Circutor RGU-10, RGU-10C Instruction Manual

INSTRUCTION MANUAL
Electronic earth leakage protection relay
RGU-10, RGU-10C
(M98203201-03-18A)
2
Instruction Manual
3
Instruction Manual
SAFETY PRECAUTIONS
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicatesthatspecialattentionshouldbepaidtoaspecicpoint.
Follow the warnings described in this manual with the symbols shown below.
If you must handle the unit for its installation, start-up or maintenance, the following should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit. In particular, handling with voltages applied may result in electric shock, which may cause death or serious injury to personnel. Defective installation or maintenance may also
leadtotheriskofre.
Read the manual carefully prior to connecting the unit. Follow all installation and maintenance instructions throughout the unit’s working life. Pay special attention to the installation stan­dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result in injury or damage to the unit and /or installations.
CIRCUTOR,SAreservestherighttomodifyfeaturesortheproductmanualwithoutpriornotication.
DISCLAIMER
CIRCUTOR, SAreservestherighttomakemodicationstothedeviceortheunitspecica-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device
specicationsandthemostupdatedmanuals.
www.circutor.com
CIRCUTOR, recommends using the original cables and accessories that are supplied with the device.
4
Instruction Manual
CONTENTS
SAFETY PRECAUTIONS ���������������������������������������������������������������������������������������������������������������������������������������3 DISCLAIMER ���������������������������������������������������������������������������������������������������������������������������������������������������������� 3 CONTENTS ������������������������������������������������������������������������������������������������������������������������������������������������������������� 4 REVISION LOG �������������������������������������������������������������������������������������������������������������������������������������������������������5 SYMBOLS ��������������������������������������������������������������������������������������������������������������������������������������������������������������� 5 1�- VERIFICATIONS UPON RECEPTION �������������������������������������������������������������������������������������������������������������6 2�- DESCRIPTION OF THE PRODUCT ������������������������������������������������������������������������������������������������������������������ 6 3�- INSTALLING THE DEVICE �������������������������������������������������������������������������������������������������������������������������������8
3�1�- PRELIMINARY RECOMMENDATIONS ����������������������������������������������������������������������������������������������������8 3�2�- INSTALLATION �����������������������������������������������������������������������������������������������������������������������������������������9
3�2�1�- INSTALLATION OF DEVICE IN PANEL ���������������������������������������������������������������������������������������������9
3�3�- TERMINALS OF THE DEVICE ����������������������������������������������������������������������������������������������������������������10
3�4�- CONNECTION DIAGRAMS �������������������������������������������������������������������������������������������������������������������� 11
3�4�1�- CONNECTION WITH CURRENT EMISSION COIL �������������������������������������������������������������������������� 11
3�4�2�- CONNECTION WITH UNDERVOLTAGE COIL ���������������������������������������������������������������������������������16
3�4�3�- CONNECTING THE DEVICE IN POSITIVE SAFETY ����������������������������������������������������������������������� 19
4�- OPERATION ���������������������������������������������������������������������������������������������������������������������������������������������������� 21
4�1�- DESCRIPCIÓN GENERAL ���������������������������������������������������������������������������������������������������������������������� 21 4�2�- DESCRIPTION OF THE DEVICE ������������������������������������������������������������������������������������������������������������ 22 4�3�- LEDs INDICATORS ��������������������������������������������������������������������������������������������������������������������������������� 22 4�4�- KEYBOARD FUNCTIONS �����������������������������������������������������������������������������������������������������������������������23 4�5�- DISPLAY �������������������������������������������������������������������������������������������������������������������������������������������������� 24 4�6�- OPERATION �������������������������������������������������������������������������������������������������������������������������������������������� 25 4�7�- TROUBLESHOOTING OR REASONS FOR TRIPPING ������������������������������������������������������������������������� 26
4�7�1�- POOR TOROID CONNECTION TRIP �����������������������������������������������������������������������������������������������26
4�7�2�- PRE-ALARM TRIP ����������������������������������������������������������������������������������������������������������������������������26 4�7�3�- FAULT TRIP ���������������������������������������������������������������������������������������������������������������������������������������27
4�7�4�- REMOTE TRIP ����������������������������������������������������������������������������������������������������������������������������������� 27
5�- CONFIGURATION �����������������������������������������������������������������������������������������������������������������������������������������28
5�1�- DIRECT SETTING �����������������������������������������������������������������������������������������������������������������������������������28
5�1�1�- SETTING THE SENSITIVITY TRIP ���������������������������������������������������������������������������������������������������28
5�1�2�- DELAY SETTING AND MAIN RELAY CURVE ����������������������������������������������������������������������������������28
5�1�3�-POSITIVE SECURITY SETTING OF THE MAIN RELAY ������������������������������������������������������������������� 29
5�1�4�- SETTING THE PRE-ALARM RELAY ������������������������������������������������������������������������������������������������ 29 5�2�- SETTING BY SETUP �������������������������������������������������������������������������������������������������������������������������������31 5�3�- CONFIGURATION THE MEASUREMENT SETUP ��������������������������������������������������������������������������������� 32
5�3�1�- OPERATING FREQUENCY ��������������������������������������������������������������������������������������������������������������32
5�3�2�- SCALE LIMIT �������������������������������������������������������������������������������������������������������������������������������������33 5�4�- CONFIGURATION THE COMMUNICATION SETUP ������������������������������������������������������������������������������ 33
5�4�1�- PERIPHERAL NUMBER �������������������������������������������������������������������������������������������������������������������34
5�4�2�- BAUD RATE ��������������������������������������������������������������������������������������������������������������������������������������34
5�4�3�- PARITY ����������������������������������������������������������������������������������������������������������������������������������������������35
6�- RS-485 COMMUNICATIONS ���������������������������������������������������������������������������������������������������������������������������36
6�1�- CONNECTIONS ��������������������������������������������������������������������������������������������������������������������������������������� 36 6�2�- MODBUS PROTOCOL ����������������������������������������������������������������������������������������������������������������������������37
6�2�1� READ EXAMPLE: Function 0x04� ���������������������������������������������������������������������������������������������������37
6�2�2� WRITE EXAMPLE : Function 0x10� �������������������������������������������������������������������������������������������������� 38 6�3�- MODBUS COMMANDS ���������������������������������������������������������������������������������������������������������������������������38
7�- TECHNICAL FEATURES ��������������������������������������������������������������������������������������������������������������������������������40 8�- TECHNICAL SERVICE �����������������������������������������������������������������������������������������������������������������������������������42 9�- WARRANTY �����������������������������������������������������������������������������������������������������������������������������������������������������42 10�- CE CERTIFICATE ������������������������������������������������������������������������������������������������������������������������������������������ 43
5
Instruction Manual
REVISION LOG
Table 1: Revision log�
Date Revision Description
5/18 M98203201-03-18A New Version
Note: The images of the devices are for illustrative purposes only and might differ from the original device.
