Pressure Reducing Valve with Low Flow By-Pass
The Cla-val Model 90-48 automatically reduces a higher inlet pressure to a steady lower downstream pressure regardless of changing flow rate. The pressure reducing valve is hydraulically operated and controlled by a CRD pilot control, which senses pressure at the main valve outlet. An increase in outlet pressure forces the CRD pilot control to close and a decrease in outlet pressure opens the control. This causes the main valve cover pressure to vary, modulating the main valve and thereby maintaining constant outlet pressure. sensitive to slight pressure changes and immediately controls the main valve to maintain the desired downstream pressure. Pressure setting adjustment is made with a single adjusting screw
INSTALLATION
1. Allow sufficient room around the valve assembly to make adjustments and for servicing.
2. lt is recommended that gate or line block valves be installed on both ends of the 90-48/690-48 valve assembly to facilitate isolating the valve for maintenance. Minimum one pipe diameter apart.
NOTE: BEFORE THE VALVE IS INSTALLED, PIPE LINES SHOULD BE FLUSHED OF ALL CHIPS, SCALE, AND FOREIGN MATTER.
3. Place the valve assembly in the line with flow through the valve in the direction indicated on the inlet plate or by flow arrows. Check all fittings and hardware for proper makeup and that no apparent damage is evident. Be sure main valve cover nuts/bolts are tight. Pressure in some applications can be very high so be thorough in checking and inspecting for proper installation and makeup.
4.Cla-Val Valves operate with maximum efficiency when mounted in hor­izontal piping with the cover UP: however, other positions are acceptable. Due to size and weight of cover and internal components of six inch and larger valves, installation with the cover up is advisable. This makes period­ic inspection of internal parts readily accessible.
5.
Caution must be taken in the installation of this valve to insure that galvanic and/or electrolytic action does not take place. The proper use of dielectric fittings and gaskets are required in all systems using dis­similar metals.
OPERATION AND START-UP
1. Prior to pressurizing the valve assembly make sure the necessary gauges to measure pressure in the system are installed as required by the system engineer. A Cla-Val X101 Valve Position Indicator may be installed in the center cover port to provide a visual indication of the valve movement during startup. CAUTION: During start-up and test procedures a large volume of water may be discharged downstream. Check that the downstream venting is adequate to prevent damage to personnel and equipment. All adjustments
in pressure should be made slowly while under flowing conditions.
If the main valve closes too fast it may cause surging in upstream piping.
2.
If isolation valves (B) are installed in pilot system open these
valves (see schematic).
3. Optional Cla-Val CV Flow Controls (C or S) provide adjustable regula­tion of flow in and out of the main valve chamber to minimize pulsations that sometime occur at very low flow rates. If CV Controls are installed, loosen jam nut and turn adjustment screw counterclockwise from closed position 3.5 turns for an initial setting.
4. Open the upstream gate or block valve just slightly to allow the main valve assembly and pilot system to fill with liquid. Downstream gate or block valve must be closed.
5. Carefully loosen tube fittings at highest points and bleed air from pilot control system. Carefully loosen the plug at top of main valve cover to bleed air from cover. If an indicator is installed, carefully loosen the air bleed valve at top of indicator. Tighten tube fittings.
6. Open the upstream gate or block valve fully.
7. Slowly open the downstream gate or block valve. Flow should occur and pressure should remain constant.
8. Adjust the Pilot Controls to desired pressure. To change pressure setting, turn the adjusting screw clockwise to increase pressure, counterclock-
Pressure Reducing Valve with Low Flow By-Pass
The control system is very
MODEL
wise to decrease pressure. There must be liquid flowing through the valve during pressure adjustments. When the desired setting has been made, tighten jam nut and replace CRD cover. Low flow by-pass control (4) must be set higher (minimum 5 psi) than main CRD (3).
9. To check the operation of the valve, open and close the downstream gate valve. The downstream pressure should remain constant.
10. If opening and closing speed controls (C or S) are installed in the valve pilot system, fine tune the opening and closing speed of the main valve while performing step 9. Turn the CV adjustment screw clockwise on the opening speed control to make the main valve open slower. Turn the adjustment screw clockwise on the closing speed control to make the main valve close slower. When adjustments have been completed tighten jam nuts.
MAINTENANCE
1. Cla-Val Valves and Controls require no lubrication or packing and a minimum of maintenance. However, a periodic inspection schedule should be established. Minimum of once per year.
2. Repair and maintenance procedures of the Cla-Val Hytrol Main Valve and pilot control components are included in a more detailed IOM manual. It can be downloaded from our web site (www.cla-val.com) or obtained by contacting a Cla-Val Regional Sales Office.
