out annunciation and system diagnostics provided by
a 2 row by 20 column Vacuum Fluorescent Display (VFD) located on the Keyboard Display Module.
First-out expanded annunciation with 26 Light Emitting
Diodes (LEDs) for limits and interlocks (optional).
Five sequence information Light Emitting Diodes (LEDs).
Five function Run/Test Switch.
Interchangeable plug-in flame amplifiers.
Local or remote annunciation of operation and fault
information.
Nonvolatile memory for retaining history files and sequenc-
ing status after loss of power.
Remote reset (optional).
Report generation (optional).
Burner controller data:
—Sequence status. —Sequence time. —Hold status. —Lockout/alarm status.
—Flame signal strength. —Expanded annunciator status. —Total cycles of operation. —Total hours of operation. —Fault history of six most recent faults:
• Cycles of operation at time of fault.
• Expanded annunciator data at time of fault.
• Fault message and code.
• Hours of operation at time of fault.
• Sequence status at time of fault.
• Sequence time at time of fault.
—Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time.
• Manufacturing code.
• On/Off status of all digital inputs and outputs.
• Selected prepurge time.
• Software revision and version of CB780/CB784 and Keyboard Display Module.
• Status of configuration jumpers.
• Status of Run/Test Switch.
CONTENTS
Specifications ............................................................... 2
Principle Technical Features ...................................... 6
Safety Provisions ......................................................... 7
Installation ................................................................... 9
Wiring ........................................................................ 11
Assembly .................................................................... 15
Operation ................................................................... 18
Static Checkout .......................................................... 25
Checkout .................................................................... 27
Troubleshooting ......................................................... 34
750-166 1-1
CB780/CB784 SPECIFICATIONS
Specif ications
ELECTRICAL RATINGS, see Table 1:
Voltage and Frequency: 120 Vac (+10/-15%), 50 or
60 Hz (+/- 10%)5.
Keyboard Display Module: 13 Vdc peak full wave
rectified (+20/-15%).
Power Dissipation:
CB780/CB784: 10W maximum.
Display Module: 3W maximum. Maximum Total Connected Load: 2000 VA. Fusing: Total Connected Load: 20A maximum, type
FRN or equivalent.
TABLE 1—TERMINAL RATINGS.
Terminal No. Description Ratings
G Flame Sensor Ground
Earth G Earth Ground
1
1
L2(N) Line Voltage Common
3 Alarm 120 Vac, 1A pilot duty. 4 Line Voltage Supply (L1) 120 Vac (+10/-15%), 50 or 60 Hz (±10%).
2,5
5 Burner Motor 120 Vac, 9.8AFL, 58.8ALR (inrush). 6 Burner Controller and Limits 120 Vac, 1 mA. 7 Lockout/Running Interlock 120 Vac, 9A. 8 Pilot Valve/Ignition 120 Vac, 4.5A ignition and 50VA pilot duty. 9 Main Fuel Valve 120 Vac, 2A pilot duty.
10 Ignition 120 Vac, 4.5A Ignition.
4
3
3
F(11) Flame Sensor 60 to 220 Vac, current limited.
12 Firing Rate High Fire 120 Vac, 75 VA pilot duty. 13 Firing Rate Common 120 Vac, 75 VA pilot duty. 14 Firing Rate Low Fire 120 Vac, 75 VA pilot duty. 15 Firing Rate Modulate 120 Vac, 75 VA pilot duty. 16 Unused 17 Unused 18 Low Fire Switch Input 120 Vac, 1 mA. 19 High Fire Switch Input 120 Vac, 1 mA. 20 Preignition Interlock Input 120 Vac, 1 mA. 21 Interrupted/Pilot Valve/First Stage Oil Valve 120 Vac, 2A pilot duty. 22 Shutter 120 Vac, 0.5A.
1
The CB780/CB784 must have an earth ground providing a connection between the subbase and the control panel or the equipment. The earth ground wire must be capable of conducting the current to blow the 20A fuse (or breaker) in event of an internal short circuit. The CB780/CB784 needs a low impedance ground connection to the equipment frame which, in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection must be made by minimum length conductors having maximum surface areas. Wide straps or brackets are preferred rather than leadwires. Be careful to ensure that mechanically tightened joints along the ground path, such as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coatings and are protected against mating surface corrosion.
2
2000 VA maximum connected load to CB780/CB784 Assembly.
3
Can also be 120 Vac, 1A pilot duty.
4
Can also be 65 VA pilot duty with motorized valve, 1150 VA inrush, 460 VA open, 250 VA hold.
5
Operating frequency chosen by CB780/CB784 selection.
1-2 750-166
CB780/CB784
SPECIFICATIONS
ENVIRONMENTAL RATINGS:
Ambient Temperature:
Operating: -40°F to 140°F.
WEIGHT:
CB780/CB784: 1 pound 10 ounces, unpacked. Keyboard Display Module: 4 ounces, unpacked.
Storage: -40°F to 150°F. Humidity: 85% RH continuous, noncondensing. Vibration: 0.5G environment.
DIMENSIONS: Refer to Figs. 1 and -2.
IMPORTANT: Flame Detection System available for use
with CB780/CB784. To select your Plug-in Flame Signal Amplifier and matching Flame Detector, see Table 2.