SYMBOLS
Table 2: Symbols�
Symbol Description
In compliance with the relevant European directive.
The device complies with the 2012/19/EC European directive. Do not dispose of the device in a household waste container at the end of its useful life. Observe the local electronic device recycling regulations.
Direct current.
~
Alternating current.
6
Instruction Manual
1�- VERIFICATIONS UPON RECEPTION
The following must be checked upon reception of the device:
a)Thedevicehasbeensuppliedaccordingtothespecicationsinyourorder.
b) The device has not been damaged during transport. c) Perform an external visual inspection of the device before connecting it. d) Check that it has been supplied with the following:
- An installation guide.
Immediately contact the carrier and/or CIRCUTOR’s after-sales service if you detect any problem in the device upon reception.
2�- DESCRIPTION OF THE PRODUCT
The RGU-10 earth leakage relay is type A programmable electronic earth leakage protection device with two independent relays: the main output for checking the cut off device and perform­ing the protection function and the pre-alarm relay for installation prevention and maintenance.
Allows the setting and adjustment of all parameters required for complete protection and main­tenance checking in the installation. A series of parameters may be set directly from the key­board (buttons) and by setting menus on the device itself.
Before starting the earth leakage device carefully read sections: power supply, connection dia­gram and setting.
The RGU-10 measures, calculates and displays the earth leakage current in three-phase, bal­anced or unbalanced industrial systems.
Measurements are in true effective value, via one earth leakage current input, from the WGC family external measuring toroid.
Under normal operating conditions the main values determining earth leakage protection in an installation are shown on the display. These include sensitivity, delay and instant current leak­age. Bearing in mind the high degree of protection required by installations, the device has a display
7
Instruction Manual
and LED indicators for the different events which usually occur.
Datadisplayedorpre-alarmindication,trips,leakagereadings,etc.assistinprovidingsufcient
information for proper maintenance.
Under normal operating conditions the backlit display is green. However, after any event caus­ing a main relay to trip, the backlight is red, indicating the reason.
The version for RS-485 communications (RGU-10C) and appropriate software allows setting, data and information to centralised for the proper monitoring and checking of the maintenance of electricity lines.
The measurement of earth leakage current from which the RGU-10/RGU-10C operates by indicating the instant leakage current, pre-alarm or trip is determined by the WGC series earth leakagetransformers.Theinnerdiameterofthetransformerisdenedbytheinstallation’swir­ing dimensions.
There are 2 models of the device:
RGU-10, without communications.
 RGU-10C, with communications RS-485.
Main features:
- Measuring in true effective value (TRMS)
- Type A differential (IEC 61008.1)
- Insulation against transients (IEC 61008.1)
-Highfrequencyltering(IEC61008.1)  -Tripsettingbetween80and100%I∆n
- Inverse curve (IEC 61008.1)
- Associated standard : IEC 61008.1, IEC755
- 3 modules. DIN rail. In a panel using front accessory
- Displaying instant leakage values.
- Backlit LCD display.
- RGU-10C Model : Built-in RS485 communications (Modbus RTU®).
8
Instruction Manual
3�- INSTALLING THE DEVICE
3.1.- PRELIMINARY RECOMMENDATIONS
The operators using and handling the device must follow the safety measures established in the country where the device will be used to guarantee its safe operation, using personal protective equipment if needed.
The RGU-10devicemustbeinstalledbyauthorisedandqualiedstaff.
Disconnect the device from the mains and disconnect the measuring devices before handling, changing the connections of or replacing the device. Handling the device while it is connected is hazardous to people nearby.
The cables must be in perfect working order to prevent accidents or injuries to people and/or damage to the facilities/installations.
Limittheoperationofthedevicetomeasuringthespeciedcurrentorvoltagevalues.
The manufacturer of the device shall not be held responsible for any damage resulting from the user or installation company failing to observe the warnings and/or recommendations indicated in this manual nor for any damage resulting from the use of non-original products or accesso­ries or those from other brands.
Do not use the device to take measurements if you detect an anomaly or malfunction.
Check the environment in which the device is installed before taking a measurement. Do not use the device to take measurements in dangerous, explosive, wet or damp environments.
Disconnect the device from the mains and from the power supply (both the device and its measuring system) before performing any maintenance work, repairs or handling any of the connections of the device. Contact the after-sales service if you detect that the device is not working prop­erly.
9
Instruction Manual
3.2.- INSTALLATION
While the device is connected, the terminals, opening the cover or removing el­ements can expose parts that are hazardous to the touch. The device must not be used until the installation process is complete.
The device is installed on a DIN rail or on a panel (drilled panel 67+1 x 67+1mm, according to DIN 43 700 using accessory). All connections must remain inside the electrical board.
