Clearfield FieldShield, FieldShield Flexdrop Installation Manual

FieldShield & FieldShield Flexdrop
Installation Manual
______________________________________________________
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
When to push, pull, or both? 3 Recommended Installation Distances 3 Fiber Installation 4 Attaching Pull String to Fiber 5 Pre-Terminated Pushable LC Drops 6 Pre-Terminated Pushable LC Drops 6 Terminating Fiber 7 Connector Cleaning 7 SC Pushable Connector 9 Simplex LC Pushable Connector 10 Duplex LC Pushable Connector 11 Fiber Polarity Switch 12 Preparing FieldShield Pushable Fiber for Splice-On Connectors 13 CraftSmart Splice-On Connectors 19 Drop Cable Options 22 Standard Warranty 23 Proprietary Notice 24 Technical Support 24
_________________________________________________________
2
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
When to push, pull, or both?
Every situation is different, but as a general rule, it is typically easier to install
ber using a push and pull combination, rather than pushing or pulling by itself. By using a combination push/pull method, installers have access to the ber from both ends of the microduct when troubleshooting.
Recommended Installation Distances
Installation Manual
NOTE: If a ber gets stuck or snags during installation, the ber can be pulled back a couple inches from the end being fed into the duct and re­pulled past the bind point. Sometimes the connector needs to be rocked past a snag point by carefully alternating pushing and pulling from both
ends.
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
3
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
Fiber Installation
Whether pre-connectorized or not, here are a couple quick tips to use when installing pushable ber into the microduct. These techniques have been used to install single ber, connectorized ber and multi-ber assemblies at distances in excess of 500 feet.
_________________________________________________________
Never Remove Protective Cover from Pushable Connectors Prior to Installation
If the protective plastic cover is removed from a pre-connectorized pushable assembly before you place the ber in the microduct, the connector acts as a sort of “cheese grater” down the length of the microduct. It will shave off the inner liner and then those particles bind around the ber. In some cases, this causes the ber to become stuck and usually results in a broken ber.
Pulling is Faster than Pushing
Pull with Constant Pressure and Speed to Overcome Initial Friction
Maintain the Same Feed and Pull Rate on Both Ends
4
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Attaching Pull String to Fiber
FieldShield Microduct comes preinstalled with a nylon pull string that can handle pull strengths up to 50 lbs. When attaching the pull string, never tie the pull string directly to the ber or connector. This will cause damage to or pull the connector off. Also, never use tape over the string because the outside jacket of the ber is slippery enough that tape usually comes off and clogs the microduct. Depending upon connector type there are two different methods to attach the pull string to the pushable ber assembly.
Pre-Terminated Pushable SC and Blunt Drops
The rst method uses a nylon pulling eye that slides over the end of the assembly and works with blunt drops as well as pre-terminated SC pushable assemblies.
Step 1: Slide the open end of the pulling eye over the plastic sheath of the SC Pushable Connector or the blunt end of the assembly (Figure 1). Make sure to push the assembly all the way to the end of the pulling eye and pull the pulling eye taut (Figure 2).
Installation Manual
Step 2: After the nylon pulling eye has been slid over the end of the cable, simply tie the pull string to the loop of the pulling eye
(Figure 3).
Figure 3
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Manual 018956 REV A- July 2017
Figure 2Figure 1
Note: When using SC Pushable Connectors, make sure to cut back the excess string left behind after tying the pull string to the pulling eye. Failure to remove the excess string can cause the connector to bind between the string and the microduct during installation.
5
FieldShield & FieldShield Flexdrop
Installation Manual
Pre-Terminated Pushable LC Drops
The second method uses a crimped pulling eye that was attached to the assembly during factory termination.
Installation Procedure
Step 1: Access the pulling eye by sliding the
connector’s protective sheath approximately 1” towards the opposite end of the assembly, stop­ping at the metal crimp ring.
