CIRCUTOR OPTIM P-P User Manual

Low voltage capacitor banks switched by
contactors.
OPTIM P&P Series
INSTRUCTION MANUAL
(M063B01-03-15A)
OPTIM P&P Series
2
Instruction Manual
OPTIM P&P Series
Follow the warnings described in this manual with the symbols shown below.
DANGER
Warns of a risk, which could result in personal injury or material damage.
ATTENTION
Indicates that special attention should be paid to a speci c point.
If you must handle the unit for its installation, start-up or maintenance, the following should be taken into consideration:
Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit. In particular, handling with voltages applied may result in electric shock, which may cause death or serious injury to personnel. Defective installation or maintenance may also lead to the risk of  re. Read the manual carefully prior to connecting the unit. Follow all installation and maintenance instructions throughout the unit’s working life. Pay special attention to the installation stan­dards of the National Electrical Code.
Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result in injury or damage to the unit and /or installations.
CIRCUTOR, SA reserves the right to modify features or the product manual without prior noti cation.

DISCLAIMER

CIRCUTOR, SA reserves the right to make modi cations to the device or the unit speci ca-
tions set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device speci cations and the most updated manuals.
www.circutor.com
Instruction Manual
3
OPTIM P&P Series

CONTENTS

SAFETY PRECAUTIONS .......................................................................................................................................3
DISCLAIMER ..........................................................................................................................................................3
CONTENTS ............................................................................................................................................................. 4
REVISION LOG .......................................................................................................................................................5
1.- VERIFICATION UPON RECEPTION ................................................................................................................. 6
1.1.- RECEPTION PROTOCOL .......................................................................................................................... 6
1.2.- TRANSPORT AND HANDLING .................................................................................................................6
1.3.- STORAGE...................................................................................................................................................7
2.- PRODUCT DESCRIPTION ................................................................................................................................ 8
3.- INSTALLATION .................................................................................................................................................8
3.1.- PRELIMINARY RECOMMENDATIONS .....................................................................................................8
3.2.- PREPARATION ...........................................................................................................................................9
3.3.- INSTALLATION LOCATION ..................................................................................................................... 10
3.4.-CONNECTION OF THE CAPACITOR BANK TO THE MAINS ................................................................. 10
3.5.-POWER CIRCUIT ...................................................................................................................................... 11
3.6.- EXTERNAL CIRCUIT BREAKER AND PROTECTION ELEMENTS .......................................................11
3.7.- AUXILIARY CONTROL VOLTAGE ...........................................................................................................11
3.7.1. CAPACITOR BANK WITH AUXILIARY VOLTAGE OBTAINED FROM AN INTERNAL AUTO-
TRANSFORMER ..........................................................................................................................................12
3.7.2. CAPACITOR BANK WITH AUXILIARY VOLTAGE OBTAINED BETWEEN PHASE-NEUTRAL......12
3.8.- EARTH CABLE CONNECTION ...............................................................................................................13
3.9.- CURRENT TRANSFORMER (CT) CONNECTION .................................................................................13
4.- CAPACITOR BANK START-UP ..................................................................................................................... 15
4.1.- BEFORE START-UP .................................................................................................................................15
4.2.- START-UP .................................................................................................................................................15
4.3.- CHECKS ONCE THE CAPACITOR BANK HAS BEEN CONNECTED AND THE REGULATOR ......... 17
5.- MAINTENANCE ............................................................................................................................................... 18
5.1.- SAFETY REGULATIONS ......................................................................................................................... 18
5.2.- MAINTENANCE WITH THE CAPACITOR BANK DISCONNECTED ...................................................... 18
5.2.1. BASIC MAINTENANCE PROTOCOL ................................................................................................18
5.2.2. TIGHTENING TORQUE OF THE ELECTRICAL CONNECTIONS ..................................................... 19
5.2.3. KEY POINTS FOR INSPECTING CONTACTORS ............................................................................. 19
5.2.4. KEY POINTS FOR INSPECTING CAPACITORS ............................................................................... 20
5.2.5. KEY POINTS FOR INSPECTING THE REGULATOR ....................................................................... 20
5.2.6. CLEANING THE CABINET ................................................................................................................21
5.3.- MAINTENANCE WITH THE CAPACITOR BANK CONNECTED ........................................................... 21
5.3.1. REGULATOR CHECKS ...................................................................................................................... 22
5.4.- ENVIRONMENTAL CONDITIONS ............................................................................................................ 22
6.- TECHNICAL FEATURES ................................................................................................................................ 23
7.- STANDARD ELECTRICAL DIAGRAMS ......................................................................................................... 24
8.- MAINTENANCE AND TECHNICAL SERVICE ................................................................................................ 33
9.- GUARANTEE ...................................................................................................................................................33
10.- CE CERTIFICATE .......................................................................................................................................... 34
4
Instruction Manual
OPTIM P&P Series

REVISION LOG

Table 1: Revision log.
Date Revision Description
02/15 M063B01-03-15A Initial Version
Note: The images of the units are solely for the purpose of illustration and may differ from the original unit.
Instruction Manual
5
OPTIM P&P Series

1.- VERIFICATION UPON RECEPTION

1.1.- RECEPTION PROTOCOL

Check the following points when you receive the unit:
a) The unit meets the specications described in your order. b) The unit has not suffered any damage during transport. c) Perform an external visual inspection of the unit prior to switching it on. d) Check that it has been delivered with the following:
- The unit manual
- The installed regulator manual.
If any problem is noticed upon reception, immediately contact the transport company and/or CIRCUTOR's after-sales service.