3�2�1�- INSTALLATION OF DEVICE IN PANEL
A 72x72 mm front adapter accessory is used to install the device on a panel. All connections must remain inside the electrical board.
The front adapter accessory has a base, a frame two tabs and three screws, Figure 1.
Figure 1:Adapter accessory�
The steps to follow to perform the installation of the adapter accessory are:
1�- The base is mounted on top of the device.
2�- The device is attached by screwing the holes in the device on the upper right corner and
lower left corner on the front of device.
3�- The front frame is attached to cover the mounting points.
4�- Three green pressure tabs on the side runners of the base are attached.
5�- The device is mounted in the hole in the panel with the adapter.
6�- The tabs run towards the panel to obtain the mounting pressure.
10
Instruction Manual
Figure 2: Installation of adapter accessory
3.3.- TERMINALS OF THE DEVICE
Table 3:Terminal description RGU-10�
Terminals of the device 1: Voltage input ON/OFF external L 9: Toroid current input 1S2 2: Voltage input ON/OFF external N 10: Power supply voltage input A1 4: Output common contact pre-alarm 11: Power supply voltage input A2 5: NC output contact pre-alarm 13: NO output contact trip 6: NO output contact pre-alarm 14: NC output contact trip 8: Toroid current input 1S1 15: Output common contact trip
Note: Terminals 3, 7 and 12 are free.
Figure 3: RGU-10 terminals�
11
Instruction Manual
3.4.- CONNECTION DIAGRAMS
Note : It is recommended that meshed cable is used to connect the toroid over large distances.
3�4�1�- CONNECTION WITH CURRENT EMISSION COIL
3�4�1�1�- Powering the device before the breaking device
In the event of powering the device before the breaking device (automatic switch) in an earth leakage trip situation because of a fault, test or toroid error:
1�- Note the cause of the trip on the red display. 2�- Reset the breaking device. 3�- Press the RESET device.
NL1 L2
L3
1S1
1S2
Type
WGC
1S 1
1S 2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
ON / OFF externo
External ON / OFF
Disparo por BOBINA DE EMISIÓN
- Rearme Manual
Trip by SHUNT COIL
- Manual reclose
Figure 4: 24 ��� 230 Vac power supply
12
Instruction Manual
L1 L2
L3
1S1
1S2
Type
WGC
1S 1
1S 2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
Reset exterior
External Reset
Disparo por BOBINA DE EMISIÓN
- Rearme Manual
Trip by SHUNT COIL
- Manual reclose
Figure 5: 400 Vac power supply
13
Instruction Manual
3�4�1�2�- Powering the device after the breaking device
The following has to be taken into consideration in the event of powering device after the break­ing device.
1�- The breaking device has to be a manually resettable device. 2�- After dripping, the device is disconnected losing all information on the reasons for the trip.
The system is reset only by resetting the breaking device. It is reconnected by the power supply.
NL1 L2
L3
1S1
1S2
Type
WGC
1S 1
1S 2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
ON / OFF externo
External ON / OFF
Disparo por BOBINA DE EMISIÓN
- Rearme Automático mediante corte de alimentación
Trip by SHUNT COIL
- Automatic reclose by power supply out
Figure 6: 24 ��� 230 Vac power supply
14
Instruction Manual
L1 L2
L3
1S1
1S2
Type
WGC
1S 1
1S 2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
Disparo por BOBINA DE EMISIÓN
- Rearme Automático mediante corte de alimentación
Trip by SHUNT COIL
- Automatic reclose by power supply out
Reset exterior
External Reset
Figure 7: 400 Vac power supply
The device operates to its maximum whenever it is supplied from the installation itself before the breaking device or from an independent auxiliary power supply. However if the power sup­ply from the installation is below the breaking device the system continues to be properly pro­tected even though with limitations in terms of its disconnection performance through lack of power supply.
15
Instruction Manual
3�4�1�3�- Power supply of the device independent of the installation
NL1 L2
L3
1S1
1S2
Type
WGC
1S
1 1S
2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
ON / OFF externo
External ON / OFF
Disparo por BOBINA DE EMISIÓN
- Rearme Manual
Trip by SHUNT COIL
- Manual reclose
+
-
Figure 8: 24 ��� 120 Vdc power supply
16
Instruction Manual
3�4�2�- CONNECTION WITH UNDERVOLTAGE COIL
3�4�2�1�- Powering the device before the breaking device
This breaking device may be an automatic switch or contactor. Using a Contactor the protection is reset by pressing RESET, or by using an automatic switch. The breaking device must be rearmed beforehand.
NL1 L2
L3
1S1
1S2
Type
WGC
1S 1
1S 2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
ON / OFF externo
External ON / OFF
Disparo por BOBINA DE MÍNIMA
- Rearme Manual
Trip by UNDERVOLTAGE COIL
- Manual reclose
Figure 9: 24 ��� 230 Vac power supply
17
Instruction Manual
L1 L2
L3
1S1
1S2
Type
WGC
1S
1 1S
2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
Reset exterior
External Reset
Disparo por BOBINA DE MÍNINA
- Rearme Manual
Trip by UNDERVOLTAGE COIL
- Manual reclose
Figure 10: 400 Vac power supply
18
Instruction Manual
3�4�2�2�- Power supply of the device independent of the installation
NL1 L2
L3
1S1
1S2
Type
WGC
1S 1
1S 2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
ON / OFF externo
External ON / OFF
Disparo por BOBINA DE MíNIMA
- Rearme Manual
Trip by UNDERVOLTAGE COIL
- Manual reclose
+
-
Figure 11: 24 ��� 120 Vdc power supply
19
Instruction Manual
3�4�3�- CONNECTING THE DEVICE IN POSITIVE SAFETY
This installation mode provides the most conservative protection from the point of view of per­sonal and property safety in electrical installations.
