C&K systems SYS3316RF Installation Instructions Manual

16.5 VAC
25 - 40 VA
50-60 Hz
Protected by Fuse F2: 3 AG, 0.75 A Shared with keypads and AUX Power
AUX POWER
KEYPAD INFORMATION
Do not exceed 4 keypads or max AUX POWER Protected by Fuse F3: 3 AG, 0.75 A
REDRED
REDRED
RED
BLKBLK
BLKBLK
BLK
BATTERYBATTERY
BATTERYBATTERY
BATTERY
Capacity forCapacity for
Capacity forCapacity for
Capacity for emergencyemergency
emergencyemergency
emergency standby atstandby at
standby atstandby at
standby at least 4 hoursleast 4 hours
least 4 hoursleast 4 hours
least 4 hours
CAUTION: Total power from Terminals 3, 5, 7, and 8 NOT to exceed 750 mA, combined.
NOTE: Z7 and Z8 must be wired manually to the panel.
All ratings listed on this page are in compli­ance with UL 985, UL 1023, and UL 1635.
DIRECT
CONNECT
WATCH
DOG
DS1DS1
DS1DS1
DS1
WARNING: Circuit
Damage May Result From Incorrect Wiring Connections.
Red = incoming ring Green = incoming tip Gray = seized ring Brown = seized tip Blue = tamper Orange = tamper
WARNINGS:WARNINGS:
WARNINGS:WARNINGS:
WARNINGS: For continued protectionFor continued protection
For continued protectionFor continued protection
For continued protection against risk of fire,against risk of fire,
against risk of fire,against risk of fire,
against risk of fire, replace fuses only withreplace fuses only with
replace fuses only withreplace fuses only with
replace fuses only with fuses of same type andfuses of same type and
fuses of same type andfuses of same type and
fuses of same type and ratingrating
ratingrating
rating
PHONE CORDSPHONE CORDS
PHONE CORDSPHONE CORDS
PHONE CORDS
Use either:
- 9.X PCF
- 9.X PCP
U14U14
U14U14
U14
U6U6
U6U6
U6
F1 2.5A
BELL FUSE
F2 0.75A
AUX DEVICES
F3 0.75A
KEYPAD
SN913-I/O PROTECTED BY FUSE F2: 3AG, 0.75A
P/N 5-051-396-00 Rev AP/N 5-051-396-00 Rev A
P/N 5-051-396-00 Rev AP/N 5-051-396-00 Rev A
P/N 5-051-396-00 Rev A
- All outputs are power limited
- Connect ground wire from door hinge to earth ground using 16 AWG, green jacketed, solid-conductor wire
- If programmed for EOL or Supervised loop, the 2.2K ohm EOL resistor (Model 9.X, 2.2K) must be at end of circuit
GENERAL INFORMATIONGENERAL INFORMATION
GENERAL INFORMATIONGENERAL INFORMATION
GENERAL INFORMATION
- Loop voltages:
- Loop 8 can be used as standard loop or used for switched 10-
12.5 VDC at 50 mA for 2-wire powered devices. Loop 8 can support up to 10 BRK Model 2400 2-wire smoke detectors.
Loop 7
0 - 2 VDC = short 2 - 3 VDC = normal 3 - 5 VDC = open
Loop 8
0 - 2.5 VDC = short
2.5 - 8.5 VDC = normal
8.5 - 15 VDC = open
- SN913-I/O card requires 2.2 K ohm resistor (P/N 5-162-024-00)
- are electrically common
4 3 2 1
S1
TX GND V+ RX
ON
SWITCHED
AUX POWER
10 - 12 VDC Protected by
Fuse F2:
3 AG, 0.75 A
12 VDC
6.5 AH or 9.5 AH sealed lead-acid
POWER SUPPLY INFORMATION
- For non-Cal-Fire requirements, only use 12 VDC, 6.5 AH sealed lead-acid battery, C&K Model #1265.
- For Cal-Fire Installations, use 12 VDC, 9.5 AH, sealed lead-acid battery, C&K Model 1295.
- Replace battery every 3 - 5 years with C&K Model 1265 or 1295.
- Power demand for AUX POWER, keypads, and sounders not to exceed maximum ratings.
- Install transformer (C&K Model 1097-B) on unswitched power recepticle.
- Remove AC and battery power before replacing fuses.
- Maximum battery charge current = 350 mA.
- Standby battery time table with 1 Alpha keypad:
Battery Time Current
6.5 AH 7.5 Hrs. 500 mA 12 Hrs. 200 mA
9.5 AH 12 Hrs. 450 mA 24 Hrs. 56 mA
SYS3316RF Installation InstructionsSYS3316RF Installation Instructions
SYS3316RF Installation InstructionsSYS3316RF Installation Instructions
SYS3316RF Installation Instructions
AUDIBLE
10.5-13.5 VDC
Protected by Fuse
F1: 3AG, 2.5 A
Fuse F4 3 AG,
3 A battery
protection
SYS3316RF Installation Manual
Table of Contents
Subject Page No.