TABLE 2—FLAME DETECTION SYSTEMS (FIGS. 3, 4, 5).
Plug-In Flame Amplifiers Applicable Flame Detectors
Flame
Failure
Part
Type Color Self-Checking
Number
Infrared Red No 833-2722 3 sec. Gas, oil,
Dynamic AMPLI-
Dynamic Auto-Check
CHECK™
833-2723
Response
Time Fuel Type
coal
c
Gas, oil, coal
Infrared (Lead Sulfide)
Infrared (Lead Sulfide)
Part
Number
817-1742
817-1742
Ultraviolet Purple No 833-2724 Gas, oil Ultraviolet 817-1743 Ultraviolet
Self-Check
Green Dynamic Self-
Check
833-2741
b
Gas, oil, coal
Ultraviolet (Purple
817-1121
Peeper)
a
The 817-1743 Flame Detector should be used only on burners that cycle on-off at least once every twenty-four hours. Appliances with burners that remain on for twenty-four hours continuously or longer should use the 817-1121 Flame Detector with the 833-2741 Amplifier as the ultraviolet flame detection system.
b
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during burner operation and shuts down the burner if the detection system fails.
c
Circuitry tests the flame signal amplifier 12 times a minute during burner operation and shuts down the burner if the amplifier fails.
a
Firing
Rate
2
Energy
Saving
No FM/IRI
Approval
Code
Modulating
TABLE 3—SEQUENCE TIMING FOR NORMAL OPERATION.
Flame
Establishing
Period
Device Initiate Standby Purge Pilot Main Run
CB 780/ CB 784
* STANDBY and RUN can be an infinite time period.
** PURGE will be determined by which purge card is selected.
1
The MFEP will be determined by which terminal is used, see Figs. 7 and 18.
2
The operating sequence of the CB780 and CB784 Relay Modules are identical. The only difference between the Relay
10 sec * ** 4 or
10 sec
10 or 15 sec
* 15 sec Preignition,
1
Post
Purge Interlock
Timing Circuits Circuit Prepurge Bodies
Lockout, High and Low Fire
4-wire modulating
Modules is that the Keyboard Display Module is standard with the CB780 and optional with the CB784.
APPROVAL BODIES:
Underwriters Laboratories Inc. listed, File No. MP268,
Guide No. MCCZ. Canadian Standards Association certified, LR9S329-3.
Factory Mutual approved, Report No. JI1V9A0.AF. IRI acceptable. Federal Communications Commission, Part 15, Class B—
Emissions.
750-166 1-3
CCB780/CB784 SPECIFICATIONS
MOUNTING: 833-2725 for panel mount. REQUIRED COMPONENTS:
CB780: 120 Vac/60 Hz, 833-2718. CB780: 120 Vac/50 Hz, 833-2719. CB784: 120 Vac/60 Hz, 833-2720. CB784: 120 Vac/ 50 Hz, 833-2721 Plug-in Flame Signal Amplifier, see Table 2. Plug-in Purge Timer Cards: selectable:
833-2730 30 sec. 833-2731 60 sec. 833-2732 90 sec. 833-2733 2-1/2 min.
ACCESSORIES:
Optional:
Control Bus—part no. 833-2729. Provides
communication and remote reset capabilities on CB784; remote display capabilities on CB780
and CB784. CB783 Expanded Annunciator—part no. 833-2726. Keyboard Display Module—part no. 833-2727.
(Standard on CB780; optional on CB784.) Remote Mounting Kit for the Keyboard Display,
NEMA 4—part no. 833-2740. Tester—part no. 626-5050.
NOTE: The CB780 and CB784 are identical except for the
Keyboard Display Module which is standard with the CB780 and optional with the CB784.
Fig. 1—Mounting dimensions of CB780/CB784 Relay Module and 833-2725 Subbase, in inches (mm)
BURNER CONTROL
SCROLL MODE
SAVE
5
(127)
POWER PILOT FLAME MAIN ALARM
RESET
5 (127)
1
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
5-1/4 (133)
M7399
1-4 750-166
CB780/CB784
,
,
SPECIFICATIONS
Fig. 2—Mounting dimensions of Keyboard Display Module, in inches (mm).
BURNER CONTROL
2-3/4 (69)
15/ 32 (12)
1-15/16 (49)
29/32 (23)
SCROLL MODE
19/32 (15)
5/32 (4)
4-27/32 (123)
1-1/4 (32)
7/16 (11)
2-5/16 (58)
3-7/8 (99)
SAVE
4-3/32 (104)
1-1/32 (26)
13/ 32 (11)
5/32 (4)
1/2 (13)
5/16 (8)
2-1/32 (52)
5/15 (8)
29/32 (23)
M7405
Fig. 4—Ultraviolet detector.
4 (102)
3-1/2 (89)
COLLAR WITH 1/2-14 NPSM INTERNAL THREADS
817-1743
Fig. 5—Infrared detector.
2-3/4
(70)
2 LEADS IN A 48 INCH [1.2 METER] FLEXIBLE CONDUIT
BUSHING WITH MAGNIFYING LENS
COLLAR, 3/4-14 NPSM INTERNAL THREADS
817-1742
1-1/4
(32)
APERTURE
6 FOOT (1.83 METER) LEADWIRES (2)
1-1/16
(27)
HEAT BLOCKCELL MOUNT
1-5/8 (41)
1-1/16 (27)
1-1/4
3/4-14 NPSM
3/4-14 NPSM INTERNAL THREADS
M7419
(32)
M1982A
833-2727
(Standard with CB780, optional with CB784)
Fig. 3—Ultraviolet Self-Check detector.
