SYS3316RF Terminal LabelFront Cover
UL Compliance2
Installation2
Wiring the Panel3 - 4
System Start-Up4
Keypad Setup4 - 5
Addressing Keypads5
Factory Default Settings5
Programming Options (Alphabetical List)5 - 6
Programming the Panel6 - 7
Programming with the LED Keypad6
Programming with the Alpha Keypad6
Entering Hexidecimal Numbers6
Programming the Alpha Keypad7
Programming Letters & Numbers7
Special Function Keys7
Programming Options (Numerical Order)8 - 19
Keypad Label Drawer20
Telephone Line Problems20
Watchdog Indicator20
FCC Notice / Industry Canada20
Keypad Operation Command Summary21
Help with Common Problems (Troubleshooting)22 - 23
Reducing False Alarms24 - 25
Warranty Information26
Programming Worksheets27 - 30
BEFORE YOU STARTBEFORE YOU START
BEFORE YOU START
BEFORE YOU STARTBEFORE YOU START
Introduction
The SYS3316RF is a fully-programmable 16-zone control panel. It can be
programmed from the Alpha or LED keypad or remotely via the COMMANDER II/MONITOR II software package.
Scope of This Manual
This manual contains basic installation and programming information for
the SYS3316RF. For additional information about remote programming,
please refer to the Commander II/Monitor II Operating Manual.
Accuracy
This manual has been carefully checked for accuracy. However, C&K
SYSTEMS assumes no liability for inaccuracies or actions resulting from
the use of this manual. In addition, C&K reserves the right to modify the
SYS3316RF hardware, software, and manuals without prior notice.
UL Compliance (continued)
8. The Dynamic Battery Test must be enabled.
9. The Unit Status Report must be enabled.
10.The 24-hour Check-in must be enabled.
11.The unit must not be programmed to dial a police station.
12.Use screws (supplied) to secure cover or a lock must be
installed on the cabinet.
13.All devices must be UL listed.
Zone Programming
FIRE LOOP
.
24-hour arming
.
Pulsing audible
.
Supervised
- latching for heat
- resetting for smoke
.
Not shuntable
INSTALLATIONINSTALLATION
INSTALLATION
INSTALLATIONINSTALLATION
Mounting
The SYS3316RF should be mounted in a location which allows convenient
access to AC power, telephone connections, and earth ground.
.
Remove the SN913-I/O from its card cage and the control panel
circuit board from the cabinet. This will prevent possible
damage to the circuit boards when removing the knock-outs.
.
Remove the knock-outs.
.
Mark the screw mounting holes on the wall.
.
Mount the cabinet at the desired height and pass the cables
through the knock-outs.
.
Replace the circuit boards, remembering to connect the ground
lug to the lower left corner of the control panel circuit board.
.
Reconnect the spade lug to the lower door hinge. This provides
the earth ground connection for the door.
Earth Ground
To ensure the effectiveness of the lightning and transient protection
circuits, the control panel must be connected to "Earth Ground". Ideally,
this should be a common ground to the power lines, telephone system, and
security system. This type of ground, called a "Unified Earth Ground",
provides the best protection. The ground connection, from a grounding
rod, cold water pipe or other established ground point, is made to the green
jacketed wire providing a ground to the panel housing.
BURGLAR LOOP
.
Steady Audible
.
NO/NC with EOL
UL COMPLIANCEUL COMPLIANCE
UL COMPLIANCE
UL COMPLIANCEUL COMPLIANCE
The SYS3316RF is in compliance with Underwriters Laboratories, Inc.
Standards UL 985, Household Warning System Units; UL 1023, Household Burglar Alarm System Units; and UL 1635, Digital Burglar Alarm
Communicator System Units. The following programming restrictionsmust be observed to meet UL standards.
1. The audible must be programmed to sound at least four
minutes before silencing.
2. No zone may be programmed for silent alarm.
3. Fire zones must be programmed for pulsing audible alarm.
4. Burglar zones must be programmed for a steady audible.
5. Burglar loops (non-24-hour loops) must be programmed
for NO/NC.
