Cla-Val 90-21 Quick Manual

Page 1
INSTALLATION / OPERATION / MAINTENANCE
U
¤
L
The Cla-Val 90-21 Pressure Reducing Valve is a pilot-operated regulator, capable of holding downstream pressure to a predeter­mined pressure.
1. Special Note: For system protection, a pressure relief valve is to be installed downstream (system side) of the 90-21 Pressure Reducing Valve. Adequate drainage of the relief valve discharge must be provided. The relief valve should be set above the “no flow” or “dead end” shutoff pressure which will be 5 to 8 psi higher than the set pressure.
2. Allow sufficient room around the valve assembly to make adjust­ments and for disassembly.
3. It is recommended that isolation valves be installed on both ends of the 90-21 valve to facilitate isolating the valve for start-up, testing and preventative maintenance.
4. BEFORE THE VALVE IS INSTALLED, PIPE LINES SHOULD
BE FLUSHED OF ALL CHIPS, SCALE, AND FOREIGN MAT­TER.
5. Place the 90-21 valve in the line with flow through the valve in the direction indicated on the inlet nameplate mounted on inlet flange or by arrow on nameplate mounted on side of threaded ends valves. Check all fittings and hardware for proper makeup and that no apparent damage is evident.
6. Cla-Val valves operate with maximum efficiency when mounted in horizontal piping with the cover UP; however, other positions are acceptable. Due to size and weight of cover and internal com­ponents of six inch and larger valves, installation with the cover up is advisable. This makes periodic inspection of internal parts read­ily accessible.
Start-Up and Adjustment
1. Upon initial start-up and after any valve servicing, it is necessary to follow these steps.
2. Prior to pressurizing the valve make sure the necessary gauges to measure pressure are installed. Gauges should be installed upstream (inlet) and downstream (outlet) of the valve. Unused ports on main valve body can be used for this purpose.
Caution: During start-up and test procedures a large volume of water may be discharged downstream. Check to make sure that the downstream venting is adequate to prevent damage to per­sonnel and equipment.
3. Close upstream and downstream isolation valves.
4. Slowly open the upstream isolation valve enough to allow the valve and pilot control system to fill with liquid.
5. Bleed air from the main valve (1) cover and pilot system by slightly loosening fittings or plugs at all high points until a steady flow of water is observed retighten. It may be necessary to do this more than once.
6. Open fully the upstream isolation valve.
7. Slowly open the downstream isolation valve part way to estab­lish a low flow rate.
There must be liquid flowing through the valve during pressure adjustments. Optimum valve performance occurs when
pressure setting is done with flow rate as low as practical.
8. Adjust the CRD Control (3) to desired pressure. To change pres­sure setting, turn the adjusting screw in (clockwise) to increase delivery pressure. Turn the adjusting screw out (counterclockwise) to decrease delivery pressure. The pressure should change approximately 27 psi per turn. Only slight changes in adjustment should be made to avoid damage to equipment. When the desired setting has been made, tighten jam nut and replace cover.
MODEL
90-21 UL
UL Listed Pressure Reducing Valve
NOTE: The “no flow” or “dead end” shutoff pressure will be 5 to 8
psi above the set pressure.
9. Open downstream isolation valve fully.
Maintenance
1. The Cla-Val 90-21 Pressure Reducing Valve requires no lubri­cation or packing and a minimum of maintenance. However, a peri­odic inspection schedule should be established to determine how the fluid handled is affecting the efficiency of the valve. Minimum of once per year.
2. When servicing the pilot control system, use care to prevent damage. If it is necessary to remove fittings or components, be sure they are kept clean and replaced exactly as they were.
3. Repair and maintenance procedures of the Cla-Val Hytrol Main Valve and pilot control components are included in a more detailed IOM manual. It can be downloaded from our web site (www.cla­val.com) or obtained by contacting a Cla-Val Regional Sales Office.
4. When ordering parts always refer to the catalog number
and stock number on the valve nameplate.
SYMPTOM PROBABLE CAUSE REMEDY
Main valve fails to open
Main valve fails to close
Fails to Regulate
No pressure at valve inlet
Main valve diaphragm assembly inoperative
Pilot Valve (CRD) not opening:
1. No. spring compression
2. Damaged spring
3. Spring guide not in place
4. Yoke dragging on inlet nozzle
Foreign matter between disc and seat or worn disc. Scale on stem or Diaphragm ruptured Flow Clean Strainer plugged CK2 (isolation valves) closed
Pilot Valve (CRD) remain open:
1. Spring compressed solid
2. Mechanical obstruction
3. Worn disc
4. Yoke dragging on inlet nozzle diaphragm nut. Leakage from vent hole in cover
5. Diaphragm damaged or loose diaphragm nut. Leakage from vent hole in cover
Air in main valve cover and/or tubing
Pilot Valve (CRD) yoke dragging on inlet nozzle
Pilot Valve (CRD) spring not in correct range to control
Check inlet pressure
Disassemble, clean and polish stem, replace detective parts
1. Tighten adjusting screw
2. Disassemble and replace
3. Assemble properly.
4. Assemble properly
Disassemble main valve, remove matter, clean parts and replace defective parts Remove and clean or replace Open isolation valves
1. Back off adjusting screw
2. Disassemble and remove obstruction
3. Disassemble remove and replace disc retainer assembly
4. Assemble properly
5. Disassemble. replace diaphragm and/or tighten nut
Loosen top cover plug and fit­tings and bleed air
Assemble properly
Check outlet pressure require­ments
Page 2
90-21 UL SCHEMATIC
inlet
Cover vent
(3/8" NPT)
Cap
Adjusting Screw
Jam Nut
Cover
Spring
Hex Nut
Belleville Washer
Diaphragm Washer
Diaphragm*
Yoke
Body and Seat Assy
Disc Retainer Assy
Gasket*
Plug, Body
*Machine Screw (Fil.Hd) 8 Req’d
Spring Guide
Pressure Setting Adjusting Screw (Turn Clockwise to Increase Setting)
Tube Connector
(NPT)
Restriction Plug
Orifice
2
3
X58C
2.
INLET
4
BASIC COMPONENTS
1 100-01 Hytrol (Main Valve) 2 X58C Restriction Fitting 3 CRD Pressure Reducing Control 4 X46A Flow Clean Strainer
1.
HYTROL MAIN VALVE
COVER
Cover Bolt
6" and Smaller
SPRING
*
DIAPHRAGM
1
PIPE PLUG
COVER BEARING
STEM NUT
DIAPHRAGM WASHER
HEX NUT
8" and Larger
PIPE PLUG
OUTLET
CRD
3.
X140-1
Security Cap
Option
BODY
(Globe
For a more detailed IOM Manual go to www.cla-val.com or contact a Cla-Val Regional Sales Office.
CLA-VAL
DISC RETAINER
*
*
DISC
DISC GUIDE
SEAT
or
Angle)
SPACER WASHERS
STEM
Seat Screw
8" and Larger
SEAT O-RING
STUD
8" and Larger
PIPE PLUG
Minimum Flow Required When Setting Pressure
Valve Size (inch)
1 1/2 2 2 1/2 3 4 6 8 10
Min. Flow (GPM)
16 26 37 57 100 220 390 620
X58C
2.
X46A
4.
*
Repair Parts
*SUGGESTED REPAIR PARTS
P.O. Box 1325 Newport Beach, CA 92659-0325 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: claval@cla-val.com Website cla-val.com
©
Copyright Cla-Val 2005 Printed in USA Specifications subject to change without notice.
N-90-21 UL (R-5/05)
Loading...