WRU-10 RAL 0.3-1 Electronic Earth-leakage Protection Relay
Código
RAL
REC
REC
Super-inmunized Type A electronic relay. Built-in core balance
transformer, 28 mm.Device with self-reclosing system. Symbol on
display. It has programmables relays, 3 outputs. Main trip and 2 pre-alarm signals. It has 1
free voltage input for external ON / OFF. Mounting in DIN rail 46277 (En50022) or PANEL
72x72 by means of accesories M5ZFF1. Displays setting values and instantaneous earth
leakage current value (TRMS)
code
R
P24457
GENERAL DESCRIPTION
Tipo
Type
WRU-10 RAL 0.3-1
0,3-0,5-1 por ajuste directo/by direct setting
Sensibilidad (A)
Sensivity
REC
PRELIMINARY CONSIDERATIONS
CHECKS ON RECEPTION
On receving the instrument, check the following points:
- The unit’s specifications are the same as those on your order.
- Check that the device has not suffered any damage during transport.
You can download more information from CIRCUTOR website, www.circutor.es
SAFETY PRECAUTIONS
The staff using or handling the unit must follow the common safety measures and warnings included in the
instruction manual.
The WRU-10 unit has been specifically designed for its installation in a electric board, enclosure to a DIN
rail or mounted in panel by means of accesories. It has a flashing green led (ON) when it is operation and,
therefore, it shows that there is voltage and current in the electronic circuit. The user must make sure that
the equipment is not conected to the power supply at all the times, even when the LED is not flashing.
INSTALLATION AND STAR-UP
The user must take into account and observe the informations and warnings included in this instruction
manual to guarantee the correct operation of the equipment and comply whit the safety specifications. The
equipment must not turned on until is fully installed in the electrical panel.
¡ IMPORTANT !
The unit´s protections systems might not be effective if the unit is used for purpose other than
!
those specifications by the manufacturer.
Disconnect the equipment from the power supply when the unit´ssafety protection systems are not working
or there are signs of a problem (in case of visible damage). In this case, contact a qualified technical service
or with our own technical service (TAS).
INSTALLING THE EQUIPMENT
DIN rail installation. On the inside of the hole must pass all live conductors supplyng electrical energy to
loads or part of the installation which requires it to earth leakage protection with this device. In single-phase
installation (phase and neutral, L and N), three phase - 3 wires (three phases, L1, L2 and L3) or three
phases - 4 wires (L1, L2, L3 and N). Depending on the level of wiring insulation can be pass through the hole
of 28 mm (inner diameter) 4-wire 35 mm of section, although it advisable is 25 mm . All connections
should be inside the electrical board. Please note that with the connected equipment, terminals and
opening covers or removing elements, can give access to dangerous parts to touch. The equipment must
not be used until it has completely finished installation. The unit must be connected to a power supply circuit
protected by fuses in line with the range and power consumption. In turn, the supply circuit must be
provided with a circuit breaker or equivalent device to disconnect the equipment from the mains. During the
wiring cable is advisable a section permitted between 1 - 1.5 mm2. A recommended torque of 0.5-0.6 N.M.
Cable Stripping Tools length 7 mm.
2 2
Peso / Wheight : 168
Power supply Operating conditions Safety
Voltage 230 Va.c..
Frequency 50!60 Hz
Burden 4,5 VA
Temperature -20...70 C
+/- 30%
Relative humidity 95%
Max. Altitude 2.000 m
Protection Ip20
Category III - 300 Vac (En61010)
Double - insulated electric shock protection
clas II - UL 1053 UL Certification IEC 60755 - IEC 60947-2 Annex M
CONNECTIONS BY MEANS OF PLUG-IN CONNECTORS
TERMINAL DESCRIPCIÓN FEATURES
1 - 2 EXTERNAL INPUT TRIP / RECLOSE
3 PRE-ALARM OUTPUT RELAY, NO
4 PRE-ALARM OUTPUT RELAY COMMON
5 LOCKED OUTPUT RELAY, NC
6 LOCKED OUTPUT RELAY COMMON
7 SUPPLY 230 Va.c. (Phase or Neutral)
8 SUPPLY 230 Va.c. (Neutral or Phase)
9 TRIPPING OUTPUT RELAY, NC
10 TRIPPING OUTPUT RELAY, NA
11 TRIPPING OUTPUT RELAY COMMON
12 WITHOUT USE
Free voltage, not isolated
Rated current: 0,25 Ac.a.
Rated voltage: 230 Vc.a.
Rated Load: 62,5 V·A
Protected by varistor:
420 Vc.a. - 10 Ac.a.
Rated current: 5 Ac.a.
Rated voltage: 250 Vc.a.
Rated Load: 1.250 V·A
RAL
Technical Assistance Service (T.A.S)
If you have any doubts about the running of the equipment or any faults, contact the service staff.
Vial Sant Jordi s/n
08232 Viladecavalls (Bacelona) SPAIN
Tel: (+34) 93 745 29 19
Fax: (+34) 93 745 29 14
email: central@circutor.com
Retardo disparo (s)
Tripping delay
INS 0,02 por ajuste directo / by direct setting
.