6. No Entry Delay may be greater than 45 seconds.
7. No Exit Delay may be greater than 60 seconds.
Power Lines
Power Line
Earth Ground
Unified Earth Ground
with Bonded Ground Roots
Control
Panel
Telephone
Earth Ground
Telephone Lines
FIGURE 1 Unified Earth Ground
2
SYS3316RF Installation Manual
WIRINGWIRING
WIRING
Standby Battery
The SYS3316RF is designed to operate with a 12-volt, 6.5 AH, sealed
lead-acid battery (C&K Model 1265)**. Do not use non-rechargeable
batteries or batteries other than sealed lead-acid. It is recommended
that you replace the standby battery every three to five years.
Connect the red lead to the positive terminal of the battery and the black
lead to the negative battery terminal. The battery is reverse-polarity
protected by a 3 amp, 3 AG, fast-blow fuse (F4).
**To comply with CAL-FIRE requirements for 24-hour standby, a 12
VDC, 9.5 A-H, sealed lead-acid battery must be connected in place of
the 6.5 AH battery. Use C&K Model 1295 Battery.
AC POWERAC POWER
AC POWER
AC POWERAC POWER
AC power is supplied by a 16.5 VAC, 25 - 40 VA
transformer at 50 or 60 Hz. A UL listed Class 2
transformer (such as the C&K Model 1097-B) must be
used. Connect the transformer secondary to terminals 1 and 2. Use at least 18 AWG (1.02 mm) wire to
reduce voltage drops. The transformer primary must be connected to
an unswitched receptacle. Do not connect primary to Ground-FaultInterrupt (GFI) circuits. Secure the transformer to the wall.
PrecautionsPrecautions
Precautions
PrecautionsPrecautions
DO NOT share the secondary of the transformer with other
devices. A foreign ground can damage the power supply,
voiding the warranty.
DO NOT use any transformer other than that specified in the
AC POWER section above.
AC Power Failure
If an AC power failure lasts more than 15 minutes, the keypads will display
a system trouble. An AC failure report will be sent, if programmed. When
AC is restored for five minutes, a restoral report will be sent.
Available Power
The maximum total power available from the Audible, AUX (Switched
and Unswitched), and Keypad Terminals (terminals 3, 5, 7, and 8) is
750 mA. The Switched Aux, Unswitched Aux, Receiver/Interface Board
and Keypads Terminals share the same power bus. Combined power
for these outputs should not exceed 500 mA.
WIRINGWIRING
Terminals 1 and 2
AUXILIARY POWERAUXILIARY POWER
AUXILIARY POWER
AUXILIARY POWERAUXILIARY POWER
Terminals 5 and 7 provide positive 10 - 12.5 VDC power.
Terminal 5 is used for devices that require switched power for
resetting. Typical devices are glass-breaks and smoke detectors. Terminal 6 provides the common for Switched AUX,
Unswitched AUX, and Keypad power. The SN913-I/O Interface Board is connected to terminals 6 and 7 at the factory.
Fuse F2
Terminals 5 and 7 (AUX POWER) are protected by a 0.75 amp, 3 AG, fastblow fuse (F2).
power.
Terminal 9 (green) is data from the keypad to the
panel.
Maximum wire length for connecting any keypad is 500' (152 m) of 22
AWG (0.643 mm) copper wire.
The SYS3316RF is capable of addressing up to 16 keypads (8 Alpha II and
8 LED). Each LED keypad uses 35 mA of current. Each LCD (Alpha)
keypad uses 64 mA of current. See Available Power for current limitations. See page 4 for additional information on keypad setup.
Fuse F3
Terminal 8 (keypad power) is protected by a 0.75 amp, 3 AG, fast-blow
fuse (F3).
LOOP INPUTSLOOP INPUTS
LOOP INPUTS
LOOP INPUTSLOOP INPUTS
EOL Loop
N.C.
++
+
++
Alarm
N.O.
