Circutor CBS-4 Series, CBS-4, CBS-4C Instruction Manual

CONTROL DEVICE FOR E LECTRONIC EARTH
LEAKAGE PROTECTION RELAYS
CBS-4 SERIES
INSTRUCTION MANUAL
M98228301-03-17B
Page 2 of 29
Earth leakage protection relay
Verifications upon receipt
This manual provides installation tips and a guide for use of the control device for CBS-4 ea rth leakage relays with the purpose of achieving its optimum performance. Upon receiving the device, check the following points:
That the device meets the specifications of your order.
That it has not been damaged during shipping.
Check that it is supplied with the corresponding Instruction Manual.
The safe use of the CBS-4/CBS-4C requires that the persons installing or using it follow the customary safety measures, as well as the different warnings indicated in the Instructions Manual. This analyzer should only be installed and maintained by qualified staff.
CONTENTS
General features ……… ………………..…………..…………… page 4
Installation and start-up …………………………………..……………… page 6
Connection diagram …………………. ………………………………………..page 9
Description …………………………………….. page 13
Operation …………………………………..… page 18
Device adjustments ….……………………………….……………… page 21
COMMUNICATION SETUP programming ….……………………………….…… page 23
Measurement SETUP programming …………………………… page 25
SETUP menus diagram …………………………………..……………… page 26 MODBUS protocol …………………………………..…… page 27
MODBUS memory map …………………………………..……………… page 27
RS - 485 Connections …………………………………..…… page 29
Scada Power Studio applications …………………………………..…… page 30
Page 3 of 29
Earth leakage protection relay
Page 4 of 29
Earth leakage protection relay
GENERAL FEATURES
The CBS-4 earth leakage device is a type A programmable electronic earth leakage protection device with 5 independent relays: 4 relays for controlling the circuit breaker elements of the four channels and performing the protection and pre-alarm function, which has prevention and maintenance functions in the installation.
It enables programming and adjustment of all the required parameters to obtain full maintenance protection and control of the installation. A set of parameters can be configured via direct adjustments using the keypad (buttons) and setup menus in the device.
Before starting up the earth leakage device, please read carefully the sections on power supply, connection and programming.
The CBS-4 measures, calculates and displays the earth leakage current of balanced or unbalanced three-phase industrial networks.
The measurement is made in RMS, via an earth leakage current input, from the WG/WGS series exterior toroidal measuring transformer.
In normal operating conditions, the main values that determine the earth leakage protection of the installation, such as the sensitivity, delay and instantaneous leakage current, are shown on the display.
We are aware of the high levels of prevention and maintenance required for installations, and so have provided the device with a display and indicator LEDs for any events that might arise.
Data displayed or indications of prealarms, trips, leakage readings, etc. help provide us with enough information for good maintenance.
The backlit display is in green under normal operating conditions, but in the case of any event causing a trip of the main relay, the display is backlit, indicating the reason.
The version with RS - 485 communications and the adequate software enable configuration, data and information centralisation to obtain effective monitoring and control of the maintenance status of our power lines.
Measurement of the earth leakage current from which the CBS- 4/CBS-4C acts by indicating the instantaneous leakage current, pre­alarm or trip is determined by the earth leakage transformers of the WG series. The interior diameter of the transformer is defined by the dimensions of the installation w iring.
Page 5 of 29
Earth leakage protection relay
Main Features
True RMS measurement.  Type A earth leakage protection. IEC 61008.1  Immunity to transients. IEC 61008.1  Filtering of high frequencies IEC 61008.1  Trip adjustment between 80 and 100% I
n
Inverse curve. IEC 61008.1  Associated standards IEC 61008.1, IEC755
Other features
3 modules. DIN rail. In panel, via front panel accessory Code M5ZZF1 Display of instantaneous leakage values.  Backlit LCD display.  Built-in RS - 485 (Modbus RTU®) communicat ion s system . Only CBS-4C
Available types
RGU-10 SERIES
Code
CBS-4 P12711 CBS-4C P12712
Page 6 of 29
Earth leakage protection relay
INSTAL LATION AND START-UP
This manual contains information and warnings that the user must adhere to in order to guarantee the safe operation of the CBS-4/CBS-4C, keeping it in a generally safe condition. The device should not be switched on until it has been mounted in its final location in the electr ic pan el.