SYS3316RF Terminal Label Front Cover UL Compliance 2 Installation 2 Wiring the Panel 3 - 4 System Start-Up 4 Keypad Setup 4 - 5 Addressing Keypads 5 Factory Default Settings 5 Programming Options (Alphabetical List) 5 - 6 Programming the Panel 6 - 7
Programming with the LED Keypad 6 Programming with the Alpha Keypad 6 Entering Hexidecimal Numbers 6
Programming the Alpha Keypad 7
Programming Letters & Numbers 7
Special Function Keys 7 Programming Options (Numerical Order) 8 - 19 Keypad Label Drawer 20 Telephone Line Problems 20 Watchdog Indicator 20 FCC Notice / Industry Canada 20 Keypad Operation Command Summary 21 Help with Common Problems (Troubleshooting) 22 - 23 Reducing False Alarms 24 - 25 Warranty Information 26 Programming Worksheets 27 - 30
BEFORE YOU STARTBEFORE YOU START
BEFORE YOU START
BEFORE YOU STARTBEFORE YOU START
Introduction
The SYS3316RF is a fully-programmable 16-zone control panel. It can be programmed from the Alpha or LED keypad or remotely via the COM­MANDER II/MONITOR II software package.
Scope of This Manual
This manual contains basic installation and programming information for the SYS3316RF. For additional information about remote programming, please refer to the Commander II/Monitor II Operating Manual.
Accuracy
This manual has been carefully checked for accuracy. However, C&K SYSTEMS assumes no liability for inaccuracies or actions resulting from the use of this manual. In addition, C&K reserves the right to modify the SYS3316RF hardware, software, and manuals without prior notice.
UL Compliance (continued)
8. The Dynamic Battery Test must be enabled.
9. The Unit Status Report must be enabled.
10.The 24-hour Check-in must be enabled.
11.The unit must not be programmed to dial a police station.
12.Use screws (supplied) to secure cover or a lock must be installed on the cabinet.
13.All devices must be UL listed.
Zone Programming
FIRE LOOP
.
24-hour arming
.
Pulsing audible
.
Supervised
- latching for heat
- resetting for smoke
.
Not shuntable
INSTALLATIONINSTALLATION
INSTALLATION
INSTALLATIONINSTALLATION
Mounting
The SYS3316RF should be mounted in a location which allows convenient access to AC power, telephone connections, and earth ground.
.
Remove the SN913-I/O from its card cage and the control panel circuit board from the cabinet. This will prevent possible damage to the circuit boards when removing the knock-outs.
.
Remove the knock-outs.
.
Mark the screw mounting holes on the wall.
.
Mount the cabinet at the desired height and pass the cables through the knock-outs.
.
Replace the circuit boards, remembering to connect the ground lug to the lower left corner of the control panel circuit board.
.
Reconnect the spade lug to the lower door hinge. This provides the earth ground connection for the door.
Earth Ground
To ensure the effectiveness of the lightning and transient protection circuits, the control panel must be connected to "Earth Ground". Ideally, this should be a common ground to the power lines, telephone system, and security system. This type of ground, called a "Unified Earth Ground", provides the best protection. The ground connection, from a grounding rod, cold water pipe or other established ground point, is made to the green jacketed wire providing a ground to the panel housing.
BURGLAR LOOP
.
Steady Audible
.
NO/NC with EOL
UL COMPLIANCEUL COMPLIANCE
UL COMPLIANCE
UL COMPLIANCEUL COMPLIANCE
The SYS3316RF is in compliance with Underwriters Laboratories, Inc. Standards UL 985, Household Warning System Units; UL 1023, House­hold Burglar Alarm System Units; and UL 1635, Digital Burglar Alarm Communicator System Units. The following programming restrictions must be observed to meet UL standards.
1. The audible must be programmed to sound at least four minutes before silencing.
2. No zone may be programmed for silent alarm.
3. Fire zones must be programmed for pulsing audible alarm.
4. Burglar zones must be programmed for a steady audible.
5. Burglar loops (non-24-hour loops) must be programmed for NO/NC.
6. No Entry Delay may be greater than 45 seconds.
7. No Exit Delay may be greater than 60 seconds.
Power Lines
Power Line Earth Ground
Unified Earth Ground
with Bonded Ground Roots
Control Panel
Telephone Earth Ground
Telephone Lines
FIGURE 1 Unified Earth Ground
2
SYS3316RF Installation Manual
WIRINGWIRING
WIRING
Standby Battery
The SYS3316RF is designed to operate with a 12-volt, 6.5 AH, sealed lead-acid battery (C&K Model 1265)**. Do not use non-rechargeable batteries or batteries other than sealed lead-acid. It is recommended
that you replace the standby battery every three to five years.
Connect the red lead to the positive terminal of the battery and the black lead to the negative battery terminal. The battery is reverse-polarity protected by a 3 amp, 3 AG, fast-blow fuse (F4).
**To comply with CAL-FIRE requirements for 24-hour standby, a 12 VDC, 9.5 A-H, sealed lead-acid battery must be connected in place of the 6.5 AH battery. Use C&K Model 1295 Battery.
AC POWERAC POWER
AC POWER
AC POWERAC POWER
AC power is supplied by a 16.5 VAC, 25 - 40 VA transformer at 50 or 60 Hz. A UL listed Class 2 transformer (such as the C&K Model 1097-B) must be used. Connect the transformer secondary to termi­nals 1 and 2. Use at least 18 AWG (1.02 mm) wire to
reduce voltage drops. The transformer primary must be connected to
an unswitched receptacle. Do not connect primary to Ground-Fault­Interrupt (GFI) circuits. Secure the transformer to the wall.