Alarm
SYSTEM 3316 Loops Terminals
--
-
--
Loop 7
0 - 2 VDC = short
2 - 3 VDC = normal
3 - 5 VDC = open
Loop 8
0 - 2.5 VDC = short
2.5 - 8.5 VDC = normal
8.5 - 15 VDC = open
Terminals 5, 6, and 7
Terminals 6, 8, and 9
Terminals 19, 20, and 21
Two loops may be independently
configured through programming.
Loops can be wired with an open
circuit switch, closed circuit switch,
or with a 2.2K-ohm end-of-line (EOL)
resistor.
When programmed as an EOL circuit, either an open or a short will
be reported as an alarm if the system
is in an armed state.
AUDIBLE OUTPUTAUDIBLE OUTPUT
AUDIBLE OUTPUT
AUDIBLE OUTPUTAUDIBLE OUTPUT
Terminal 3 provides up to 0.75 Amps at 10.5 - 13.5
VDC. The type of voltage (steady, pulsed, or chirp)
and the time is programmable.
Fuse F1
Terminal 3 is protected by a 2.5 Amp, 3 AG fast-blow fuse (F1).
If any fuse opens, remove AC and DC power, remove the
NOTE:
short or overload condition, then replace the fuse before
restoring power. Do not substitute a higher rated fuse.
Electromagnetic Interference
Vibrating horns and bells can produce electromagnetic interference
(EMI). While EMI will not damage the SYS3316RF, it can cause transmission errors and mis-dialing. To minimize EMI, install a 0.01 mfd, 100
volt capacitor across the terminals of the horn or bell. The capacitor
must be located at the source of the EMI (horn or bell).
Terminals 3 and 4
Supervised Loop
N.C.
++
+
++
Alarm
N.O.
Alarm
--
-
--
SYSTEM 3316 Loops Terminals
Pre-wired Loops
Loops 1 - 6 and 9 - 16 are pre-wired to the SN913-I/O Interface Board
and are configured as supervised loops for use with the WIRELESS
transmitters. EOL resistors for these loops are installed on the SN913I/O Interface Board.
Loop 8
The terminals for zone 8 (20 and 21) are a standard loop that can also
power 2-wire devices. The loop supplies 10 - 12.5 VDC at 50 mA. Use
Loop 8 to power 2-wire glass-breaks and smoke detectors. The 50 mA
on Loop 8 is part of the 500 mA AUX Power.
3
When operated as a Supervised
Loop, an open will be reported as
a Trouble, whether the system is
armed or disarmed. A short on a
Supervised Loop is reported as an
alarm if the system is armed, but
will have no effect if the system is
disarmed.
TAMPER SWITCH INSTALLATIONTAMPER SWITCH INSTALLATION
C&K has designed the SYS3316RF cabinet to use the Ademco Model
19 tamper switch. The cabinet is constructed in order to accommodate
two switches. One tamper for the cover and a second switch for a wall
tamper. To install the tamper switches:
Position the tamper switch inside the cabinet at the lower right corner
1.
of the cabinet. For the wall tamper, the plunger should go through
the small hole in the back of the cabinet. For the door tamper, the
plunger should face out from the cabinet. Refer to the drawingbelow.
Connect the tamper switches in series and wire the tamper terminals
2.
to a dedicated zone of the control panel.
3.
Program the dedicated zone as desired: NC, EOL, 24-hour, etc.
Once the tamper switches are installed, opening the cabinet door or
removing the cabinet from the wall will result in a tamper signal at the
panel.
Tamper Switches installed in the SYS3316RF cabinet
PRINTED CIRCUITPRINTED CIRCUIT
PRINTED CIRCUIT
PRINTED CIRCUITPRINTED CIRCUIT
BOARDBOARD
BOARD
BOARDBOARD
SN913SN913
SN913
SN913SN913
I/OI/O
I/O
I/OI/O
9.X PCF
The 9.X PCF has eight flying leads on the other end. Wire them to the
phone line terminals as follows:
RED = ringBROWN = tip seized
GREEN = tipBLUE and ORANGE = tamper
YELLOW and BLACK = not usedGRAY = ring seized
SYSTEM START-UP
Five minutes after the panel is powered up, it will dynamically test the
standby battery by interrupting AC power for two minutes and monitoring
the battery under load.