IF THE DEVICE IS USED IN A MANNER OTHER THAN THAT SPECIFIED BY THE MANUFACTURER, ITS PROTECTIO N ELEMENTS MAY BE COMPROMISED.
When it is likely that the device has lost its safety protection (signs of visible damage), it should be disconnected from the auxiliary power supply. In this case, contact a qualified technical service representative.
Installing the device
The following points must be checked before the device is powered:
Power supply voltage. Operating conditions. Safety.
A. Power supply voltage:
Standard Version:
- Power supply: 230 Vac (± 20%)
- Frequency: 50/60 Hz
- Terminals 10-11: A1-A2
- Device consumption: 6 VA
Special Version:
- Power supply: 24..230Vac // 400 Vac // 12...230Vdc
- Frequency: 50/60 Hz
- Terminals 10-1: A1-A2
B. Changeover contacts of main/pre-alarm relay output:
- Trip contact terminals. : 13-14-15
- NO output terminal channel 1 : 13
- Common output terminal : 14
- NO output terminal channel 2 : 15
- Trip contact terminals : 7-8-9
- NO output terminal channel 3 : 7
- Common output terminal : 8
- NO output terminal channel 4 : 9
- Material : AgCdO
- Instantaneous nominal/max imum curr ent : 6 / 10 A
AC
- Rated/maximum switching voltage : 230 Vac
- Nominal load in AC. : 2500 VA
- Contacts protected by varistor : 275 Vac
- Useful mechanical life : 10·10
6
- Ambient temperature range : - 40…+85ºC
- Useful electrical life for AC loads. Cut off power for DC loads.
Page 7 of 29
Earth leakage protection relay
C. External input for Trip/Rearm:
- Terminals : 10 – 12
- Type of input. : Optocoupled
- Maximum voltage / Maximum power : 110 – 230 Vac (± 20%) / 0.7 W
D. E art h leakage cur r ent meas ur ement ci rcui t
Scale range
Scale background:
Display resolution
30 mA
75 mA
± 1 mA
300 mA
750 mA
± 1 mA
3 A
7.5 A
±0.1 A
30 A
75 A
± 1 A
E. Operating conditions
- Operating temperature : -10ºC…+50ºC
- Relative humidity : 5 ... 95 RH (without condensation)
- Altitude : up to 2000 m
F. Safety:
- Designed for category III 300 Vac installations. (EN 61010).
- Double-insulated electric shock protection class II.
INSTALLATION AND ASSEMBLY
The device is installed on DIN rail or panel (panel drill 67
+1
x 67+1 mm, in accordance with DIN 43 700 with
accessory M5ZZF1). All the connections are located inside the electric panel.
Take into account that when the device is connected, the terminals may be hazardous to the touch, and opening the covers or removing elements may provide access to parts that are dangerous. Do not use the device unti l it is fully installed.
To install the device on a panel, use a 72x72 mm frontal adapter. All the connections remain inside the electric panel.
The frontal adapter accessory has a base, a frame, two tabs and
three screws.
1. Place the base on the drill hole made on the panel.
2. Locate the unit behind the base.
3. Screw the base onto the unit using the holes in the top right and bottom left hand corners of the front panel.
4. Fit on the front panel to cover the fixing holes.
5. Fit the green pressure tabs on the side rails of the base.
6. Move the tabs towards the panel to fix it.
Example. How to connect the
different parts of the front panel
accessory to the unit.
Page 8 of 29
Earth leakage protection relay
Connection features
Device connection using cable with cross-section from 0.5 a 2 mm2 Recommended torque 0.5-0.6 Nm Length of stripped cable 5-7 mm
To connect the earth leakage transformer over long distances, the use of braided cable is recommended..
List of terminals
No. Description of terminals
1 Pre-alarm signalling contact 2 Common 1S2 input 3 1S1-T4 input 4 1S1-T3 input 5 1S1-T2 input 6 1S1-T1 input 7 Channel 3 NO trip contact 8 Common output contact 9 Channel 9 NO trip contact 10 A1 power supply voltage input / trip-rearm 11 A2 power supply voltage input 12 Trip-rearm input 13 Channel 1 NO trip contact 14 Common output contact
15 Channel 2 NO trip contact
Page 9 of 29
Earth leakage protection relay
CONNECTION DIAGRAMS
Connection of CBS-4/CBS-4C circuit breaker elements with current shunt coil. In the event of an earth leakage relay trip due to a fault, test or error of the earth leakage current transformer.