PrecautionsPrecautions
Precautions
PrecautionsPrecautions
DO NOT share the secondary of the transformer with other devices. A foreign ground can damage the power supply, voiding the warranty.
DO NOT use any transformer other than that specified in the AC POWER section above.
AC Power Failure
If an AC power failure lasts more than 15 minutes, the keypads will display a system trouble. An AC failure report will be sent, if programmed. When AC is restored for five minutes, a restoral report will be sent.
Available Power
The maximum total power available from the Audible, AUX (Switched and Unswitched), and Keypad Terminals (terminals 3, 5, 7, and 8) is 750 mA. The Switched Aux, Unswitched Aux, Receiver/Interface Board and Keypads Terminals share the same power bus. Combined power for these outputs should not exceed 500 mA.
WIRINGWIRING
Terminals 1 and 2
AUXILIARY POWERAUXILIARY POWER
AUXILIARY POWER
AUXILIARY POWERAUXILIARY POWER
Terminals 5 and 7 provide positive 10 - 12.5 VDC power. Terminal 5 is used for devices that require switched power for resetting. Typical devices are glass-breaks and smoke de­tectors. Terminal 6 provides the common for Switched AUX, Unswitched AUX, and Keypad power. The SN913-I/O Inter­face Board is connected to terminals 6 and 7 at the factory.
Fuse F2
Terminals 5 and 7 (AUX POWER) are protected by a 0.75 amp, 3 AG, fast­blow fuse (F2).
ARMING STATIONSARMING STATIONS
ARMING STATIONS
ARMING STATIONSARMING STATIONS
Terminal 6 (black) is common. Terminal 8 (red) provides 11 - 14 VDC keypad
power. Terminal 9 (green) is data from the keypad to the
panel.
Maximum wire length for connecting any keypad is 500' (152 m) of 22 AWG (0.643 mm) copper wire.
The SYS3316RF is capable of addressing up to 16 keypads (8 Alpha II and 8 LED). Each LED keypad uses 35 mA of current. Each LCD (Alpha) keypad uses 64 mA of current. See Available Power for current limita­tions. See page 4 for additional information on keypad setup.
Fuse F3
Terminal 8 (keypad power) is protected by a 0.75 amp, 3 AG, fast-blow fuse (F3).
LOOP INPUTSLOOP INPUTS
LOOP INPUTS
LOOP INPUTSLOOP INPUTS
EOL Loop
N.C.
++
+
++
Alarm
N.O.
Alarm
SYSTEM 3316 Loops Terminals
--
-
--
Loop 7 0 - 2 VDC = short 2 - 3 VDC = normal 3 - 5 VDC = open
Loop 8 0 - 2.5 VDC = short
2.5 - 8.5 VDC = normal
8.5 - 15 VDC = open
Terminals 5, 6, and 7
Terminals 6, 8, and 9
Terminals 19, 20, and 21
Two loops may be independently configured through programming. Loops can be wired with an open circuit switch, closed circuit switch, or with a 2.2K-ohm end-of-line (EOL) resistor.
When programmed as an EOL cir­cuit, either an open or a short will be reported as an alarm if the system is in an armed state.
AUDIBLE OUTPUTAUDIBLE OUTPUT
AUDIBLE OUTPUT
AUDIBLE OUTPUTAUDIBLE OUTPUT
Terminal 3 provides up to 0.75 Amps at 10.5 - 13.5 VDC. The type of voltage (steady, pulsed, or chirp) and the time is programmable.
Fuse F1
Terminal 3 is protected by a 2.5 Amp, 3 AG fast-blow fuse (F1).
If any fuse opens, remove AC and DC power, remove the
NOTE:
short or overload condition, then replace the fuse before restoring power. Do not substitute a higher rated fuse.
Electromagnetic Interference
Vibrating horns and bells can produce electromagnetic interference (EMI). While EMI will not damage the SYS3316RF, it can cause trans­mission errors and mis-dialing. To minimize EMI, install a 0.01 mfd, 100 volt capacitor across the terminals of the horn or bell. The capacitor must be located at the source of the EMI (horn or bell).
Terminals 3 and 4
Supervised Loop
N.C.
++
+
++
Alarm
N.O.
Alarm
--
-
--
SYSTEM 3316 Loops Terminals
Pre-wired Loops
Loops 1 - 6 and 9 - 16 are pre-wired to the SN913-I/O Interface Board and are configured as supervised loops for use with the WIRELESS transmitters. EOL resistors for these loops are installed on the SN913­I/O Interface Board.
Loop 8
The terminals for zone 8 (20 and 21) are a standard loop that can also power 2-wire devices. The loop supplies 10 - 12.5 VDC at 50 mA. Use Loop 8 to power 2-wire glass-breaks and smoke detectors. The 50 mA on Loop 8 is part of the 500 mA AUX Power.
3
When operated as a Supervised Loop, an open will be reported as a Trouble, whether the system is armed or disarmed. A short on a Supervised Loop is reported as an alarm if the system is armed, but will have no effect if the system is disarmed.
SYS3316RF Installation Manual
TAMPER SWITCH INSTALLATIONTAMPER SWITCH INSTALLATION
TAMPER SWITCH INSTALLATION
TAMPER SWITCH INSTALLATIONTAMPER SWITCH INSTALLATION C&K has designed the SYS3316RF cabinet to use the Ademco Model
19 tamper switch. The cabinet is constructed in order to accommodate
two switches. One tamper for the cover and a second switch for a wall tamper. To install the tamper switches:
Position the tamper switch inside the cabinet at the lower right corner
1. of the cabinet. For the wall tamper, the plunger should go through the small hole in the back of the cabinet. For the door tamper, the plunger should face out from the cabinet. Refer to the drawing below.