_________________________________________________________
Figure 1
Step 2: Tie the pull string to the loop of the
pulling eye and cut back the excess string left behind.
Note: Do not to cut the string directly at the knot. Leave about 2 to 3 mms of excess string next to the knot.
Step 3: Make sure that the springs are staggered one on top of each other then, push the protective sheath over the connector and knot from the pull string.
Note: Failure to stagger the springs increases the width of the pushable connector, making it too wide to pass tight corners.
Figure 2
6
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 3
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Connector Cleaning Procedure
Whether factory terminated or eld spliced, clean connectors are essential for proper system operation. Even the smallest dust particle can cause transmission problems, so for optimal network performance, inspect and if necessary, clean all connectors and adapters prior to mating.
I.T.C…Inspect Then Connect!
ALWAYS inspect the connector rst thing with a clean ber scope inspect the pair. Three types of contamination require different cleaning techniques. The use of Chemtronics end face and bulkhead cleaning products and techniques ensures a clean end face, no matter the type of contamination.
These are Cleareld recommended products/application. Use the product you feel will complete your cleaning procedures. Create a “best practice” for your company and follow those procedures.
Installation Manual
Figure 1
**NOTE: It is NOT recommended to use IPA to clean the end-face.
Cleaning the end-face…but not just the end-face
• Place one wiping paper on QbE-2 FiberSafe™ Cleaning Platen. Figure 1
• Apply small amount of precision cleaner (about 1” in diameter) with Elec­tro-Wash MX pen on to one end of the wipe. Figure 2
• Hold end face 90 degree. Adjust for APC connection by slightly tilting the container or end face. Angle is correct when no drag is left on the end face.
Figure 3
• Draw end face from wet to dry part of the wipe 3 times. Use just enough pressure to ensure complete contact between end face and the wipe.
DO NOT retrace previous step.
Figure 2
Figure 3
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
7
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
CLEAN THE FERRULE…Lightly moisten the ber optic swab (2.5mm/38542F or 1.25mm/38040) by spotting a small amount (about 1”) of Electro-Wash PX or Electro-Wash MX pen onto the QBE-2. Hold the swab, 1 side down to the wetted area and hold for a count of 1-2-3-4-5.
Figure 4
• Insert swab into side of ferrule, wet side to the ceramic ferrule and circle around 2-3 times and remove. Turn swab to dry side and repeat.
Figure 5
_________________________________________________________
Cleaning the mate through a bulkhead adapter AND the adapter itself!
• Lightly moisten the ber optic swab(2.5mm/38542F or 1.25mm/38040) by spotting a small amount (about 1”) of Electro-Wash PX or Elec­tro-Wash MX pen onto the QBE-2. Hold the tip of the swab onto the wetted area and hold for a count of 1-2-3-4-5.
• Insert the swab into the adapter to the connector, press lightly against the connector, twist 2-3 times, remove and discard.
• Dry with a second dry swab.
• Inspect (re-clean if necessary) and test for signal strength.
• Use additional swabs to clean inside the actual adapter. Moisten swab, like above, insert through hole and remove while twisting. Figure 6
Figure 4
Figure 5
8
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 6
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Cleaning an MPO/MTP Connector
Female Connector
• Place one wiping paper on QbE-2 FiberSafe™ Cleaning Platen and apply small amount of precision cleaner (about 1” in diameter) with Elec­tro-Wash MX pen on to one end of the wipe. Figure 1
• Hold end face 90 degree. Adjust for APC connection by slightly tilting the container or end face. Angle is correct when no drag is left on the end face. Figure 2
Installation Manual
Figure 1
Male Connector
• Lightly moisten the ber optic swab (CC505F) like above, moistening 1 side.
• Place swab, wet side down at one end of connector end-face and draw across in a diagonal sweep (ie: from ber 1 up and across to ber 12). Turn swab over to dry and draw back from ber 12 to ber 1. Figure 3
BEFORE cleaning any connector…be sure you know what type of con­taminate you are cleaning…dry? Fluidic?...All the available products are good, it’s the process that you need to be aware of. Using a dry cleaning method to clean “dirt” can lead to scratching of the end-face. Learn the process of cleaning properly!