1. See cause of the tripped channel on the red display.
2. Rearm the circuit breaker element.
3. Press the RESET button of the device for the tripped channel.
Page 10 of 29
Earth leakage protection relay
Connection of the CBS-4/CBS-4C circuit breaker elements with the current undervoltage coil. In the event of an earth leakage relay trip due to a fault, test or error of the earth leakage current transformer.
For connections via the current undervoltage coil, you need to activate the positive safety. More information about this on page 12.
1. See cause of the tripped channel on the red display.
2. Rearm the circuit breaker element.
3. Press the RESET button of the device for the tripped channel.
Page 11 of 29
Earth leakage protection relay
Connection of the earth leakage transformers of the WG series to the CBS-4/CBS-4C devices, which are associated with each channel to control, as follows:
Page 12 of 29
Earth leakage protection relay
CBS-4/CBS-4C connection with the voltage undervoltage coil is the same as the current shunt coil, with
the main difference being the activation of the positive safety. In this way, by using a CONTACTOR you can rearm the protection by pressing RESET; however, if using
a CIRCUIT BREAKER, you must rearm the circuit breaker element first.
Connection of the device in positive safety mode
This installation mode provides the most conservative protection from the point of view of the safety of people and materials in electrical installations.
With this type of connection and configuration of the device, you can be confident that people and materials are protected against faults in situations in which the earth leakage relay loses its protective capability. Whether due to power supply problems in the device itself or an absence of voltage in the installation (neutral or phase failure), the last order of the relay is to open the installation.
1. The circuit breaker element must be able to trip by means of the undervoltage coil, whether internal (CONTACTOR) or external (CIRCUIT BREAKER).
2. Program the device to set it by pressing the Std/+ button in positive safety mode. The symbol “+” appears on the display.
3. The device's power supply must be from the same installation or part that it protects.
Page 13 of 29
Earth leakage protection relay
DESCRIPTION
The device's front panel, which is made up of the display, buttons and LEDs, is protected by a sealable plastic cover, conveniently perforated for access to the RESET, TEST and PROGRAMMING buttons.
Generic functions of the LEDs and buttons on the front panel:
The device has two light indicator s.
Dual-colour Green / Red LED
Off, the device is not operating or is not receiving power supply voltage.  Green, the device is operating. It is receiving power supply voltage  Red, the device has tripped.
Yellow LED. Pre-alarm indication.
Off, there is no prealarm trip.  Permanently lit, prealarm trip.
The device has 7 buttons, described in order of accessibility.
Accessible with presealed cover and tool.
RESET button
Initialisation of device after trip.
TEST button
Causes a trip to test if relay is operating correctly.
PROG/PAG button
Dual-function button.  Short press to alternate between the different channels.  Press and hold to enter device programming by SETU P.
Accessible with raised cover. Dual-function buttons. Press and hold to enter and configure values and tap to select the option in a series of values defined in the device.
Page 14 of 29
Earth leakage protection relay
SENSITIVITY I
n
button
Allows to choose from values of 30, 100, 300, 500 mA , 1 and 3 A  Use extended scale in SETUP programming to add 5, 10 and 30 A to the above values list.
DELAY, t
d
button
Allows you to choose from values of 20, 100, 200, 300 , 400, 500, 750 ms 1 s  Use extended scale in SETUP programming to add 3, 5 and 10 s to the above list of values.
This button also allows you to browse the SETUP MENU.
Accessible with raised cover and tool. Flush buttons.
NORMAL OR POSITIVE SAFETY button
This allows you to configure the polarity of the output contacts.  With normal safety, (Std) the relay activates with a fault, status is NO.  With positive safety (+), the relay activates when there is voltage in the device and deactivates
when there is a fault, status is NC.
REC button
This allows you to activate the automatic re-establishment option and use the device for signalling
faults. It must not be used as an earth leakage protection function.
When activa ting the REC, the device automatically resets the trip relay, when the leakage current
drops below the programmed threshold once again.
The device enables all the parameters to be displayed and configured by direct adjustment or by programming the SETUP via a display.
Backlight LCD display
The screen background is green in normal status. The required parameters of the earth leakage
protection are displayed along with the sensitivity and delay of its associated devices. The actual leakage current and channel being viewed are also displayed.
For any event that causes a trip in the device, the screen background changes to red and the
display shows the reason for the trip.