Connect the tamper switches in series and wire the tamper terminals
2.
to a dedicated zone of the control panel.
3.
Program the dedicated zone as desired: NC, EOL, 24-hour, etc.
Once the tamper switches are installed, opening the cabinet door or removing the cabinet from the wall will result in a tamper signal at the panel.
Tamper Switches installed in the SYS3316RF cabinet
PRINTED CIRCUITPRINTED CIRCUIT
PRINTED CIRCUIT
PRINTED CIRCUITPRINTED CIRCUIT BOARDBOARD
BOARD
BOARDBOARD
SN913SN913
SN913
SN913SN913
I/OI/O
I/O
I/OI/O
9.X PCF
The 9.X PCF has eight flying leads on the other end. Wire them to the phone line terminals as follows:
RED = ring BROWN = tip seized GREEN = tip BLUE and ORANGE = tamper
YELLOW and BLACK = not usedGRAY = ring seized
SYSTEM START-UP
Five minutes after the panel is powered up, it will dynamically test the standby battery by interrupting AC power for two minutes and monitoring the battery under load.
If you replace the battery after a SYSTEM TROUBLE - LOW BATTERY message, you must test the battery under load conditions. Press [*] [6] [4] [#] to start the Dynamic Battery Test.
Voltage Variations
Output voltages at terminals 5, 7, and 8 may vary from 9.0 to 14.4 VDC (worst case), depending on the load, battery condition, and AC line voltage.
KEYPAD SETUP
TB1TB1
TB1
TB1TB1
6.5 A-H6.5 A-H
6.5 A-H
6.5 A-H6.5 A-H oror
or
oror
9.5 AH9.5 AH
9.5 AH
9.5 AH9.5 AH
LEAD-ACIDLEAD-ACID
LEAD-ACID
LEAD-ACIDLEAD-ACID
BATTERYBATTERY
BATTERY
BATTERYBATTERY
TELEPHONE INTERFACE
Connect the SYS3316RF to the phone line using the
9.X PCP or 9.X PCF cord (not included). Each of the cords has an 8-pin telco plug on one end. Plug this end of the cord into J1 at the lower right corner of the PCB. Connect the other end as outlined below:
R1 = Seized Ring
T1 = Seized Tip
1
R1
T1
876
House
Phones
DOORDOOR
DOOR
DOORDOOR TAMPER SWITCHTAMPER SWITCH
TAMPER SWITCH
TAMPER SWITCHTAMPER SWITCH
WALLWALL
WALL
WALLWALL TAMPER SWITCHTAMPER SWITCH
TAMPER SWITCH
TAMPER SWITCHTAMPER SWITCH
Control Panel Telco Jack (J1)
23
4
Red
Green
5
Tamper Jumper
Protector
Ring
Tip
RJ-38X Wiring Diagram
Incoming
Telco Line
ALPHA II KEYPAD INFORMATION
The Alpha II keypad uses a top viewing display. This means the display reads most clearly when viewed from a top angle rather than straight on or from below. Mounting the keypad at light switch level and adjusting the viewing angle gives the best results.
Adjusting the LCD Display
To adjust the viewing angle, remove the keypad from the back mounting plate. Towards the bottom center of the circuit board is a small hole. Insert a small screwdriver into the hole and adjust R23 for optimum viewing, while holding the keypad at its mounting height.
ADDRESSING KEYPADS
Each Alpha II and LED keypad installed in the system must have an address. Addresses must not be repeated. When replacing a keypad, make sure the replacement has the same address as the previous keypad. Once all keypads have been addressed, reset the panel by
pressing [Master Combination] [*] [6] [8] [#] or by removing and restoring both AC and DC power.
Addressing Alpha II Keypads
The first time you power up the system, unaddressed Alpha II keypads will display KEYPAD ADDRESS?. Press any number from 0 through 7 at each keypad. The exact number you press is not important, as long as each keypad has a different address number. The keypad will not accept values outside of this range. Should you accidentally use the same address for more than one keypad, the system will fail to properly respond to keypad input. Refer to page 23 for assistance in correcting this problem.
Addressing LED Keypads
The LED keypad also requires an address. The address on the LED keypad is set by the three hook switches on the LED keypad's PCB.
Hook switches SW1, SW2, and SW3 are used to set the address of LED keypads. Refer to the chart at the top of page 5.
4
HOOKHOOK
HOOK
HOOKHOOK
SWITCHESSWITCHES
SWITCHES
SWITCHESSWITCHES
SW1SW1
SW1
SW1SW1 SW2SW2
SW2
SW2SW2 SW3SW3
SW3
SW3SW3
J1J1
J1
J1J1 J2J2
J2
J2J2
SW1SW1
SW1
SW1SW1
Closed Closed Closed Closed Open Open Open Open
LED Keypad Backlighting
Hook switch J1 controls the LED keypad's backlighting. When J1 is closed (default setting), the backlighting will be enabled. Open J1 to disable the backlighting.
LED Keypad Piezo
Hook switch J2 controls the LED keypad's piezo audible. When J2 is closed (default setting), the piezo is enabled. Open J2 to disable the piezo.
