CIAT Aeroconnect Installation, Operation, Commissioning, Maintenance

N 08.132 B
11 - 2008
Installation Fonctionnement Mise en service
Maintenance
Installation
Operation
Maintenance
Montage-
Betriebs-und
Wartungs-
Anweisung
AEROCONNECT
Contents
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Sections Page
General......................................................................................................................
Board functions..........................................................................................
Limits of use ...............................................................................................
Compatible equipment...............................................................................
Control console.........................................................................................................4
Description of control console .................................................................
Display ........................................................................................................
Menu tree structure....................................................................................
Menu list .......................................................................................
Structure of the menus................................................................
Navigation...................................................................................................
Board functions: description ..................................................................................
Control choices ..........................................................................................
On/Off control (stages) ................................................................
Speed control ...............................................................................
Mixed control................................................................................
Automatic operation control .....................................................................
Manual override..........................................................................................
Two setpoints .............................................................................................
Stage runtime balancing............................................................................
Spray ...........................................................................................................
Free cooling................................................................................................
Link with CIAT chiller.................................................................................
BMS link......................................................................................................
Options......................................................................................................................
Relay boards...............................................................................................
Remote control console ............................................................................
Electrical connections .............................................................................................
General........................................................................................................
Connection diagram...................................................................................
Board connections.....................................................................................
Dry cooler configuration..........................................................................................
Configurations............................................................................................
Commissioning and configuration ...........................................................
Information available while the unit is running .......................................
Factory-set parameters..............................................................................
Condenser configuration.........................................................................................
Configurations............................................................................................
Commissioning and configuration ...........................................................
Information available while the unit is running .......................................
Factory-set parameters..............................................................................
BMS communication protocol ................................................................................
Communication interface ..........................................................................
Transmission mode ...................................................................................
Remote signalling register ........................................................................
Remote alarm register ...............................................................................
Remote measurement register..................................................................
Fault memory..............................................................................................
Counters .....................................................................................................
Remote configuration register ..................................................................
Functions 1 and 2.......................................................................................
Remote alarm and operating status ...........................................
Remote control.............................................................................
Remote diagnostics.....................................................................
Event counter ...............................................................................
Glossary....................................................................................................................
3
3 3 3
4
5 5 5 5 6
7
7 7 7 8 8 8 8 8 8 9 9
9
10
10 10
10
10 11 13
16
16 16 18 19
20
20 20 21 23
24
24 24 24 25 25 26 26 27 29 29 29 29 29
30
EN - 2
General
Board functions
Limits of use
Electrical
Compatible equipment
Integrated in an electrical panel, this board performs the following functions:
temperature or pressure control,
operation parameter monitoring,
communication with CIAT chillers,
diagnostics and fault storage,
communication with the remote control console, ancillary boards,
and customer BMS (bus).
Ambient air: During operation: min./max. temperatures = -25°C/40°C Stored: min./max. temperatures = -40°C/80°C
Single-phase fluid: min./max. adjustment temperature = 5/90°C (up to 150°C optional)
Refrigerant: min./max. set pressure: 5/45 bar
Board supply voltage: 230 V
The AeroConnect board is used to control the dry coolers and air-cooled condensers
Possible configurations and identification conventions:
Flatbed or V-type coils
Flatbed
+6%
-10%
V-type
Unit with one or two fan lines
Unit with one or two coils
Unit with one or two circuits
Line 1
Circuit 1 Circuit 2
Line 2
Coil 2
Coil 1
Coil 1
Line 1
Line 2
Coil 2
EN - 3
Control console
Description of control console
(local and remote)
Letter Illustration Function
A
B
F
A
B
I
C
D
E
J
H G
Power button
LED Meaning
Off On Flashing
LED on = system energised.
Machine off Machine on Machine shut off by automatic control
C
D
E
F
G
H
I
LED flashing = fault
Press this button to select setpoint 1 or 2. The corresponding LED lights up.
Press this button to activate or deactivate the fan manual override. Flashing LED = manual override on.
Display screen.
Status of the fan stages:
Top row = Fan line 1
Bottom row = Fan line 2
LED Meaning
Off On Flashing
Measurement faults
LED No. Meaning
1 2 3 4 5
Menu navigation buttons: see the Navigation section.
Circuit 1 coil 1 Circuit 2 coil 1 Circuit 1 coil 2 Circuit 2 coil 2 Outdoor temperature
Stage off Stage on Stage fault
J
Reset button for certain faults. Does not work with the remote control console.
EN - 4
Control console (continued)
Display
Menu tree structure
Menu list
Two-line LCD – Displays system readings and controls.
There are seven main menus for controlling the system. Each menu contains different parameters.
MENUS Description
1-Setpoints Change setpoints - Menu not displayed if the unit is
run with a CIAT chiller.
2-Machine status Default menu. Contains read-only information on the
operation of the machine.
3-Measured values Displays read-only temperature and pressure values.
4-Machine parameters Machine configuration parameters.
5-Settings parameters Parameters set for the control and various options.
6-Reading parameters Displays the status of the inputs, outputs, counters,
etc. (read-only).
7-Fault memory Shows the nine most recent faults (read-only).
Structure of the menus
All information in the menus is displayed in a tree structure.
This tree structure is split into three levels, as shown by the diagram below.
