5-Settings parameters Parameters set for the control and various options.
6-Reading parameters Displays the status of the inputs, outputs, counters,
etc. (read-only).
7-Fault memory Shows the nine most recent faults (read-only).
Structure
of the menus
All information in the menus is displayed in a tree structure.
This tree structure is split into three levels, as shown by the diagram below.
MENUS
MENUS
PARAMETRES
PARAMETERS
MODIFICATION DES
CHANGING OF
VALEURS
VALUES
1-Consigne
1-Setpoint
2-Machine
2-Etat
status
machine
3-Measured
3-Valeurs
values
mesurees
4-Machine
4-Param
parameters
machine
5-Settings
-Param
parameters
de réglage
6-Read
6-Param de
parameters
Lecture
7-Fault
7-Memoire
memory
defauts
P100 Language
100 Langue
P203 ---------------
English
Français
-------
P100 Language
P100 Langue
P100 Langue
P100 Language
English
Français
----------
-------------
EN - 5
Control console (continued)
Navigation
Navigating through
the menus
Four buttons are available for
navigating through the menus:
Each button is described in the table below:
Î Press these buttons firmly!
Button Level
Menus
Select menu Select parameter
Scroll
through the
menus
Level
Parameters
Back to
Menus level
Scroll
through the
parameters
Pressing and holding the ‘+’ or ‘-‘ buttons
will cause the display to scroll faster.
Level
Values
Back to
Parameters level
Confirm value and
go back to
parameters
Lower the
parameter value or
scroll through the
values
Raise the
parameter value or
scroll through the
values
When the machine is turned on, the "machine off – on/off" menu
[2-Machine status] screen appears. Press to go back to the menu
list.
If the control console is not used for one hour, the [2-Machine status]
menu reappears. Press to go back to the menu list.
Arrows on the right of the screen indicate that additional information is
available. To see this information, press the ‘+’ or ‘-‘ buttons.
Example
The active line in a menu is shown by a flashing box to the left of the menu
number.
Example
▮100 LANGUAGE
COIL PRESSURE ↑
20.7 B↓
ENGLISH
EN - 6
Board functions: descriptions
Control
choices
On/Off control
Three types of control are possible. Refer to your order acknowledgement
to see which type you have selected:
• On/Off: Cascade control by activation of fan stages.
• Speed control: Fan speed control.
• Mixed: Speed control on stage 1, cascade control for the following
stages.
Used for cascade control of fan stages:
The diagram below illustrates this type of control:
A160 : Hystérésis étage 6
A 160: Stage 6 hysteresis
EXAMPLE FOR CIRCUIT 1
EXEMPLE POUR CIRCUIT 1
A 158 : Hystérésis étage5
A 158: Stage 5 hysteresis
C
E
O
T
N
A
A156 : Hystérésis étage4
A 156: Stage 4 hysteresis
T
G
R
E
O
L
D
A 154: Stage 3 hysteresis
E
A154 : Hystérésis étage3
S
T
R
A
E
G
G
A152 : Hystérésis étage 2
A 152: Stage 2 hysteresis
E
ULAT
A 150: Stage 1 hysteresis
A150 : Hystérésis étage 1
ION
A155 : Ǝtage 4
A153 : Ǝtage 3
A151 : Ǝtage 2
stage 3
stage 2
A159 : Ǝtage 6
A157 : Ǝtage 5
stage 5
stage 4
Stage 6
Speed control
With a speed drive
(option)
A121 or A122 Setpoint
A121ou A122 Consigne
Used to adjust the speed of all the fans.
The diagram below illustrates this type of control:
Voltage
Tension
EXAMPLE FOR COIL 1, CIRCUIT 1,
EXEMPLE BATTERIE 1 CIRCUIT 1
SETPOINT 1
CONSIGNE 1
10V
0V
(A150=hystérésis)
(A150=hysteresis)
A121 + A150
Measurement
Mesure
Measurement
EN - 7
Board functions: descriptions (continued)
Control
choices
(continued)
Mixed control
With a speed drive
(option)
Used to adjust the speed on stage 1. Cascade control is used for the other
fan stages.