1.2.- TRANSPORT AND HANDLING

The transport, loading and unloading and handling of the unit must be carried out with proper precautions and using the proper manual and mechanical tools so as not to damage it. If the unit is not to be immediately installed, it must be stored at a location with a rm and level oor, and the storage conditions listed in the technical features section must be observed. In this case, it is recommended that the unit be stored with its original protective packaging.
To move the unit a short distance, the unit's oor support proles facilitate handling with a pallet jack or forklift. (Figure 1)
Figure 1: Transport with pallet jack.
The centre of gravity of some units may be found at a considerable height. Therefore, when handling with a forklift, it is recommended that the unit be securely fastened and that no abrupt manoeuvres made. The unit should not be lifted more than 20 cm off the ground
6
Instruction Manual
OPTIM P&P Series
When unloading and moving the unit, use a forklift with forks long enough to support the entire length of the base. Otherwise, the forks should be long enough to support at least ¾ of said depth. The forks must be at and supported rmly by the base. Raise the cabinet by placing the forks underneath the prole that supports the unit. (Figure 2).
There might be an offset in the centre of gravity from the centre of the cabinet, as a result of the uneven distribution of loads inside the unit. The necessary precautions must be taken to prevent the unit from tipping over during abrupt operations.
Figure 2: Unloading with a forklift.

1.3.- STORAGE

The following storage recommendations must be followed for the hybrid capacitor banks:
Avoid placing them on uneven surfaces.
Do not store them in outdoor areas, humid areas or areas exposed to splashing
water.
Avoid hot spots (maximum ambient temperature: 40 ºC) Avoid salty and corrosive environments.
Avoid storing the units in areas where a lot of dust is generated or where the risk of
chemical or other types of contamination is present.
 Do not place any weight on top of the unit cabinets.
Instruction Manual
7
OPTIM P&P Series

2.- PRODUCT DESCRIPTION

The purpose of this manual is to assist during the installation, start-up and maintenance of OPTIM P&P series low voltage (LV) capacitor banks switched by contactors. Carefully read the manual to achieve the best performance from those units.

3.- INSTALLATION

3.1.- PRELIMINARY RECOMMENDATIONS

In order to use the unit safely, it is critical that individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use the personal protective equipment necessary, and pay attention to the vari­ous warnings indicated in this instruction manual.
Installation or maintenance personnel should read and understand this manual before operating the unit. A copy of this manual should always be available to maintenance personnel for reference purposes
Connecting the unit to the public mains must be carried out in compliance with the EN-IEC60204-1 standard, regarding the safety of LV electrical installations.
It is recommended that several personnel are present when handling the unit for installation or maintenance. If damage or faults are detected during unit operation, or in circumstances that compromise safety, immediately stop work in that area and disconnect the unit in order to check it without voltage.
The manufacturer of the unit is not responsible for any damage resulting from failure by the user or installer to heed the warnings and/or recommendations set out in this manual, nor for damage resulting from the use of products or accessories that did not come with the unit or that were made by other manufacturers.
If an anomaly or malfunction is detected in the unit, do not use it to perform any operation.
Modifying, upgrading or rebuilding the unit without written authorisation from the manufacturer is prohibited.
The installation, operation and maintenance of low voltage (LV) units must only be carried out by authorised installers. LV regulations (Art. 22) specically dene the requirements that authorised installers must meet.
8
Instruction Manual
OPTIM P&P Series
Do not access the active elements of a capacitor bank with static operation that has been powered and might have voltages present. Wait at least 5 minutes af­ter the power supply has been disconnected.
Do not touch the terminals or active parts of the unit until you have veried that voltage is not present. If you have to handle or touch the terminals or other control panel components, use adequately insulated personal protection equipment and tools.
After any maintenance and before re-connecting the power supply to the unit, check that its enclosure is properly closed and that no items or tools were left inside that could cause a short-circuit.
Do not disconnect the current transformer secondary without short-circuiting it rst. The operation of a current transformer with an open secondary will cause an overvoltage that could damage it and electrocute the person handling it.

3.2.- PREPARATION

The CIRCUTOR OPTIM P&P static capacitor banks come ready for easy installation and start­up.
Remove the packaging of the unit and verify that its electrical features are suitable for connec­tion to the available mains. To do so, check the features label located inside the cabinet next to the FP regulator, see Figure 3.
Key data to be checked:
Mains frequency and voltage, Un / fn. Nominal power of the capacitor bank, Qn (kvar) and composition
Current consumption, In . This current must be considered to select the proper size of the power supply cable of the unit and ultimately the circuit breakers and protection elements to be connected in front of it.
 Auxiliary control voltage, U
.( See “3.7.- AUXILIARY CONTROL VOLTAGE”)
aux
Environmental conditions. (See “6.- TECHNICAL FEATURES”)
Instruction Manual
Figure 3: Features label.
9
OPTIM P&P Series