Page 15 of 29
Earth leakage protection relay
OPERATION
When the device is powered at its rated voltage, the LED on the front panel is ON, the backlit LCD is lit in green to indicate the version of the software and hardware. After a short period, the version disappears and the default display values are displayed.
The display indicates the programmed delay and sensitivity setting values, as well as a reading of the instantaneous leakage current.
During operation, the device display shows the following symbols while configuring and programming the device.
The following magnitudes associated with the earth leakage protection are shown in the display in normal operating status.
MAGNITUDE
UNIT
Instantaneous leakage current mA / A Delay of programmed trip, td
ms / s
Sensitivity of programmed trip, Id = I
N
mA / A
State of main relay contacts
+ (contact 13-14 NC) / none (contact 13 - 14 NO)
+ (contact 15-14 NC) / none (contact 15 - 14 NO)
+ (contact 7-8 NC) / none (contact 7 - 8 NO)
+ (contact 9 -8 NC) / none (contact 9 - 8 NO)
Page 16 of 29
Earth leakage protection relay
The CBS-4/CBS-4C allows for the display and programming of all the parameters required to complete the setting of the earth leakage protection with pre-alarm and communications.
MAGNITUDE
UNIT
Pre-alarm sensitivity in % I
N
% Working frequency (*) Hz No. of peripherals (*) ­Communication speed (*) Bauds Type of parity (*) -
(*) Only for CBS-4C
INCIDENTS OR CAUSES OF DEVICE TRIPPING
BAD CONNECTION OF TRANSFORMER. The device carries out a check from time to time to detect the presence of the sensor or associated earth leakage transformer. In addition, the LCD will indicate an error message constantly: “ERRt”. If the transformer secondary short circuits, it also detects it as an error. When this error is detected, to re-establish correct operations, make sure there is a good connection with the earth leakage transformer and perform the RESET. If it detects the transformer again, it recovers normal status and the error message disappears.
PREALARM TRIP. If the fault current exceeds the programmed prealarm threshold, the yellow LED is lit, the LCD backlit in green indicates the level of leakage and the prealarm output relay is enabled. When the pre-alarm situation disappears, it reverts to normal status (indication relay and LED).
TRIP DUE TO FAILURE. When it trips due to the fault current, the red and yellow LEDs are lit and the LCD backlit in red. The display of the current of the last cycle that tripped the relay is maintained. To reconnect, press RESET to return to the initial status.
Page 17 of 29
Earth leakage protection relay
REMOTE TRIP. When a trip is forc ed (inpu t termi nals 10-12, applying a 230 Vac voltage) the device trips
all the channels and is disabled, reporting this incident through the “EXT” message on the display lit up in red and the ON LED. It has to stay permanently lit in this situation until there is a change in status. Manual or communications-based rearming is not possible.
When it is remotely rearmed (remote input terminals 10-12, cutting voltage of 230 Vac) the device is
reconnected with the backlight display in green, the ON LED in green as in the normal status.
For the CBS-4C, a remote trip/rearm can be completed via RS - 485 communications, the device stays tripped and the incident is indicated via the “REM” message on the display lit in red and the ON LED as well. It has to stay permanently lit in this situation until there is a change in status.
It rearms when it is rearmed remotely via RS - 485 communications, applying a voltage of 230 Vac between the remote input terminals 10-12 or by means of the reset button. The device is reconnected with the backlight display in green, ON LED in green as in normal status.
DEVICE TRIP DISPLAY MESSAGES
CAUSE OF TRIP DISPLAY MESSAGE
TEST
TESt
Bad connection with the toroidal transformer
ERRt
On/off remote signal
EXT
RS485 communications
REM
Current leakage Instantaneous value
OTHER DISPLAY MESSAGES
MESSAGE
SAVE
Validates configuration values
EXIT
Exits programming mode
OVR
Reading of leakage current out of scale.
Page 18 of 29
Earth leakage protection relay
DEVICE ADJUSTMENTS
Direct adjustments
Hold and press one of t he direct adjustment buttons to enter PROG mode (ico n in LCD) and change the relay setting. I f while in PROG mode any oth er direct function is activated (I
d
, td,
S
td
/+ and Auto), the sett ing of the parameter in the relay viewed is also enabled. Leaves the
PROG mode after a period in which no button is pressed, with the last “SAVE” setting.