With this type of device connection and setting, persons all goods are protected against faults where the earth leakage relay loses its protection capacity. The last order from the relay is to open the installation in the event of this power supply problems to the device itself or through lack of voltage in the installation (neutral or face fault).
3�4�3�1�- Connection with undervoltage coil
1�- The breaking device has the power to trip using the undervoltage coil, either internally (con­tactor) or externally (automatic switch). 2�- The device is set by programming by pressing Std/+ key in positive safety mode. The +”symbol appears on the display. 3�- The device’s power supply has to be the same as the installation or section it is protecting.
NL1 L2
L3
1S1
1S2
Type
WGC
1S 1
1S 2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
ON / OFF externo
External ON / OFF
Disparo por BOBINA DE MÍNIMA
- Rearme Manual
Trip by UNDERVOLTAGE COIL
- Manual reclose
Figure 12: Positive safety, undervoltage coil�
20
Instruction Manual
3�4�3�2�- Connection with current emission coil
When this type of safety is used using the current emission coil, it can only be assured that the system will trip went the earth leakage relay is not operating correctly.
1�- The breaking device has the power to trip using the maximum current coil (automatic switch). 2�- The device is set by programming by pressing Std/+ key in positive safety mode. The “+
symbol appears on the display.
NL1 L2
L3
1S1
1S2
Type
WGC
1S 1
1S 2
Reset
Test
1 2 4
5 6 8 9
10
11
13
14
15
UTILIZACIÓN
USE
ON / OFF externo
External ON / OFF
Disparo por BOBINA DE EMISIÓN
- Rearme Manual
Trip by SHUNT COIL
- Manual reclose
Figure 13: Positive safety, current emission coil�
21
Instruction Manual
4�- OPERATION
4.1.- GENERAL DESCRIPTION
DIN RAIL PANEL ( ADAPTER ACCESSORY)
INSTANT CURRENT LEAKAGE DISPLAY
PRE-ALARM RELAY
RS-485 MODBUS COMMUNICATIONS
PROGRAMMING OF PARAMETERS
BACKLIT LCD DISPLAY
SMALL SIZE: 3 MODULE
OUTPUT RELAY CONTACT STATUS
SENSITIVITY from 50 ... 80% I∆N DELAY from 20 ms ... 10 seconds
SENSITIVITY from 30 mA ... 30A DELAY from 20 ms ... 10 seconds
GREEN Normal operation status.
RED Trip status by fault or other
event.
. MINIMUM Voltage
· Current EMISSION
ASSOCIATED BREAKING DEVICE
CONTACTOR. Connection by undervoltage coil
EARTH LEAKAGE DEVICE WITH TRIP COIL
TRIP COIL
ASSOCIATED MEASURING DEVICE
EARTH LEAKAGE TOROIDAL WGC FAMILY
22
Instruction Manual
4.2.- DESCRIPTION OF THE DEVICE
The front of the equipment which is formed by the display, buttons and LEDs, is protected with a sealable plastic cover which has the appropriate holes to access the RESET, TEST and PROG keys.
Generic functions of the LEDs and front keypad:
Green LED : Device on Red LED: Leakage trip
Yellow LED: Pre-alarm
Reset key
Sensitivity setting
Test key
Setup conguration Pre-alarm conguration
Reset pre-alarm setting
Safety setting
Delay setting Setup menu rotation
Figure 14: LEDs and keyboard description�
4.3.- LEDs INDICATORS
The device has 2 indicators LEDs, Figure 14.
Table 4: LEDs description: ON dual colour LED
ON Dual colour: Green - Red LED
State Description
Off The device is not operating or is not receiving power supply voltage.
Green The device is operating. It is receiving power supply voltage.
Red The device has tripped.
23
Instruction Manual
Table 5:LEDs description: Yellow LED�
Yellow LED
State Description
Off There is no pre-alarm trip. On Pre-alarm trip without reclosing. On
ashing
Pre-alarm trip in reclosing situation.
4.4.- KEYBOARD FUNCTIONS
The device has 7 keys, Figure 14.
1�- Keys accessible with sealed cover and tool�
RESET, Starts the equipment after a trip.
TEST, Carries out a trip to check the proper operation of the relay.
PROG/PAG, The function of the key depends on the duration of the touch.
Table 6:Operation of the PROG/PAG key�
Key Operation
PROG/
PAG
Short press
Access to Pre-alarm programming.
Long press
Access to the programming of the device by Setup.
2�- Keys accessible with cover raised
Keys with dual function. With a long press, the device is entered to set the values. With a short
press,theoptionwithinaseriesofvaluesdenedinthedeviceisselected.
SENSITIVITY,
It allows to choose between the values of 30, 100, 300, 500 mA, 1 and 3 A This scale can be extended using the SETUP program to add 5, 10 and 30 A to the
above values.
DELAY,
It allows to choose between the values of 20,100, 200, 300, 400, 500, 750 ms and 1s.
 This scale can be extended using the SETUP program to add 3, 5 y 10 s to the above values.  This key also allows navigation within the SETUP MENU.
3�- Keys accessible with sealed cover and tool�
Flush buttons.
SAFETY, This allows the output contacts’ polarity to be set for both the main relay and the pre-alarm.
With normal safety (Std) the relay is activated with a fault, the status is NO. With positive safety (+) the relay is activated on supplying the device and is deactivated
24
Instruction Manual
with the fault, the status is NC.
RESET PRE-ALARM, This allows the automatic re-establishment of the pre-alarm sig- nal to be enabled. In Automatic Mode (REC), if the detected leakage current is below the preset pre-alarm threshold, the relay becomes de-activated. In manual mode, the device has to be RESET from the alarm screen in order to re-es­tablish the pre-alarm system.
4.5.- DISPLAY
The device has a backlit display with green or red light, depending on the state of the device.
The background to the screen in normal mode is green. The parameters required for earth leakage protection, sensitivity and delay in its associated units are displayed. It also displays the current leakage current.