3.3.- INSTALLATION LOCATION

It is important to maintain a minimum distance around the unit to facilitate cooling.
In self-supporting cabinets, the back and front sides of the cabinet must be kept at least 50 cm away from walls of other units and other infrastructure to allow for ventilation. In terms of the side walls, it is recommended that a separation of 10 cm be maintained between adjacent cabinets.
On wall-mounted cabinets, it is recommended that at least 20 cm of separation be maintained between the sides of adjacent cabinets.
Make sure the unit can be accessed easily.
The environmental conditions of the location where the unit is installed must not exceed the limits set forth in the technical features (See “6.- TECHNICAL FEATURES”)
To ensure proper ventilation, the unit must be installed in a vertical position.
In accordance with the LVR, once the unit is installed, it must be protected against direct and in­direct contacts; therefore, a circuit breaker and earth leakage protection for the capacitor bank power supply line should be installed.

3.4.-CONNECTION OF THE CAPACITOR BANK TO THE MAINS

Check that the rated voltage of the capacitor bank matches the voltage between phases of the network to which it is being connected. Also check the operating circuit voltage (contactors). ( See “3.7.- AUXILIARY CONTROL VOLTAGE”)
For feeding cables into the capacitor bank cabinet, always and only use the cable entry points available for this purpose. There is a cable entry point on the bottom (base of the cabinet) in all the models and also an entry point on the side in some models.
If another part of the cabinet is cut out to be used for cable entry, the CIR­CUTOR manufacturer's guarantee shall be rendered void.
10
Do not cut holes in other parts of the cabinet for feeding cables through or for installing support brackets. It may produce trimmings that can cause short-circuits.
Instruction Manual
OPTIM P&P Series

3.5.-POWER CIRCUIT

Connect input terminals L1, L2 and L3 (power circuit) to the mains using proper sized cable in accordance with the LVR, ITC-BT-19. Generally, the cables of the phases adhere to the following colour code: L1 (black), L2 (brown), L3 (grey). If auxiliary voltage is required, the neutral cable will be connected to N (blue colour)
In order to determine the size of the phase cables, the nominal current In must be taken into account, indicated on the unit label, and it should be able to withstand an overload in transients of 1.5 times In. The neutral cable will be a minimum of 1.5 mm2.

3.6.- EXTERNAL CIRCUIT BREAKER AND PROTECTION ELEMENTS

If the capacitor bank does not have an internal switch or isolation switch, it must be connected to a line that has an external switch or isolation switch.
The protection elements, isolation switches and/or switches that are added exter­nally to the capacitor bank must be of a minimum size to withstand a current 1.5 times greater than what is indicated on the label (LVR, ICT-BT-48)
If an earth leakage protection for the capacitor bank is installed, its sensitivity and trip delay must be adjustable.
When the capacitor bank is connected to the mains, it is recommended that the current transformer (CT) is placed on the phase going to L1 (black cable). Outputs S1 and S2 of the CT must be connected to the terminals with the same name.

3.7.- AUXILIARY CONTROL VOLTAGE

Control circuits are dened as those related with regulator output relays and the capacitor's operating contactors. These circuits are usually powered with an auxiliary voltage of 230 V ~ (the most common case) or other voltages such as 110 V ~ (frequently for 500 V or 690 V capacitor banks).
There are two possible ways of powering the circuit:
Instruction Manual
11
OPTIM P&P Series

3.7.1. CAPACITOR BANK WITH AUXILIARY VOLTAGE OBTAINED FROM AN INTERNAL AUTOTRANSFORMER

Does not require connection of the external neutral. The label indicates U
Figure 4: Auxiliary power supply with autotransformer.
/f … internal
aux

3.7.2. CAPACITOR BANK WITH AUXILIARY VOLTAGE OBTAINED BETWEEN PHASE-NEUTRAL

Requires the connection of the external neutral to terminal N (see Figure 5 and Figure 7 ) The label indicates Uaux/f … (control voltage)
Figure 5: Auxiliary power supply with neutral.
12
Instruction Manual
OPTIM P&P Series

3.8.- EARTH CABLE CONNECTION

Connect the earth cable to the capacitor bank's earth terminal located on the operating panel of the unit. The earth cable cross-section will be selected in accordance with the admissible current limits established in the LVR (ITC-BT-19 – Internal or receiver installations) for each type of cable and their location.