If you replace the battery after a SYSTEM TROUBLE - LOW BATTERY
message, you must test the battery under load conditions. Press [*] [6]
[4] [#] to start the Dynamic Battery Test.
Voltage Variations
Output voltages at terminals 5, 7, and 8 may vary from 9.0 to 14.4 VDC
(worst case), depending on the load, battery condition, and AC line
voltage.
KEYPAD SETUP
TB1TB1
TB1
TB1TB1
6.5 A-H6.5 A-H
6.5 A-H
6.5 A-H6.5 A-H
oror
or
oror
9.5 AH9.5 AH
9.5 AH
9.5 AH9.5 AH
LEAD-ACIDLEAD-ACID
LEAD-ACID
LEAD-ACIDLEAD-ACID
BATTERYBATTERY
BATTERY
BATTERYBATTERY
TELEPHONE INTERFACE
Connect the SYS3316RF to the phone line using the
9.X PCP or 9.X PCF cord (not included). Each of the
cords has an 8-pin telco plug on one end. Plug this end
of the cord into J1 at the lower right corner of the PCB.
Connect the other end as outlined below:
R1 = Seized Ring
T1 = Seized Tip
1
R1
T1
876
House
Phones
DOORDOOR
DOOR
DOORDOOR
TAMPER SWITCHTAMPER SWITCH
TAMPER SWITCH
TAMPER SWITCHTAMPER SWITCH
WALLWALL
WALL
WALLWALL
TAMPER SWITCHTAMPER SWITCH
TAMPER SWITCH
TAMPER SWITCHTAMPER SWITCH
Control Panel
Telco Jack (J1)
23
4
Red
Green
5
Tamper Jumper
Protector
Ring
Tip
RJ-38X Wiring
Diagram
Incoming
Telco Line
ALPHA II KEYPAD INFORMATION
The Alpha II keypad uses a top viewing display. This means the display
reads most clearly when viewed from a top angle rather than straight
on or from below. Mounting the keypad at light switch level and adjusting
the viewing angle gives the best results.
Adjusting the LCD Display
To adjust the viewing angle, remove the keypad from the back mounting
plate. Towards the bottom center of the circuit board is a small hole.
Insert a small screwdriver into the hole and adjust R23 for optimum
viewing, while holding the keypad at its mounting height.
ADDRESSING KEYPADS
Each Alpha II and LED keypad installed in the system must have an
address. Addresses must not be repeated. When replacing a keypad,
make sure the replacement has the same address as the previous
keypad. Once all keypads have been addressed, reset the panel by
pressing [Master Combination] [*] [6] [8] [#] or by removing and
restoring both AC and DC power.
Addressing Alpha II Keypads
The first time you power up the system, unaddressed Alpha II keypads
will display KEYPAD ADDRESS?. Press any number from 0 through
7 at each keypad. The exact number you press is not important, as long
as each keypad has a different address number. The keypad will not
accept values outside of this range. Should you accidentally use the
same address for more than one keypad, the system will fail to properly
respond to keypad input. Refer to page 23 for assistance in correcting
this problem.
Addressing LED Keypads
The LED keypad also requires an address. The address on the LED
keypad is set by the three hook switches on the LED keypad's PCB.
Hook switches SW1, SW2, and SW3 are used to set the address of
LED keypads. Refer to the chart at the top of page 5.
4
HOOKHOOK
HOOK
HOOKHOOK
SWITCHESSWITCHES
SWITCHES
SWITCHESSWITCHES
SW1SW1
SW1
SW1SW1
SW2SW2
SW2
SW2SW2
SW3SW3
SW3
SW3SW3
J1J1
J1
J1J1
J2J2
J2
J2J2
SW1SW1
SW1
SW1SW1
Closed
Closed
Closed
Closed
Open
Open
Open
Open
LED Keypad Backlighting
Hook switch J1 controls the LED keypad's backlighting. When J1 is closed
(default setting), the backlighting will be enabled. Open J1 to disable the
backlighting.