Adjustment of main relay current
Press Id and hold for more than one second and PROG appears; press repeatedly to increase an adjustment in the list. The current adjustment can be seen in small figures, and the new adjustment in large ones. 30 mA, 100 mA, 300 mA, 500 mA, 1 A, 3 A, 5 A, 10 A, 30 A. There are limitations of scale, these are modified in the SETUP of the device. The default scale is 3 A
Adjustment of time and curve of the main relay Press I
d
for more than one second, PROG appears; press repeatedly to increase an adjustment in the list, including the types of curves. The current adjustment can be seen in small figures, and the new adjustment in large ones. INS Curve, SEL Curve [S], 20, 100, 200, 300, 400, 500, 750 ms, 1, 3, 5, 10 s. There are limitations of scale, these are modified in the SETUP of the device. The curves belong to the scale of 1 s, which is the default. If the adjustment of
I
N
is 30 mA, only instantaneous, 20 ms, INS or SEL Curves
adjustments are permitted.
Positive safety settings (main relays) “S
td
”, the contacts are in idle stat us, they are not shown on
the display (NO). “+”, the contacts change s tatus when the y power the device,
this is shown on the display. (NC).
Recovery setting
The device operates by signalling the faults. This option must not be used as earth leakage protection. When activating the REC, the device automatically resets when the leakage current drops below the programmed threshold once again.
Adjustments via SETUP
Press and hold to show a “PROG” on the display and the first menu option. Enter the menu programming mode, and press PROG to make different text indications appear on the display.
When you enter the desired menu, you can change the parameter by pressing the t
d
(rotating) button. To confirm the adjustments, press the PROG button again and the “SAVE” message appears showing the device version, returning to the home screen.
If the keypad is inactive for a period of time an “EXIT” message is displayed and the main relay settings are displayed without saving anything.
Press briefly to display the different parameters of each channel.
Page 19 of 29
Earth leakage protection relay
COMMUNICATION SETUP Programming*(ONLY FOR TYPES WITH COMMUNICATION)
One or more CBS-4C devices can be connected to a computer or PLC to automate a production process or an energy control system. This system can be used to centralise data at one single point as well the day-to-day operations of each one; for this reason the CBS-4C has an RS - 485 serial communication output. If more than one device is connected to a single line (RS - 485), a number or address has to be assigned to each one (from 1 to 99) so that the central computer or PLC can send the right requests for each peripheral to the addresses.
The communication parameters of the CBS-4C can be displa yed a nd/o r modif ied f rom th e comm unica tion SETUP; and the parameters can be adapted to the requirements of the network and/or application topologies.
The device does not record the programming changes until they are confirmed with the PROG button. When the keypad is detected as inactive for a certain period, it “EXITs” and leaves the programming menu without saving any changes.
After entering programming mode, a screen is displayed reporting that the device has entered the communications programming mode.
Press the PROG button to enter the configuration mode.
Peripheral number
The display shows PERI and the peripheral number in the top left hand corner of the screen.
To write or modify the peripheral number, press the td button repeatedly to increase the value of the digit in the top left hand corner.
When the desired screen value is shown, confirm and go to the next menu by pressing the PROG button to modify the other device configuration values.
The peripheral number ranges from 1 to 99.
To access the COMMUNICATIONS SETUP, press the PROG button to enter programming mode.
Page 20 of 29
Earth leakage protection relay
Transmission speed
The display shows the letters “bd” in the top left hand corner indicating bauds and the communication speed in devices of a thousand in the centre.
To modify the communication speed, press the td button repeatedly to increase the value of the digi ts in the centre of the screen.
When the desired value is shown on the screen, press the PROG button to go to the next digit and modify the other values there.
The possible programming values are as follows:
Value by screen
Bauds
2.4
2 400
4.8
4 800
9.6
9 600
19.2
19 200
38.4
38 400
54.6
54 600
115
115 000
Parity
The display shows the term “PARI” with the configured value in the top left hand corner.
To modify the parity, press the td button repeatedly to change the value of the digits in the top left hand corner of the screen.
When the desired value is shown on the screen, confirm and go to the next screen by pressing the PROG button and modify the configuration.
The communication programming via SETUP ends at this screen. It directly links with the first device measurement screen of SETUP.
Page 21 of 29
Earth leakage protection relay
MEASUREMENT SETUP PROGRAMMING
The configuration parameters of the CBS-4/CBS-4C can be displayed and/or modified from the measurement SETUP menu; and the parameters can be adapted to the requirements of the network and/or application topologies. This SETUP menu is preceded by the communications SETUP me nu if the device is a CBS-4C. If there are no CBS-4 communications, it is the only device SETUP menu.