3.9.- CURRENT TRANSFORMER (CT) CONNECTION

A current transformer (CT) that is external to the capacitor bank must be installed to measure the total load current plus that of the capacitor bank
(Figure 6).
The standard transformer must have a nominal output of 5 A at the secondary. We recommend connecting the CT to phase L1 in the direction of the current ow from P1 to P2 (see Figure 6) and connecting the secondary (terminals S1, S2) to the terminals with the same name on the capacitor bank (see Figure 6)
Avoid current ow through the CT primary winding prior to connecting it to termi­nals S1 S2 of the bank. If the CT must be installed while the installation is under load, short-circuit S1 and S2 while they are not connected to the capacitor bank.
The current value of the CT primary winding must be equal to or slightly greater than the size of the mains switch of the installation. Therefore, the CT must be able to measure the maximum current expected to be consumed by all the loads being compensated.
Figure 6: Installation of the external current transformer (CT).
The connection point of the CT for a capacitor bank that compensates an entire installation is after the mains switch of the installation.
To prevent excessive attenuation of the signal, it is recommended that the minimum cross-sec­tion of the secondary section winding cable (terminals S1, S2) is at least 2.5 mm2.
Instruction Manual
13
OPTIM P&P Series
Figure 7: Current transformer (CT) and neutral connection terminals (if required).
Once the cables are installed, disconnect the jumper connecting the S1 and S2 terminals or the yellow jumper according to the terminals of the capacitor bank (Figure 8)
Figure 8: Jumper for short-circuiting the secondary winding of the current transformer (CT).
Any time you wish to change or disconnect a current transformer that is already installed, it is important to install the jumper connecting S1 and S2.
14
Instruction Manual
OPTIM P&P Series

4.- CAPACITOR BANK START-UP

4.1.- BEFORE START-UP

The automatic capacitor banks include a power factor regulator.
The operation of said regulator must be known prior to start-up; for this reason, all the capacitor banks include a specic manual for the regulator used. Ensure you have this manual available for the start-up process.
In order to adjust the regulator incorporated to the capacitor bank and for opti­mum start-up, the installation load must be at least 30% or 40% of the nominal load for which the capacitor bank has been dimensioned. If all the stages are not included, they can be manually connected to check them all.
During low load periods, the entire capacitor bank should not be connected man­ually, as in some cases resonance with the power transformer of the installation could occur.
The capacitors are connected in manual mode, rst allow enough time for the ca­pacitors to discharge (as indicated in the capacitor bank's features label) before reconnecting them to the network. Otherwise, they could start-up out of phase with a voltage of up to 2xUn causing the destruction of the capacitor.

4.2.- START-UP

Apply the safety regulations listed in section “3.- INSTALLATION” of this manual before operating the units.
The National Electric Code of the country where the capacitor bank is in­stalled or operated should be strictly followed.
1.- Ensure that the inner circuit breaker that starts the regulator (Figure 11) is connected.
2.- Connect the power supply to the panel and check that the regulator display illuminates im-
mediately. Otherwise, stop and check the previous step.
3.- Check the regulator's cos φ indication. If the indication is out of range 0.5 to 1, it may be possible that the current transformer and/or the power supply to the regulator are not properly connected. Most of the regulators use only one current transformer. In this case, connect according to
Figure 10 (place the current transformer on phase L1 and take the power supply voltage from
phases L2 and L3).
Instruction Manual
15
OPTIM P&P Series
Figure 9: Plug&Play Computer Max Regulator. (Photo as an example, it may not coincide with the model used on
your unit).
POWER SUPPLY
400 V ac
L1 L2 L3
N
A B
S1 S2
P1 P2
1 2
-
- + C1 ... C6
5
3
6
4
C D
0
Figure 10: Connection of a regulator with only one CT. (If using Computer SMART III or Computer Plus, 3 CT are
used. Check the specic manual. )
16
Figure 11: Two-pole circuit breaker for the auxiliary power circuit.
4.- Once ensured that the regulator is properly connected, adjust the regulator parameters for
the installation you are attempting to compensate. For this, follow the instructions on the man­ual of the regulator, included with the capacitor bank.
Instruction Manual
OPTIM P&P Series

4.3.- CHECKS ONCE THE CAPACITOR BANK HAS BEEN CONNECTED AND THE REGULATOR

1.- After start-up, make sure that the unit is operating correctly. A sign of proper operation is the display indicating a cos φ close to 1 and the reactive energy meter should stop (if it is electro­mechanical) or the blinking light of the indicator LED of the kvar.h/pulse ratio should reduce its rate.
2.- Check that the power supply voltage does not exceed the nominal value +10% (IEC 60831-1).
3.- Check the current absorbed by each capacitor. Under normal conditions, it must be close to the nominal value indicated on its dataplate and never exceed 1.3 times this value constantly.
Continuous consumption over the nominal value may be caused by the presence of harmonics in the network or an excessively high power supply voltage. Both circumstances are harmful for capacitors.
4.- In accordance with the IEC 60831-1 Standard, the capacitor is prepared to operate at the permanent voltage assigned to it and with an overvoltage of up to 10% for 8 out of every 24 hours.
Check the working temperature of the capacitors after they have been operating for 24 hours. The housing must be below 40 ºC.
Instruction Manual
17

5.- MAINTENANCE

5.1.- SAFETY REGULATIONS
Take the safety regulations listed in section of this manual into account before operating the units “3.1.- PRELIMINARY RECOMMENDATIONS” The National Electric Code of the country where the capacitor bank is installed or operated should be strictly followed.
5.2.- MAINTENANCE WITH THE CAPACITOR BANK DISCONNECTED