3-3/4
(95)
7-7/32
(183)
1/2–14 NPSM
LEADWIRES
MOUNTING FLANGE
817-1121
5-1/8 (130)
3-7/16
(87)
FACEPLATE
3/4–14 NPT
5-1/4 (133)
M1962A
750-166 1-5
CB780/CB784 PRINCIPAL TECHNICAL FEATURES
Principal T echnical Features
The CB780/CB784 provides all customary flame safe­guard functions while providing significant advancements in the areas of safety, annunciation and system diagnostics.
SAFETY SHUTDOWN (LOCKOUT) OCCURS IF:
1. INITIATE Period a. Purge card is not installed or removed. b. Purge card is bad. c. Configuration jumpers were changed (after
200 hours). d. AC line power errors, see Operation. e. Four minute INITIATE period is exceeded.
2. STANDBY Period a. Flame signal is present after 40 seconds. b. Preignition Interlock is open an accumulative time
of 30 seconds.
c. Interlock check feature is enabled and the Inter-
lock String (including the airflow switch) is closed for 120 seconds with controller closed.
d. Ignition/pilot valve/intermittent pilot valve termi-
nal is energized. e. Main valve terminal is energized. f. Internal system fault. g. Purge card is not installed or removed. h. Purge card is bad.
3. PREPURGE Period a. Preignition Interlock opens anytime during
PREPURGE.
b. Flame signal detected after first ten seconds during
PREPURGE.
c. High Fire Switch fails to close within four minutes,
fifteen seconds after firing rate motor is commanded to drive to high fire position at start of PREPURGE.
d. Low Fire Switch fails to close within four minutes,
fifteen seconds after firing rate motor is commanded
to drive to low fire position at end of PREPURGE. e. Lockout Interlock does not close within 10 seconds. f. Lockout Interlock opens during PREPURGE. g. Ignition/pilot valve/intermittent pilot valve termi-
nal is energized. h. Main valve terminal is energized.
i. Internal system fault. j. Purge card is removed. k. Purge card is bad.
4. PILOT FLAME ESTABLISHING Period (PFEP) a. Low Fire Switch opens. b. Lockout Interlock opens. c. Ignition/pilot valve/intermittent pilot valve terminal
is not energized.
d. Early Spark Termination terminal is energized af-
ter five seconds. e. No flame is present at end of PFEP. f. Internal system fault. g. Purge card is removed. h. Purge card is bad.
5. MAIN FLAME ESTABLISHING Period (MFEP) a. Low Fire Switch opens. b. Lockout Interlock opens. c. Ignition/pilot valve/intermittent pilot valve termi-
nal is not energized. d. Main valve terminal is not energized. e. No flame is present at end of MFEP. f. Internal system fault. g. Purge card is not installed or removed. h. Purge card is bad.
6. RUN Period a. No flame is present. b. Lockout Interlock opens. c. Main valve terminal is not energized. d. Internal system fault. e. Purge card is not installed or removed. f. Purge card is bad.
7. POSTPURGE Period a. Preignition Interlock does not close within five sec-
onds or opens after five-second time period.
b. Ignition/pilot valve/intermittent pilot valve termi-
nal is energized. c. Main valve terminal is energized. d. Internal system fault. e. Purge card is removed. f. Purge card is bad.
1-6 750-166
CB780/CB784
SAFETY PROVISIONS
Safety Pro visions
INTERNAL HARDWARE STATUS MONITORING
The CB780/CB784 checks the purge card for correct parity to prevent purge timing shifts and circuitry failures. It also analyzes the integrity of the configuration jumpers and internal hardware. The POWER LED blinks every four seconds, signifying an internal hardware check.
CLOSED LOOP LOGIC TEST
The test verifies the integrity of all safety critical loads, terminals 8, 9, 10 and 21. If the loads are not energized properly; i.e., the main valve terminal is powered during PREPURGE, the CB780/CB784 will lockout on safety shut­down. The CB780/CB784 must react to input changes but avoid the occurrence of nuisance shutdown events. Signal conditioning is applied to line voltage inputs to verify proper operation in the presence of normal electrical line noise such as transient high voltage spikes or short periods of line dropout. Signal conditioning is tolerant of synchronous noise (line noise events that occur at the same time during each line cycle).
DYNAMIC AUTO-CHECK
Dynamic Auto-Check circuitry tests the flame signal amplifier during burner operation and shuts down the CB780/ CB784 if the flame amplifier fails.
DYNAMIC FLAME AMPLIFIER AND SHUTTER CHECK
Self-checking circuitry tests all electronic components in the flame detection system and amplifier 10 to 12 times per minute and shuts down the CB780/CB784 if the detection system fails.
DYNAMIC INPUT CHECK
All system input circuits are examined to verify that the CB780/CB784 is capable of recognizing the true status of external controls, limits and interlocks. If any input fails this test, a safety shutdown occurs and the fault is annunciated.
DYNAMIC SAFETY RELAY TEST
Checks the ability of the dynamic safety relay contacts to open and close. It also verifies that the safety critical loads, terminals 8, 9, 10 and 21, can be de-energized, as required, by the Dynamic Self-Check logic.