Figure 2
Figure 3
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
9
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
SC Pushable Connector
Housing Assembly
Step 1: Remove the white protective dust cap from the unassembled connector (Figure 1).
Note: The SC Pushable Connector has a keyed locking feature that holds the inner housing to the connector and aligns the ferrule when the two are correctly mated.
To properly mate the connector, the key on the inner housing must bypass the ferrule alignment notch to properly lock into place.
Step 2: Align the black mark on the inner housing with the black line on the connector, then rotate the inner housing 45 degrees to offset the lock (Figure 2) and slide the inner housing half way over the connector.
_________________________________________________________
Figure 1
Step 3: Rotate counter-clockwise 45 degrees to realign the
inner housing and connector and push the inner housing onto the connector until it snaps into place (Figure 3).
Step 4: Align the key on the outer housing with the black line on the connector, then slide the outer housing over the entire assembly until it snaps into place (Figure 4).
Step 5: Re-install the white protective dust cap (Figure 5).
Figure 2
Figure 3
Figure 4
10
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 5
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Simplex LC Pushable Connector
Connector Housing Assembly
Step 1: Remove protective dust cap and cut the pull string loop close to crimp (Figure 1).
Step 2:
A. Slide the inner clip over the ber (Figure 2).
B. Align slot with housing latch and press together.
Note: APC connectors will have dots on the ferrule to align with latch on housing.
Installation Manual
Figure 1
Figure 2
Step 3: Insert the cable crimp into the back of the lower body (Figure 3). Snap the connector into the front half of the lower body (Figure 4).
Figure 3 Figure 4
Step 4: Snap body cover onto lower half (Figure 5). Install the protective dust cap (Figure 6).
Figure 5
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 6
11
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
Duplex LC Pushable Connector
Connector Housing Assembly
Step 1: Remove protective dust cap and cut the pull string loop close to crimp (Figure 1).
Step 2:
A. Slide inner clips on the same colored ber and over the springs (Figure 2).
B. Align slot with housing latch and press together.
_________________________________________________________
Figure 1
Note: APC connectors will have dots on the ferrule to align with latch on housing.
Step 3: Insert the cable crimp into the back of the lower body (Figure 3). Snap the connector into the front half of the lower body (Figure 4).
Figure 3 Figure 4
Step 4: Snap body cover onto lower half (Figure 5). Install the protective dust cap (Figure 6).
Figure 2
Figure 5
12
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 6
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Fiber Polarity Switch
Step 1: Remove the top half of the body by prying the bottom half sides apart (Figure 1).
Step 2: Remove the lower half of the body (Figure 2).
Installation Manual
Figure 1
Figure 2
Step 3: Choose either a straight through or reversed polarity conguration and assemble the colored bers
as shown.
Note: All pre-assembled Cleareld Dual LC connectors are factory congured as straight through.
Straight Through Reversed
Step 4: Snap body cover onto lower half (Figure 3).
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 3
13
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
Preparing FieldShield Pushable Fiber for Splice-On Connectors
1-Fiber 250um FieldShield Cable
Recommended Tools / Parts List
_________________________________________________________
1/8 Inch Adhesive Lined Heatshrink
900um Furcation Tubing
3-4mm Rotary Tube Cutter
Snips/Cutting Utensil
Installation Procedure
Step 1: Determine the required 900um breakout
length needed for your application and mark the FieldShield cable using an appropriate writing
utensil (Figure 1).
Step 2: Ring cut and remove the jacket using
a rotary tube cutter available from Cleareld
(Figure 2).
