The Cla-Val Model 60-73 Booster Pump Control Valve is a pilotoperated valve designed for installation on the discharge of booster
pumps to eliminate pipeline surges caused by the starting and
stopping of the pump.
The pump starts against a closed valve. When the pump is started,
the solenoid control is energized and the valve begins to open slowly,
gradually increasing line pressure to full pumping head. When the
pump is signaled to shut-off, the solenoid control is de-energized and
the valve begins to close slowly, gradually reducing flow while the
pump continues to run. When the valve is closed, a limit switch
assembly, which serves as an electrical interlock between the valve
and the pump, releases the pump starter and the pump stops.
Schematic Diagram
Item Description
1 Powercheck Main Valve 100-30
2 CV Flow Control
3 CSM11-A2-2 Solenoid Control
4 X105LCW Switch Assembly
5 CVS-1 Shuttle Valve
Optional Features
Item Description
A X46A Flow Clean Strainer
B CK2 Isolation Valve
Y X43 "Y" Strainer
Should a power failure occur, a built-in lift-type check valve closes
the moment flow stops, preventing reverse flow regardless of
solenoid or diaphragm assembly position.
Typical Installation
Install Model 60-73 valve as shown. Flexible conduit should be used for
electrical connections to the solenoid control and the limit switch. The
Model 52-02 or 652-03 Surge Anticipator Valve is recommended for
power failure protection.
Note:
Valve stem can be located in either vertical up or horizontal position.
Page 2
Pressure Ratings
Y
Z
G
GG
GGG
D
Inlet
DD
DDD
F
FF
X
100-30
Threaded &
Flanged
A
E
C
(MAX)
K
J
H
Inlet
Outlet
AA
AAA
B
(Diameter)
65
279
279
295
203
262
140
140
148
43
89
95
102
102
110
0.50
0.50
0.50
18
30
432
254
254
80
318
305
337
232
284
159
152
168
52
95
105
114
102
111
0.50
0.50
0.50
20
43
457
279
279
100
381
397
292
362
191
198
—
—
—
81
114
127
127
135
0.75
0.75
0.75
28
86
533
305
305
150
508
533
400
468
254
267
—
—
109
140
159
—
152
165
0.75
0.75
0.75
43
145
864
508
508
200
645
670
508
554
322
335
—
—
—
135
171
191
203
216
1.00
1.00
1.00
58
295
940
1067
1067
Valve Size (mm)
A Threaded
AA 150 ANSI
AAA 300 ANSI
B Diameter
C Maximum
D Threaded
DD 150 ANSI
DDD 300 ANSI
E
F 150 ANSI
FF 300 ANSI
G Threaded
GG 150 ANSI
GGG 300 ANSI
H NPT Body Tapping
J NPT Cover Center Plug
K NPT Cover Tapping
Stem Travel
Approx. Ship Weight (kgs)
Approx. X Pilot System
Approx. Y Pilot System
Approx. Z Pilot System
Valve Body & Cover
GradeMaterial
(Recommended Maximum Pressure - psi)
Pressure Class
FlangedThreaded
ANSI
Standards*
150
Class
300
Class
End‡
Details
ASTM A536Ductile Iron B16.42250640400
ASTM A216-WCB Cast SteelB16.5285720400
UNS 87850BronzeB16.24225500400
Note: * ANSI standards are for flange dimensions only.
Flanged valves are available faced but not drilled.
‡ End Details machined to ANSI B2.1 specifications.
Valves for higher pressure are available; consult factory for details
For material options not listed, consult factory.
Cla-Val manufactures valves in more than 50 different alloys.
Cast IronCast SteelBronze
Bronze is Standard
Stainless Steel is Optional
®
Rubber
®
Rubber
60-73 Series Dimensions
(Full Internal Port 100-30) (
mm)
Page 3
Auto
Off
Hand
L1
SW
1
A
3CR
3
L2
1CR
H
1CR
1CR
3CR
1
N.C.
2CR
PVS
2CR
3CR
M
COM.
SW
2
N.O.
3CR
2
2CR
00-30 Pattern:Globe (G), Angle (A), End Connections:Threaded (T), Grooved (GR), Flanged (F) Indicate Available Sizes
60-73
Valve
Selection
Main Valve
100-30
Suggested
Flow
(gpm)
Suggested
Flow
(Liters/Sec)
100-30 Series is the full internal port Powercheck.
millimeters
(mm)
Pattern
End DetailT, FT, FFFF
Maximum
aximum
M
Intermittent
aximum
M
Maximum
Intermittent
1
6580100150200
G, AG, AG, AG, AG, A
30046080018003100
37058099022503900
192950113195
233762142246
CSM11 Solenoid Control Power
Consumption
VoltsAmperesVoltsAmperes
DC Holding Pull In AC 60 Hz Holding InrushOhms
24.60324242.8825.40.5
629120
28.
32.500208208.3302.9340
48.293240240.2882.5458
122440
115.
125.119480440.1431.27233
0722.45
252.
