Clarkson Manuals: Knifegate valves Figure 738 IOM larger sizes, Clarkson-EN Manuals & Guides

CLARKSON FIGURE 738 PNEUMATIC ACTUATOR
DN 250 - 600 MOUNTING INSTRUCTIONS
Mounting instructions for F738 pneumatic cylinder, DN 250 - 600 knife gate valves
GENERAL NOTES
1. A filter (5 micron), lubricator, regulator set is recommended on incoming air lines and fitted before the valve, particularly on large cylinders (DN 250 - NPS 10 bore and above) which are made of glass epoxy composite tube.
2. Where speed control is required, the speed control valves should be fitted to control the air exhausting from the cylinder (meterout control). These can be fitted in the lines adjacent to the cylinder ports. If the control lines are relatively short the can be fitted to the exhaust ports of the directional valve.
CAUTION
Some combinations of knife gate valves and pneumatic cylinders are only suitable for operation at low air line pressures and pipe line pressures. Do not exceed operating conditions on valve and cylinder tags otherwise damage may occur.
MOUNTING INSTRUCTIONS
1. Ensure pipeline is not pressurized and any hazardous medium is drained away.
2. Remove bridge nuts (26) and washers (22).
3. Remove pillar nut and washer.
4. Loosen upright mounting bolts (12) at valve body.
5. Remove clevis retaining bolts and washers.
6. Remove handwheel, bridge and spindle assembly.
7. Screw supplied cylinder mounting bridge onto threaded pillar until it is nearly flush with top of pillar (7).
8. Replace upright (23) and tighten mounting bolts (26).
9. Remove four mounting nuts and washers from the actuator. Locate pneumatic cylinder on mounting bridge, ensuring air ports are in the required position.
10. Replace cylinder mounting nuts and washers, loosely.
11. Fit the clevis to the piston rod and adjust if necessary to align with the gate.
12. Fit the clevis bolts (13) and tighten.
13. Check alignment of piston rod and gate (2), then tighten mounting nuts.
14. Remove port plugs and fully extend piston rod either manually or pneumatically.
15. Connect air supply to both ports.
16. Open and close valve to ensure it operates correctly.
1. All air line and electrical cable entries should be plugged. If cylinders are not fitted to a valve, they should be stored with the piston rod fully retracted.
2. Cylinders are assembled with a light coating of grease on internal components.
26, 22
7
13
23
2
12
Emerson.com/FinalControl
© 2017 Emerson. All Rights Reserved. VCIOM-02596-EN 19/09
CLARKSON FIGURE 738 PNEUMATIC ACTUATOR
DN 250 - 600 MOUNTING INSTRUCTIONS
ALIGNMENT
For correct valve operation, it is important that the valve gate is correctly aligned and seating in the valve, and that the cylinder stroking movement is correctly aligned to the valve gate. Prior to fitting cylinder, check:
Valve:
Check gate alignment (gate closed) If correctly fitted and aligned:
• Height of pillars (7) to bridge bolts (12) should be equal.
• Gate will be fitting firmly and evenly up against seating face in valve body.
• Gate and gland box will be approximately centerd with the valve body viewed from frontand sides
• Gate will be true and parallel to valve body axis viewed from the side.
• Gate will not have significant movement when rocked backwards and forwards (upstreamand downstream, not sideways)
If not fitted correctly:
• Gate is not seating properly into the wedges in the base of the valve and/or the gate guides in the upper body of the valve are badly worn, missing or incorrectly adjusted - fix as necessary.
Actuator:
After fitting cylinder to closed valve and before stroking cylinder:
• With cylinder rod fully extended, viewing from the side of the valve, check that the center line of the cylinder and it’s extended rod are directly in line with valve blade axis, the valve body axis and the pillar supports. Then check center line alignment of valve and cylinder and rod viewing from the front of the valve. Ifeither check reveals an out of alignment, then cylinder is not mounted squarely onto the valve and adjustment is necessary.
CYLINDER ACTUATED VALVES ­INSTALLATION GUIDELINES
Cylinder actuated valves tend to be large and heavy and consideration must be given to adequately supporting both the actuated valve and adjoining pipe work particularly where light weight pipe or tube is being used. Heavycylinder actuated valves mounted in other than the vertical position can also cause the pipeline to twist. Where possible, the cylinder actuated valves should be mounted in the vertical position with the cylinder uppermost to prevent gate misalignment and possible structural damage to the valve assembly. If mounted in any other position (angled,horizontal etc.), the cylinders must be properly supported by a suitable structure. Large valves using cylinders (not vertically mounted) in size 14 (400 mm bore x 600stroke) and above must have a fully engineered structure. Contact Emerson for advice or assistance.
NOTE:
To minimize risk to personnel, Emerson recommend the use of purpose built guards and shrouds. Refer to the Emerson data sheet or consult factory fordetails.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Clarkson is a mark owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric Co. Emerson Automation Solutions, Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of their respective owners.
The contents of this publication arepresented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such products at any time without notice.
Emerson.com/FinalControl
2
Loading...