V34612 WS2H/3 AC ADAPTER
V3461EU WS2H/3 AC ADAPTER EU
V3461UK WS2H/3 AC ADAPTER UK
V34612 WS2H/3 AC ADAPTER
V3461EU WS2H/3 AC ADAPTER EU
V3461UK WS2H/3 AC ADAPTER UK
V3461-01 WS2H/3 AC ADAPTER 20V
3
V3461EU-01 WS2H/3 AC ADAPTER EU 20V
V3461UK-01 WS2H/3 AC ADAPTER UK 20V
1
It is recommended to maintain one version throughout a system.
2
Replacement V3461 power supplies have screw terminals and are shipped less a cord. Use cord from existing power supply to connect to the screw terminals.
3
V3461EU-01 and V3461UK-01 will not be available for sale until August 2010.
Page 6
Page 6 WS2H and WS3 Programming and Wiring Manual
Set clock from any USER eld.
a
Medium Reset
From User 1 Screen - Volume Remaining
Press and hold the Set Clock and Regen buttons for 10 seconds to reset valve
to factory default programming. History and Diagnostics are not changed.
Recommended System Setup Sequence:
1. Connect all wiring and communication cables.
2. Apply power.
3. Enter system setup screens and set screen 2 to number of units in the particular system.
a. Setting this valve assigns master status to that unit.
b. The master unit will establish communication with the remaining units and transfer the remaining settings to
them.
4. Set cycle sequence.
5. Set cycle times.
6. Set installer data.
Wiring for custom AC Adapter
1. See Table 2 Software and Power Supply Compatibility.
2. Cable should be one unshielded pair of 22AWG, UV resistant UL2464
compliant wire.
3. Connector details:
a. Terminate end with one Molex white housing,
P/N 09-50-8043 and four Molex pins, P/N 08-50-0108.
b. Pin 1 = AC from power supply (White)
Pin 2 = Jumper to Pin 3
Pin 3 = Jumper to Pin 2
Pin 4 = AV from power supply (Black)
Molex
Housing
Pin 1
Custom Meter Wiring:
1) Terminate end with a Molex series 2695 housing, part number 2201-3037 and (3) Molex series 41572 (or 40445) pins, part number
08-65-0805 (or 97-00-44).
2) Auxilliary meter must be able to operate on 5VDC
3) Acceptable pulse input is .1 – 999 pulses/gallon, or
.4 –519 pulses / liter.
Page 7
WS2H and WS3 Programming and Wiring Manual Page 7
Main PC Board with System Board
1) Power Supply
2) Manual Override Switch
3) Flow
Meter
4) Motorized
Alternating
Valve
5) POD
Display
Connection
10) System Board
Connection
6) Auxiliary
Input
11) Auxiliary
Drive
13) Relay 212 ) Relay 1
11) Programming
Port
9) Drive
Motor
1) Unit’s main power supply. Labeled POWER.
2) Isolation valve manual override switch will force the unit on-line or off-line. The corresponding LED indicator on the display
POD will fl ash rapidly, 2 times per second, to warn that the unit is in a forced state.
3) Flow meter input. Labeled FLOW.
4) Drive circuit for Motorized Alternating Valve (MAV) or for a Motorized Bypass valve (V3060). It will bring a unit on-line or
off-line based on the programming of the current system. Labeled BYPASS.
5) POD connection for the display. This connection is also used as the data extraction port with the proper software and cabling.
6) Auxiliary Input to control/ trigger when or how a unit can regenerate based on the setting of the dP screen in the programming
setup. External inputs should be dry contacts and units wired in parallel require matching each unit’s polarity. Labeled AUX
INPUT.
7) Programming port connection for Main PC Board is for factory use only.
8) Main board communication port can be used as the communication port for a 2 unit master and is the communication port for
every slave unit of a system. Labeled MASTER/ SLAVE.
9) Drive Motor circuit power the motor that drives the piston during regeneration. Labeled REGEN.
10) Connection for Optional System Board. This board would be added to units requiring the extra drive circuit to operate a
separate source valve, if a 2, 3, or 4 unit progressive fl ow/ alternator system was needed, or when relays would need to operate
external devices. Labeled SYSTEM BOARD.
11) Auxiliary Drive circuit is used to operate a Motorized Alternating Valve (MAV) based on the program setting of the separate
source inlet on or off. This drive circuit is timed to sequence after a unit is isolated from a system, or prior to regen for units
with no isolation. Labeled AUX DRIVE.
12) Dry contact outputs to operate external devices based on the program setting of Relay 1. Labeled AUX 1.
13) Dry contact outputs to operate external devices based on the program setting of Relay 2. Labeled AUX 2.
14) Additional communication ports used on the master control valve for systems with 3 or 4 units. See wiring diagrams for
examples. Labeled SLAVE 1, SLAVE 2, and SLAVE 3.
8) Communication
Port
7) Programming
Port
14) Communication Ports
Page 8
Page 8 WS2H and WS3 Programming and Wiring Manual
Communication Cable Connection to PC Board Layout
Revised communication cable connectivity.
View Of Revised 3 Wire Communication
Cable On 4 Terminal Header
3 Wire Cables Being Installed On 4
Terminal Headers Need Left Polarizer
Remove
Ear
"Ear" Removed
Install cable flush to the
right side leaving left terminal
pin with no connection
View Of 4 Wire Communication Cable On 3
Terminal Header (System Board Is Optional)
C
A
Install right side of cable flush
to terminal leaving a vacant
position on the left of the cable
Page 9
WS2H and WS3 Programming and Wiring Manual Page 9
Separate
Source Inlet
Motor Drive
Relay 2Relay 1
Optional System Board, Required For Relay Output And
Separate Source Inlet
1) Relay outputs 1 & 2 have N.O., N.C. and common dry
contacts.
2) Maximum power through relays to be:
a. 1A, 30 VDC
b. 1A, 30 VAC
3) Separate source inlet drives require connection to a V3063
or V3063BSPT, V3076 or V3076BSPT motorized alternating
valve (MAV).
