CIRCUTOR MK-363-B User Manual

3 PHASE ENERGY ELECTRONIC
METERS
MKB-363-M
INSTRUCTION MANUAL
( M98119801-20 / 04A )
(c)
CIRCUTOR S.A.
-- MKB-363-M ELECTRONIC METERS -- M-981198 -- Page Nº 2
THREE-PHASE THREE-WIRE ACTIVE ENERGY ELECTRONIC METERS TYPE: MKB-363-M
1.- BASIC INSTRUCTIONS
1.1.- Delivery spot check
This manual is issued to help all the ENERGY METERS users to install and use them in order to get the best from them. After receiving the unit please check the following points:
(a) Does this device correspond to your order specifications? (b) Check if any damage was done during the shipment process. (c) Verify that includes: one instruction manual.
1.2.- Safety considerations
This manual contains information and warnings that must be followed for operating the ENERGY METER safely and maintaining the instrument in a safe operating condition.
-- MKB-363-M ELECTRONIC METERS -- M-981198 -- Page Nº 3
2.- MAIN CHARACTERISTICS
Three-phase electronic energy meters for low voltage networks at 230 V a.c. ( code 771 053 ) or 400 V a.c. ( code 771 054 ) , provided with mechanical rotatory display, which are designed to measure the active energy consumed by a three-phase three-wire loads Those are suitable for such installations where a partial energy consumption analysis is required.
Direct connection for the voltage signal (3 x 230 V a.c. ) or ( 3 x 400 V a.c.) and current through current transformers inside phases L1 and L3.
Available models
:
- Meter type MKB-363M: Three-phase three-wire active energy meter single tariff with build-in current transformers. Display by means of an electromechanical integrating meter in kW·h.
-- MKB-363-M ELECTRONIC METERS -- M-981198 -- Page Nº 4
Basic Features:
- Active energy computation algorithm uses Aron connection
principle, so phases L1 and L3 include current transformers and L2 is the voltage reference phase. This allows to use this active energy meter in any three-phase three-wire system without neutral or earth currents.
- All energy meters operate over two quadrants: consumed
power.
- Current transformer (only phases L1 and L3):
nominal current : 63 A maximum current : 90 A
- Electrical accurancy : Class 2
- All energy meters have two pulse outputs: one for the kW·h
consumed and the other with a timer. The energy output permits a remote transmission of the measurement of the kW·h consumed to a PLC or an energy meter centralisation unit like CIRCUTOR LM24. The timer output allows to compute the average active power for 15’ periods.
-- MKB-363-M ELECTRONIC METERS -- M-981198 -- Page Nº 5
Pulses
:
- Optocoupled outputs (2500 V respect to the electric network)
- Open collector type: 100 ms of duration
max. ratings 35 Vdc/30 mA
both outputs share the same common
Energy output
- Energy ratio : 100 pulses/kW·h
Timer output
- Timer ratio : 4 pulses/h
-------------------------------------------------------------------------------
- The meter has two LED’s at its frontal cover:
a green LED of POWER, which indicates that the meter is connected to the supply
a red LED for the metrology control and the energy flow visualisation (it blinks only with consumed power).
Such led blinks each 10 W·h.