DEFAULT PROGRAM SETUP
The default programming of the SYS3316RF will allow you to operate it as a local panel without any additional programming. The actual default programming values are shown on the Programming Worksheet (last 4 pages of this manual).
Note: If you connect power before wiring the loops, install a
2.2K-ohm EOL resistor across each loop.
Any address from 8 to 15 can be used. The exact number is not important, as long as each LED keypad in the system has a different address number. Should you accidentally use the same address for more than one keypad, the system will fail to respond to keypad input. Refer to page 23 (Alpha II keypads with same addresses) for assistance in correcting this problem.
SW2SW2
SW2
SW2SW2
Closed Closed Open Open Closed Closed Open Open
FACTORY SETTINGSFACTORY SETTINGS
FACTORY SETTINGS
FACTORY SETTINGSFACTORY SETTINGS
SW3SW3
SW3
SW3SW3
Closed Open Closed Open Closed Open Closed Open
KEYPAD ADDRESSKEYPAD ADDRESS
KEYPAD ADDRESS
KEYPAD ADDRESSKEYPAD ADDRESS
88
8
88 99
9
99 1010
10
1010 1111
11
1111 1212
12
1212 1313
13
1313 1414
14
1414 1515
15
1515
Combinations
Installer combination: 0 1 2 3 4 5 User #1 (Master) combination: 1 2 3 4 Users #2 - 32: disabled Default installer combination: yes Guest combination: no Combination required: no Faulted Arming type: goof-proof Opening/Closing: no Users authorized to send reports Duress: disabled
Reporting
Account #1 and #2: disabled Dialing type: pulse RPS allowed: yes
Zones
Zone 1 = Entry/Exit delay - SUPERVISED EOL circuit Zone 2 = doors or windows - SUPERVISED EOL circuit Zone 3 = doors or windows - SUPERVISED EOL circuit Zone 4 = doors or windows - SUPERVISED EOL circuit Zone 5 = doors or windows - SUPERVISED EOL circuit Zone 6 = doors or windows - SUPERVISED EOL circuit Zone 7 = doors or windows - EOL circuit Zone 8 = fire or smoke - supervised EOL circuit
SYS3316RF Installation Manual
Zones (cont.)
Zone 9 = interior - SUPERVISED EOL circuit Zone 10 = interior - SUPERVISED EOL circuit Zone 11 = interior - SUPERVISED EOL circuit Zone 12 = interior - SUPERVISED EOL circuit Zone 13 = interior - SUPERVISED EOL circuit Zone 14 = interior - SUPERVISED EOL circuit Zone 15 = interior - SUPERVISED EOL circuit Zone 16 = interior - SUPERVISED EOL circuit Emergency soft zone: chirp audible, non-reporting Fire soft zone: pulsed audible, non-reporting Police soft zone: steady audible, non-reporting
Testing
Test report interval: 7 days and disabled
Timing
Entry time: 60 seconds and prewarn Exit time: 30 seconds and prewarn Bell time: 5 minutes
Unit Control
Local system: yes Dynamic battery test: off
PROGRAMMING OPTIONSPROGRAMMING OPTIONS
PROGRAMMING OPTIONS
PROGRAMMING OPTIONSPROGRAMMING OPTIONS
The following is an alphabetical listing of all SYS3316RF programming options, including Command Locations and Digit Positions. Digit Posi­tions are inside parentheses ( ). NOTE: All Command Locations are in Hexadecimal.
Option Location
Account #1 0C (1 - 6) Account #2 10 (1 - 6) AC Power Line Frequency 2F (5) Alarm Receiver Select by Loop 1F - 26 & 49 - 50 (1) Alarm Reporting Code by Loop 17 - 1E & 40 - 47 (1 - 2) Audible Time 2D (5) Bell Reverse Operation 2E (3) Cancel Report Code 2A (5) Cancel Report Receiver Select 2A (6) Closing Report Code 2C (3) Closing Report Receiver Select 2C (4) Combination Command 09 (2) Daily Battery Test Enable 2F (2) Default Installer Combination 09 (3) Delay Before Dial by Loop 30 - 3F (4) Delay Before Dial Time 0B (1) Dial Attempts 0B (6) Dial Type 0B (2) Disable Loop LEDs 2E (5) Door Chime Enable by Loop 30 - 3F (1) Duress Report Code 2D (1) Duress Report Receiver 2D (2) Emergency Bell Type 27 (4) Emergency Receiver Select 27 (3) Emergency Report Code 27 (1 - 2) Entry Delay Time 2D (3) Entry Pre-alarm Enable 2E (1) Exit Delay Time 2D (4) Exit Pre-alarm Enable 2E (2) Faulted Arming Type 09 (4) Fire Bell Type 28 (4) Fire Receiver Select 28 (3) Fire Report Code 28 (1 - 2) Four Minute Power Up Delay Enable 2F (3) Group Shunt Enable 30 - 3F (3) Guest Combination 08 (2 - 6) Guest Combination Time 09 (1) Installer Combination 00 (1 - 6)
5
SYS3316RF Installation Manual
OptionOption
Option
OptionOption