Motorized Drive Operation
Viewing the piston rod through the clear dome
is a visual indicator of the drive’s current
position. On the WS2 motorized bypass
drive, viewing the rod indicates that the unit
is in service. Viewing the rod as shown on
the MAV indicates that the common port is
currently connected to the “B” port. If the
rod is not visible the unit is offl ine in the case
of a bypass, or the common port is currently
connected to the “A” port of a MAV. In this
state the “B” port of a MAV is shut off. This
drive logic is reversible to meet specifi c
plumbing applications by reversing the polarity
of the drive motor wiring harness as shown
below.
Push in Locking Tab
While Pulling On Wire
Factory Wired
As White Wire
"Com" Port
Flow Path
"B" Port
Piston MAVPoppet MAV
Reversing Motorized Drive Direction
WS2 motorized bypass and MAV drives are factory wired
with the white wire on the right when viewing the wiring
harness as shown, reversing the wires reverses the logic of
the drive. The wires can be removed from the housing by
holding down the locking tab in the small window while
applying light pressure to the wire, being careful not to
disengage the wire from its crimped on connector. The wires
can then be re-inserted, being sure the locking tab re-engages
in the window.
Piston Rod
Is Visible
"A" Port
Page 10
Page 10 WS2H and WS3 Programming and Wiring Manual
WS2H Single Unit System Operations
Single tank system with a MAV valve for No Hard Water Bypass
• MAV valve will need to be installed on the control valve’s outlet port
• Port “B” or “C” of the MAV valve needs to be connected to the control valve’s outlet port
• Port “A” of the MAV valve needs to be plugged off
• The MAV valve’s motor wire needs to be connected to the two pin connection labeled “BYPASS” on the control valve’s PC Board
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Piston Style
MAV motor wire
MAV valve for NHWBP
Plug off “A”
port when
using as No
Hard Water
Bypass
Poppet Style
Page 11
WS2H and WS3 Programming and Wiring Manual Page 11
Single tank system with System Board and MAV valve for Separate Source with a secondary MAV valve for No Hard Water Bypass
• System Board required to operate Separate Source MAV valve
• The MAV valve for Separate Source needs to be installed on the control valve’s inlet port
• Port “C” of the MAV valve for Separate Source needs to be connected to the control valve’s inlet port
• Port “B” of the MAV valve for Separate Source will become the raw water inlet to the control valve
• Port “A” of the MAV valve for Separate Source will become the Separate Source inlet feed to the control valve
• The MAV valve’s motor wire for Separate Source needs to be connected to the two pin connection on the System Board labeled
“AUX DRIVE”
• The MAV valve for No Hard Water Bypass will need to be installed on the control valve’s outlet port
• Port “B” or “C” of the MAV valve for No Hard Water Bypass needs to be connected to the control valve’s outlet port
• Port “A” of the MAV valve for No Hard Water Bypass needs to be plugged off
• The MAV valve’s motor wire needs to be connected to the two pin connection labeled “BYPASS” on the control valves PC Board
Single tank system with System Board for Relay Outputs
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Piston Style
MAV for Separate Source
No Hard Water Bypass
MAV motor wire
Separate Source MAV motor wire
MAV valve for NHWBP
Plug off “A”
port when
using as No
Hard Water
Bypass
Poppet Style
Separate
Source
Inlet
Untreated
water inlet
Connect
to Inlet on
Control
Valve
Page 12
Page 12 WS2H and WS3 Programming and Wiring Manual
WS2H Two Unit System Operations
Two tank system, Simple Alternator with (1) MAV valve
• (1) MAV valve and (1) communication cable is required for a Simple Alternator
• The MAV valve’s motor wire needs to be connected to the two pin connection labeled “BYPASS” on Unit 2’s PC Board
• The communication cable needs to be connected to Unit 1’s three pin connection labeled “MASTER/SLAVE” and Unit 2’s three
pin connection labeled “MASTER/SLAVE”
• To regenerate with raw/ untreated water the outlet port of Unit 1 needs to be piped to Port “A” of the MAV valve, the outlet port of
Unit 2 needs to be piped to Port “B” of the MAV valve, and Port “C” or common will be the common outlet for Unit 1 & Unit 2
• To regenerate with soft/ treated water the MAV valve needs to be installed on the main inlet feed line to Unit 1 & Unit 2, Port “C”
of the MAV valve will become the new common inlet for both Unit 1 & Unit 2. Port “A” of the MAV valve will need to be piped
to the inlet port of Unit 1, and Port “B” of the MAV valve will need to piped to the inlet port of Unit 2
• As a Alternator only, the unit in Stand-By will perform a Pre-Service downfl ow rinse to drain before coming on-line
• If a single external meter is to be used, the wire connection for that meter needs to be connected to Unit 2’s PC Board three pin
connection labeled “FLOW.” Also when a single external meter is to be used, in System Setup Screens under system setup 10
“System Pulses” needs to be selected and then the proper meter pulses for the external meter needs to be set in the next screen.