5.2.1. BASIC MAINTENANCE PROTOCOL

Monthly:
Visually inspect the capacitors.
OPTIM P&P Series
Check the protection fuse. Control the ambient temperature (average of 35 ºC. In accordance with IEC 60831 ).
 Control the service voltage (especially during moments of low load, it must not exceed the nominal +10%).
Bi-annually:
Keep the capacitor terminals clean.
Verify the state of the contacts of operating elements. Check that the capacitor current is not lower than 25% nor greater than 120% of the
nominal value by phase and that there is no phase unbalance greater than 15%.
Annually:
Carry out a dielectric rigidity test by applying 2.5 kV for 1 second between the terminals of the capacitor and earth.
Check the capacity of the capacitors at the different steps. One indirect check may be to check that the consumption is manual.
Check the tightness of all terminal connections.
18
Inspect the fuses.
- Power Circuit: NH fuses. Check continuity and temperature.
- Power Circuit: Check the continuity and temperature of the three-pole or four-pole circuit breaker.
- Control Circuit: Check the continuity and temperature of the two-pole circuit breaker.
Instruction Manual
OPTIM P&P Series

5.2.2. TIGHTENING TORQUE OF THE ELECTRICAL CONNECTIONS

The connections must be tight. The tightening torques for the fuse bases, circuit breakers and the contactors are indicated in
Table 3 , Table 4 and Table 4.
Table 2:Tightening torques of the cables to the fuse bases.
Fuse base Torque (Nm)
NH-00 15.2
Table 3:Torques of power cables to two-pole and three-pole circuit breakers.
Circuit breaker Torque (Nm)
In ≤ 3 x 63 A 2
In ≤ 2 x 6 A 2
Table 4:Torques of cables to connector terminals
Model Auxiliary (Nm) Power (Nm)
CMC-12 1.3 1.6 CMC-18 1.3 2.2 CMC-32 1.3 2.9 CMC-40 1.3 2.9 CMC-50 1.3 4.5 CMC-65 1.3 4.5 CMC-75 1.3 4.5 CMC-85 1.3 5.1
CMC-150 1.3 9

5.2.3. KEY POINTS FOR INSPECTING CONTACTORS

Check that the plastic parts are not blackened and do not show signs of burning or hardening. Check that the head is properly inserted.Check the tightness of cables and terminals, as shown in Table 4. The terminals must be clean.If the capacitor bank includes RD discharge resistors, check they are in good condition (that
they are not open or show signs of burning). (Figure 12)
Instruction Manual
19
OPTIM P&P Series
RD
Figure 12: Connection of the discharge resistors.
K1
Cleaning the contactors: In dirty environments (dust, sawdust, rust particles, etc.) vacuum the contactor periodically. There is no estimated time frame for cleaning, it depends on the amount of dirt that is inside the capacitor bank.

5.2.4. KEY POINTS FOR INSPECTING CAPACITORS

Inspect the cables and terminals. They should not be overheated or blackened. The terminals must be clean. The slow discharge resistors must be in good condition. They must not be open or show
signs of burning. Check the tightness of the capacitor terminals, as shown in Table 5.
Table 5:Torques of the cables to the capacitor terminals.
Cylindrical capacitor Power terminal torque (Nm)
CLZ FP 2
Prismatic capacitor
CV 4.49 6.2
CSB 21 6.2
Torque
Power terminal (Nm)
Earth terminal (Nm)
Torque

5.2.5. KEY POINTS FOR INSPECTING THE REGULATOR

Check that the regulator does not show signs of deterioration and the display is lit as normal.Inspect the cables and terminals. They should be clean and should not be hardened or over-
heated.
20
Inspect the connections and the insertion of removable power strips:
- The power strips must be well fastened on removable regulators.
- Check that the terminals are tightened properly. The recommended torque is 0.6 Nm.
Instruction Manual
OPTIM P&P Series

5.2.6. CLEANING THE CABINET

Remove possible metallic and non-metallic particles. Clean the inside of the cabinet. Clean ventilation grilles.
5.3.- MAINTENANCE WITH THE CAPACITOR BANK CONNECTED
Check that the main switch turns on and off without having to force the mechanism. If there is an individual earth leakage protection for the capacitor bank, check its proper
operation by pressing the test button. Check that the auxiliary control voltage is within the tolerance limits. If the capacitor bank has an autotransformer, check that it is in good condition and shows no
signs of deterioration. Force the connection and disconnection of the capacitors in manual mode. (refer to the reg-
ulator's manual before carrying out these actions) and perform the following checks:
- Check that the contactors connect and disconnect properly.
- Check that the contactor, once connected, does not rattle or vibrate.
- Check the consumption of the capacitors in each of the phases. The nominal values are shown in Table 6. .
Table 6:Nominal consumption of the capacitor paths, by power and voltage.
Power
3 x 230V ~
2.5 kvar 6.28 A 5 kvar 12.56 A
7.5 kvar 18.85 A
10 kvar 25.12 A
12.5 kvar 31.41 A 15 kvar 37.7 A 20 kvar 50.24 A 25 kvar 62.82 A 30 kvar 75.4 A 40 kvar 100.48 A 50 kvar ­60 kvar ­80 kvar -
In, Current
3 x 400V~
3.6 A
7.2 A
10.8 A
14.4 A
18 A
21.6 A
28.8 A
36 A
43.2 A
57.6 A
72 A
86.4 A
115 A
Note: If consumption is ±25% less than that indicated in Table 6 and the voltage is within the tolerance limits, this is usually a sign of degradation of the capacitors. If this is detected in any capacitor, it should be replaced with another capacitor.
Instruction Manual
21
OPTIM P&P Series

5.3.1. REGULATOR CHECKS

Refer to the manual of the specic regulator used in the capacitor bank. This manual is always supplied with the capacitor bank
Check that there are no faulty segments on the display. Check that the keyboard is operating properly:
- Enter Setup and check the adjusted values
- Force the manual connection and disconnection of a step.