Keypad RPS Enable 0B (3) Local System Only 2F (1) Loop Arming Type 1F - 26 & 49 - 50 (4) Loop Bell Type 1F - 26 & 49 - 50 (5) Loop Circuit Type 1F - 26 & 49 - 50 (6) Loop Response Time 1F - 26 & 49 - 50 (2) Loop Restore Type 1F - 26 & 49 - 50 (3) Master Code (User #1) 01 (2 - 6) Opening Report Code 2C (1) Opening Report Receiver 2C (2) Phone Ring Type 0B (5) Police Bell Type 29 (4) Police Receiver Select 29 (3) Police Report Code 29 (1 - 2) Receiver #1 Message Format 0A (2) Receiver #1 Phone Number 0D - 0F (1 - 6) Receiver #1 Receiver Format 0A (1) Receiver #2 Message Format 0A (4) Receiver #2 Phone Number 11 - 13 (1 - 6) Receiver #2 Receiver Format 0A (3) Restore Receiver Select 2A (2) Restore Reporting Code by Loop 17 - 1E & 40 - 47 (3 - 4) Ring Back Enable 2E (4) RPS Enable 0B (4) RPS Phone Number 14 - 16 (1 - 6) Set Test Report Countdown Timer A0 (1) Set Real-Time Clock B3 & B4 (1 - 6) Shunt Enable 30 - 3F (2) Shunt Receiver Select 2A (1) Shunt Reporting Code by Loop 17 - 1E & 40 - 47 (5 - 6) Soft Zone Operation Enable 2F (4) Test Report Code 2B (1 - 2) Test Report Interval 2B (4) Test Report Receiver Select 2B (3) Trouble Report Code 48 (1) Trouble Report Receiver Select 48 (2) Trouble Restore Code 48 (3) Trouble Restore Receiver Select 48 (4) Unit Status Code 2A (3) Unit Status Receiver 2A (4) User Arming Type 01 - 08 & 51 - 68 (1) User Combinations 01 - 08 & 51 - 68 (2 - 6)
PROGRAMMING THE PANELPROGRAMMING THE PANEL
PROGRAMMING THE PANEL
PROGRAMMING THE PANELPROGRAMMING THE PANEL
You can program the SYS3316RF from the LED or LCD keypad, as well as remotely using the COMMANDER II software. Information on remote programming is available in the COMMANDER II/MONITOR II Operating Manual. This installation manual includes a brief description of each programming option beginning on page 8.
Starting Panel Programming
Key in the [Installer Combination] [*] [0] [#]. The default Installer Combina­tion is 0 1 2 3 4 5. When using the SYSTEM 2316 LED keypad, the PROGRAM LED will light steady to indicate programming mode. On the 2316 Plus LED keypad the READY, ARM, and SERVICE LED's will flash to indicate programming mode. The Alpha II keypad will display CMD
DATA across the top of the LCD display to indicate programming mode. Programming with the LED Keypad
Programming with an LED keypad is a one-step process. Key in the two­digit address (Command Location), followed immediately by the desired programming values (program data), then press the [#] key to store the data. The LED keypad does not display any programmed values. If you are not sure that the correct programming values have been entered, program the Command Location again.
LocationLocation
Location
LocationLocation
NOTE: To program Command Locations A0, B3, and B4 with an
LED keypad, remember to enter the Command Location, followed by the program data, then press the [#] key.
Warning: If you enter a Command Location and then press the
[#] key without entering any program data, the key­pad will beep 5 times, indicating an error. To correct this problem, simply re-enter the Command Loca­tion and Data, then press the [#] key.
Programming with the Alpha Keypad
Entering program data with an Alpha keypad is a two-step process. First, key in the two-digit address (Command Location) to be programmed and press the [#] key. The Alpha keypad displays the Command Location and the data previously stored. Enter the new data you wish to store and press the [#] key to write the data. You can also scroll through the Command Locations in numerical order by alternately pressing and releasing the [#] key.
NOTE: Command Location A0 must be addressed directly. When pro-
gramming this Command Location with an Alpha keypad, the previously stored data is not displayed. To program this location, enter the Command Location followed by the [#] key. Then enter the data to be stored and again press the [#] key.
Programming Hexadecimal Numbers
The Alpha keypad may be used to program the control panel. The cursor is moved using the "E" and "P" keys, as indicated in the figure below. The "F" key enters a blank space and moves the cursor one position to the right.
Panel Programming Keys
B 132
E 45 6
789
Data is programmed into the panel using the hexadecimal number system, which consists of the digits 0 - 9 and the letters A - F. The digits 0 - 9 are entered directly from the keypad. The chart below shows how to enter the hexadecimal digits A through F.
PROGRAMMING CONVERSIONSPROGRAMMING CONVERSIONS
PROGRAMMING CONVERSIONS
PROGRAMMING CONVERSIONSPROGRAMMING CONVERSIONS
Hexadecimal ValueHexadecimal Value
Hexadecimal Value
Hexadecimal ValueHexadecimal Value
A B C D E F
The same procedure is used with both the LED and the Alpha keypads.
C
F
A 0
D
Key StrokesKey Strokes
Key Strokes
Key StrokesKey Strokes
0 1 2 3 4 5
6
SYS3316RF Installation Manual
The last two Command Locations are CL 37 and CL A0. Pressing the [#] key at these locations will advance you to CL 38 or CL A1, respectively. Locations CL 38 and CL A1 are not used in the SYS3316RF. If you accidentally enter either of these locations, press [*] [#] to exit program­ming, or enter the Command Location number, followed by the [#] key, for the location you wish to program.