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Piston StylePoppet Style
Unit 1/Alt AUnit 1/Alt A
Unit 2
Communication Cable
MAV motor wire
MAV for twin alternating
Connect
to outlet
of control
valve set for
ALT A
Common
outlet
Unit 2
Connect
to outlet
of
control
valve
deemed
as ALT b
Page 13
WS2H and WS3 Programming and Wiring Manual Page 13
Two tank system, Alternator and/or Progressive Flow with a MAV valve on each for No Hard Water Bypass
• (2) MAV valves and (1) communication cable are required
• The communication cable needs to be connected to Unit 1’s three pin connection labeled “MASTER/SLAVE” and Unit 2’s three
pin connection labeled “MASTER/SLAVE”
• Each MAV valve’s motor wire will need to be connected to the two pin connection on the PC Board labeled “BYPASS” for each
control valve
• Each MAV valve will need to be installed on the outlet port of each control valve for No Hard Water Bypass, which allows for
raw/ untreated water regeneration for twin alternating and/or progressive fl ow
• Port “B” or “C” of each MAV valve needs to be connected to the control valve’s outlet port
• Port “A” of each MAV valve needs to be plugged off
• To regenerate with soft/ treated water each MAV valve would need to be installed on the inlet port of each control valve for No
Hard Water Bypass. This will allow soft/ treated water from the opposing unit to back feed through the outlet of the unit that
requires regeneration for twin alternating and/or progressive fl ow
• As a Alternator only, the unit in Stand-By will perform a Pre-Service downfl ow rinse to drain before coming on-line
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Piston StylePoppet Style
Unit 1
Communication Cable
MAV motor wire
Unit 2
MAV valve for NHWBP
Plug off “A”
port when
using as No
Hard Water
Bypass
MAV motor wire
MAV valve for NHWBP
Plug off “A”
port when
using as No
Hard Water
Bypass
Unit 1
Unit 2
Page 14
Page 14 WS2H and WS3 Programming and Wiring Manual
Two tank system, Alternator and/or Progressive Flow with System Boards for Separate Source/ Relay Outputs and (2) MAV valves
on each for Separate Source and No Hard Water Bypass
• (2) System Boards are required to operate Separate Source MAV valve and/or Relay Outputs
• (4) MAV valves and (1) communication cable are required
• The communication cable needs to be connected to Unit 1’s three pin connection labeled “MASTER/SLAVE” and Unit 2’s three
pin connection labeled “MASTER/SLAVE”
• (2) MAV valves for Separate Source need to be installed on each of the control valve’s inlet ports
• Port “C” of the MAV valves for Separate Source need to be connected to each of the control valve’s inlet ports
• Port “B” of the MAV valves for Separate Source will become the raw water inlets to each of the control valves
• Port “A” of the MAV valves for Separate Source will become the Separate Source inlet feeds to each of the control valves
• Each MAV valve’s motor wire for Separate Source need to be connected to the two pin connections on each of the System Boards
labeled “AUX DRIVE”
• The MAV valves for No Hard Water Bypass will need to be installed on each of the control valve’s outlet ports
• Port “B” or “C” of the MAV valves for No Hard Water Bypass need to be connected to each of the control valve’s outlet ports
• Port “A” of the MAV valves for No Hard Water Bypass need to be plugged off
• The MAV valve’s motor wire for No Hard Water Bypass need to be connected to the two pin connection labeled “BYPASS” on
each of the control valve’s PC Boards
• As a Alternator only, the unit in Stand-By will perform a Pre-Service downfl ow rinse to drain before coming on-line
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Unit 1
No Hard Water Bypass
MAV motor wire
Communication Cable
Unit 2
Piston Style
Separate Source MAV motor wire
No Hard Water Bypass MAV
Plug off “A”
port when
using as No
Hard Water
Bypass
Separate Source MAV
Separate
Source
Inlet
Connect
to Control
Valve
Inlet
Untreated
Water
Inlet
Poppet Style
Unit 1
Unit 2
Page 15
WS2H and WS3 Programming and Wiring Manual Page 15
WS2H Three Unit System Operations
Three tank system, Alternator and/or Progressive Flow with System Board and MAV valve on each for No Hard Water Bypass
• (1) System Board and (2) communication cables required to communicate between 3 units
• (3) MAV valve’s are required
• (1st) communication cable needs to be connected to Unit 1’s System Board three pin connection labeled “SLAVE 1” and Unit 2’s
three pin connection on the PC Board labeled “MASTER/SLAVE”
• (2nd) communication cable needs to be connected to Unit 1’s System Board three pin connection labeled “SLAVE 2” and Unit 3’s
three pin connection on the PC Board labeled “MASTER/SLAVE”
• Each MAV valve’s motor wire will need to be connected to the two pin connection on the PC Board labeled “BYPASS” for each
control valve
• Each MAV valve will need to be installed on the outlet port of each control valve for No Hard Water Bypass, which allows for
raw/ untreated water regeneration for triplex alternating and/or progressive fl ow
• Port “B” or “C” of each MAV valve needs to be connected to each of the control valve’s outlet ports
• Port “A” of each MAV valve needs to be plugged off
• To regenerate with soft/ treated water each MAV valve would need to be installed the inlet port of each control valve for No Hard
Water Bypass. This will allow soft/ treated water from the opposing unit to back feed through the outlet of the unit that requires
regeneration for triplex alternating and/or progressive fl ow
• As a Alternator only, the unit in Stand-By will perform a Pre-Service downfl ow rinse to drain before coming on-line
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Unit 1
Unit 2
Piston StylePoppet Style
MAV motor wire
Communication Cables
MAV for No Hard Water Bypass
Plug off “A”
port when
using as No
Hard Water
Bypass
Unit 1
Unit 2
Unit 3
Unit 3
Page 16
Page 16 WS2H and WS3 Programming and Wiring Manual
Three tank system, Alternator and/or Progressive Flow with System Boards for Separate Source/ Relay Outputs and (2) MAV valves
on each for Separate Source and No Hard Water Bypass
• (3) System Boards are required to communicate 3 units and operate Separate Source MAV valves and/or Relay Outputs
• (6) MAV valves and (2) communication cable are required
• (1st) communication cable needs to be connected to Unit 1’s System Board and three pin connection labeled “SLAVE 1” and Unit
2’s three pin connection on the PC Board labeled “MASTER/SLAVE”