5.4.- ENVIRONMENTAL CONDITIONS

Check that the maximum environmental conditions listed in section “6.- TECHNICAL FEA- TURES” are being observed.
22
Instruction Manual
OPTIM P&P Series

6.- TECHNICAL FEATURES

Electrical features
Usage voltage and nominal frequency Un / fn, listed on the label
Design voltage Un+ 10% (440 V for 400 V units)
Nominal power and distribution of steps Qn and composition, (see label)
Total losses < 0.5 W / kvar
Residual discharge voltage 75 V after 3 minutes
Overload capacity 1.3 In in all the elements
Contactor operating voltage Uaux, marked on the label
Current Transformer Secondary winding 5 A, (Transformer In/5 A)
NOTE: Minimum cable section of 2.5 mm2.
(1)
For standard OPTIM 3 P&P and OPTIM 5 P&P models, supply external voltage with a 1.5 mm
cable. If “Internal” is marked, this circuit does not require power. For the rest of the models, an autotransformer is already included for auxiliary power supply, so no
external auxiliary power supply is required.
Capacitor features
Capacity tolerance - 5% / + 10%
Insulation level from earth 3 kV /50 Hz
Impulse test 15 kV, ray-type wave 1.2/50 µs
Protections Internal fuses and over-pressure system
In accordance with Standards UNE EN 60831
(1)
2
Environmental features
Category D in accordance with EN 60831-1
Maximum temperature of capacitors
Maximum during 1 h. 24 h average Annual mean
55 ºC 45 ºC 35 ºC
Cabinet ventilation
For outdoor Tamb > 30 ºC forced ventilation should be pro­vided in the cabinet
Maximum relative humidity 80%
Maximum altitude 1000 m
(For higher altitude, forced ventilation should always be
provided)
Protection degree Marked on the label
Mechanical features
Model OPTIM 3 P&P OPTIM 5 P&P OPTIM 9 P&P
Dimensions (Width x Height
(2)
x Depth) 400x600x260 mm 600x740x260 mm 700x1350x440 mm
Weight 40 Kg 55 Kg 134 Kg
Model OPTIM 8 P&P OPTIM SC8 P&P OPTIM SC12 P&P
Dimensions (Width x Height
(2)
x Depth)
1000x1750x440 mm 1180x1340x460 mm 1930x1895x460 mm
Weight 265 Kg 155 Kg 595 Kg
Model OPTIM SC16 P&P
Dimensions (Width x Height
(2)
x Depth)
2460x1895x460 mm
Weight 700 Kg
Paint Epoxy type, oven-dried
Standard colours RAL 7035 Grey; RAL 3005 Maroon
(2)
Maximum dimensions.
Instruction Manual
23
OPTIM P&P Series
Standards
Power capacitors. Low voltage power factor correction capacitor banks. UNE-EN 61921:2004 Low voltage switchgear sets. Part 1: General rules.