Isopropyl Alcohol /Cleaning Wipes
Heat Source (Hot Air Gun/Blow Torch)
Super Glue
Ruler
Figure 1
14
Note: The jacket is removed using a score and snap process. Make sure that the rotary tube cutter blade has been adjusted so that it scores the outside of the jacket, but does not entirely cut through. Do not cut or nick the ber.
Figure 2
Step 3: Pulling from the cable, pull the 3mm jacket off in a straight line (Figure 3).
Figure 3
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Step 4: Using a cleaning wipe and some Isopro­pyl alcohol, wipe clean the exposed 250um ber
(Figure 4).
Step 5: Cut a piece of 900um furcation tubing
6” longer than the desired breakout. Mark the 900um tubing 6” from the end of the cut (Figure
5). This 6 inch mark will tell you how far to insert the 900um tubing into the 3mm cable.
Installation Manual
Figure 4
Step 6: Cut a 1” piece of 1/8” adhesive lined
heatshrink (available from Cleareld), fold the Kevlar strength members back over the outside of the cable. Slide the heatshrink over the ber and on to the outside of the 3mm cable holding back the Kevlar (Figure 6).
Step 7: Place heatshrink ush to the end of the cable and then apply even heat until the tubing is fully shrunk (Figure 7).
Figure 5
Figure 6
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 7
15
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
Step 8: Slide the 900um tubing over the 250um ber inserting the 900um tube into the FieldShield 3mm cable (Figure 8).
Step 9: Stop inserting the 900um tubing keeping the 6 inch mark approximately 1 inch from going into the 3mm cable as seen in (Figure 9).
_________________________________________________________
Figure 8
Step 10: Now apply a generous amount of super
glue to the 900um furcation tubing between the FieldShield cable and the mark and then while rotating, slide the furcation tubing up to the 6 inch mark on the 900um tubing (Figure 10).
Step 11: Allow the glue to dry, and then trim the excess Kevlar strength members behind the heatshrink (Figure 11).
Note: The CraftSmart Splice-On Connector can now be installed per standard instructions to the 900um furcated ber.
Figure 9
Figure 10
16
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 11
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
2, 6, and 12-Fiber 250um FieldShield Cable
These instructions detail the installation of 2, 6, and 12 ber 900um furcation upjacketing kits. Each kit breaks out 250um bers from a multiber loose tube into individual 900um buffer tubes. The ber can then be terminated using the 900um CraftSmart Splice-On Connector installation instructions.
Recommended Tools / Parts List
Installation Manual
Cover
Base
24” 900um 2, 6, or 12 Fiber Terminal
Assembly
Heatshrink
Heat Source (Hot Air Gun/Blow Torch)
Installation Procedure
Step 1: Locate and setup your work surface as close to the patch panel location as possible. This will minimize the strip
length.
Step 2: Route the cable through the patch panel to the work surface. Step 3: Measure backwards, from the end of the cable to the point at which it will attach to the patch panel, and add 39
inches (1 meter) to the length. Mark this length with a piece of tape. This is the strip point for the cable being terminated.
Step 4: Strip the cable back to the tape mark. Step 5: Secure the cable to the patch panel. Step 6: Clean any dirt and/or gel surrounding the loose tube. Step 7: Select the rst buffer tube and measure back 36 inches (90cm) and place a mark. Step 8: Score the buffer tube and strip the loose buffer tube at the mark. Step 9: Thread the heatshrink until it is ush with the end of the buffer tube and shrink in place.
Note: Be careful not to melt or distort the tube due to excessive heat.
Electrical or Masking Tape
Lint Free Wipes
Indelible Marker
Buffer Tube Stripper
Gel Cleaner
Needle Nose Pliers
Step 10: Tape the buffer tube to the work surface with 2 inches (50mm) overhanging the end of the work surface (Figure 1).
Step 11: Wipe all the gel from the exposed bers using a gel cleaner.
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 1
17
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
Step 12: Place the buffer tube in the bottom of the furcation kit. Using pliers, press the tabs of the crimping xture to hold the loose tube.