• (2nd) communication cable needs to be connected to Unit 1’s System Board three pin connection labeled “SLAVE 2” and Unit 3’s
three pin connection on the PC Board labeled “MASTER/SLAVE”
• (3) MAV valves for Separate Source need to be installed on each of the control valve’s inlet ports
• Port “C” of the MAV valves for Separate Source need to be connected to each of the control valve’s inlet ports
• Port “B” of the MAV valves for Separate Source will become the raw water inlets to each of the control valves
• Port “A” of the MAV valves for Separate Source will become the Separate Source inlet feeds to each of the control valves
• The MAV valve’s motor wire for Separate Source need to be connected to the two pin connections on each of the System Boards
labeled “AUX DRIVE”
• The (3) MAV valves for No Hard Water Bypass will need to be installed on each of the control valve’s outlet ports
• Port “B” or “C” of the MAV valves for No Hard Water Bypass need to be connected to each of the control valve’s outlet ports
• Port “A” of the MAV valves for No Hard Water Bypass need to be plugged off
• The MAV valve’s motor wire for No Hard Water Bypass need to be connected to the two pin connection labeled “BYPASS” on
each of the control valve’s PC Boards
• As a Alternator only, the unit in Stand-By will perform a Pre-Service downfl ow rinse to drain before coming on-line
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Unit 1
No Hard Water Bypass
MAV motor wire
Communication Cables
Unit 2
Unit 3
Piston StylePoppet Style
Separate Source MAV
Separate Source MAV motor wire
No Hard Water Bypass MAV
Plug off “A”
port when
using as No
Hard Water
Bypass
Separate
Source
Inlet
Connect
to Control
Valve
Inlet
Untreated
Water
Inlet
Unit 1
Unit 2
Unit 3
Page 17
WS2H and WS3 Programming and Wiring Manual Page 17
WS2H Four Unit System Operations
Four tank system, Alternator and/or Progressive Flow with System Board and MAV valve on each for No Hard Water Bypass
• (1) System Board and (3) communication cables required to communicate between 4 units
• (4) MAV valves are required
• (1st) communication cable needs to be connected to Unit 1’s System Board three pin connection labeled “SLAVE 1” and Unit 2’s
three pin connection on the PC Board labeled “MASTER/SLAVE”
• (2nd) communication cable needs to be connected to Unit 1’s System Board three pin connection labeled “SLAVE 2” and Unit 3’s
three pin connection on the PC Board labeled “MASTER/SLAVE”
• (3rd) communication cable needs to be connected to Unit 1’s System Board three pin connection labeled “SLAVE 3” and Unit 4’s
three pin connection on the PC Board labeled “MASTER/SLAVE”
• Each MAV valve’s motor wire will need to be connected to the two pin connection on the PC Board labeled “BYPASS” for each
control valve
• Each MAV valve will need to be installed on the outlet port of each control valve for No Hard Water Bypass, which allows for
raw/ untreated water regeneration for triplex alternating and/or progressive fl ow
• Port “B” or “C” of each MAV valve needs to be connected to each of the control valve’s outlet ports
• Port “A” of each MAV valve needs to be plugged off
• To regenerate with soft/ treated water each MAV valve would need to be installed the inlet port of each control valve for No Hard
Water Bypass. This will allow soft/ treated water from the opposing unit to back feed through the outlet of the unit that requires
regeneration for triplex alternating and/or progressive fl ow
• As a Alternator only, the unit in Stand-By will perform a Pre-Service downfl ow rinse to drain before coming on-line
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Unit 1
Unit 2
Unit 3
Piston StylePoppet Style
MAV motor wire
Communication Cables
MAV for No Hard Water Bypass
Plug off “A”
port when
using as No
Hard Water
Bypass
Unit 1
Unit 2
Unit 3
Unit 4
Unit 4
Page 18
Page 18 WS2H and WS3 Programming and Wiring Manual
Four tank system, Alternator and/or Progressive Flow with System Boards for Separate Source/ Relay Outputs and (2) MAV valves
on each for Separate Source and No Hard Water Bypass
• (4) System Boards are required to communicate 4 units and operate Separate Source MAV valves and/or Relay Outputs
• (8) MAV valves and (3) communication cable are required
• (1st) communication cable needs to be connected to Unit 1’s System Board and three pin connection labeled “SLAVE 1” and Unit
2’s three pin connection on the PC Board labeled “MASTER/SLAVE”
• (2nd) communication cable needs to be connected to Unit 1’s System Board three pin connection labeled “SLAVE 2” and Unit 3’s
three pin connection on the PC Board labeled “MASTER/SLAVE”
• (3rd) communication cable needs to be connected to Unit 1’s System Board three pin connection labeled “SLAVE 3” and Unit 4’s
three pin connection on the PC Board labeled “MASTER/SLAVE”
• (4) MAV valves for Separate Source need to be installed on each of the control valve’s inlet ports
• Port “C” of the MAV valves for Separate Source need to be connected to each of the control valve’s inlet ports
• Port “B” of the MAV valves for Separate Source will become the raw water inlets to each of the control valves
• Port “A” of the MAV valves for Separate Source will become the Separate Source inlet feeds to each of the control valves
• Each MAV valve’s motor wire for Separate Source need to be connected to the two pin connections on each of the System Boards
labeled “AUX DRIVE”
• The (4) MAV valves for No Hard Water Bypass will need to be installed on each of the control valve’s outlet ports
• Port “B” or “C” of the MAV valves for No Hard Water Bypass need to be connected to each of the control valve’s outlet ports
• Port “A” of the MAV valves for No Hard Water Bypass need to be plugged off
• Each MAV valve’s motor wire for No Hard Water Bypass need to be connected to the two pin connection labeled “BYPASS” on
each of the control valve’s PC Boards
• As a Alternator only, the unit in Stand-By will perform a Pre-Service downfl ow rinse to drain before coming on-line
• System Board required to operate available Relay Outputs
• System Board provides (2) Relay Outputs with N.O. , COM , and N.C. SPST dry contacts
Unit 1
No Hard Water Bypass
MAV motor wire
Communication Cables
Unit 2
Unit 3
Piston StylePoppet Style
Separate Source MAV motor wire
No Hard Water Bypass MAV
Plug off
“A” port
when using
as No Hard
Water
Bypass
Separate Source MAV
Separate
Source
Inlet
Connect
to Control
Valve
Inlet
Untreated
Water
Inlet
Unit 1
Unit 2
Unit 3
Unit 4
Unit 4
Page 19
WS2H and WS3 Programming and Wiring Manual Page 19
THIS PAGE LEFT
INTENTIONALLY BLANK.
