CLA-VAL 60-73, 660-73 User Manual

Page 1
MODEL
Discharge to
Atmosphere
Discharge to
System
Isolation Valve
Pump
CLA-VAL 52-03/652-03 Surge Anticipator Valve
CLA-VAL 60-73 Booster Pump Control
Valve
60-73
Booster Pump Control Valve
Simple Hydraulic Operation
Low Head Loss
Horizontal or Vertical Mounting
Built-in Check Valve
Proven Reliable Design
The pump starts against a closed valve. When the pump is started, the solenoid control is energized and the valve begins to open slowly, gradually increasing line pressure to full pumping head. When the pump is signaled to shut-off, the solenoid control is de-energized and the valve begins to close slowly, gradually reducing flow while the pump continues to run. When the valve is closed, a limit switch assembly, which serves as an electrical interlock between the valve and the pump, releases the pump starter and the pump stops.
Schematic Diagram
Item Description
1 Powercheck Main Valve 100-30 2 CV Flow Control 3 CSM11-A2-2 Solenoid Control 4 X105LCW Switch Assembly 5 CVS-1 Shuttle Valve
Optional Features
Item Description
A X46A Flow Clean Strainer B CK2 Isolation Valve Y X43 "Y" Strainer
Should a power failure occur, a built-in lift-type check valve closes the moment flow stops, preventing reverse flow regardless of solenoid or diaphragm assembly position.
Typical Installation
Install Model 60-73 valve as shown. Flexible conduit should be used for electrical connections to the solenoid control and the limit switch. The Model 52-02 or 652-03 Surge Anticipator Valve is recommended for power failure protection.
Note:
Valve stem can be located in either vertical up or horizontal position.
Page 2
Pressure Ratings
Y
Z
G
GG
GGG
D
Inlet
DD
DDD
F
FF
X
100-30
Threaded &
Flanged
A
E
C
(MAX)
K
J
H
Inlet
Outlet
AA
AAA
B
(Diameter)
65
279
279
295
203
262
140
140
148
43
89
95
102
102
110
0.50
0.50
0.50
18
30
432
254
254
80
318
305
337
232
284
159
152
168
52
95
105
114
102
111
0.50
0.50
0.50
20
43
457
279
279
100
381
397
292
362
191
198
81
114
127
127
135
0.75
0.75
0.75
28
86
533
305
305
150
508
533
400
468
254
267
109
140
159
152
165
0.75
0.75
0.75
43
145
864
508
508
200
645
670
508
554
322
335
135
171
191
203
216
1.00
1.00
1.00
58
295
940
1067
1067
Valve Size (mm)
A Threaded
AA 150 ANSI
AAA 300 ANSI
B Diameter
C Maximum
D Threaded
DD 150 ANSI
DDD 300 ANSI
E
F 150 ANSI
FF 300 ANSI
G Threaded
GG 150 ANSI
GGG 300 ANSI
H NPT Body Tapping
J NPT Cover Center Plug
K NPT Cover Tapping
Stem Travel
Approx. Ship Weight (kgs)
Approx. X Pilot System
Approx. Y Pilot System
Approx. Z Pilot System
Valve Body & Cover
Grade Material
(Recommended Maximum Pressure - psi)
Pressure Class
Flanged Threaded
ANSI
Standards*
150
Class
300
Class
End‡
Details
ASTM A536 Ductile Iron B16.42 250 640 400
ASTM A216-WCB Cast Steel B16.5 285 720 400
UNS 87850 Bronze B16.24 225 500 400
Note: * ANSI standards are for flange dimensions only. Flanged valves are available faced but not drilled. ‡ End Details machined to ANSI B2.1 specifications.
Valves for higher pressure are available; consult factory for details
Dimensional Data
Materials
Component Standard Material Combinations
Body & Cover Ductile Iron Cast Steel Bronze
100-30 Sizes (mm) 65 - 200 mm 65 - 200 mm 65 - 200 mm
Disc Retainer & Diaphragm Washer
Trim: Disc Guide, Seat & Cover Bearing
Disc Buna-N
Diaphragm Nylon Reinforced Buna-N
Stem, Nut & Spring Stainless Steel
For material options not listed, consult factory. Cla-Val manufactures valves in more than 50 different alloys.
Cast Iron Cast Steel Bronze
Bronze is Standard
Stainless Steel is Optional
®
Rubber
®
Rubber
60-73 Series Dimensions
(Full Internal Port 100-30) (
mm)
Page 3
Auto
Off
Hand
L1
SW
1
A
3CR
3
L2
1CR
H
1CR
1CR
3CR
1
N.C.
2CR
PVS
2CR
3CR
M
COM.
SW
2
N.O.
3CR
2
2CR
00-30 Pattern:Globe (G), Angle (A), End Connections:Threaded (T), Grooved (GR), Flanged (F) Indicate Available Sizes
60-73
Valve
Selection
Main Valve
100-30
Suggested
Flow
(gpm)
Suggested
Flow
(Liters/Sec)
100-30 Series is the full internal port Powercheck.
millimeters
(mm)
Pattern
End Detail T, F T, F FFF
Maximum
aximum
M Intermittent
aximum
M
Maximum Intermittent
1
65 80 100 150 200
G, A G, A G, A G, A G, A
300 460 800 1800 3100
370 580 990 2250 3900
19 29 50 113 195
23 37 62 142 246
CSM11 Solenoid Control Power Consumption
Volts Amperes Volts Amperes
DC Holding Pull In AC 60 Hz Holding Inrush Ohms
24 .603 24 24 2.88 25.4 0.5
629120
28. 32 .500 208 208 .330 2.93 40 48 .293 240 240 .288 2.54 58
122440
115.
125 .119 480 440 .143 1.27 233
0722.45
252.