7.- STANDARD ELECTRICAL DIAGRAMS

UNE-EN 61439: 2012
The electrical diagrams indicated in this manual are for the standard models in each range, and do not include the various additional accessories which these may equip, such as those listed below:
Autotransformer for auxiliary power supply (in those models in which this is not tted as standard).
Forced ventilation system. General manual load cut-off switch. Circuit breaker for general protection. Earth leakage protection device. Automatic regulator not for the Plug & Play Computer Max range.
And they are exclusively for the standard 3 x 440 V / 50 Hz rated voltage range, for use in three­phase networks with a rated voltage of 3 x 400 V / 50 Hz.
24
Instruction Manual
DENOMINACION
FECHA
UNIDAD DIM
ESCALA
APROBADO
DIBUJADO
NOMBRE
SUSTITUIDO POR
SUSTITUYE A
CODIGO
EQUIPO/S
02/10/2014
02/10/2014
C04 C04 C04
CIR_058
L1L2L3
L1L2L3
K1 K2
RG1
C1 C2
3N
N
K3
C3
50 Hz 440 V3N
OPTIM 3 P&P-XXX-440
BATERIA AUT. CONDENSADORES
RED CARGA
50 Hz 400 V
TI .../5A
Q1
Q2
TB1
65432
1
cos φ
Paso 1 Paso 2
S1 S2
S1 S2
Paso 3
Com
Regulador Automático
N
400Vac
0
S2
S1
POWER
SUPPLY
A B C D
08232 Viladecavalls (Barcelona)
Vial Sant Jordi s/n
OPTIM P&P Series
Figure 13: Standard electrical diagram of automatic capacitor banks in the OPTIM 3 P&P model.
Instruction Manual
25
DENOMINACION
FECHA
UNIDAD DIM
ESCALA
APROBADO
DIBUJADO
NOMBRE
SUSTITUIDO POR
SUSTITUYE A
CODIGO
EQUIPO/S
02/10/2014
02/10/2014
C04 C04 C04C04 C04
CIR_058
L1L2L3
L1L2L3
K1 K2 K4
RG1
C1 C2 C4
3N
N
K3
C3
50 Hz 440 V3N
BATERIA AUT. CONDENSADORES SIN AUTOTRAFO
RED CARGA
50 Hz 400 V
TI .../5A
OPTIM 5 P&P-XXX-440
K5
C5
Q6
TB1
TB2
Q1 Q2 Q3 Q4 Q5
65432
1
cos φ
Paso 1 Paso 2 Paso 4
S1 S2
S1 S2
Paso 3
Com
Regulador Automático
N
Paso 5
400Vac
0
S2
S1
POWER
SUPPLY
A B C D
08232 Viladecavalls (Barcelona)
Vial Sant Jordi s/n
OPTIM P&P Series
26
Figure 14: Standard electrical diagram of automatic capacitor banks in the OPTIM 5 P&P model.
Instruction Manual
DENOMINACION
FECHA
UNIDAD DIM
ESCALA
APROBADO
DIBUJADO
NOMBRE
SUSTITUIDO POR
SUSTITUYE A
CODIGO
EQUIPO/S
02/10/2014
02/10/2014
K06 K06 K06
C04 C04 C04
K06
C04
K06
C04
K06
C04
CIR_058
400Vac
0
S2
S1
12
11
10
9
876
5
4
3
2
1
COM
cos φ
S1 S2
Regulador Automático
S1 S2
Paso 1 Paso 2 Paso 4Paso 3 Paso 5 Paso 6
POWER
SUPPLY
0V
230V
400V
AUTOTRAFO
GRIS
AZUL
MARRÓN
A B C D
L1L2L3
L1L2L3
RED CARGA
RG1
50 Hz 440 V3N
3N 50 Hz 400 V
TI .../5A
N
K1 K2 K4
C1 C2 C4
K3
C3
K5
C5
K6
C6
PARTE 1
SIGUE EN PARTE 2
SIGUE EN PARTE 2
NH-00
NH-00
(SÓLO MODELOS CON MÁS
BATERIA AUT. CONDENSADORES CON AUTOTRAFO
DE 6 ESCALONES)
OPTIM 9 P&P-XXX-440
TB1
Q1
SIGUE EN
PARTE 2
AT1
08232 Viladecavalls (Barcelona)
Vial Sant Jordi s/n
TB1
OPTIM P&P Series
Instruction Manual
Figure 15: Standard electrical diagram of automatic capacitor banks in the OPTIM 9 P&P (1/2) model.
27
DENOMINACION
FECHA
UNIDAD DIM
ESCALA
APROBADO
DIBUJADO
NOMBRE
SUSTITUIDO POR
SUSTITUYE A
CODIGO
EQUIPO/S
02/10/2014
02/10/2014
L1L2L3
50 Hz 440 V3N
OPTIM 9 P&P-XXX-440
BATERIA AUT. CONDENSADORES CON AUTOTRAFO
K7 K8
C7 C8
K9
C9
PARTE 2/2
VIENE DE PARTE 1/2
VIENE DE PARTE 1/2
VIENE DE PARTE 1/2
NH-00
CIR_058
08232 Viladecavalls (Barcelona)
Vial Sant Jordi s/n
K06 K06
C04 C04
K06
C04
Paso 7 Paso 8 Paso 9
8
7
9
F7 F8 F9
OPTIM P&P Series
28
Figure 16: Standard electrical diagram of automatic capacitor banks in the OPTIM 9 P&P (2/2) model.
Instruction Manual
Q 1
RG1
L1L2L3
PARTE 1/2
AT1
OPTIM 8 P&P-XXX-440
50 Hz 440 V3N
BATERIA AUT. CONDENSADORES CON AUTOTRAFO
TB1
L1L2L3
RED
CARGA
3N 50 Hz 400 V
N
K1 K2 K3 K4
C1C1 C2C2 C3C3 C4C4
TB1
CODIGO
SUSTITUYE A
SUSTITUIDO POR
UNIDAD DIM
ESCALA
DENOMINACION
DIBUJADO
APROBADO
FECHA NOMBRE
EQUIPO/S
02/10/2014
02/10/2014
08232 Viladecavalls (Barcelona)
Vial Sant Jordi s/n
S1 S2
T.I.
Escalón 1
0V
230V
400V
AUTOTRAFO
C6
C5
C4
C3
C2
C1
COM
cos φ
Regulador Automático
Sigue en PARTE 2/2
Sigue en PARTE 2/2
Sigue en PARTE 2/2
Escalón 2 Escalón 3 Escalón 4
Sigue en PARTE 2/2
C8
C7
S1 S2
400Vac
0
S2
S1
POWER
SUPPLY
A B C D
12
11
10
9
GRIS
AZUL
MARRÓN
K06 K06 K06 K06
C04C04 C04C04 C04C04 C04C04
OPTIM P&P Series
Instruction Manual
Figure 17:Standard electrical diagram of automatic capacitor banks in the OPTIM 8 P&P (1/2) model.
29
PARTE 2/2
OPTIM 8 P&P-XXX-440
50 Hz 440 V3N
BATERIA AUT. CONDENSADORES CON AUTOTRAFO
CODIGO
SUSTITUYE A
SUSTITUIDO POR
UNIDAD DIM
ESCALA
DENOMINACION
DIBUJADO
APROBADO
FECHA NOMBRE
EQUIPO/S
02/10/2014
02/10/2014
08232 Viladecavalls (Barcelona)
Vial Sant Jordi s/n
K06 K06
C04C04 C04C04
K06 K06
C04C04 C04C04
K5 K6
C5C5 C6C6
K7 K8
C7C7 C8C8
Viene de PARTE 1/2
Viene de PARTE 1/2
Viene de PARTE 1/2
Viene de PARTE 1/2
Viene de PARTE 1/2
6
5
Escalón 5 Escalón 6 Escalón 7 Escalón 8
8
7
OPTIM P&P Series
30
Figure 18:Standard electrical diagram of automatic capacitor banks in the OPTIM 8 P&P (2/2) model.
Instruction Manual
Q 1
RG1
L1L2L3
PARTE 1/2
AT1
OPTIM SC8 P&P-XXX-440
50 Hz 440 V3N
BATERIA AUT. CONDENSADORES CON AUTOTRAFO
TB1
C1 C2 C3 C4
L1L2L3
RED
CARGA
3N 50 Hz 400 V
N
K1 K2 K3 K4
TB1
CODIGO
SUSTITUYE A
SUSTITUIDO POR
UNIDAD DIM
ESCALA
DENOMINACION
DIBUJADO
APROBADO
FECHA NOMBRE
EQUIPO/S
02/10/2014
02/10/2014
08232 Viladecavalls (Barcelona)
Vial Sant Jordi s/n
S1 S2
T.I.
0V
230V
400V
AUTOTRAFO
C6
C5
C4
C3
C2
C1
COM
cos φ
Regulador Automático
Sigue en PARTE 2/2
Sigue en PARTE 2/2
Sigue en PARTE 2/2
Sigue en PARTE 2/2
C8
C7
S1 S2
400Vac
0
S2
S1
POWER
SUPPLY
A B C D
12
11
10
9
GRIS
AZUL
MARRÓN
Escalón 1 Escalón 2 Escalón 3 Escalón 4
K06 K06 K06 K06
C04 C04 C04 C04
OPTIM P&P Series
Instruction Manual
Figure 19:Standard electrical diagram of automatic capacitor banks in the OPTIM SC8 P&P (1/2) model.
31
PARTE 2/2
50 Hz 440 V3N
BATERIA AUT. CONDENSADORES CON AUTOTRAFO
OPTIM SC8 P&P-XXX-440
C5 C6 C7 C8
CODIGO
SUSTITUYE A
SUSTITUIDO POR
UNIDAD DIM
ESCALA
DENOMINACION
DIBUJADO
APROBADO
FECHA NOMBRE
EQUIPO/S
02/10/2014
02/10/2014
08232 Viladecavalls (Barcelona)
Vial Sant Jordi s/n
K06 K06 K06 K06
C04 C04 C04 C04
K5 K6 K7 K8
Viene de PARTE 1/2
Viene de PARTE 1/2
Viene de PARTE 1/2
Viene de PARTE 1/2
Viene de PARTE 1/2
6
5
8
7
Escalón 5 Escalón 6 Escalón 7 Escalón 8
OPTIM P&P Series
32
Figure 20:Standard electrical diagram of automatic capacitor banks in the OPTIM SC8 P&P (2/2) model.
Instruction Manual
OPTIM P&P Series