Page 20
Page 20 WS2H and WS3 Programming and Wiring Manual
WS2H/WS3 Programming Screen Quick Reference
1. Individual screen descriptions and settings are detailed on the following pages.
2. Some screens have been omitted for clarity.
Page 21
WS2H and WS3 Programming and Wiring Manual Page 21
Page 22
Page 22 WS2H and WS3 Programming and Wiring Manual
Typical User Screens
“REGEN TODAY” will
display when a regeneration
is scheduled, or fl ash for a
manually set regeneration.
“HOLD” or “START” REGEN
will fl ash in all user screens while
the auxiliary input is actuated.
USER 1
USER 1
Displays capacity remaining Does not
display if volumetric capacity is set to OFF.
Capacity remaining can be adjusted in 10 gallon
increments by holding the DOWN arrow for >3 seconds.
USER 2
USER 2
Displays days remaining Does not display if days
override is set to OFF.
Days remaining can be decremented one day at a
time by holding the DOWN arrow >3 seconds.
USER 3
USER 3
Displays time of day.
USER 4
USER 4
Displays the unit’s current fl ow rate.
USER 5
USER 6
USER 7
USER 5
Displays total unit volume since
install/reset Individually re-settable
using history reset sequence.
USER 6
Displays the current system fl ow rate
Does not display on single tank units.
USER 7
Displays total system volume since install/reset
Individually re-settable using history reset sequence
Does not display on single tank units.
User 1
Page 23
WS2H and WS3 Programming and Wiring Manual Page 23
Setting Time of Day
SET TIME
Accessed by pressing Set Clock while in the
User Screens. Use UP and DOWN arrows to
scroll hours. AM/PM alternates at midnight.
Return to
Normal Operation
UNIT COUNT ERROR
Error and the slave’s unit number will fl ash when it is
not detected. Pressing any button will return the user
to the #units set up screen to correct the value.
ERROR SCREEN
Error and its code alternate. The unit returns to home
and fl ashes its 3 LEDs. The unit continues to try and
function, but must be reset to correct the error screen.
Automatically toggles.
Indicates that a specifi ed volume per day has been reached.
(All LED lights fl ash).
Only displayed if Timer 2 or Timer 3 is set to
“Day & Gal” or “Day & Gal & System”.
Resettable by pressing any button.
Page 24
Page 24 WS2H and WS3 Programming and Wiring Manual
System Setup Screens
Accessed by pressing NEXT and DOWN
simultaneously for >3 seconds.
SYSTEM SETUP 1
SYSTEM SETUP 1
Select country.
US or SI.
This sets the use of a 12 or 24 hour clock and the display of gallons or liters.
SYSTEM SETUP 2
SYSTEM SETUP 2
Select the total number of units, from 1-4, in a system. This screen will only allow 1 or 2 if a system board is not
installed.
Communication cables are required to link multiple units together.
Returns to normal operation after 5 minutes
SYSTEM SETUP 3A
SYSTEM SETUP 3A
The screen will not display if set to 1 unit.
Select unit fl ow rate unit add point.
1. If set to 0, all units are online unless one is regenerating.
2. If greater than 0, the system acts as a progressive fl ow system by adding units
as fl ow rate increases.
3. If set to ALT the system acts as an alternator system, keeping one unit off line
at all times. An additional screen will appear after ALT is set that will allow
the programmer to adjust a pre-service rinse to drain to the stand-by unit
before it is called on-line for service.
1. Unit Flow Rate Add Point
- 0: operates the system as a parallel fl ow system keeping all units online and
only allowing one unit to regen at a time. When one unit needs to regenerate it will fl ag all units to regenerate in series.
- Units in a parallel fl ow system will determine the need to regenerate based on:
- Any unit reaching 0 capacity;
- Delayed units will regenerate at the next available time slot
- Day over ride
- 1 day; all units will regen every day as long as it has been >12 hours since any other regenerations
- Day triggered regens will run in the sequence of times set in the delayed time screens.
2. - 1 – 499: the system acts as a stage by fl ow keeping one unit online at all times and adding units at this set point.
- Additional units will be brought online when the adder point is exceeded for >30 seconds or immediately if the fl ow
exceeds 120% of the adder point.
- Additional units will go offl ine when system fl ow reduces to 95% of adder point / unit for > 1 minute.
- Any unit in a demand recall system will determine the need to regenerate based on:
- Reaching 0 capacity
- Delayed units will regenerate at the next available time slot
- Day over ride
- 1 day; 1 unit will regen / day as long as it has been >12 hours since any other regenerations
- Day triggered regens will run at the time set in DEL-1
- Units can not regenerate if fl ow demands them to remain online
- On 0 units regen immediately after fl ow allows them offl ine
- Delayed units regen at the next available time slow
- Day units regen at the next time slot
3. - ALT: operates the system as an alternator, having one unit off line at all times either regenerating or fully
regenerated.
- A unit in an alternator system will determine the need to regenerate based on:
- The current “lead” unit reaching 0 capacity
Progressive Flow Unit
UnitsRangeIncrements
US
SI
(L)
0-4991
0-18964
(GAL)
Page 25
WS2H and WS3 Programming and Wiring Manual Page 25
- Delayed systems will immediately remove depleted units & regenerate at the next available time slot
- “Lead” unit regenerates based on “Lag” units
(i) The fi rst “lag” unit depleting down to 15% less than its ratio of system capacity
1. 1/3 for a 4 unit; ½ for a 3 unit
(ii) The second “lag” unit depleting down to 15% less than its ratio of system capacity
1. 2/3 for a 4 unit
- Delayed systems will fl ag “lead” units based on “lag” capacity, but will not alternate with remaining capacity until the
next available delayed time.