The diagram below illustrates this type of control:
2nd stage
2°étage
EXAMPLE FOR CIRCUIT 1
EXEMPLE POUR CIRCUIT1
3°étage
3rd stage
4°étage
4th stage
5°étage
5th stage
6°étage
6th stage
1st stage
1°étage
5%
A121
Setpoint
Consigne
55% 65% 75% 85%
(A150=hysteresis)
(A150=hystérésis
95% 15% 25% 35% 45%
Measurement
A121 + A150
Automatic
machine operation
control
Manual
override
Two setpoints
Stage runtime
balancing
Spray
(units with spray
ducts)
Used to remotely authorise or prohibit the operation of the machine.
The machine is on when the contact is closed.
Used to turn on all the fans. The machine is in override mode when the
contact is closed.
Manual override can be activated and deactivated either directly on the unit or
remotely.
Used, for example, for summer/winter or day/night operation. Each circuit can
have up to two control setpoints. These setpoints can be switched via the dry
contact (On/Off), the console or over a BMS.
The running time of each fan stage is balanced by a time counter.
Used to increase the efficiency of the AeroConnect by spraying very fine
droplets of water into the ambient air to cool it through evaporation.
Two options:
- Optimised water consumption: the water spray does not start until all the
stages are on and the setpoint is exceeded.
- Optimised electricity consumption: the water spray does not come on until
the outdoor temperature reaches a preset value.
EN - 8
Board functions: descriptions (continued)
p
Free cooling
During free cooling, the dry cooler is run with a CIAT chiller. Both units are
controlled by the board.
The three-way valve can be controlled by the board provided the maximum
current is 3 A and the maximum voltage is 230 V. Refer to the chiller pump
curve to size the valve.
DC only
Chiller (CH)
Selection
temperature
P
CH only DRY COOLER + CHILLER
Process
return
tem
.
Text
Link with CIAT
chiller
BMS link
The following information is exchanged between the dry cooler (DC) or the
condenser (CO) and the chiller (CH):
CH > (DC / CO) (DC / CO) > CH
Dry cooler (DC)
• Chiller on/off • DC or CO on/off
• Setpoint (CO) • Free cooling
• Pressure value (CO) • Fan stage fault
With the exception of the language, control type (local, remote),
communication mode and bus number, all the parameters can be accessed
in read and write modes.
•Sensor fault
EN - 9
Options
Relay boards
Main board
Additional board
Remote control
console
Console mounting
dimensions (mm)
The boards must be installed in a cabinet.
It has dry contacts for displaying three parameters: unit operation, sensor faults
and fan stage faults.
For units with a motherboard and a daughterboard. It has dry contacts for
displaying two parameters: sensor faults and fan stage faults.
Used to view and control the operation of the unit from a distance.
Maximum distance of 1000 m.
Must be installed indoors.
Height = 55
Electrical connections
General
Communication bus
connection
On/Off input
connections
(automatic operation
control, manual override,
changeover of two
setpoints)
Analogue output
connections
Single-pair shielded cable required. Capacitance between wire and shield:
120 pF/m – Resistance of 56 Ω/km.
Examples: Filotex FMA 2P or Filotex IBM 7 362 211.
The shield must be connected at each end to the 0 V line (terminal 3 on J13 or
J12) on the units and the earth to the PLC end. The shielding braid must be as
short as possible (2 cm max.).
The cables must be routed at a distance of at least 30 cm from the power
cables. However, if a power cable intersects with a computer cable, they must
do so at a right angle.
For distances of less than 30 metres, use a shielded cable and keep it at least
30 cm away cm from all lines that could generate interference.
For distances of over 30 metres, install a relay for each input near the board.
Signal output of 0/10 V. Minimum VFD input impedance of 1 kΩ. Shielded cable
connections. Shield connected at both ends to earth. Minimum cross-section of
0.32 mm
2
(1.5 mm2 max.).
On/Off output
connections
(General operation signal,
general fault signal)
Potential-free dry contacts. Maximum current of 10 A (AC1 load), minimum of
5 mA. Voltage of 12 to 230 V AC. Maximum connection cross-section of
2.5 mm
2
.
EN - 10
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.