If the device trips through any event, the screen’s background changes to red and the reason for the trip is displayed.
Figure 15: Display RGU-10�
Display messages by device trip, Table 7.
Table 7: Display messages by device trip
Message Cause of trip
TESt Test
ERRt Poor toroid connection
EXT Remote signal ON/OFF
REM RS-485 Communications
Instant value Current leakage
Other display messages, Table 8.
Table 8: Other display messages�
Message Description
SAVE Validatecongurationvalues
EXIT Exits programming mode OVR Current leakage reading off scale
25
Instruction Manual
4.6.- OPERATION
When the device is powered at its rated voltage, the green LED ON the front is on, the backlit LCD is green indicating the software and hardware version. After a short while, the version disappears and the default display values appear on the display.

Figure 16:Initial screens�
The display shows the delay and sensitivity settings as well as the instant leakage current reading.
While the device is operating, the display shows the following symbols while the device is being programmed and set, Figure 17.
Conguration by communications
Trip sensitivity
Instant current leakage
Pre-alarm conguration
Pre-alarm reclosing
Contact polarity
Trip delay
Adjustment of conguration
Figure 17: Display description�
In normal operating status the display shows the following parameters associated with the earth leakage protection. Table 9�
Table 9: Parameters visible by display�
Parameter Units
Instant current leakage mA / A Programmed trip delay, td ms / s
Programmedsensitivityoftrip,Id=I∆N mA / A
Main relay contact status
+ (contact 14-15 NO) / nothing (contact 14 - 15 NC) + (contact 16-15 NC) / nothing (contact 16 - 15 NO)
26
Instruction Manual
The RGU-10/ RG5-10C allow the display and setting of all required parameters to complete the earth leakage protection adjustment with pre-alarm and communications.
Table 10: Adjustment parameters�
Parameter Units
Programmed pre-alarm trip delay ms / s
Sensitivityofpre-alarmin%I∆N %
Pre-alarm relay contact status
+ (contact 6-5 NO) / nothing (contact 6 - 5 NC) + (contact 4-5 NC) / nothing (contact 4 - 5 NO)
Operating frequency
(1)
Hz
Peripheral No
(1)
-
Baud rate
(1)
Bauds
Type of parity
(1)
-
(1)
RGU-10C only.
4.7.- TROUBLESHOOTING OR REASONS FOR TRIPPING
4�7�1�- POOR TOROID CONNECTION TRIP
After a certain time the device will carry out a test to detect the presence of the sensor or asso­ciated earth leakage transformer. Also the “ERRt” error message will permanently appear on the RGU-10 display.
A short-circuit in the transformer secondary will also be detected as an error.
When this error is detected, the correct connection with the earth leakage transformer has to be ensured and a RESET made to re-establish proper working. If the transformer is detected again, normal status is returned and the error message disappears.
Figure 18: Trip by poor toroid connection�
4�7�2�- PRE-ALARM TRIP
In the event of the defaults current exceeding the programmed pre-alarm threshold, the yellow LED will come on, the green backlit LCD will show the leakage level and the pre-alarm output relay will be activated. In automatic mode (REC) when the pre-alarm situation is removed, normal status is resumed (LED and signal relay). In manual mode, the device has to be RESET to unblock the pre-alarm.
27
Instruction Manual
4�7�3�- FAULT TRIP
When the device is tripped by a current fault, the red and yellow LED comes on and the backlit LCD is red. There remains the display of the current of the last cycle that the relay has tripped. To reconnect press RESET to return to the initial status.
Figure 19: Fault trip�
4�7�4�- REMOTE TRIP
When a trip is forced (input terminals 1-2, by applying 230 V) the device is tripped and disabled and an “EXT” message is shown on the display in red and also the LED is on. It has to remain permanently in this situation until the change in status no longer exists. It is not possible to manually reset or reset using communications.
Figure 20: Remote trip�
When it is remotely reset (input terminals 1-2, removing the 230 Vac) the equipment is recon­nected with the display backlit in green, LED ON in green as in normal status.
For the RGU-10C, a remote trip/reset can also be made via RS-485 communications. The de­vice remains tripped showing this incidence on the display with a “REM” message in red with also the LED ON. It has to remain permanently in this situation until the change in status no longer exists.
Figure 21: Remote trip via RS-485�
It is reset when the remote reset is carried out using RS-485 communications, applying 230 Vac between the remote 1-2 input terminals or by pressing the RESET button. The device is reconnected with the display backlit in green, LED ON in green as in normal status.
28
Instruction Manual
5�- CONFIGURATION
5.1.- DIRECT SETTING
By pressing for a long time on any of the direct setting buttons, PROG mode is entered (icon on isplay) and the relay’s setting may be changed. While in PROG mode if any other direct function is used (Id, td, Std/+ y Auto), the parameter for the displayed relay can also be set.
PROG mode is exited if no buttons are pressed for a while with the last setting being “SAVE”.
5�1�1�- SETTING THE SENSITIVITY TRIP
Pressing Id for more than one second, PROG appears and a setting from the list is increased
witheverypress.Thecurrentsettingisseeninsmallguresandthenewsettinginthemain gures.
Figure 22: Setting the sensitivity trip�
Possible setting values are: 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, 5 A, 10 A and 30 A. Note : The scale is limited, this is changed in the device’s SETUP. The default setting is a 3A
scale.
5�1�2�- DELAY SETTING AND MAIN RELAY CURVE
Pressing td for more than one second, PROG appears and a setting from the list including curve types is increased with every press.
Thecurrentsettingisseeninsmallguresandthenewsettinginthemaingures.