8.- MAINTENANCE AND TECHNICAL SERVICE

In the case of any query in relation to unit operation or malfunction, please contact the
CIRCUTOR, SA Technical Support Service.
Technical Assistance Service
Vial Sant Jordi, s/n, 08232 - Viladecavalls (Barcelona) Tel: 902 449 459 ( España) / +34 937 452 919 (outside of Spain) email: sat@circutor.es

9.- GUARANTEE

CIRCUTOR guarantees its products against any manufacturing defect for two years after the
delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee period.
No returns will be accepted and no unit will be repaired or replaced if it is not ac­companied by a report indicating the defect detected or the reason for the return.
•The guarantee will be void if the units has been improperly used or the stora­ge, installation and maintenance instructions listed in this manual have not been followed. “Improper usage” is de ned as any operating or storage condition con­trary to the national electrical code or that surpasses the limits indicated in the technical and environmental features of this manual.
CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the installation, nor will it cover any possible sanctions derived from a pos­sible failure, improper installation or “improper usage” of the unit. Consequently, this guarantee does not apply to failures occurring in the following cases:
- Overvoltages and/or electrical disturbances in the supply;
- Water, if the product does not have the appropriate IP classi cation;
- Poor ventilation and/or excessive temperatures;
- Improper installation and/or lack of maintenance;
- Buyer repairs or modi cations without the manufacturer’s authorisation.
Instruction Manual
33

10.- CE CERTIFICATE

OPTIM P&P Series
34
Instruction Manual
OPTIM P&P Series
Instruction Manual
35
CIRCUTOR, SA
Vial Sant Jordi, s/n 08232 -Viladecavalls (Barcelona) Tel.: (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14 www.circutor.es central@circutor.es
Loading...