DYNAMIC SELF-CHECK SAFETY CIRCUIT
The microcomputer tests itself and related hardware while at the same time the safety relay system tests the micro­computer operation. If a microcomputer or safety relay failure occurs and does not allow proper execution of the self-check routine, safety shutdown will occur and all safety critical loads will be de-energized.
EXPANDED SAFE-START CHECK
The conventional safe-start check, which prevents burner start-up if flame is indicated at start-up, is expanded to include a flame signal check during STANDBY, a preigni­tion interlock check, an interlock check, and a safety critical load check.
HIGH FIRE PURGE AND LOW FIRE START SWITCH TESTS
High Fire Purge Switch Test examines the Purge Posi­tion Interlock Switch at the moment the firing rate motor is commanded to the high fire position. If the switch is by­passed, welded or otherwise closed prematurely, the system will automatically add 30 seconds to allow additional drive time for the firing rate motor to reach or near the open position before starting the purge timing; otherwise, purge timing starts when the High Fire Switch is closed. This switch will also cause a hold (four minutes, fifteen seconds) condition when the switch is open before purge or opens during purge. The CB780/CB784 will lockout and annunci­ate an alarm if the switch fails to close within the hold time period.
Low Fire Start Switch Test examines the Low Fire Start Switch at the moment PREPURGE is completed. If the switch is bypassed, welded or otherwise prematurely closed, the system automatically adds 30 seconds to allow the firing rate motor additional time to reach or near the low fire start position before ignition trials; otherwise, ignition trials start after the Low Fire Switch closes. The test also is used to prove that the firing rate motor is at low fire position throughout the ignition trial period. This switch will also cause a hold (four minutes, fifteen seconds) condition if the switch opens after purging is complete. The CB780/CB784 will lockout and annunciate an alarm if the switch fails to close within the hold time period.
750-166 1-7
CB780/CB784 SAFETY PROVISIONS
MANDATORY PURGE
If lockout occurs after the initiation of ignition trials, (or at anytime during a sequence when the fuel valves may have been energized), a mandatory POSTPURGE period is imposed.
OFF CYCLE (STANDBY OR PREPURGE) FLAME SIGNAL CHECK
The flame detection subsystem (flame detector and am­plifier) is monitored during STANDBY. If a flame simulat­ing condition or an actual flame exists, a system hold occurs and start-up is prevented. If the flame signal exists at any time after the first 40 seconds of STANDBY, a safety shut­down will occur and be annunciated. A shutter-check ampli­fier and self-checking detector are energized for the first 40 seconds during STANDBY and the last two seconds before exiting STANDBY. If a flame exists, a safety shut­down occurs. An Auto-Check Amplifier is energized con­tinually through STANDBY and PREPURGE to detect any possibility of a runaway detector or a flame. If either situa­tion happens, a safety shutdown occurs. A standard amplifier is energized continually through STANDBY and PREPURGE. If either situation happens, a safety shutdown occurs.
PREIGNITION OUTPUT CIRCUIT CHECK
At the end of PREPURGE, the Dynamic Safety Relay operation is checked. Also, all safety critical loads, terminals 8, 9, 10 and 21 are checked to verify the terminals are not powered. If the Dynamic Safety Relay operation is faulty, or if any of the safety critical loads are powered, safety shut­down occurs and is annunciated.
TAMPER RESISTANT TIMING AND LOGIC
Safety and logic timings are inaccessible and cannot be altered or defeated.
VERIFIED SPARK TERMINATION
The ignition terminal is monitored to verify early spark termination (five seconds ignition and pilot and five seconds pilot only).
FIRST-OUT ANNUNCIATION AND SELF-DIAGNOSTICS
Sequence Status Lights (LEDs) provide positive visual indication of the program sequence: POWER, PILOT, FLAME, MAIN and ALARM. The green POWER LED blinks every four seconds to signify the CB780/CB784 hardware is running correctly.
Multi-function Keyboard Display Module (standard with CB780, optional with CB784) shows elapsed time during PREPURGE, PILOT IGN, MAIN IGN, and POSTPURGE. As an additional troubleshooting aid, it provides sequence timing, diagnostic information, historical information and expanded annunciator information when a safety shutdown or hold or normal operation occurs.
First-out Annunciation reports the cause of a safety shut­down or identifies the cause of a failure to start or continue the burner control sequence with an English text and num­bered code via the Keyboard Display Module. It monitors all field input circuits, including the Flame Signal Amplifier and Firing Rate Position Switches. The system distinguishes 118 modes of failure and detects and annunciates difficult­to-find intermittent failures.
Self-Diagnostics adds to the First-out Annunciation by allowing the CB780/CB784 to distinguish between field (external device) and internal (system related) problems. Faults associated within the flame detection subsystem, CB780/CB784 or plug-in Purge Card, are isolated and re­ported by the Keyboard Display Module. See the Diagnos­tics and Troubleshooting section of the CB780/CB784 Op­eration and Maintenance Manual, Manual Number 750-166.
INTERLOCK REQUIREMENTS
The following interlock inputs are provided:
Low Fire Interlock
This interlock verifies the firing rate motor is in the low fire position before and during ignition trials.