To Exit Panel Programming
When you have finished programming, press [*] [#].
exit the programming mode if you do not press any key within a five minute period.
PROGRAMMING the ALPHA KEYPADPROGRAMMING the ALPHA KEYPAD
PROGRAMMING the ALPHA KEYPAD
PROGRAMMING the ALPHA KEYPADPROGRAMMING the ALPHA KEYPAD
Ensure the Alpha keypad is wired to the SYS3316RF and power is applied to the control panel. You can only access the programming mode when
the control panel is disarmed.
NOTE: Programming the Keypad is not the same as Keypad
Programming.
The panel will also
The Alpha Keypad
You can program the Alpha keypads for special messages, each of the 16 zone labels, and the keypad address. Zone Labels display during the walk-test and when the [#] key is pressed during alarm memory or faults. The programmable Service Message is displayed during AC failure, fuse failure, communication failure, or low battery. The Dealer Message displays when the system is disarmed. The keypad address is initially displayed only during system start up (see page 4, Keypad Addressing).
These messages can be programmed directly from the Alpha keypad or remotely using the Commander II/Monitor II software package. For more detailed information about remote programming, refer to the Commander II/Monitor II Operating Manual.
Keypad Message Programming
The Alpha keypad programming template is used to allow the installer to program messages and zone descriptions into the Alpha keypads. The template shown on the next page should be used when program­ming the keypad.
To activate the keypad progr amming mode, enter the [Installer's Code] [*] [0] [1] [#]. Information may be entered into the keypad in the form of letters (upper and lower case), numbers (0 - 9), and 22 special symbols. All characters are displayed in the order listed above, i.e. upper and lower case letters, numbers, and special symbols. The [Space] char­acter precedes the letter A.
To enter a Message or Label, use the [2] key to scroll through the characters until you reach the desired character. If you scroll past the desired character, the [8] key may be used to scroll backwards. When the desired character is displayed, press the [6] key to move the cursor to the next character position. The [4] key moves the cursor to the left. When all characters have been entered, press the [#] key to write the message and move to the next message position. Use the [0] key to move backward through the messages.
The message order is:
• SERVICE MESSAGE
• DEALER MESSAGE
• SOFT ZONE IDENTIFIERS (A, B, and C)
• HARDWIRED LOOP IDENTIFIERS
• KEYPAD ADDRESS
ALPHA II Programming TemplateALPHA II Programming Template
ALPHA II Programming Template
ALPHA II Programming TemplateALPHA II Programming Template
11
1
11
44
4
44
77
7
77
ALPHA PLUS Programming TemplateALPHA PLUS Programming Template
ALPHA PLUS Programming Template
ALPHA PLUS Programming TemplateALPHA PLUS Programming Template
11
1
11
44
4
44
77
7
77
NOTE: If you do not press any key for 5 minutes, the
keypad will automatically exit the programming mode.
22
2
22
55
5
55
88
8
88
00
0
00
22
2
22
55
5
55
88
8
88
00
0
00
33
3
33
66
6
66
99
9
99
33
3
33
66
6
66
99
9
99
To Exit Keypad Programming
When you have finished programming, press [*] [#].
exit the programming mode if you do not press any key within a five minute period.
The keypad will also
Both the Alpha (shown at the top of the next column) and the Alpha Plus (shown below in the next column) use the same procedure to program messages.
7
SYS3316RF Installation Manual
Command Location 00: Installer CombinationCommand Location 00: Installer Combination
Command Location 00: Installer Combination
Command Location 00: Installer CombinationCommand Location 00: Installer Combination
Default ValuesDefault Values
Default Values
Default ValuesDefault Values
Digit Positions (1) - (6): Installer Combination
Combination must have 6 digits. Valid entries are 0 - 9.
00
00
0
0
00
00
CL 00 - 08 & 51 - 68CL 00 - 08 & 51 - 68
CL 00 - 08 & 51 - 68
CL 00 - 08 & 51 - 68CL 00 - 08 & 51 - 68
012345
(1) (2) (3) (4) (5) (6)
#
Command Location 01 - 08 and 51 - 68:Command Location 01 - 08 and 51 - 68:
Command Location 01 - 08 and 51 - 68:
Command Location 01 - 08 and 51 - 68:Command Location 01 - 08 and 51 - 68:
**Default Values**Default Values
**Default Values
**Default Values**Default Values
01 = User #1 (Master) 02 = User #2 03 = User #3 04 = User #4 05 = User #5 06 = User #6 07 = User #7 08 = User #8 (Guest) 51 = User #9 52 = User #10 53 = User #11 54 = User #12 55 = User #13
Digit Position (1): Arming Type
1 = Arm Only, No Closing (C) Report, No Shunting 2 = Disarm Only, No Opening (O) Report, No Shunting 3 = Arm and Disarm, No O/C Reports, No Shunting
4 = Arm Only, with Closing Report, No Shunting 5 = Disarm Only, with Opening Report, No Shunting 6 = Arm and Disarm, with O/C Reports, No Shunting
7 = Arm Only, No Closing Report, Shunting Allowed 8 = Disarm Only, No Opening Report, Shunting Allowed 9 = Arm and Disarm, No O/C Reports, Shunting Allowed
0 = Arm Only, with Closing Report, Shunting Allowed 1 = Disarm Only, with Opening Report, Shunting Allowed 2 = Arm and Disarm, with O/C Reports, Shunting Allowed
56 = User #14 57 = User #15 58 = User #16 59 = User #17 5A = User #18 5B = User #19 5C = User #20 5D = User #21 5E = User #22 5F = User #23 60 = User #24 61 = User #25 62 = User #26
63 = User #27 64 = User #28 65 = User #29 66 = User #30 67 = User #31 68 = User #32
NOTE: Opening and Closing Reports
User Arming Type and CombinationUser Arming Type and Combination
User Arming Type and Combination
User Arming Type and CombinationUser Arming Type and Combination
91234E
11
00
1
0
11
00
(1) (2) (3) (4) (5) (6)
must be enabled. See CL 2C Digit Positions 1 and 3 for additional information.