Figure 23: Delay setting�
Possible setting values are: INS curve, SEL [S] curve, 20, 100, 200, 300, 400, 500, 750 ms, 1, 3, 5 and 10 s�
Note : The scale is limited, this is changed in the device’s SETUP. The curves belong to the 1 s scale which is the default scale. Note : If the setting for I∆N is 30 mA, only instant settings are permitted: 20 ms, INS curves
29
Instruction Manual
or SEL.
5�1�3�-POSITIVE SECURITY SETTING OF THE MAIN RELAY
Std”, contacts are on standby, terminals 14 - 15 (NC) and 13 - 15 (NO). “+”, contacts change status on powering the device, the + sign is displayed. Terminals 14 -15 (NO) and 13 -15 (NC).
Figure 24: Positive security setting�
5�1�4�- SETTING THE PRE-ALARM RELAY
The PROG/PAG key control the pre-alarm relay and main relay settings using SETUP.
If the button is pressed for a short time the pre-alarm setting is entered. “Alarm” appears on the display. Also the pre-alarm threshold appears as a % of the sensitivity setting and the pre-alarm delay. To exit press PROG.
Figure 25: Setting the pre-alarm relay�
5�1�4�1�- Setting of the pre-alarm current
This is in terms of the program value in the main relay. Pressing Id enters to change the value. Relative values are shown as a % of the preset trip current. Pressing Id changes the values: OFF, 50, 60, 70, 80 and MAIN� Where: OFF: pre-alarm disabled MAIN: the pre-alarm continues to trip the main channel.
Figure 26: Setting of the pre-alarm current�
30
Instruction Manual
5�1�4�2�- Pre-alarm time setting
This is in terms of the program value in the main relay. Pressing td enters to change the values. Pressing td changes the values: 20, 50, 75, 100, 300, 500, 750 ms, 1, 3, 5 and 10 s�
Figure 27: Pre-alarm time setting�
5�1�4�3�- Pre-alarm positive safety setting
Std”, contacts are on standby . Terminals : 4 - 5 (NC) and 6 - 5 (NO). “+”, contacts change status on powering the device, the + sign is displayed. Terminals :4 – 5 (NO) and 6 – 5 (NC).
Figure 28: Pre-alarm positive safety setting�
5�1�4�4�- Reset pre-alarm setting
In the pre-alarm menu the REC function is shown as disabled or enabled. REC appears on the display when it is enabled.
Figure 29: Reset pre-alarm setting�
31
Instruction Manual
5.2.- SETTING BY SETUP
PROG”andtherstmenu option appearonthedisplaybypressingalongtimethePROG/ PAG key. Once in menu setting mode, the different text indicators appear on the display after each time PROG is pressed.
When the correct menu is reached, the parameter can be changed by pressing td (rotating). In order to enter the settings press the PROG but on again with the “SAVE” message showing the version of the device. The display the turns to the initial screen.
If, after a certain time, the keyboard remains inactive the “EXIt” message appears and the main relay settings are shown without any information being saved.
A�- RGU-10C congurationmenu
PROG
td
PROG
PROG
td
td
td
PROG
td
PROG
td
td
PROG
Figure 30: RGU-10C conguration menu.
32
Instruction Manual
B�- RGU-10 congurationmenu
PROG
td
PROG
td
td
PROG
Figure 31: RGU-10 conguration menu.
5.3.- CONFIGURATION THE MEASUREMENT SETUP
From measurement SETUP, the parameter settings for the RGU-10/RGU-10C can be displayed and/or changed; this may match these parameters to the requirements of the system topologies and/or applications If it is an RGU-10C, this SETUP menu is preceded by the communications SETUP menu. If there is no communications, RGU-10, is the only SETUP on the device.
The device does not save the setting changes until all of the setting has been entered using the PROG key. When it detects that the keyboard has been inactive for a certain time it displays “EXIt” and the setting menu is exited it without saving the changes.
Onenteringcongurationmode,ascreenisdisplayedinformingthatthedevicehasentered congurationmodewiththePROGsymbolontheuppersectionoftherstmenuscreen.
5�3�1�- OPERATING FREQUENCY
The display shows FREQ. In order to change this press PROG. The value of the current frequency appears on the upper left of the screen
In order to change the operating frequency, repeatedly press the td button increase in the digit in the upper left corner.
When the value on the screen is the required value, enter and move onto the next menu by pressing the PROG key. SETUP is exited with the SAVE message.
33
Instruction Manual
5�3�2�- SCALE LIMIT
The display shows LIM. In order to change this press PROG.Thenaldelayscalevaluesand the actual current sensitivity settings appear on the upper section of the screen.
In order to modify the operational scale, repeatedly press the td button increasing the values of the digits on the upper section of the screen. There are two scales, one in 10 seconds and 30 A and the other default scale in 1 second and 3 A.
When the required values are shown on the screen they are entered by pressing the PROG button. SETUP is exited with the SAVE message.
5.4.- CONFIGURATION THE COMMUNICATION SETUP
Note: Only for RGU-10C models.
One or more RGU-10C devices may be connected to a computer or PLC in order to automate a production process or an energy control system. As well as the usual operation of each device, this system may centralize data at one single point; for this reason the RGU-10C has an RS­485 communication output.
If more than one device is connected to one single series line (RS-485), it is necessary to as­sign to each a number or address (from 1 to 99) so that the central computer or PLC sends the appropriate requests to these addresses for each peripheral.
From communication SETUP, the RGU-10C’s communication parameters may be displayed and/or changed; this may match these parameters to the requirements of the system topologies and/or applications.
The device does not save the setting changes until all of the setting has been entered using the PROG button. When it detects that the keyboard has been inactive for a certain time it displays “EXIt” and the setting menu is exited it without saving the changes.
To access communications SETUP press the PROG key.
On entering setting mode a screen is displayed showing that the device has entered commu­nication setting mode.
34
Instruction Manual
To enter setting mode the PROG key must be pressed.
5�4�1�- PERIPHERAL NUMBER
The display shows PERI and the peripheral number on the upper left of the screen.