High Fire Interlock
This interlock verifies the firing rate motor is in the high fire position prior to and during PREPURGE.
Lockout Interlock
This interlock (ILK) input signifies a Lockout Interlock. If the Lockout Interlock is open for more than ten seconds into PREPURGE, the CB780/CB784 will lockout. After entering PREPURGE, if the Lockout Interlock opens during the first ten seconds, the purge timer will be reset. This provides a continuous PURGE to occur without interruption before the Pilot Flame Establishing Period. If a Lockout Interlock opens anytime after ten seconds into PURGE, during the Ignition Trials or Run, it causes a lockout.
A typical Lockout Interlock string contains an airflow switch (see Fig. 7). The Interlock Check is a site configur­able option (see Table 7). If this feature is enabled, the CB780/CB784 will lockout after 120 seconds whenever control terminal 6 is energized, and the Lockout Interlock string (including airflow switch) is closed during STANDBY.
Preignition Interlock
The Preignition Interlock input is typically connected to proof-of-closure switches for fuel valve(s). The Preignition Interlock must be energized throughout PREPURGE. If the Preignition Interlock opens during STANDBY, it causes a hold (30 seconds). The CB780/CB784 will lockout if the interlock does not close within 30 seconds during STANDBY. If the Preignition Interlock opens during PREPURGE, it will lockout. If the Preignition Interlock is open after five sec­onds into POSTPURGE, the CB780/CB784 will lockout. The Preignition Interlock is ignored during the ignition trials state and during RUN.
1-8 750-166
WARNING
FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH.
To prevent possible hazardous burner operation, verification of safety requirememts must be per- formed each time a control is installed on a burner.
WHEN INSTALLING THIS PRODUCT…
1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and marked on the product to make sure the product is suitable for the application.
3. Installer must be a trained, experienced, flame safe­guard service technician.
4. After installation is complete, check out the product operation as provided in these instructions.
CA UTION
1. Disconnect the power supply before beginning installation to prevent electrical shock, equip- ment and control damage. More than one power supply disconnect may be involved.
2. Wiring connections for the CB780/CB784 are unique; therefore, refer to Figs. 6, 7, 8 o r 9 or the correct Specifications for proper subbase wiring.
3. Wiring must comply with all applicable codes, ordinances and regulations.
4. Wiring, where required, must comply with NEC Class 1 (Line Voltage) wiring.
5. Loads connected to the CB780/CB784 must not exceed those listed on the CB780/CB784 label or the Specifications, see Table 1.
6. Limits and interlocks must be rated to simulta- neously carry and break current to the ignition transformer, pilot valve, and main fuel valve(s).
7. All external timers must be listed or component recognized by authorities who have jurisdiction for the specific purpose for which they are used.
IMPORTANT:
1. For on-off gas-fired systems, some authorities who have jurisdiction prohibit the wiring of any limit or operating contacts in series between the flame safe­guard control and the main fuel valve(s).
2. Two Flame Detectors can be connected in parallel with the exception of Infrared Flame Detector (817-1742).
CB780/CB784
INSTALLATION
Installation
3. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause interfer­ence to radio communications. It has been tested and found to comply with the limits for a Class B comput­ing device of Part 15 of FCC rules which are designed to provide reasonable protection against such inter­ference when operated in a commercial environment. Operation of this equipment in a residential area may cause interference; in which case, the users at their own expense may be required to take whatever mea­sures are required to correct this interference.
4. This digital apparatus does not exceed the Class B limits for radio noise for digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
HUMIDITY
Install the CB780/CB784 where the relative humidity never reaches the saturation point. The CB780/CB784 is designed to operate in a maximum 85% RH continuous, noncondensing, moisture environment. Condensing mois­ture may cause a safety shutdown.
VIBRATION
Do not install the CB780/CB784 where it could be sub­jected to vibration in excess of 0.5G continuous maximum vibration.
WEATHER
The CB780/CB784 is not designed to be weather tight. If installed outdoors, the CB780/CB784 must be protected by an approved weather-tight enclosure.
MOUNTING WIRING SUBBASE
NOTE: For installation dimensions, see Fig. 1.
1. Mount the subbase in any position except horizontally with the bifurcated contacts pointing down. The standard vertical position is recommended. Any other position de­creases the maximum ambient temperature rating.
2. The 833-2725 Wiring Subbase can be mounted di­rectly in the control cabinet. Be sure to allow adequate clear­ance for servicing, installation, access or removal of the CB780/CB784, Expanded Annunciator, Keyboard Dis­play Module, flame amplifier, flame amplifier signal voltage probes, Run/Test Switch, electrical signal voltage probes and electrical field connections.
3. For surface mounting, use the back of the subbase as a template to mark the four screw locations. Drill the pilot holes.
4. Securely mount the subbase using four no. 6 screws.
750-166 1-9
CB780/CB784 INSTALLATION
Fig. 6—Internal block diagram of the CB780/CB784 (see Figs.7,8,9, or 10 for detailed wiring instructions).