- Day over ride
- 1 day; 1 unit will regen / day as long as it has been >12 hours since any other regenerations
SYSTEM SETUP 3B
SYSTEM SETUP 4
- Day triggered regens will run at the time set in DEL-1
SYSTEM SETUP 3B
Set Pre-Service Rinse time for units coming online. Adjustable from OFF - 20 minutes in 30 second increments. This
screen only displays for alternator systems. Default: 1:00
SYSTEM SETUP 4
Hardwater Bypass
- Single units have a selection of Hbp, noHbP or Relay
- 2 unit alternators have a selection of noHbP, Relay or ALT-A
- All other systems have a choice of noHbP or Relay
SYSTEM SETUP 5
1. If set to HbP: Units will have hard water bypass while in a regeneration
2. If set to noHbP: Single units or multiple tank systems require a motorized bypass valve or motorized alternating
valve to be connected to the bypass connector on the main valve PC board. This setting will force an initialization of
the motorized drive to determine its current position.
3. If set to Relay: Units will have other types of external valves controlling the water supply. If relay 1 & 2 are both
set to STbY, relay 1 will close to remove a unit from service & open to add a unit. Relay 2 will actuate 15 seconds
after relay 1 and will operate in the opposite sequence as relay 1. To come back online is the opposite; relay 2 actuates
1st & relay 1 actuates after 15 seconds relay 2.
4. If set to ALT-A: requires a Motorized Alternating Valve (MAV) to be connected to the two pin connection labeled
“BYPASS” on Unit 2’s PC Board. A communication cable is required to connect ALT-A and Unit 2 together.
- Any setting requiring a motorized bypass valve or motorized alternating valve will cause the drive to initialize to
determine its current position.
- Units going through a reset or initial startup, the bypass or motorized alternating valve may torque early which
would cause the unit to run the drive in the opposite direction, then re-home
- Pressing any button while in the Error / Hbp screen will kick the user into hbp setting screen and allow correction.
Upon exiting the unit will try to re-initialize the motorized drive.
Piston Rod
SYSTEM SETUP 5
Is Visible
Select between piston or poppet style bypass drive.
Default - PISTn
SYSTEM SETUP 6
SYSTEM SETUP 6
Select day control type.
Time clock 1-28 day; Time clock 7 day; or OFF.
When volumetric capacity is set, volume regeneration can be combined with time clock control. OFF will not be an
option if volumetric capacity is OFF.
"Com" Port
Flow Path
Piston MAVPoppet MAV
"A" Port
"B" Port
Page 26
Page 26 WS2H and WS3 Programming and Wiring Manual
System Setup Screens (continued)
SYSTEM SETUP 7
SYSTEM SETUP 8
SYSTEM SETUP 9
SYSTEM SETUP 7
Select regeneration type.
Delayed (dEL-1)
Delayed, 2 regenerations per day (dEL-2)
Delayed, 3 regenerations per day (dEL-3)
Delayed, 4 regenerations per day (dEL-4)
On 0
Delayed regeneration times are set in installer screens.
Delayed with multiple regenerations allowed per day would be used either to reduce the reserve volume, or to
accommodate a small system relative to the treatment demand.
SYSTEM SETUP 8
Select reserve calculation ON or OFF.
OFF will schedule a regen when the volumetric capacity reaches 0. This screen will not display for “on0”
units or systems.
SYSTEM SETUP 9
Set auxiliary initiated regen.
START TIME REGEN: regeneration will start immediately after 2 cumulative minutes of switch closure.
START TIME REGEN dEL: regeneration will start at the delayed time after 2 cumulative minutes of switch
closure.
START REGEN: regeneration will start immediately upon switch closure.
START REGEN dEL: regeneration will start at the delayed time upon switch closure.
HOLD REGEN: regeneration will not be allowed as long as there is switch closure.
SYSTEM SETUP 10A
SYSTEM SETUP 10B
SYSTEM SETUP 11
SYSTEM SETUP 10A
Select meter type, meter pulses or system pulses.
2.0 meter (type)
3.0 meter (type)
Meter Pulses (used on single units for non-Clack meters)
System Pulses (used on two unit systems that share one meter)
SYSTEM SETUP 10B
Select meter type pulses.
Screen does not show if Pulses or System Pulses is not selected in
the previous screen.
SYSTEM SETUP 11
Separate source inlet. This screen will not display if a system board is not installed.
One System Board is required and 2 Motorized Alternating Valves (MAV) are needed. One will be used on
the inlet water supply to alternate between the raw water supply and the separate source regeneration water
supply. The other MAV will be used on the outlet to create No Hard Water Bypass. Refer to wiring diagrams
for proper connections.
Return To
Normal Operation
Page 27
WS2H and WS3 Programming and Wiring Manual Page 27
Cycle Setup Screens
Returns to normal operation after 5 minutes.
Accessed by pressing NEXT and DOWN simultaneously for >3 seconds,
then by pressing NEXT and DOWN simultaneously again for >3 seconds,
then by pressing NEXT and DOWN simultaneously for >3 seconds a third time.
Available Cycles
Backwash
CYCLE SETUP 1A
CYCLE SETUP 1A
Select fi rst cycle.
Draw
Slow RinseSeparate cycle from Draw
2nd Backwash
Rinse (fast)
Fill
End
HoldPiston in Service position
CYCLE SETUP 1B
CYCLE SETUP 1C
CYCLE SETUP 1B
Select second cycle.
CYCLE SETUP 1C
After cycles are confi gured, an END is added.
(9 cycles maximum.)
Cycle #
1Backwash
2Draw
32nd Backwash
4Rinse
5Fill
6End
Cycle
Default
Page 28
Page 28 WS2H and WS3 Programming and Wiring Manual
Cycle Setup Screens (continued)
CYCLE SETUP 2
CYCLE SETUP 3A
CYCLE SETUP 3B
CYCLE SETUP 2
Select regeneration repeats, 1-10 or OFF.
Repeats regeneration cycle Sequence 1 a selected number
of times before regenerating a single time with Sequence 2.
The following screens only show if the unit is
programmed for multiple regenerations in the
previous screen.
CYCLE SETUP 3A
Select fi rst cycle of “alternate” regeneration sequence (Sequence 2).
CYCLE SETUP 3B
Select second cycle of ‘alternate’ regeneration sequence.
Return To
Normal Operation
CYCLE SETUP 3C
CYCLE SETUP 3C
After cycles are confi gured, an END is added.
(9 cycles maximum.)