20.5755.1
1
40.1561.38
4
Volts Amperes
(AC 50 Hz) Holding Inrush Ohms
110 .48 4.6 15.7 220 .24 2.3 66 240 .22 2.1 88
esistance
R
esistance
R
C
1
1
Coil
oil
4.1
74
CSM11 Solenoid Control How to Order
When Ordering, Please Specify:
1. Catalog No. 60-73
2. Valve Size
3. Pattern - Globe or Angle
4. Pressure Class
5. Trim Material
6. Electrical Selection
7. Desired Options
8. When Vertically Installed
9. Epoxy Coating
CSM11 Specifications
Enclosure General purpose NEMA Type 3; Aluminum
Note: For other enclosures and NEMA Types, consult factory
Housing Body — Aluminum
Trim — Stainless Steel
Operating Pressure: Maximum pressure 300 psi, for higher pressure consult factory. AC or DC
Coil Insulation Class A (molded)
AC voltage 15.4 watts
DC voltage 16.8 watts
Wiring Diagram
Auto-Off-Hand = Selector Switch
1CR = Relay, DPST Normally Open
2CR = Relay, DPST Normally Open
3CR = Relay, TPST Normally Open
SW1 = Switch, Remote Start, Automatic
SW
Connect to N.C. Terminal
PVS = Pilot Valve Solenoid
M = Pump Motor Starter
2
= Switch, SPDT, Valve Limit Switch
Pilot System Specifications
Temperature Range
Water to 82°C Max
Materials
Standard Pilot System Materials
Pilot Control: Low Lead Bronze Trim: Stainless Steel Type 303 Rubber: Buna-N®Synthetic Rubber
Optional Pilot System Materials Pilot Systems are available with
optional Aluminum, Stainless Steel or Monel materials.
Note:
SW2and PVS supplied by Cla-Val. All other electrical items supplied by customer. SW2is included in the X105L switch as­sembly which is mounted on the pump control valve cover.
Shown In Pump Off Position
Page 4
Sequence Of Operation
Drain P
T.1
A
D
E
H
Enter PT.2
C
B
J
F
D
rain
A
E
H
D
Enter
PT.2
PT.1
F
B
C
A
Drain
Enter
C
PT.1
PT.2
E
H
D
F
B
CLA-VAL
1701 Placentia Ave Costa Mesa CA 92627 Phone: 949-722-4800 Fax: 949-548-5441 E-mail: info@cla-val.com www.cla-val.com
Copyright Cla-Val 2019
Printed in USA • Specifications subject to change without notice.
©
10 20 30 40 60 80 100 200 500 1000 2000 5000 10,000 20,000 50,000
1
2
3
4
6
8
1
0
20
30
40
60
80
1
00
5
3
Angle Valve Sizes (Inches)
Globe Valve Sizes (Inches)
8
0
100
150
200
65
Pressure Drop  psi
Flow Rate gpm (water)
100
150
200
65
80
Pump Off...
With pump off, static line pressure is transmitted through strainer "F", shuttle valve "C", solenoid control "A", and speed control "E" to the chamber above the diaphragm, thus holding the valve closed. If power failure occurs when valve is open, the built-in check valve "J" closes immediately to prevent reverse flow.
Starting Cycle...
Starting switch closes, pump starts, solenoid control "A" energizes and shifts allowing fluid from upper diaphragm chamber to drain to atmosphere. High pressure fluid from pump enters strainer "B" and shifts shuttle valve "C", which always supplies the highest pressure from either strainer "B" or "F". High pressure fluid is transmitted to the lower diaphragm chamber and opens the valve.The opening speed of the valve is controlled by speed control "E", which limits the rate fluid is relieved from above the diaphragm.
Model 60-73 Flow Chart Uses Basic Valve Model 100-30
Stopping Cycle...
Starting switch opens, solenoid control "A" de­energizes and shifts, pump continues to run. High Pressure fluid from the pump is directed above the diaphragm, applying force to close the valve. The valve closes slowly as fluid from the lower diaphragm chamber is gradually released to atmosphere through speed control "D" and solenoid "A". When the valve closes fully, the limit switch "H" shuts off the pump.
Valve Sizing
Sizing Model 60-73 Booster Pump Control Valves is similar to sizing non-modulating type valves. Simply select the smallest size valve that will handle the pump output at an acceptable head loss for the application.
Do not oversize. Oversizing a Booster Pump Control Valve will nullify its ability to prevent surges caused by the starting and/or stopping of the pump. Maximum flow values are given in the selection table above. For further information on flow characteristics for this valve, reference the 100-30 (60-73) technical data sheet.
Liquid Volume Displaced from Diaphragm Chamber When Valve Opens or Closes
Sizes (mm) 65 80 100 150 200
60-73
.163 liters .303 liters .640 liters 2.01 liters 4.77 liters
Example:
A booster pump station with a rated output of 1000 GPM and 4 psi is an acceptable head loss for the application.
Optional Electronic Control
The Cla-Val PC-22D provides control of the pump and pump control valve, preventing surges in the system when the pump starts or stops. It consists of a pre-wired electrical control panel employing a programmable valve controller to sequence the pump and pump control valve during all modes of operation. Provides
Drain Provisions
Each time the valve opens or closes, water is discharged from the solenoid exhaust port, the amount varying with the valve size. Provisions should be made for the disposal of this water. Exhaust tube must be free of any back pressure. Provide an air gap between the solenoid exhaust tube and drain facility.
added protection to the pumping system from damage caused by mechanical, hydraulic or power failure.
The PC-22D offers all the control features found in the recommended wiring diagrams for Cla-Val pump control valves, plus alarms, automatic shutdown and adjustable timers.
E-60-73 Metric (R-02/2019)
Loading...