4
RESET PUSHBUTTON
STATUS LEDs
RUN/TEST SWITCH
CONFIGURATION JUMPERS
MICROCOMPUTER
SAFETY RELAY CIRCUIT
RELAY DRIVE CIRCUIT
L1 (HOT) L2
1
120 Vac
2K 3K 4K 5K
6K 7K 8K 9K
1K
POWER SUPPLY
PLUG-IN PURGE TIMER CARD
FLAME SIGNAL
PLUG-IN FLAME AMPLIFIER
TEST
L2
TEST JACK
F
G
22
RELAY STATUS FEEDBACK AND LINE VOLTAGE INPUTS
CONTROL POWER
20
PRE-IGNITION INTERLOCK
LIMITS CONTROLLER
6K1
3K1
KEYBOARD
DDL
DISPLAY MODULE
RS485
DDL COMMUNICATIONS
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
1
1
2
LOCKOUT INTERLOCK
6
LOW FIRE SWITCH
18
HIGH FIRE SWITCH
19
REMOTE
3
RESET
1K1 2K1 5K1
7
4K1
7K1
2K2
HIGH FIRE
8K1
COMMON
8K2
MODULATE
9K2
LOW FIRE
2
9K1
12
13
15
14
2 REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
10
8
21
9
5
3
INDICATES FEEDBACK SENSING TO RELAY STATUS FEEDBACK AND LINE VOLT INPUTS
FIELD WIRING INTERNAL WIRING
IGNITION
PILOT
PILOT/V2
MAIN VALVE
BLOWER
ALARM
M7420
1-10 750-166
CB780/CB784
Wiring
WIRING
1. a. For proper subbase wiring, refer to Fig. 7. b. For proper remote wiring of the Keyboard Dis-
play Module, refer to Fig. 8, 9 or 10 or to the Specifications for the Keyboard Display Module, Communication Interface Base Unit or Control Bus.
2. Disconnect the power supply from the main discon-
nect before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may be involved.
3. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where required, must comply with NEC, Class 1 (Line Voltage) wiring.
4. Recommended wire size and type: a. All Line Voltage terminals use no. 14 or 16 cop-
per conductor (90°C or higher) 600 volt insula­tion wire (wire size must be coordinated with fuse protection). For high temperature installations, use wire selected for a temperature rating above the maximum operating temperature. All leadwires should be moisture resistant.
b. Keyboard Display Module—For communica-
tions purposes, use an unshielded 22 AWG 2-wire twisted cable and one wire for ground if the leadwire run and noise conditions permit; how­ever, some installations may need up to five wires, three for communications and two for remote reset (in either a single cable or separate cables for com­munications or remote reset) or use Belden 8771 shielded cable or equivalent. The Keyboard Dis­play Module, Control Bus (for remote mounting or communications) or Communication Interface ControlBus Module must be wired in a daisy chain configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connectors, for connec­tions over 100 feet, see Fig. 8, 9 and 10.
c. Control Bus—For communications purposes,
use an unshielded 22 AWG 2-wire twisted cable if the leadwire run and noise conditions permit; however, some installations may need up to five wires, three for communications and two for re­mote reset (in either a single cable or separate cables) or use a Belden 8771 shielded cable or equivalent. The Keyboard Display Module, Con­trol Bus (for remote mounting or communications) or Communication Interface ControlBus Module must be wired in a daisy chain configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of inter­connection of all the devices listed above is not
important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resis­tor termination across terminals 1 and 2 of electri­cal connectors, for connections over 100 feet, see Fig. 8, 9 and 10.
d. Remote Reset*—Use no. 22 AWG or greater
twisted pair wire, insulated for low voltage; see Fig. 8, 9 and 10.
e. Communication Interface ControlBus Module—
For communications purposes, use an unshielded 22 AWG 2-wire twisted cable if the leadwire run and noise conditions permit or use a Belden 8771 shielded cable or equivalent. The Keyboard Display Module, Control Bus (for remote mount­ing or communications) or Communication Inter­face ControlBus Module must be wired in a daisy chain configuration, (1(a)-1(a), 2(b)-2(b), 3(c)-3(c)). The order of interconnection of all the devices listed above is not important. Be aware that modules on the closest and farthest end of the daisy chain configuration string require a 120 ohm (1/4 watt minimum) resistor termination across terminals 1 and 2 of the electrical connec­tors, for connections over 100 feet, see Fig. 8, 9 and 10.
f. Use the recommended wire size for the 13 Vdc
full wave rectified transformer power input of no. 18 AWG wire insulated for voltages and tem­peratures encountered in the application. Sug­gested wire types include TTW(60C), THW(75C) and THHN(90C).
5. Recommended grounding practices: a. The earth ground provides for a connection be-
tween the subbase and the control panel of the equip­ment. The earth ground wire must be capable of conducting the current to blow the 20A fuse (or breaker) in event of an internal short circuit. The CB780/CB784 needs a low impedance ground connection to the equipment frame which, in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF frequencies, the connection must be made with minimum length conductors that have a maximum surface area. Wide straps or brackets are preferred rather than leadwires. Be careful to ensure that mechanically tightened joints along the ground path, such as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coatings and are protected against corrosion on mating surfaces.
b. Keyboard Display Module,
Comm
unication Interface ControlBus Module—
Control Bus, or
750-166 1-11
*Note: Remote Reset must be mounted within sight of the boiler control panel.