Page 29
WS2H and WS3 Programming and Wiring Manual Page 29
Timer Screens
Returns to normal operation after 5 minutes.
Accessed by pressing NEXT and DOWN simultaneously
for >3 seconds, then by pressing NEXT and DOWN
simultaneously again for >3 seconds.
“1” is displayed if
set for more than
one sequence
TIMER 1A
TIMER 1B
TIMER 1A2
TIMER 1A
Select time of cycle 1.
A NEXT & DN reset from
this screen unlocks the
setup screens.
TIMER 1B
Select time of cycle 2.
The following screens only show if the unit is
programmed for multiple regenerations in the
Cycle Setup 2 screen.
TIMER 1A2
Select time of alternate regen, cycle 1.
CycleUnitsRangeIncrements
BackwashMinutes
DrawMinutes
Slow RinseMinutes
RinseMinutes
FillMinutes
HoldMinutes
1-30
30-95
1-30
30-100
100-180
1-30
30-95
1-30
30-95
0.1-10.0
10.0-30.0
30.0-99.0
1-30
30-100
100-480
1
5
1
5
10
1
5
1
5
0.1
0.2
1.0
0.1
2.0
10.0
TIMER 1B2
TIMER 1B2
Select time of alternate regen, cycle 2.
Page 30
Page 30 WS2H and WS3 Programming and Wiring Manual
Timer Screens (continued)
TIMER 2
TIMER 2
TIMER 3
TIMER 4
TIMER 2
Set output for Relay 1.
These settings will only be allowed with the system board installed.
Time: Relay is activated after specifi ed time from the start of regen and is left on for a specifi ed time.
Cycle: Relay is activated after the start of a specifi ed cycle and is left on for a specifi ed time.
Volume: Relay is activated, during service fl ow only, every specifi ed number of volume units and is left on for a specifi ed time.
Volume & Regen: Relay is activated every specifi ed number of volume units, and is left on for a specifi ed time.
Volume & System: This option, only available on master units, would calculate relay actuation based on system fl ow, monitoring all
units current fl ow rate.Day & Gal: Relay actuates at specifi ed daily volume & “Usage High” is displayed on the screen. Pressing any button resets relay and
returns unit to user screens.
Day & Gal & System: Only available on the master unit. Relay actuates after a specifi ed daily volume is used by the system &
“Usage High” fl ashes on the screen. Pressing any button resets relay and returns unit to user Screens.
STbY: Relay would be used to control external valving, closing for unit regeneration, or when it would be offl ine in system operation.
REGEN: Relay is activated when the unit is in regen.
Err: Relay is activated when the unit is in any error mode.
TIMER 3
Set output for Relay 2.
These settings will only be allowed with the system board installed.
Time: Relay is activated after specifi ed time from the start of regen and is left on for a specifi ed time.
Cycle: Relay is activated after the start of a specifi ed cycle and is left on for a specifi ed time.
Volume: Relay is activated, during service fl ow only, every specifi ed number of volume units and is left on for a specifi ed time.
Volume & Regen: Relay is activated every specifi ed number of volume units, and is left on for a specifi ed time.
Volume & System: This option, only available on master units, would calculate relay actuation based on system fl ow, monitoring all
units current fl ow rate.Day & Gal: Relay actuates at specifi ed daily volume & “Usage High” is displayed on the screen. Pressing any button resets relay and
returns unit to user screens.
Day & Gal & System: Only available on the master unit. Relay actuates after a specifi ed daily volume is used by the system &
“Usage High” fl ashes on the screen. Pressing any button resets relay and returns unit to user Screens.
STbY: Relay would be used to control external valving, closing for unit regeneration, or when it would be of
REGEN: Relay is activated when the unit is in regen.
Err: Relay is activated when the unit is in any error mode.
TIMER 4
Select Relay 1 output “ON” trigger set point, per units previously selected.
This screen will not display if the unit does not have a system board, or if STbY was selected as the trigger.
Time: Time after the start of a regen before relay is activated.
Cycle: Select a cycle which will actuate output 1.
Volume: Volume of water interval during service between relay actuations.
Timer 4 and 6 screens will not display if display if STbY, REGEN or Err are selected in TIMER 2 and TIMER 3.
fl ine in system operation.
TIMER 5
TIMER 6
TIMER 7
Return To
Normal Operation.
TIMER 5
Set duration of how long Relay 1 output will be on before
turning “OFF.” This screen will not display if the unit does not
have a system board.
TIMER 6
Select Relay 2 output “ON”, per units previously selected.
This screen will not display if the unit does not have a system board, or
if STby was selected as the trigger
Time: Time after the start of a regen before relay is actuated.
Cycle: Select a cycle which will actuate output 1.
Volume: Volume of water interval during service between relay
actuations.
TIMER 7
Set duration of how long Relay 2 output will be on before turning “OFF.”
This screen will not display if the unit does not have a system board.
Page 31
WS2H and WS3 Programming and Wiring Manual Page 31
Installer Setup Screens
Accessed by pressing NEXT and
UP simultaneously for >3 seconds.
Set current day and regen days
when set as a 7 day time clock
or hybrid in System Setup 1.
INSTALLER 1
INSTALLER 2 INSTALLER 2
INSTALLER 3
Returns to normal operation after 5 minutes.
INSTALLER 1
Set volumetric capacity or OFF. OFF will not be an
option if the day control is set to OFF.
X1000 Indicator Illuminates At 10,000 Gallons
Units
US
(GAL)
SI
(L)
INSTALLER 2
Set day override. 1-28 days between regenerations, or if set
to 7 day time clock, see 7 day setup below. OFF will only be
displayed if “OFF” is selected in System Setup Screen 6.
INSTALLER 3
Select time of regen. Use up and down arrows to scroll
hours. AM/PM alternates at midnight. “on0” will be
displayed on units with no time dependent regen control.
(“1” only shows if set for multiple regens.)
RangeIncrements
10-10,000
10,000-100.00 x 1000
100.00-999.00 x 1000
50-50,000
50,000-50.00 x 1000
500.00-5000.0 x 1000
10
100
1000
50
50
5000
Return To
Normal Operation.