#
**Default Values are different for each user. Refer to the SYS3316RF Programming Worksheet at the end of this manual for other user default values.
NOTE: Some programming locations allow
variable-length data and require an End­of-Number (EON) character. Program 4 ("E") after the last digit. Fill remaining unused Positions with "0". The EON character is not required if the last digit is in Position 6.
Digit Positions (2) - (6): Arming Combination (PIN)
Combination may have from 2 - 5 digits. Valid entries are 0 -9.
PROGRAMMING CONVERSIONSPROGRAMMING CONVERSIONS
PROGRAMMING CONVERSIONS
PROGRAMMING CONVERSIONSPROGRAMMING CONVERSIONS
Key StrokesKey Strokes
Key Strokes
Hexadecimal ValueHexadecimal Value
Hexadecimal Value
Hexadecimal ValueHexadecimal Value
A B C D E F
8
Key StrokesKey Strokes
0 1 2 3 4 5
CL 09 and 0ACL 09 and 0A
CL 09 and 0A
CL 09 and 0ACL 09 and 0A
Command Location 09: Arming/Combination OptionsCommand Location 09: Arming/Combination Options
Command Location 09: Arming/Combination Options
Command Location 09: Arming/Combination OptionsCommand Location 09: Arming/Combination Options
Default ValuesDefault Values
Default Values
Default ValuesDefault Values
SYS3316RF Installation Manual
0011
00
99
0
9
00
99
#
Digit Position (1): Guest Combination Time
0 = Guest Time Disabled 1 = 1 day 2 = 2 days 3 = 3 days 4 = 4 days
Digit Position (2): Combination Command
0 = No 1 = Yes; requires combination for Bypass, Group Bypass, Instant Arm,
keypad activated RPS, and Test (central station and bell)
Digit Position (3): Default Installer Combination
0 = No; this enables the Pirate-GuardTM feature for added security 1 = Yes; combination changes back to factory value on power loss
Digit Position (4): Faulted Arming Type
1 = Goof-Proof: zones must be normal or shunted to arm 2 = Force Arm: faulted zones will be shunted at end of Exit Delay 3 = Chirp Alert: faulted zones will chirp bell upon transition from Exit Delay to Entrance Delay
Command Location 0A: Communications FormatsCommand Location 0A: Communications Formats
Command Location 0A: Communications Formats
Command Location 0A: Communications FormatsCommand Location 0A: Communications Formats
5 = 5 days 6 = 6 days 7 = 7 days 8 = 8 days 9 = 9 days
Default ValuesDefault Values
Default Values
Default ValuesDefault Values
0 = 10 days 1 = 11 days 2 = 12 days 3 = 13 days 4 = 14 days 5 = 15 days
00
0
00
(1) (2) (3) (4)
1212
AA
A
AA
#
Digit Position (1): Receiver #1 Receiver Format
1 = Fast "A", 2300 Hz 2 = Slow "B", 1400 Hz
Digit Position (2): Receiver #1 Message Format
2 = 3/1 Extended 3 = 4/2 (2-digit reporting code)
Digit Position (3): Receiver #2 Receiver Format
1 = Fast "A", 2300 Hz 2 = Slow "B", 1400 Hz
Digit Position (4): Receiver #2 Message Format
2 = 3/1 Extended 3 = 4/2 (2-digit reporting code)
Valid combinations of Receiver Format and Message Format are listed below.
Message Format Receiver Format(s)
3/1 Extended All formats, 4/2 (2-digit reporting) Fast "A", 2300 Hz and Slow "B", 1400 Hz only CFSK III CFSK III only SumCheck (DTMF) DTMF, 1400 Hz only
3 = SumCheck, 1400 Hz 4 = SumCheck, 2300 Hz
5 = CFSK III 6 = SumCheck (DTMF)
3 = SumCheck, 1400 Hz 4 = SumCheck, 2300 Hz
5 = CFSK III 6 = SumCheck (DTMF)
exceptexcept
except CFSK III and DTMF, 1400 Hz
exceptexcept
5 = CFSK III 6 = DTMF, 1400 Hz
5 = CFSK III 6 = DTMF, 1400 Hz
(1) (2) (3) (4)
PROGRAMMING CONVERSIONSPROGRAMMING CONVERSIONS
PROGRAMMING CONVERSIONS
PROGRAMMING CONVERSIONSPROGRAMMING CONVERSIONS
Hexadecimal ValueHexadecimal Value
Hexadecimal Value
Hexadecimal ValueHexadecimal Value
A B C D E F
Key StrokesKey Strokes
Key Strokes
Key StrokesKey Strokes
0 1 2 3 4 5
9
Loading...
+ 21 hidden pages