The device does not record the programming changes until they are confirmed with the PROG button. When the keypad is detected as inactive for a certain period, it completes an “EXIT” and leaves the programming menu without saving any changes.
(*) Only CBS-4C. After entering the programming mode, a screen is displayed reporting that the device has entered
programming mode with the symbol PROG at the top of the first menu screen.
Working frequency
The display shows FREQ. Press PROG to enter and modify. The value of the configured current frequency appears in the top left hand corner of the screen.
To modify the working frequency, press the td button repeatedly to increase the value of the digit in the top left hand corner.
When the desired value is shown on the screen, confirm and go to the next menu by pressing the PROG button, and leave SETUP with the SAVE message.
Scale limit
The display shows LIM. Press PROG to enter and modify. The scale end values of delay scales and configured present current sensitivity appear at the top of the screen.
To modify the operating scale , press the td button repeatedly to change the value of the digits at the top. There are two scales, one extended to 10 seconds and 30 A and the default scale of 1 s and 3 A.
When the desired values are shown on the screen, press the PROG button to confirm, exit the SETUP with the SAVE message.
To access the MEASUREMENTS SETUP menu, press the PROG button to enter the programming mode(*)
Page 22 of 29
Earth leakage protection relay
ALARM SETUP PROGRAMMING
The display shows ALAR. Press PROG to enter and modify. The value of the configured current percentage appears in the bottom right hand corner of the screen.
To modify the pre-alarm current, press the td button repeatedly, modifying the percentage. When the desired value is shown on the screen, confirm and go to the next menu by pressing the PROG
button, and exit the SETUP with the SAVE message.
Page 23 of 29
Earth leakage protection relay
SETUP MENUS DIAGRAM
THE CBS-4 (CBS-4C WITH COMMUNICATIONS) STARTS PROGRAMMING VIA SETUP IN THE COM SUB-MENU.THIS WILL NOT APPEAR IN THE CBS-4 TYPE.
Page 24 of 29
Earth leakage protection relay
MODBUS PROTOCOL©
The CBS-4 multipoint earth leakage system communicates using the MODBUS RTU© protocol (Pulling Question / Response).
In the MODBUS protocol, the RTU (Remote Terminal Unit) mode is used; each 8-bit byte in a m essage contains two 4-bit hexadecimal characters. The format for each byte in RTU mode is:
Code 8-bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8-bit field of the message. Bits per byte 8 data bits Check-Error field CRC (Cyclical Redundancy Check) type
Modbus functions used: Function 04h Read
Function 10h Write
MODBUS MEMORY MAP©
Magnitude Symbol Values Uds Address
Read Write
No. of peripheral
PERI 1 – 99 - 0000h R/W
Communication speed
bd
2 400 (0h) – 4 800 (1h) – 9 600 (2h) – 19 200 (3h)
38 400 (4h)– 57 600 (5h)– 115 200 (6h)
Bauds 0001 h R/W
Type of parity PARI None (0h), Odd (1h), Even (2h) - 0002 h R/W
Working frequency FREQ 50 – 60 Hz 0003 h R/W
Trip current Main relay in channels
Id
0.03 (1h) – 0.1 (2h) – 0.3 (3h) – 0.5 (4h) – 1 (5h) 3 (6h)– 5 (7h) – 10 (8h) –30 (9h)
A
0004h (C1)
R/W
0005h (C2)
0006h (C3)
0007h (C4)
Delay time Main relay in channels
td
INS(0h) – SEL(1h) – 0.02(2h) – 0.1(3h) – 0.2(4h)
– 0.3(5h) – 0.4(6h)
0.5 (7h)– 0.75 (8h) – 1(9h) – 3(10h) – 5(11h) –
10(12h)
s
0008h (C1)
R/W
0009h (C2)
000Ah (C3)
000Bh (C4)
Contact polarity Relays
Std/+
Channel 1:0000h (NO), 0001h (NC)
Channel 2: 0000h (NO), 0002h (NC) Channel 3: 0000h( NO), 0003h (NC)
Channel 4: 0000h (NO), 0004h (NC)
- Dh 000 R/W
Trip current Pre-alarm
Id’ OFF(0h) – 50 (1h) – 60 (2h) – 70 (4h) – 80 (5h) % 000Eh R/W