Note: Crimp only enough to start to deform the tube. Twist and pull the terminal body to check if the crimp is secure. The tube should not slip or move in the crimp xture.
Step 13: Tape the terminal assembly in the vertical position 3 inches (75mm) to the side of the loose buffer tube (Figure 2).
_________________________________________________________
Figure 2
Step 14: Untangle the bers and make sure they are completely free of gel lling compound. Step 15: Talc the bers to facilitate the threading operation. Cup the talc in the palm of your hand and apply along the whole
length of the bers. Step 16: Select the blue ber and thread 6 inches (150mm) into the blue tube of the terminal assembly (Figure 3).
Repeat this procedure for the remaining bers, making sure the color coded bers match the color coded 900um tubing.
Step 17: When all bers have been threaded, push the bers as a group until the bers start to protrude from the ends of the buffer tubes.
Step 18: Gently pull the bers from the ends of the buffer tubing.
Figure 3
Note: Do not pull the bers taught. Leave sufcient slack so the bers are not stressed.
Step 19: Untape the buffer tube assembly and slide the assembly toward
the loose tube while pulling the bers from the end of the 900um tubing. If the bers twist, rotate the terminal assembly in the opposite direction of the twist (Figure 4)
18
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 4
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Step 20: Place the terminal assembly into the bottom of the terminal body. Align the top cover and snap into place (Figure 5).
Step 21: Remove the tape from the loose tube and repeat this procedure for the remaining loose tubes.
Note: The CraftSmart Splice-On Connector can now be installed per standard instructions to the 900um furcated
ber.
Installation Manual
Figure 5
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
19
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
CraftSmart Splice-On Connectors
Safety Precautions
Please read and follow all fusion splicer manufacturer recommended procedures concerning splicing operation and precautions.
Safety glasses should be worn when handling cleaved bers. Cleaved bers are sharp and can pierce eyes, skin or clothing.
Never look into the end of a microscope or optical cable connected to an operating optical output device. Laser radiation is invisible, and direct exposure can severely injure the human eye.
Note: Before starting this process, completely read through the entire installation document. If the splice machine you are using has a tensile test option, be sure to shut this option off on your machine.
Recommended Tools/Parts List
1. Fusion Splicer
2. Cleaver
3. Jacket Ringer and Stripper
4. Kevlar Shears
5. Fiber Stripper
6. Splice Holders for Splicer
7. Marking Pen
_________________________________________________________
Installation Procedure
Step 1: Remove the connector and components from
the individually packaged tube.
Step 2: Separate all the parts and identify the parts you will be using for your application.
Dust Cap with Handle
Outer Housing
Inner Housing Connector Assembly
Fusion Splice Protection Sleeve
Strain Relief Boot
Step 3: Remove the dust cap from the connector sub-assembly and put aside for later use (Figure 1).
Figure 1
Figure 2
20
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Figure 3
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Step 4: Remove Install the dust cap with the handle on to the ferrule (Figure 2).
Step 5: Carefully remove the ber protection cover from the back side of the connector (Figure 3). Do not to touch the stripped end of the ber or let anything bump against it.
Note: The Fiber is already stripped, cleaned and cleaved to the exact dimension needed.
Installation Manual
Figure 2
Figure 3
Step 6: Insert the connector sub-assembly in to
the fusion splice holder, making sure the ber sits into the center of the ber groove (Figure 4).
Figure 4
Step 7: Following the splice machines
instructions carefully insert the splice holder with the connector inside of the holder into one side of the machine (Figure 5). Using extreme caution, do not touch or bump the stripped ber against anything.
Figure 5
Step 8: Insert the Strain Relief Boots narrow end rst on to the 900um ber that you will be splicing to.
Step 9: Insert the Fusion Splice Protection Sleeve on to the 900um ber after the Strain Relief Boot.
Step 10: Following the Fusion Splicer’s manufacturers recommendations strip the ber to length.