20.5755.1
1
40.1561.38
4
VoltsAmperes
(AC 50 Hz) Holding InrushOhms
110.484.615.7
220.242.366
240.222.188
esistance
R
esistance
R
C
1
1
Coil
oil
4.1
74
CSM11 Solenoid ControlHow to Order
When Ordering, Please
Specify:
1.Catalog No. 60-73
2.Valve Size
3.Pattern - Globe or Angle
4.Pressure Class
5.Trim Material
6.Electrical Selection
7.Desired Options
8. When Vertically Installed
9. Epoxy Coating
CSM11 Specifications
Enclosure General purpose NEMA Type 3; Aluminum
Note: For other enclosures and
NEMA Types, consult factory
Housing Body — Aluminum
Trim — Stainless Steel
Operating Pressure: Maximum pressure 300 psi,
for higher pressure consult factory. AC or DC
Coil Insulation Class A (molded)
AC voltage 15.4 watts
DC voltage 16.8 watts
Wiring Diagram
Auto-Off-Hand = Selector Switch
1CR = Relay, DPST Normally Open
2CR = Relay, DPST Normally Open
3CR = Relay, TPST Normally Open
SW1 = Switch, Remote Start, Automatic
SW
Connect to N.C. Terminal
PVS = Pilot Valve Solenoid
M = Pump Motor Starter
2
= Switch, SPDT, Valve Limit Switch
Pilot System Specifications
Temperature Range
Water to 82°C Max
Materials
Standard Pilot System Materials
Pilot Control: Low Lead Bronze
Trim:Stainless Steel Type 303
Rubber: Buna-N®Synthetic Rubber
Optional Pilot System Materials
Pilot Systems are available with
optional Aluminum, Stainless Steel
or Monel materials.
Note:
SW2and PVS supplied by Cla-Val. All other electrical items
supplied by customer. SW2is included in the X105L switch assembly which is mounted on the pump control valve cover.
Shown In Pump Off Position
Page 4
Sequence Of Operation
DrainP
T.1
A
D
E
H
Enter PT.2
C
B
J
F
D
rain
A
E
H
D
Enter
PT.2
PT.1
F
B
C
A
Drain
Enter
C
PT.1
PT.2
E
H
D
F
B
CLA-VAL
1701 Placentia Ave • Costa Mesa CA 92627 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: info@cla-val.com • www.cla-val.com
Copyright Cla-Val 2019
•
Printed in USA • Specifications subject to change without notice.
With pump off, static line pressure is
transmitted through strainer "F", shuttle
valve "C", solenoid control "A", and speed
control "E" to the chamber above the
diaphragm, thus holding the valve closed.
If power failure occurs when valve is open,
the built-in check valve "J" closes
immediately to prevent reverse flow.
Starting Cycle...
Starting switch closes, pump starts, solenoid control
"A" energizes and shifts allowing fluid from upper
diaphragm chamber to drain to atmosphere. High
pressure fluid from pump enters strainer "B" and shifts
shuttle valve "C", which always supplies the highest
pressure from either strainer "B" or "F". High pressure
fluid is transmitted to the lower diaphragm chamber
and opens the valve.The opening speed of the valve is
controlled by speed control "E", which limits the rate
fluid is relieved from above the diaphragm.
Model 60-73 Flow Chart Uses Basic Valve Model 100-30
Stopping Cycle...
Starting switch opens, solenoid control "A" deenergizes and shifts, pump continues to run.
High Pressure fluid from the pump is directed
above the diaphragm, applying force to close the
valve.
The valve closes slowly as fluid from the lower
diaphragm chamber is gradually released to
atmosphere through speed control "D" and
solenoid "A". When the valve closes fully, the
limit switch "H" shuts off the pump.
Valve Sizing
Sizing Model 60-73 Booster Pump Control
Valves is similar to sizing non-modulating type
valves. Simply select the smallest size valve that
will handle the pump output at an acceptable
head loss for the application.
Do not oversize. Oversizing a Booster Pump
Control Valve will nullify its ability to prevent
surges caused by the starting and/or stopping
of the pump. Maximum flow values are given in
the selection table above. For further
information on flow characteristics for this valve,
reference the 100-30 (60-73) technical data
sheet.
Liquid Volume Displaced from Diaphragm Chamber When Valve Opens or Closes
A booster pump station with a rated output of
1000 GPM and 4 psi is an acceptable head loss
for the application.
Optional Electronic Control
The Cla-Val PC-22D provides control of the pump and
pump control valve, preventing surges in the system
when the pump starts or stops. It consists of a pre-wired
electrical control panel employing a programmable
valve controller to sequence the pump and pump
control valve during all modes of operation. Provides
Drain Provisions
Each time the valve opens or closes, water is
discharged from the solenoid exhaust port, the
amount varying with the valve size. Provisions
should be made for the disposal of this water.
Exhaust tube must be free of any back pressure.
Provide an air gap between the solenoid
exhaust tube and drain facility.
added protection to the pumping system from damage
caused by mechanical, hydraulic or power failure.
The PC-22D offers all the control features found in the
recommended wiring diagrams for Cla-Val pump control
valves, plus alarms, automatic shutdown and adjustable
timers.
E-60-73 Metric (R-02/2019)
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.