To write or change the number of the peripheral repeatedly press the td button, increasing the value of the digit which is in the upper left corner.
When the required value is on the screen, it is entered and the display moves on to the next menu by pressing PROG key, to allow the remaining values to be changed.
The peripheral number varies between 1 and 99.
5�4�2�- BAUD RATE
The display shows the letters “bd” on the upper left of the screen showing the bauds and shows the baud rate in units of a thousand in the central part of the screen.
Repeatedly press the td button to change the baud rate, increasing the value of a digits on the central area of the screen.
When the required value is on the screen, move on to the following digit by pressing PROG, to allow the remaining values to be changed.
The possible setting values are as follows:
35
Instruction Manual
Table 11: Baud rate�
Value on screen Bauds
2.4
2400
4.8
4800
9.6 9600
19.2 19200
38.4
38400
54.6 54600 115
115000
5�4�3�- PARITY
The display shows “PARI” with the set a value on the upper left of the screen.
In order to change parity, repeatedly press the td key to change the values on the upper left of the screen.
When the required value is on the screen, it is entered and the display moves on the next screen by pressing PROG, to allow the setting to be changed.
ForcommunicationsettingmenuusingSETUPendsonthisscreen.Itdirectlylinkswiththerst
measurement SETUP screen on the device.
36
Instruction Manual
6�- RS-485 COMMUNICATIONS
RGU-10C devices feature one RS-485 communications port. The device has uses the MOD­BUS RTU communications protocol as the standard protocol.
6.1.- CONNECTIONS
The RS-485 cable must be wired with twisted pair cable with mesh shield (minimum 3 wires), with a maximum distance between the RGU-10C and the master device of 1200 metres. Up to 32 RGU-10C devices can be connected to this bus.
Use an intelligent RS-232 to RS-485 network protocol converter to establish the communications with the master device.
B(-) A(+)
S (GND)
B(-)A(+) S
RS-232 / USB / Ethernet / Profibus ...
PC
RS-485
RS-485
RS-232 USB Ethernet Profibus ...
Figure 32: RS-485 Connection diagram�
37
Instruction Manual
6.2.- MODBUS PROTOCOL
In the Modbus protocol, the RGU-10C uses the RTU (Remote Terminal Unit) mode. The Modbus functions implemented in the device are as follows:
Function 0x04: Reading integer registers. Function 0x10: Writing multiple registers.
6�2�1� READ EXAMPLE: Function 0x04�
Query:
Address Function
Initial
Register
No� of
registers
CRC
0A 04 0000 000A 7176
Address: 0A, Peripheral number: 10 in decimal. Function: 04, Read function. Initial Register:0000, register from which to start reading. No� of Registers: 000A, number of registers to be read: 10 in decimal. CRC: 7176, CRC character.
Response:
Address Function
No� of Bytes
Registers
CRC
nº 1 nº 2 nº 3 nº 4 nº 5 nº 6 nº 7 nº 8 nº 9 nº 10
0A 04 14 000A 0002 0000 0032 0000 0001 0000 0001 0014 0000 7EC9
Address: 0A, Responding peripheral number: 10 in decimal. Function: 04, Read function. No� of bytes: 14, No. of bytes received: 20 in decimal. Registers: 000A, Address 0000h: Peripheral number : 10 0002, Address 00001h: Baud rate : 2 = 9600 bds 0000, Address 00002h: Type of parity : 0 = None 0032, Address 00003h: Operating frequency : 50 Hz 0000, Address 00004h: Trip current : 0 = 30 mA 0001, Address 00005h: Time for trip delay : 1 = INS 0000, Address 00006h: Relay output trip polarity : 0 = Standard
0001, Address00007h:%I∆ntripbypre-alarm.:1=50% 0014, Address 00008h: Time for pre-alarm delay: 1 = 20ms 0000, Address 00009h: Pre-alarm output relay polarity : 0 = Standard CRC: 7EC9, CRC character.
Note : Each Modbus frame has a maximum limit of 26 registers.
38
Instruction Manual
6�2�2� WRITE EXAMPLE : Function 0x10�
Query:
Address Function
Initial
Register
No� of
registers
Nº de Bytes
Registers
CRC
Nº1 Nº2 Nº3 Nº4 Nº5
01 10 0000 0005 0A 0001 0003 0000 003C 0000 FF64
Address: 01, Peripheral number: 1. Function: 10, Writing multiple registers.
Initial Register: 0000, Initial register of writing.
No� of bytes: 0A, No of bytes that are sent: 10 Registers : 0001, Address 0000h: Peripheral number : 1 0003, Address 00001h: Baud rate : 3 = 19200 bds 0000, Address 00002h: Type of parity : 0 = None 003C, Address 00003h: Operating frequency : 60 Hz 0000, Address 00004h: trip current : 0 = 30 mA CRC: FF64, CRC character.
Response:
Address Function
Initial
Register
No� of
registers
CRC
01 10 0000 0005 000A
Nota : Each Modbus frame has a maximum limit of 26 registers.
6.3.- MODBUS COMMANDS
All Modbus map addresses are expressed in hexadecimal.