LED Keypad Piezo
Hook switch J2 controls the LED keypad's piezo audible. When J2 is
closed (default setting), the piezo is enabled. Open J2 to disable the piezo.
DEFAULT PROGRAM SETUP
The default programming of the SYS3316RF will allow you to operate it as
a local panel without any additional programming. The actual default
programming values are shown on the Programming Worksheet (last 4
pages of this manual).
Note: If you connect power before wiring the loops, install a
2.2K-ohm EOL resistor across each loop.
Any address from 8 to 15 can be used. The exact
number is not important, as long as each LED
keypad in the system has a different address
number. Should you accidentally use the same
address for more than one keypad, the system
will fail to respond to keypad input. Refer to page
23 (Alpha II keypads with same addresses) for
assistance in correcting this problem.
SW2SW2
SW2
SW2SW2
Closed
Closed
Open
Open
Closed
Closed
Open
Open
FACTORY SETTINGSFACTORY SETTINGS
FACTORY SETTINGS
FACTORY SETTINGSFACTORY SETTINGS
SW3SW3
SW3
SW3SW3
Closed
Open
Closed
Open
Closed
Open
Closed
Open
KEYPAD ADDRESSKEYPAD ADDRESS
KEYPAD ADDRESS
KEYPAD ADDRESSKEYPAD ADDRESS
88
8
88
99
9
99
1010
10
1010
1111
11
1111
1212
12
1212
1313
13
1313
1414
14
1414
1515
15
1515
Combinations
Installer combination: 0 1 2 3 4 5
User #1 (Master) combination: 1 2 3 4
Users #2 - 32: disabled
Default installer combination: yes
Guest combination: no
Combination required: no
Faulted Arming type: goof-proof
Opening/Closing: no Users authorized to send reports
Duress: disabled
Zone 1 = Entry/Exit delay - SUPERVISED EOL circuit
Zone 2 = doors or windows - SUPERVISED EOL circuit
Zone 3 = doors or windows - SUPERVISED EOL circuit
Zone 4 = doors or windows - SUPERVISED EOL circuit
Zone 5 = doors or windows - SUPERVISED EOL circuit
Zone 6 = doors or windows - SUPERVISED EOL circuit
Zone 7 = doors or windows - EOL circuit
Zone 8 = fire or smoke - supervised EOL circuit
SYS3316RF Installation Manual
Zones (cont.)
Zone 9 = interior - SUPERVISED EOL circuit
Zone 10 = interior - SUPERVISED EOL circuit
Zone 11 = interior - SUPERVISED EOL circuit
Zone 12 = interior - SUPERVISED EOL circuit
Zone 13 = interior - SUPERVISED EOL circuit
Zone 14 = interior - SUPERVISED EOL circuit
Zone 15 = interior - SUPERVISED EOL circuit
Zone 16 = interior - SUPERVISED EOL circuit
Emergency soft zone: chirp audible, non-reporting
Fire soft zone: pulsed audible, non-reporting
Police soft zone: steady audible, non-reporting
Testing
Test report interval: 7 days and disabled
Timing
Entry time: 60 seconds and prewarn
Exit time: 30 seconds and prewarn
Bell time: 5 minutes
Unit Control
Local system: yes
Dynamic battery test: off
PROGRAMMING OPTIONSPROGRAMMING OPTIONS
PROGRAMMING OPTIONS
PROGRAMMING OPTIONSPROGRAMMING OPTIONS
The following is an alphabetical listing of all SYS3316RF programming
options, including Command Locations and Digit Positions. Digit Positions are inside parentheses ( ). NOTE: All Command Locations are in
Hexadecimal.