CB780/CB784 WIRING
The shield, if used, should be connected to the signal ground terminal 3(c) provided as part of the CB780/CB784 device ControlBus connection. Connect the shield at both ends to earth ground.
c. CB780/CB784—Each CB780/CB784 will have
an earth ground terminal that must be grounded to the metal control panel with wire as short as prac­tical. Each ground wire must be capable of carrying a fault current equal to the rating of the protec­tive fuse (20A). A number 14 copper conductor is adequate, but wide straps or brackets are pre­ferred rather than leadwires.
6. Recommended wire routing: a. Flame detector leadwires:
1. Do not run high voltage ignition transformer wires in the same conduit with the flame detec­tion wiring.
2. Do not route scanner wires in conduit with line voltage circuits.
3. Enclose scanner wires without armor cable in metal cable or conduit.
4. Follow directions in flame detector Instructions.
b. Control Bus:
1. Do not run high voltage ignition transformer wires in the same conduit or close proximity with the Control Bus wiring.
2. Do not route Control Bus wires in conduit with line voltage circuits.
c. Keyboard Display Module (VFD): Because the
VFD is powered from a low voltage, energy lim­ited source, it can be mounted outside of a control panel if it is protected from mechanical damage.
d. Remote Reset:
1. Do not run high voltage ignition transformer wires in the same conduit with the Remote Reset wiring.
2. Do not route Remote Reset wires in conduit with line voltage circuits.
NOTE: A 13 Vdc power supply must be used any time more
than one Keyboard Display Module is used.
7. Maximum wire lengths: a. CB780/CB784 leadwires—The maximum length
of leadwire is 300 feet to terminal inputs (Control, Preignition Interlock, Running/Lockout Interlock, High Fire Switch and Low Fire Switch).
b. Flame Detector leadwires—The maximum flame
sensor leadwire length is limited by the flame signal strength.
c. Remote Reset leadwires—The maximum length
of wire is 1000 feet to a Remote Reset pushbutton.
d. Control Bus—The maximum Control Bus cable
length depends on the number of system modules connected, the noise conditions and the cable used. The maximum length of all interconnecting wire is 1000 feet.
8. Make sure loads do not exceed the terminal ratings.
Refer to the label on the CB780/CB784 or to the ratings in Specifications; see Table 1.
9. Check the power supply circuit. The voltage and fre-
quency tolerance must match those of the CB780/CB784. A separate power supply circuit may be required for the CB780/CB784. Add the required disconnect means and overload protection.
10. Check all wiring circuits and complete the Static Checkout, see Table 8, before installing the CB780/CB784 on the subbase.
11. Install all electrical connectors.
12. Restore power to the panel.
1-12 750-166
FIG. 7—WIRING CB780/CB784
833-2725
G
12
HIGH FIRE
SERIES 90 FIRING RATE MOTOR
B
SERIES 90 CONTROLLER
B
CB780/CB784
WIRING
13
14
15
16
17
18
19
20
21
22
COMMON
LOW FIRE
MODULATE
LOW FIRE START SWITCH
HIGH FIRE PURGE SWITCH
PREIGNITION INTERLOCK
15 SEC. INTERRUPTED PILOT VALVE
MASTER SWITCH
R
W
L1 (HOT)
L2
R
W
1
120V ALARM
BURNER MOTOR (BLOWER)
BURNER CONTROLLER/LIMITS
LOCKOUT INTERLOCKS (INC. AIR FLOW SWITCH)
10 SEC. INTERRUPTED PILOT/IGNITION
MAIN FUEL VALVE(S)
5 SECOND IGNITION (EARLY SPARK)t
(EARLY SPARK
(TERMINATION)
TERMINATION)
817-1742 INFRARED (LEAD SULFIDE) FLAME DETECTOR
L2
10
3
(L1)
4
5
6
7
8
9
F
OR
WHITE
817-1743 ULTRAVIOLET FLAME DETECTOR
OR
YELLOW
1 2
817-1121 ULTRAVIOLET FLAME DETECTOR
120V, 60 Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. DO NOT WIRE TO ANY UNUSED TERMINALS.
BLUE
BLUE
WHITE WHITE BLACK BLACK
FOR DIRECT SPARK IGNITION (OIL OR GAS)
IGNITION
10
TRANSFORMER
8
2ND STAGE
9
FUEL VALVE
L2 L1
L2
(OPTIONAL)
2
L2
M7408
750-166 1-13
CB780/CB784
L1 (HOT)
L2
1
1
120 OHM RESISTOR
1
120 OHM RESISTOR
A
B
A
B
C (GND)
+13 VDC
RESET
C (GND)
+13 VDC
RESET
1
23
4
5
1
23
4
5
MOMENTARY PUSH BUTTON SWITCH
833-2727 KEYBOARD DISPLAY MODULE (MOUNTED ON CB 780/CB 784)
13 VDC POWER SUPPLY
833-2727 REMOTE KEYBOARD DISPLAY MODULE
THREE WIRE SHIELDED CABLE MAY BE REQUIRED. TWO 120 OHM TERMINATING RESISTORS ARE REQUIRED FOR CONNECTIONS OVER 100 FEET. CABLE SHIELD MUST BE TERMINATED TO EARTH GROUND AT BOTH ENDS. IF SHIELDED CABLE IS NOT USED, TWISTED PAIR WIRE MUST BE USED.
M7409
WIRING
Fig. 8—Wiring the Keyboard Display Module with Communication Interface ControlBus Module.