Table 12: Modbus memory map
Parameter Symbol Address
Reading /
Writing
Values Units
Peripheral No. PERI 0000 R/W 1 - 99 -
Baud rate bd 0001 R/W
2400-4800-9600-19200-
38400-57600-115200
bauds
Type of parity PARI 0002 R/W None - Odd - Even -
Operating frequency FREC 0003 R/W 50 - 60 Hz
Trip current Main relay Id 0004 R/W
0.03 - 0.1- 0.3 - 0.5 - 1 ­3 - 5 - 10
A
Delay time Main relay td 0005 R/W
INS - SEL - 0.02 - 0.1 -
0.3 - 0.4 - 0.5 - 0.75 - 1
- 3 - 5 -10
s
Contact polarity Main relay Std/+ 0006 R/W Standard - Positive -
Trip current Pre-alarm Id’ 0007 R/W OFF - 50 - 60 - 70 - 80 %
Delay time Pre-alarm td’ 0008 R/W
0.02 - 0.1 - 0.2 - 0.3 - 0.4
- 0.5 - 0.75 -1 - 3 - 5 - 10
s
Contact polarity Pre-alarm Std/+ 0009 R/W Standard - Positive -
Pre-alarm reclosing REC 000A R/W Manual - REC -
39
Instruction Manual
Table 12 (Continuation) : Modbus memory map
Parameter Symbol Address
Reading /
Writing
Values Units
Series No. (HI) - 000B R 18AD - 188C -
Series No. (LO) - 000C R 0000 - FFFF -
Device version - 000D R 0 -100 -
Relay contacts status - 0014 R
off - on (main)
on (pre-alarm)
-
Effective value Current leakage - 0015 R 0 - 65.000 mA
Effective value Trip current. - 0016 R 0 - 65.000 mA
Trip and external reset - 0019 W
0000 : Reset
FFFF : Test
-
Enable setting saving - 001A W
0000 : Enable
FFFF : Save
-
40
Instruction Manual
7�- TECHNICAL FEATURES
Power supply CA
Rated voltage
(2)
230 V ~ ± 20% 110 V ~± 20% 400 V ~ ± 20% 24 ... 48 V ~
Frequency 50 - 60 Hz Consumption 6 VA
Power supply CC
Rated voltage
(2)
24 ... 125 V
Consumption 4 W
(2)
Depending on model.
Main relay / Pre-alarm output Rated current 6 A ~ Maximum instant current 10 A ~ Rated voltage 230 V ~ / 400 V ~
(2)
Maximum switching voltage 250 V ~ Rated load in CA 2500 VA Contacts protected by varistor 275 V ~ Mechanical useful life 10 x 10
6
Ambient temperature range - 40 ... 85 ºC
Electrical useful life for AC loads
Cut off power for DC loads
Note: Circutor guarantees that the RGU-10 / RGU-10C device complies with a response time of less than 30 ms to 5In, and in combination with the selected cutting element must guarantee a total cut-off time of less than 40 ms to comply with the IEC 60947-2-M standard.
External voltage input ON/OFF Type Optocoupled Maximum voltage
(1)
110 - 230 V ~± 20%
Maximum power 0.7 W
Earth leakage current measurement circuit
Scale range Full scale Resolution Display
30 mA 75 mA ± 1 mA
300 mA 750 mA ± 1 mA
3 A 7.5 A ± 0.1 A
30 A 75 A ± 1 A
41
Instruction Manual
Communications ( RGU-10C model) Bus RS-485 Communications protocol Modbus RTU Baud rate 2400 - 4800 - 9600 - 19200 - 38400 - 57600 - 115200 bauds Stop bits 1 Parity without - even - odd
User interface Display LCD Keyboard 7 keys LED 2 LEDs
Environmental features Operating temperature -10ºC ... +50ºC Relative humidity (without condensation) 5 ... 95% Maximum altitude 2000 m
Protection degree
Mounted device: IP41 (Frontal)
Device without mounted : IP20 (Sides and back cover)
Mechanical features Dimensions Figure 33 Weight 236 g. Enclosure V0 self-extinguishing plastic Fijación DIN rail
Connections
7 mm 0.127 ... 2.082 mm
2
0.5 ... 0.6 Nm stair road 0.4x2.5x80 mm
52,5
67,9
43,5
45
85
Figure 33: RGU-10 dimensions�
Safety / Standard Designed for installations category III 300 V~ (EN 61010) Protection against electric shock by class II double insulation� Electrical accessories - Residual current monitors for household and
similar uses (RCMs)
IEC 62020
Low-voltage switchgear and controlgear -- Part 2: Circuit-breakers IEC 60947-2-M General requirements for residual current operated protective devices IEC 60755 Residual current operated circuit-breakers without integral overcu-
rrent protection for household and similar uses (RCCBs) - Part 1: Ge­neral rules
IEC 61008-1
42
Instruction Manual
8�- TECHNICAL SERVICE
9�- WARRANTY
No returns will be accepted and no unit will be repaired or replaced if it is not ac-
companied by a report indicating the defect detected or the reason for the return.
•The guarantee will be void if the units has been improperly used or the stora­ge, installation and maintenance instructions listed in this manual have not been
followed.“Improperusage”isdenedasanyoperatingorstorageconditioncon-
trary to the national electrical code or that surpasses the limits indicated in the technical and environmental features of this manual.
CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the installation, nor will it cover any possible sanctions derived from a pos­sible failure, improper installation or “improper usage” of the unit. Consequently, this guarantee does not apply to failures occurring in the following cases:
- Overvoltages and/or electrical disturbances in the supply;
-Water,iftheproductdoesnothavetheappropriateIPclassication;
- Poor ventilation and/or excessive temperatures;
- Improper installation and/or lack of maintenance;
-Buyerrepairsormodicationswithoutthemanufacturer’sauthorisation.
CIRCUTOR
guarantees its products against any manufacturing defect for two years after the
delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee period.
In the case of any query in relation to device operation or malfunction, please contact the
CIRCUTOR, SA Technical Support Service.
Technical Assistance Service
Vial Sant Jordi, s/n, 08232 - Viladecavalls (Barcelona) Tel: 902 449 459 ( España) / +34 937 452 919 (outside of Spain) email: sat@circutor.com
43
Instruction Manual
10�- CE CERTIFICATE
44
Instruction Manual
45
Instruction Manual
CIRCUTOR, SA Vial Sant Jordi, s/n 08232 - Viladecavalls (Barcelona) Tel: (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14 www.circutor.es central@circutor.com
Loading...