3. When ordering parts always refer to the catalog number and stock
number on the valve nameplate.
SYMPTOM PROBABLE CAUSE REMEDY
Main valve No pressure at valve inlet Check inlet pressure fails to open
Main valve diaphragm assembly Disassemble, clean and polish inoperative stem, replace detective parts
Pilot Valve (CRD) not opening:
1. No spring compression 1. Tighten adjusting screw
2. Damaged spring 2. Disassemble and replace
4. Yoke dragging on inlet nozzle 4. Assemble properly
Flow Control (CV) disc inoperative. Disassemble, clean and polish corrosion or excessive scale stem. Replace worn parts buildup on stem
Main valve Foreign matter between disc and Disassemble main valve, remove fails to close seat or worn disc. Scale on stem matter, clean parts and replace
or diaphragm ruptured defective parts Flow Clean Strainer plugged Remove and clean or replace CK2 (isolation valves) closed Open isolation valves
Pilot Valve (CRD) remains open:
1.Spring compressed solid 1. Back off adjusting screw
2.Mechanical obstruction 2. Disassemble and remove
3.Worn disc 3. Disassemble remove and
4.Yoke dragging on inlet nozzle 4. Assemble properly diaphragm nut
5.Diaphragm damaged or loose 5. Disassemble. replace diaphragm nut. Leakage from diaphragm and/or tighten nut vent hole in cover
Fails to Air in main valve cover and/or Loosen top cover plug and regulate tubing fittings and bleed air
Pilot Valve (CRD) yoke dragging Assemble properly on inlet nozzle Pilot Valve (CRD) spring not Check outlet pressure in correct range to control requirements and compare
90-48/690-48
obstruction
replace disc retainer assembly
existing spring with Spring Chart
Page 2
inlet
Cover vent
(3/8" NPT)
Cap
Adjusting Screw
Jam Nut
Cover
Spring
Hex Nut
Belleville Washer
Diaphragm Washer
Diaphragm*
Yoke
Body and Seat Assy
Disc Retainer Assy
Gasket*
Plug, Body
*Machine Screw (Fil.Hd) 8 Req'd
Spring Guide
Pressure Setting Adjusting Screw (Turn Clockwise to Increase Setting)
90-48/690-48 SCHEMATIC CRD
Distributed By: M&M Control Service, Inc.
www.mmcontrol.com/claval-index.php
800-876-0036 847-356-0566
4
D4
3.
X140-1
Security Cap
Option
2
5
Y
B
BASIC COMPONENTS
1 100-01 Hytrol (Main Valve) 2 X47A Restriction Fitting 3 CRD Pressure Reducing Control 4 CRD-40 Pressure Reducing Control 5 CK2 (Isolation Valve)
D1
S
1
A
MAIN VALVE
COVER
Cover Bolt
6" and Smaller
1.
SPRING
PIPE PLUG
3
C
OUTLETINLET
HEX NUT
8" and Larger
D2
D3
B
OPTIONAL FEATURES
A X46A Flow Clean Strainer B CK2 (Isolation Valve) C Closing Speed Control D Check Valves with Isolation Valve S Opening Speed Control Y X43 “Y” Strainer
PIPE PLUG
COVER BEARING
STEM NUT
DIAPHRAGM WASHER
B
5
CRD-40
4.
CRD adjust range (psi)
2 - 30
15 - 75
30 - 300
Spring Color
Stainless Steel
Red
Green
* approximate. Use gauge at valve outlet to set
Low Flow ByPass (set higher)
CRD-40 Adjustment Range
15 to 150 psi
Use gauge at valve outlet to set
psi change per turn*
3 9
27
*
DIAPHRAGM
DISC RETAINER
*
SPACER WASHERS
CLA-VAL
BODY
(Globe
*
DISC
DISC GUIDE
SEAT
or
Angle)
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
Copyright Cla-Val 2008 Printed in USA Specifications subject to change without notice.
STEM
Seat Screw
8" and Larger
SEAT O-RING
PIPE PLUG
*
Repair Parts
KO Anti-Cavitation
KO DISC GUIDE
KO SEAT
STUD
8" and Larger
Trim Option
STEM
Seat Screw
8" and Larger
**
X46A
A.
X47A
2.
CV
C.
CK2
5.
CDC-1
D.
KO ANTI-CAVITATION TRIM CAN BE ADDED TO ANY STANDARD HYTROL VALVE
X43
Y.
N-90-48/690-48 (R-9/08)