833-2727 KEYBOARD DISPLAY MODULE (MOUNTED ON CB 780/CB 784)
MOMENTARY PUSH BUTTON
A
1
120 OHM RESISTOR
120 OHM RESISTOR
1
A
THREE WIRE SHIELDED CABLE MAY BE REQUIRED. TWO 120
1
OHM TERMINATING RESISTORS ARE REQUIRED FOR CONNECTIONS OVER 100 FEET (30 METERS). CABLE SHIELD MUST BE TERMINATED TO EARTH GROUND AT BOTH ENDS. IF SHIELDED CABLE IS NOT USED, TWISTED PAIR WIRE MUST BE USED.
2 REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
B
C (GND)
23
1
1
23
B
C
RESET
+13 VDC
4
5
833-2734 COMMUNICATIONS INTERFACE CONTROLBUS MODULE
SWITCH
2
M7406
Fig. 9—Wiring multiple Keyboard Display Modules.
2
2 REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
Fig. 10—Wiring the Control Bus with remote Keyboard Display Module.
833-2729 DATA CONTROLBUS MODULE™ (MOUNTED ON CB 780/CB 784)
833-2729 CONTROL BOX (MOUNTED ON CB780/CB784)
1-14 750-166
MOMENTARY PUSH BUTTON
A
1
120 OHM RESISTOR
120 OHM RESISTOR
1
A
833-2727 REMOTE KEYBOARD DISPLAY MODULE
THREE WIRE SHIELDED CABLE MAY BE REQUIRED. TWO 120
1
OHM TERMINATING RESISTORS ARE REQUIRED FOR CONNECTIONS OVER 100 FEET. CABLE SHIELD MUST BE TERMINATED TO EARTH GROUND AT BOTH ENDS. IF SHIELDED CABLE IS NOT USED, TWISTED PAIR WIRE MUST BE USED.
WHEN CONNECTING THE KEYBOARD DISPLAY MODULE DATA
2
CONTROL BUS, OR REMOTE RESET MODULE
CONTROLBUS MODULE™, OR REMOTE RESET MODULE EXTERNAL FROM THE CONTROL CABINET, APPROPRIATE MEASURES MUST BE TAKEN TO MEET EN60730 SAFETY LOW VOLTAGE REQURIEMENTS (SEE APPROVALS).
3 REMOTE RESET MUST BE MOUNTED WITHIN SIGHT OF THE BOILER CONTROL PANEL.
B
C (GND)
23
2
1
1
23
B
C (GND)
+13 VDC
4
4
+13 VDC
RESET
5
5
RESET
SWITCH
M7407
3
MOUNTING CB780/CB784
NOTE: For installation dimensions, see Fig. 1.
RELAY MODULE MOUNTING
1. Mount the CB780/CB784 vertically, see Fig. 11, or mount horizontally with the knife blade terminals pointing downward. The CB780/CB784 must be in an electrical enclosure.
2. Select the location in the electrical enclosure. Be sure to allow adequate clearance for servicing, installation and removal of the CB780/CB784, Keyboard Display Module, flame amplifier, flame amplifier signal voltage probes, elec­trical signal voltage probes, and electrical connections.
a. Allow an additional two inches below the CB780/CB784
for the flame amplifier mounting.
d. Allow an optional three-inch minimum to both sides
of the CB780/CB784 for electrical signal voltage probes.
3. Make sure no subbase wiring is projecting beyond the terminal blocks. Tuck wiring in against the back of the sub­base so it does not interfere with the knife blade terminals or bifurcated contacts.
CB780/CB784
ASSEMBLY
Assembly
Fig. 11—Electrical panel installation.
IMPORTANT: The CB780/CB784 must be installed with a
plug-in motion rather than a hinge action.
4. Mount the CB780/CB784 by aligning the four L shaped corner guides and knife blade terminals with the bifurcated contacts on the wiring subbase and tightening the two screws securely without deforming the plastic.
INSTALLING THE PURGE CARD
1. Remove the Keyboard Display Module or Control Bus, see Fig. 13 or 14.
2. Remove the current Purge Card from the CB780/CB784 by pulling the plastic support cover upward .
3. Make sure that the Purge Card selected has the desired timing.
4. Insert Purge Card into the opening of the CB780/CB784 compartment, see Fig. 12.
5. Reinstall the Keyboard Display Module or Control Bus onto the CB780/CB784 and restore power to the device.
6. Run the burner system through at least one complete cycle to verify the system is operating as desired.
IMPORTANT: The CB780 will not function properly with-
out one of the following mounted correctly: Keyboard Display Module, or Control Bus .
MOUNTING KEYBOARD DISPLAY MODULE (VFD)
1. Align the two interlocking ears of the Keyboard Dis­play Module with the two mating slots on the CB780/CB784; see Fig. 13.
2. Insert the two interlocking ears into the two mating slots and with a hinge action push on the lower corners of the Keyboard Display Module to secure it to the CB780/CB784.
3. Verify the Keyboard Display Module is firmly in place.
MOUNTING CONTROL BUS
1. Align the two interlocking ears with the two mating slots on the CB780/CB784; see Fig. 14.
2. Insert the two interlocking ears into the two mating slots and push on the lower corners of the Control Bus to secure it to the CB780/CB784.
3. Be sure the Control Bus is firmly in place.
750-166 1-15
Loading...
+ 42 hidden pages