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
21
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
Installation Manual
Step 11: Place the ber in the splice holder.
Step 12: Clean bare ber with clean wipe and alcohol.
Step 13: Cleave the bare ber to 10mm. If the cleave length is too long it will not be protected in the
Splice Protection Sleeve.
Step 14: Following the splice machines instructions carefully insert the splice holder with the 900um ber into the opposite side of the machine. Using extreme caution, do not touch or bump the stripped ber against anything.
Step 15: Following the Fusion Splicer’s manufacturers procedure splice the connector to the ber.
Step 16: Once the splicer has completed the process and you are satised with the results, carefully
slide the protection sleeve up to the ber holder and remove the ber and connector from the splicer.
_________________________________________________________
Step 17: Slide the protection sleeve toward the connector centering it over the stripped bare ber
splice (Figure 6).
Step 18: Insert the ber and protection sleeve
into the protection sleeve oven with the connector all the way to one side of the oven keeping it out of the oven as the best as you can (Figure 7). If you cannot close the ovens cover then you can lay the splice protection holder over the protec­tion sleeve to help keep the heat inside.
Note: If the splice protection sleeve is not shrunk down all the way then you can run the heat cycle again. You may want to increase the ovens time duration if this continues to happen.
Figure 6
Figure 7
Step 19: Slide the Strain Relief Boot up to the back of the connector and snap in place.
Step 20: Replace the dust cap with handle back to the original dust cap.
22
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Manual 018956 REV A- July 2017
__________________________________________________________
Drop Cable Options
FieldShield & FieldShield Flexdrop
Installation Manual
Product
Name
FieldShield
FLATdrop
FieldShield
D-ROP
FieldShield
FLEXdrop
Cable
Jacket
Outdoor Yes -40° to 176°F No Black Yes
Outdoor Yes -40° to 176°F Yes
Indoor
(Plenum)/
Outdoor
UV Temperature
Yes -40° to 176°F Yes
FieldShield
Connector
Jacket
Color
Black/
Orange
Black/
White
Can be
stapled
Yes
Yes
Best
Application
For use when fast installation
and low up-front cost is most
desired feature.
For use when a single pass
and restorable solution at a
competitive price is ideal.
For use when a premium
product that has maximum
workability, exibility and
restorability is desired.
FieldShield
(Classic)
Outdoor
in Duct
FieldShield
StrongFiber
Indoor/
Outdoor
in Duct
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Yes in
Duct
Yes in
Duct
-40° to 176°F Yes Black Yes
-40° to 176°F Yes Black
Manual 018956 REV A- July 2017
Yes in
Duct
For use when the distance
from the access point to the
SFU/MDU is longer than
normal and a more rigid solu-
tion is required to maintain
restorability for drops longer
than 300 feet.
For use when a reusable
pathway is needed and
maximum slack storage is
desirable.
23
FieldShield & FieldShield Flexdrop
Installation Manual
Standard Warranty
Cleareld warrants to the original purchaser of the Product sold hereunder is free from defects in material and workmanship under normal use and service, subject to exceptions stated herein.
Product Warranty
Products manufactured by Cleareld to customer prints and/or specications are warranted for one (1) year or in accordance with the Product War­ranty Classication section of this document. In all cases, the warranty period commences on the date of shipment to the original purchaser.
Warranty Claim Procedure
If any Product purchased from Cleareld is found defective under the above warranty, the following basic procedure must be followed:
a) Customer must contact Cleareld and obtain a Return Materials Authorization. b) Following authorization, the Customer ships the product per Cleareld’s freight instructions to Cleareld’s manufacturing facility. c) Cleareld shall repair or replace the defective Product at its sole option and discretion, and return the repaired or replacement Product to Custom­er’s site, freight prepaid.
_________________________________________________________
Note: If the Product is not found to be defective at Cleareld, the product will be returned to the Customer and the customer billed for freight in both directions.