DESCRIPTION LED AND BUTTONS
Shows equipment status via a
display and 2 LED's. It has 5
button equipment setup and
setting and 2 button equipment to
do TEST and RESET.
- DELAY SETTI NG
- SETUP ROTATION
- SENSIVITY SETTING
- outputs contacts SETTING.
(LOCKED SIGNAL)
- ENABLE/DISABLE
REC
SELF-RECLOSING SYSTEM
INDICATION BY LED AND DISPLAY
MAIN TRIP RELAY LED and display signals a
- .
change of status by changing from green to red.
Display event type messages or values
PREALARM SIGNAL. The LED green is blinking
-
betwen green and red.
BETWEN RECLOSURES. LED is blinking
-
LOCKED BY RECLOSURES. The yellow LED is
-
fixed. The equipment arrives al maximun number of reclosures established by the self-reclosing
sequence. Red display shows the cause.
No OF RECLOSURES. By short press on the display shows the number of reclosures by earth
-
leakage faults, partial and total number. The partial number are floating pages. In these pages
it can configure the self-reclosing sequence by press button.
REC
REC
Tripping cause
Test
Remote signal trip/reclose
.
Earth leakage fault
Other mesages by display
SAVE
EXIT
OVR
- GREEN led: ON
- RED led, tripped by fault.
- blinking led: pre-alarm
R
- Reclosures led:
fix, maximun reclosures
blinking, betwen reclosures
- RESET Button
- TEST Button
- SETUP settings
- change PAGES
Mensage display
TESt
EXT
Enter setting values
Exits setting mode
Value reading off scale
alueDIF / v
RECLOSING THE EQUIPMENT.
TRIP LOCKED BY RECLOSURES
- BY
Automatic (earth leakage fault or manual). Is shown on display
1. .
2. Manual reclose by pushing button RESET.
External reclose sytem by remote or communications signal. When it forces a trip by remote
3.
signal, only it can reclose by another remote signal. In the case 2 and 3 the partial counters
of reclosures returns to a zero.
The relay only self-recloses after a trip by earth leakage current fault. The Test (red button) only verifies the relay trips
the protection. It recloses only by manual pressing RESET button.
MAIN RELAY PARAMETER SETTING
SETTING TRIP DELAY The message and two values appear on the screen after
- , t .
pressing the button. The lowest value indicates the current set value and the highest is the
values to be configured which are displayed by pressing The selected value to be saved is
displayed by showing the message
SENSITIVITY SETTING The same operation as above setting is carried out by pressing
- , I . I .
- SIGNALLING CONTACTS RELAY STATE, std/+ . Select the default position of the relay contacts
4-5-6 that indicates the situation of locked by reclosures of the device . In (Std) 4-6 NO / 4-5 NC
and (+) 4-5 NC / 4-6 NO and appears the symbol in display .
- SELF-RECLOSING SYSTEM, REC. In reclosure partial numbers by press REC button we
configure the self-reclosing sequence referred at the page which it’s showing us. By default is
configured nº12 by earth leakage protection.
SREC No RECLOSURES TIME SEQUENCES RESET TIME
0
1 6 8, 16, 30, 59, 115 y 224 s 15 minutes
2 30 20, 40 s y 5 min. to the end. 15 minutes
3 8 30 s, 1, 2, 3, 4, 5, 6 y 7 min 15 minutes
4 6 10, 20, 30, 60, 130 y 600 s 15 minutes
5 6 2, 4 y 8 min. to the end. 15 minutes
6 7 30 s, 1, 2, 3, 4, 8 y 16 min 30 minutes
7 10 1 min 30 minutes
8 10 90 s 30 minutes
9 8 2, 4 y 6 min. To the end. 15 minutes
10 10 3 min 30 minutes
11 7 2, 4, 8, 16, 32, 32 y 32 min 15 minutes
12 31 2, 4 y 6 min. to the end. 60 minutes
13 3 2, 4 y 8 min 15 minutes
14 ... ... ...
t
d
DISABLED
SETUP SETTINGS
PROG
With the button the submenus are browsed
and with the button the values to be selected
are displayed
Press
configures the value by displaying on the
display and then exits Setting Mode If the keypad
remains inactive for a certain time, the equipment
automatically exits Setting Mode and displays
.
PROG
to enter the value. The equipment
PROG
d
SAVE.
d d
PROG
“SAVE”
.
Default values in SETUP
- FREQ, (50) frecuency (Hz)
- LIM,(1s, 3A), range of values (Id / td)
- ALAR, pre-alarm.
. Id (MAIN),100%.
. Td ( 20 ms), time.
. SP (NO),contact states.
3-4 [NA/NC]
.AU (AutO), Relay reclaim the state.
- RSTC, (NO), Reset the partial reclosures.
REC
¡ IMPORTANT !
( t , I and std/+ )
d d
.
+
FREC
LIM
ALAR
RSTC
Button PROG
I
d
Pre-alarm current %
t
d
Delay pre-alarma seg.
Contact NO/NC
SP
AU
Reconectable
50 Hz
60 Hz
10 s, 30 A
1 s, 3 A
OFF
50
60
70
80
MAIN
0,02
0,1
0,2
0,3
0,4
0,75
1
3
NO
YES
AUTO
MANU
NO
YES
Button
M008A01-03-14B