OptionLocation
Account #10C (1 - 6)
Account #210 (1 - 6)
AC Power Line Frequency2F (5)
Alarm Receiver Select by Loop1F - 26 & 49 - 50 (1)
Alarm Reporting Code by Loop17 - 1E & 40 - 47 (1 - 2)
Audible Time2D (5)
Bell Reverse Operation2E (3)
Cancel Report Code2A (5)
Cancel Report Receiver Select2A (6)
Closing Report Code2C (3)
Closing Report Receiver Select2C (4)
Combination Command09 (2)
Daily Battery Test Enable2F (2)
Default Installer Combination09 (3)
Delay Before Dial by Loop30 - 3F (4)
Delay Before Dial Time0B (1)
Dial Attempts0B (6)
Dial Type0B (2)
Disable Loop LEDs2E (5)
Door Chime Enable by Loop30 - 3F (1)
Duress Report Code2D (1)
Duress Report Receiver2D (2)
Emergency Bell Type27 (4)
Emergency Receiver Select27 (3)
Emergency Report Code27 (1 - 2)
Entry Delay Time2D (3)
Entry Pre-alarm Enable2E (1)
Exit Delay Time2D (4)
Exit Pre-alarm Enable2E (2)
Faulted Arming Type09 (4)
Fire Bell Type28 (4)
Fire Receiver Select28 (3)
Fire Report Code28 (1 - 2)
Four Minute Power Up Delay Enable2F (3)
Group Shunt Enable30 - 3F (3)
Guest Combination08 (2 - 6)
Guest Combination Time09 (1)
Installer Combination00 (1 - 6)
You can program the SYS3316RF from the LED or LCD keypad, as well
as remotely using the COMMANDER II software. Information on remote
programming is available in the COMMANDER II/MONITOR II Operating
Manual. This installation manual includes a brief description of each
programming option beginning on page 8.
Starting Panel Programming
Key in the [Installer Combination] [*] [0] [#]. The default Installer Combination is 0 1 2 3 4 5. When using the SYSTEM 2316 LED keypad, the
PROGRAM LED will light steady to indicate programming mode. On the
2316 Plus LED keypad the READY, ARM, and SERVICE LED's will flash
to indicate programming mode. The Alpha II keypad will display CMD
DATA across the top of the LCD display to indicate programming mode.
Programming with the LED Keypad
Programming with an LED keypad is a one-step process. Key in the twodigit address (Command Location), followed immediately by the desired
programming values (program data), then press the [#] key to store the
data. The LED keypad does not display any programmed values. If you are
not sure that the correct programming values have been entered, program
the Command Location again.
LocationLocation
Location
LocationLocation
NOTE:To program Command Locations A0, B3, and B4 with an
LED keypad, remember to enter the Command Location,
followed by the program data, then press the [#] key.
Warning: If you enter a Command Location and then press the
[#] key without entering any program data, the keypad will beep 5 times, indicating an error. To correct
this problem, simply re-enter the Command Location and Data, then press the [#] key.
Programming with the Alpha Keypad
Entering program data with an Alpha keypad is a two-step process. First,
key in the two-digit address (Command Location) to be programmed and
press the [#] key. The Alpha keypad displays the Command Location and
the data previously stored. Enter the new data you wish to store and press
the [#] key to write the data. You can also scroll through the Command
Locations in numerical order by alternately pressing and releasing the [#]
key.
NOTE: Command Location A0 must be addressed directly. When pro-
gramming this Command Location with an Alpha keypad, the
previously stored data is not displayed. To program this location,
enter the Command Location followed by the [#] key. Then enter
the data to be stored and again press the [#] key.
Programming Hexadecimal Numbers
The Alpha keypad may be used to program the control panel. The cursor
is moved using the "E" and "P" keys, as indicated in the figure below. The
"F" key enters a blank space and moves the cursor one position to the
right.
Panel Programming Keys
B
132
E
45 6
789
Data is programmed into the panel using the hexadecimal number system,
which consists of the digits 0 - 9 and the letters A - F. The digits 0 - 9 are
entered directly from the keypad. The chart below shows how to enter the
hexadecimal digits A through F.