Limitations of Warranty
CORRECTION OF DEFECTS BY REPAIR OR REPLACEMENT, AT THE OPTION OF CLEARFIELD INC, SHALL CONSTITUTE THE EXCLUSIVE SOLE REMEDY FOR A BREACH OF THIS LIMITED WARRANTY. CLEARFIELD SHALL NOT BE LIABLE UNDER ANY CIRCUMSTANCES FOR ANY SPECIAL, CONSEQUENTIAL, INCIDENTAL, PUNITIVE, OR EXEMPLARY DAMAGES ARISING OUT OF OR IN ANY WAY CONNECTED WITH THE PRODUCT OR WITH AGREEMENT TO SELL PRODUCT TO BUYER, INCLUDING, BUT NOT LIMITED TO DAMAGES FOR LOST PROFITS, LOSS OF USE, OR FOR ANY DAMAGES OR SUMS PAID BY BUYER TO THIRD PARTIES. THE FOREGOING LIMITATION OF LIA­BILITY SHALL APPLY WHETHER THE CLAIM IS BASED UPON PRINCIPLES OF CONTRACT, WARRANTY, NEGLIGENCE OR OTHER TORT, BREACH OF STATUTORY DUTY, PRINCIPLES OF INDEMNITY OR CONTRIBUTION, THE FAILURE OF ANY LIMITED OR EXCLUSIVE REMEDY TO ACHIEVE ITS ESSENTIAL PURPOSE, OR OTHERWISE.
CLEARFIELD WILL NOT BE RESPONSIBLE FOR ANY LABOR OR MATERIALS COSTS ASSOCIATED WITH INSTALLATION OR INCORPO­RATION OF CLEARFIELD PRODUCTS AT CUSTOMER SITES, INCLUDING ANY COSTS OF ALTERATION, REPLACEMENT OF DEFECTIVE PRODUCT, OR ANY FIELD REPAIRS.
Other Limitations
Cleareld assumes no warranty liability regarding defects caused by:
1) Customer’s modication of Product, excepting installation activities described in Cleareld documentation.
2) Customer re-packaging of Product for shipment to third parties or destinations other than those originally shipped to by Cleareld, or any defects
suffered during shipping where the Product has been re-packaged.
3) Customer’s installation or maintenance, excepting activities described in and performed in accordance with Cleareld documentation.
4) Customer’s improper or negligent use or application of Product.
5) Other causes external to the Product, including but not limited to accidents, catastrophe, acts of God, government action, war, riot, strikes, civil
commotion, sovereign conduct, or the acts or conduct of any person or persons not party to or associated with Cleareld.
6) Environmental factors and weathering resulting in aging and damage not necessary or applicable to the function of the product.
24
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
Manual 018956 REV A- July 2017
FieldShield & FieldShield Flexdrop
__________________________________________________________
Proprietary Notice
About FieldShield Product Line Application
Information contained in this document is copyrighted by Cleareld, Inc. and may not be duplicated in full or part by any person without prior written approval of Cleareld, Inc.
Its purpose is to provide the user with adequately detailed documentation to efciently install the equipment supplied. Every effort has been made to keep the information contained in this document current and accurate as of the date of publication or revision.
However, no guarantee is given or implied that the document is error free or that it is accurate with regard to any specication.
Technical Support
Cleareld, Inc. can be contacted for any issues that arise with the supplied product.
If you need to return the supplied product, you must contact the Cleareld, Inc. Customer Service Department to request a Returned Materials Authorization (RMA) number.
Installation Manual
Cleareld, Inc. 7050 Winnetka Ave N
Minneapolis, MN 55428
Toll Free: 800.422.2537 Phone: 763.476.6866 Fax: 763.475.8457
Customer Support: sales@clfd.net Technical Support: techsupport@clfd.net
Direct: 763.476.6866 • National: 800.422.2537 • www.SeeCleareld.com • techsupport@clfd.net
25
Manual 018956 REV A- July 2017
Loading...