INSTALLER 4
7 Day Option
INSTALLER 2A
INSTALLER 2B
INSTALLER 2C
INSTALLER 4
Select time of regen. Use up and
down arrows to scroll minutes.
INSTALLER 5
INSTALLER 5
Select time of 2nd regen
(if confi gured as a multiple
regenerating unit.)
INSTALLER 2A
7 day time clock option.
Set current day of the week:
Scroll through days 1-7 using the UP and DOWN arrows.
Pressing the Set Clock will toggle regen ON or OFF for
that day. (i.e., regen on Monday.)
INSTALLER 2C
(i.e., no regeneration on Saturday.)
Installer 3
Page 32
Page 32 WS2H and WS3 Programming and Wiring Manual
Diagnostic Screens
Accessed by pressing UP and DOWN
simultaneously for >3 seconds.
DIAGNOSTIC 1
DIAGNOSTIC 2
DIAGNOSTIC 3
Returns to normal operation after 5 minutes.
DIAGNOSTICS 1
Days since the last regeneration.
DIAGNOSTICS 2
Gallons or Liters x1000 since the last
regeneration.
DIAGNOSTICS 3
Reserve history. This screen only appears if valve
is set to calculate Reserve in System Setup 8.
Use arrows to select a day.
0 = Today
1 = Yesterday
6 = 6 days ago (max.)
All Diagnostic History screens are resettable
with the History Reset sequence while in the
Diagnostics 1 screen. Holding the Set Clock
and Regen buttons for > 3 seconds initiates a
totalizer or history reset.
Reserve Value
DIAGNOSTIC 4A
Automatically Toggles
DIAGNOSTICS 4A
History of volume used.
Use UP and DOWN arrows to select a day.
0 = Today
1 = Yesterday
63 = 63 days ago (max.)
Automatically Toggles
Simultaneously press
UP and DOWN.
DIAGNOSTIC 4B
Returns user back to USE Day 0 in Diagnostic 4 screen.
DIAGNOSTICS 4B
Hourly history of volume use. Use
the UP and DOWN arrow to select
the hours of the day from screen 4.
Automatically Toggles
REGEN will display if a
regeneration occurred that day.
Gallons Used
Volume used within the selected hour
Page 33
WS2H and WS3 Programming and Wiring Manual Page 33
Diagnostic Screens (continued)
DIAGNOSTIC 5A
DIAGNOSTIC 6
DIAGNOSTICS 5A
Maximum fl ow rate
for the last 28 days.
Automatically Toggles
Simultaneously press
UP and DOWN.
DIAGNOSTIC 5B
Returns back to Day 0 in Diagnostic 5 screen.
DIAGNOSTICS 6
Total volume through the unit.
Max fl ow rate of the day
DIAGNOSTICS 5B
Hourly history of maximum
fl ow rate. Use the UP and
DOWN arrow to select the
hours of the day from screen 5.
Automatically Toggles
Max fl ow within the selected hour
DIAGNOSTIC 7A
DIAGNOSTIC 8
DIAGNOSTICS 7A
Total system history of volume used use
UP and DOWN arrows to select a day.
0 = Today
1 = Yesterday
63 = 63 days ago (max.)
Automatically Toggles
Simultaneously press
UP and DOWN.
DIAGNOSTIC 7B
Returns user back to System USE Day 0 in Diagnostic 7 screen.
Automatically Toggles
DIAGNOSTICS 7B
Total system hourly history of
volume use Up and Down arrow
to select the hours of the day
from Screen 7.
Automatically Toggles
DIAGNOSTICS 8
Error log. Use UP & DN
arrows to scroll through the
last 20 errors.
Return To
Normal Operation
Page 34
Page 34 WS2H and WS3 Programming and Wiring Manual
Valve History
Returns to normal operation after 5 minutes.
Non-Resettable
Accessed by pressing UP and DOWN simultaneously
for >3 seconds, then by pressing UP and DOWN
simultaneously again for >3 seconds.
HISTORY 1
HISTORY 1
Total days since startup.
Time only accumulates while
the unit is plugged in.
HISTORY 2
HISTORY 3
HISTORY 4
HISTORY 2
Total regenerations since startup.
HISTORY 3
Total volume since startup.
HISTORY 4
Main board fi rmware revision.
Return To
Normal Operation
HISTORY 5
HISTORY 5
System board fi rmware revision. Will display -nA- if
no system board is detected.
Page 35
WS2H and WS3 Programming and Wiring Manual Page 35
Page 36
Page 36 WS2H and WS3 Programming and Wiring Manual
Revision History:
6/11/2010
PAGE 4:
Table 1
Output Voltage 20V or 24V AC see Table 2
PAGE 5:
Added Table 2
PAGE 6:
Added:
Medium Reset
From User 1 Screen - Volume Remaining
Press and hold the Set Clock and Regen buttons for 10 seconds to reset valve
to factory default programming. History and Diagnostics are not changed.
See Table 2 Software and Power Supply Compatibility.
b. Pin 1 = AC from power supply (White)Pin 2 = Jumper to Pin 3Pin 3 = Jumper to Pin 2Pin 4 = AV from power supply (Black)
PAGE 7:
Layout drawing revised.
PAGE 8:
Wiring drawing revised
PAGE 9:
System board drawing revised.
PAGE 10-18:
Revised drawings for Poppet MAV setups.
5/20/2010
PAGE 12:
change four pin to three pin
PAGE 13:
change four pin to three pin
PAGE 14:
• The communication cable needs to be connected to Unit 1’s three pin connection labeled “MASTER/SLAVE” and Unit 2’s three
pin connection labeled “MASTER/SLAVE”
PAGE 15:
change four pin to three pin
PAGE 16:
change four pin to three pin
PAGE 17:
change four pin to three pin
PAGE 18:
change four pin to three pin
Form No. V3215-10 – 5/20/2011
U.S. Patents: 6,402,944 • 6,444,127 • 6,776,901
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.