PROGRAMMING CONVERSIONSPROGRAMMING CONVERSIONS
PROGRAMMING CONVERSIONS
PROGRAMMING CONVERSIONSPROGRAMMING CONVERSIONS
Hexadecimal ValueHexadecimal Value
Hexadecimal Value
Hexadecimal ValueHexadecimal Value
A
B
C
D
E
F
The same procedure is used with both the LED and the Alpha keypads.
C
F
A
0
D
Key StrokesKey Strokes
Key Strokes
Key StrokesKey Strokes
0
1
2
3
4
5
6
SYS3316RF Installation Manual
The last two Command Locations are CL 37 and CL A0. Pressing the [#]
key at these locations will advance you to CL 38 or CL A1, respectively.
Locations CL 38 and CL A1 are not used in the SYS3316RF. If you
accidentally enter either of these locations, press [*] [#] to exit programming, or enter the Command Location number, followed by the [#] key, for
the location you wish to program.
To Exit Panel Programming
When you have finished programming, press [*] [#].
exit the programming mode if you do not press any key within a five
minute period.
PROGRAMMING the ALPHA KEYPADPROGRAMMING the ALPHA KEYPAD
PROGRAMMING the ALPHA KEYPAD
PROGRAMMING the ALPHA KEYPADPROGRAMMING the ALPHA KEYPAD
Ensure the Alpha keypad is wired to the SYS3316RF and power is applied
to the control panel. You can only access the programming mode when
the control panel is disarmed.
NOTE:Programming the Keypad is not the same as Keypad
Programming.
The panel will also
The Alpha Keypad
You can program the Alpha keypads for special messages, each of the 16
zone labels, and the keypad address. Zone Labels display during the
walk-test and when the [#] key is pressed during alarm memory or faults.
The programmable Service Message is displayed during AC failure, fuse
failure, communication failure, or low battery. The Dealer Message
displays when the system is disarmed. The keypad address is initially
displayed only during system start up (see page 4, Keypad Addressing).
These messages can be programmed directly from the Alpha keypad or
remotely using the Commander II/Monitor II software package. For more
detailed information about remote programming, refer to the Commander
II/Monitor II Operating Manual.
Keypad Message Programming
The Alpha keypad programming template is used to allow the installer
to program messages and zone descriptions into the Alpha keypads.
The template shown on the next page should be used when programming the keypad.
To activate the keypad progr amming mode, enter the [Installer's Code]
[*] [0] [1] [#]. Information may be entered into the keypad in the form
of letters (upper and lower case), numbers (0 - 9), and 22 special symbols.
All characters are displayed in the order listed above, i.e. upper and
lower case letters, numbers, and special symbols. The [Space] character precedes the letter A.
To enter a Message or Label, use the [2] key to scroll through the
characters until you reach the desired character. If you scroll past the
desired character, the [8] key may be used to scroll backwards. When
the desired character is displayed, press the [6] key to move the cursor
to the next character position. The [4] key moves the cursor to the left.
When all characters have been entered, press the [#] key to write the
message and move to the next message position. Use the [0] key to
move backward through the messages.
The message order is:
• SERVICE MESSAGE
• DEALER MESSAGE
• SOFT ZONE IDENTIFIERS (A, B, and C)
• HARDWIRED LOOP IDENTIFIERS
• KEYPAD ADDRESS
ALPHA II Programming TemplateALPHA II Programming Template
ALPHA II Programming Template
ALPHA II Programming TemplateALPHA II Programming Template
11
1
11
44
4
44
77
7
77
ALPHA PLUS Programming TemplateALPHA PLUS Programming Template
ALPHA PLUS Programming Template
ALPHA PLUS Programming TemplateALPHA PLUS Programming Template
11
1
11
44
4
44
77
7
77
NOTE:If you do not press any key for 5 minutes, the
keypad will automatically exit the programming
mode.