Device version - 0 – 100 - 0015 h R Relay contact
status
-
off - on (main)
on (prealarm)
- 0019 h R
RMS value Leakage current
- 0 – 65,000 mA
001Ah (C1)
R
001Bh (C2)
001Ch (C3)
001Dh (C4)
RMS value Trip current
- 0 – 65,000 mA
001Eh (C1)
R
001Fh (C2)
0020h (C3)
0021h (C4)
Disable channel -
0001h:1,0002h:2, 0004h:3, 0008h:4 – Reset
0100h:1, 0200h:2, 0400h:3, 0800h:4 - Test
- 0022 h W
Enable
configuration
recording
-
0000 h - Enable
FFFF h - Record
- 0023 h W
Page 25 of 29
Earth leakage protection relay
Example of MODBUS© read
QUESTION 0A 03 00 00 00 0A 71 76
0A Peripheral number, 10 in decimal 03 Reading function 00 00 Log in which reading is to start 00 0A Number of logs to read: 10 in decimal 71 76 CRC character
RESPONSE 0A 04 14 00 0A 00 02 00 00 00 32 00 00 00 01 00 00 00 01 00 14 00 00 7E C9
0A Number of peripheral that responds, 10 in decimal 03 Reading function - the one used in the question 14 Number of bytes received (20) 00 0A Address 0000 h: Peripheral number (10) 00 02 Address 0001 h: Communication speed (2- 9,600 bauds) 00 00 Address 0001 h: Type of parity (0 - None) 00 32 Address 0003 h: Working frequency (50 Hz) 00 00 Address 0004 h: Programmed trip current (0-30mA) 00 01 Address 0005 h: Programmed time for delay in trip (1-INS) 00 00 Address 0006 h: Trip output relay polarity (0-Standard) 00 01 Address 0007 h: % I
n prealarm trip. (1-50%) 00 14 Address 0008 h: Programmed time for prealarm delay. (1 -20 ms) 00 00 Address 0009 h: Output relay polarity (0-Standard) 7E C9 CRC character
Example of MODBUS© write
QUESTION 01 10 00 00 00 05 0A 00 01 00 03 00 00 00 3C 00 00 FF 64
01 Peripheral number (1) 10 Number of Modbus instruction: Multiple parameter writing (16) 00 00 Initial writing log (0) 00 05 Number of logs to be modified (5) 0A Number of bytes passed (10) 00 01 Address 0000 h: Peripheral number of device. 00 03 Address 0001 h: Communication speed (3 - 19,200 bauds) 00 00 Address 0002 h: Type of progressive parity (0 -None) 00 3C Address 0003 h: Working frequency (3C - 60 Hz) 00 1E Address 0004 h: Trip current (0 - 30mA) FF 64 CRC character
RESPONSE
01 10 00 00 00 05 00 0A
01 Peripheral numbe r (1) 10 Number of Modbus instruction: Multiple parameter writing (16) 00 00 Initial writing log (0) 00 05 Number of logs to be modified (5)
00 0A Frame CRC
Every Modbus frame has a maximum limit of 26 logs
Page 26 of 29
Earth leakage protection relay
CONNECTING THE RS485 BUS
The RS - 485 cabling should be completed using twisted pair cables with mesh shielding (minimum 3 wires), with a maximum distance of 1.2 m between the CBS-4 and the master device. A maximum of 32 devices can be connected to the Bus in series.
For communication with the master device or PC, the following should be used:
1. The RS-232 to RS– 485 Protocol Network Intelligent Converter. Intelligent Converter (M54020)
2. TCP2RS Converter (M54031) of the RS-232/RS-485 Mains p r otocol to Ethernet TCP/IP.
Page 27 of 29
Earth leakage protection relay
APPLICATIONS
This system can be used not only for the day-to-day operation of each one, but also to centralise data in a single log point (Software Power Studio®, M90221).
The different devices and CBS-4C in a network can be monitored and configured in an installation.
The system allows easy configuration of communications in the network
Page 28 of 29
Earth leakage protection relay
You can see the operating status of the device from the PC.
Page 29 of 29
Earth leakage protection relay
You can program all the values of the device that can be configured with the device's keypad from the PC.
CIRCUTOR, SA
Vial Sant Jordi, s/n 08232 Viladecavalls BARCELONA (SPAIN) Tel. +34 93.745.29.00 Fax. +34 93.745.29.14 Web: http://www.circutor.com
Loading...