22
2
22
55
5
55
88
8
88
00
0
00
22
2
22
55
5
55
88
8
88
00
0
00
33
3
33
66
6
66
99
9
99
33
3
33
66
6
66
99
9
99
To Exit Keypad Programming
When you have finished programming, press [*] [#].
exit the programming mode if you do not press any key within a five
minute period.
The keypad will also
Both the Alpha (shown at the top of the next column) and the Alpha Plus
(shown below in the next column) use the same procedure to program
messages.
Combination must have 6 digits. Valid entries are 0 - 9.
00
00
0
0
00
00
CL 00 - 08 & 51 - 68CL 00 - 08 & 51 - 68
CL 00 - 08 & 51 - 68
CL 00 - 08 & 51 - 68CL 00 - 08 & 51 - 68
012345
(1)(2)(3)(4)(5)(6)
#
Command Location 01 - 08 and 51 - 68:Command Location 01 - 08 and 51 - 68:
Command Location 01 - 08 and 51 - 68:
Command Location 01 - 08 and 51 - 68:Command Location 01 - 08 and 51 - 68:
**Default Values**Default Values
**Default Values
**Default Values**Default Values
01 = User #1 (Master)
02 = User #2
03 = User #3
04 = User #4
05 = User #5
06 = User #6
07 = User #7
08 = User #8 (Guest)
51 = User #9
52 = User #10
53 = User #11
54 = User #12
55 = User #13
Digit Position (1): Arming Type
1 = Arm Only, No Closing (C) Report, No Shunting
2 = Disarm Only, No Opening (O) Report, No Shunting
3 = Arm and Disarm, No O/C Reports, No Shunting
4 = Arm Only, with Closing Report, No Shunting
5 = Disarm Only, with Opening Report, No Shunting
6 = Arm and Disarm, with O/C Reports, No Shunting
7 = Arm Only, No Closing Report, Shunting Allowed
8 = Disarm Only, No Opening Report, Shunting Allowed
9 = Arm and Disarm, No O/C Reports, Shunting Allowed
0 = Arm Only, with Closing Report, Shunting Allowed
1 = Disarm Only, with Opening Report, Shunting Allowed
2 = Arm and Disarm, with O/C Reports, Shunting Allowed
56 = User #14
57 = User #15
58 = User #16
59 = User #17
5A = User #18
5B = User #19
5C = User #20
5D = User #21
5E = User #22
5F = User #23
60 = User #24
61 = User #25
62 = User #26
63 = User #27
64 = User #28
65 = User #29
66 = User #30
67 = User #31
68 = User #32
NOTE: Opening and Closing Reports
User Arming Type and CombinationUser Arming Type and Combination
User Arming Type and Combination
User Arming Type and CombinationUser Arming Type and Combination
91234E
11
00
1
0
11
00
(1)(2)(3)(4)(5)(6)
must be enabled. See CL 2C
Digit Positions 1 and 3 for
additional information.
#
**Default Values are different for each user.
Refer to the SYS3316RF Programming
Worksheet at the end of this manual for
other user default values.
NOTE: Some programming locations allow
variable-length data and require an Endof-Number (EON) character. Program
4 ("E") after the last digit. Fill
remaining unused Positions with "0".
The EON character is not required if the
last digit is in Position 6.
0 = Guest Time Disabled
1 = 1 day
2 = 2 days
3 = 3 days
4 = 4 days
Digit Position (2): Combination Command
0 = No
1 = Yes; requires combination for Bypass, Group Bypass, Instant Arm,
keypad activated RPS, and Test (central station and bell)
Digit Position (3): Default Installer Combination
0 = No; this enables the Pirate-GuardTM feature for added security
1 = Yes; combination changes back to factory value on power loss
Digit Position (4): Faulted Arming Type
1 = Goof-Proof: zones must be normal or shunted to arm
2 = Force Arm: faulted zones will be shunted at end of Exit Delay
3 = Chirp Alert: faulted zones will chirp bell upon transition from Exit Delay to Entrance Delay