MENUS
MENUS
PARAMETRES
PARAMETERS
MODIFICATION DES
CHANGING OF
VALEURS
VALUES
1-Consigne
1-Setpoint
2-Machine
2-Etat
status
machine
3-Measured
3-Valeurs
values
mesurees
4-Machine
4-Param
parameters
machine
5-Settings
-Param
parameters
de réglage
6-Read
6-Param de
parameters
Lecture
7-Fault
7-Memoire
memory
defauts
P100 Language
100 Langue
P203 ---------------
English
Français
-------
P100 Language
P100 Langue
P100 Langue
P100 Language
English
Français
----------
-------------
EN - 5
Control console (continued)
Navigation
Navigating through the menus
Four buttons are available for navigating through the menus:
Each button is described in the table below:
Î Press these buttons firmly!
Button Level
Menus
Select menu Select parameter
Scroll through the menus
Level Parameters
Back to Menus level
Scroll through the parameters
Pressing and holding the ‘+’ or ‘-‘ buttons will cause the display to scroll faster.
Level Values
Back to Parameters level
Confirm value and go back to parameters
Lower the parameter value or scroll through the values
Raise the parameter value or scroll through the values
When the machine is turned on, the "machine off – on/off" menu
[2-Machine status] screen appears. Press to go back to the menu
list.
If the control console is not used for one hour, the [2-Machine status] menu reappears. Press to go back to the menu list.
Arrows on the right of the screen indicate that additional information is available. To see this information, press the ‘+’ or ‘-‘ buttons.
Example
The active line in a menu is shown by a flashing box to the left of the menu number.
Example
100 LANGUAGE
COIL PRESSURE
20.7 B
ENGLISH
EN - 6
Board functions: descriptions
Control choices
On/Off control
Three types of control are possible. Refer to your order acknowledgement to see which type you have selected:
On/Off: Cascade control by activation of fan stages.
Speed control: Fan speed control.
Mixed: Speed control on stage 1, cascade control for the following
stages.
Used for cascade control of fan stages:
The diagram below illustrates this type of control:
A160 : Hystérésis étage 6
A 160: Stage 6 hysteresis
EXAMPLE FOR CIRCUIT 1
EXEMPLE POUR CIRCUIT 1
A 158 : Hystérésis étage 5
A 158: Stage 5 hysteresis
C
E
O
T
N
A
A156 : Hystérésis étage 4
A 156: Stage 4 hysteresis
T
G
R
E
O L
D
A 154: Stage 3 hysteresis
E
A154 : Hystérésis étage 3
S T
R
A
E
G
G
A152 : Hystérésis étage 2
A 152: Stage 2 hysteresis
E
U L A T
A 150: Stage 1 hysteresis
A150 : Hystérésis étage 1
I O N
A155 : étage 4
A153 : étage 3
A151 : étage 2
stage 3
stage 2
A159 : étage 6
A157 : étage 5
stage 5
stage 4
Stage 6
Speed control
With a speed drive (option)
A121 or A122 Setpoint
A121 ou A122 Consigne
Used to adjust the speed of all the fans.
The diagram below illustrates this type of control:
Voltage
Tension
EXAMPLE FOR COIL 1, CIRCUIT 1,
EXEMPLE BATTERIE 1 CIRCUIT 1
SETPOINT 1
CONSIGNE 1
10V
0V
(A150=hystésis)
(A150=hysteresis)
A121 + A150
Measurement
Mesure
Measurement
EN - 7
Board functions: descriptions (continued)
Control choices (continued)
Mixed control
With a speed drive (option)
Used to adjust the speed on stage 1. Cascade control is used for the other fan stages.
The diagram below illustrates this type of control:
2nd stage
2°étage
EXAMPLE FOR CIRCUIT 1
EXEMPLE POUR CIRCUIT 1
étage
3rd stage
4°étage
4th stage
étage
5th stage
6°étage
6th stage
1st stage
1°étage
5%
A121
Setpoint
Consigne
55% 65% 75% 85%
(A150=hysteresis)
(A150=hystérésis
95% 15% 25% 35% 45%
Measurement
A121 + A150
Automatic machine operation control
Manual override
Two setpoints
Stage runtime balancing
Spray (units with spray ducts)
Used to remotely authorise or prohibit the operation of the machine. The machine is on when the contact is closed.
Used to turn on all the fans. The machine is in override mode when the contact is closed. Manual override can be activated and deactivated either directly on the unit or remotely.
Used, for example, for summer/winter or day/night operation. Each circuit can have up to two control setpoints. These setpoints can be switched via the dry contact (On/Off), the console or over a BMS.
The running time of each fan stage is balanced by a time counter.
Used to increase the efficiency of the AeroConnect by spraying very fine droplets of water into the ambient air to cool it through evaporation.
Two options:
- Optimised water consumption: the water spray does not start until all the stages are on and the setpoint is exceeded.
- Optimised electricity consumption: the water spray does not come on until the outdoor temperature reaches a preset value.
EN - 8
Board functions: descriptions (continued)
p
Free cooling
During free cooling, the dry cooler is run with a CIAT chiller. Both units are controlled by the board.
The three-way valve can be controlled by the board provided the maximum current is 3 A and the maximum voltage is 230 V. Refer to the chiller pump curve to size the valve.
DC only
Chiller (CH)
Selection
temperature
P
CH only DRY COOLER + CHILLER
Process return tem
.
Text
Link with CIAT chiller
BMS link
The following information is exchanged between the dry cooler (DC) or the condenser (CO) and the chiller (CH):
CH > (DC / CO) (DC / CO) > CH
Dry cooler (DC)
Chiller on/off DC or CO on/off
Setpoint (CO) Free cooling
Pressure value (CO) Fan stage fault
With the exception of the language, control type (local, remote), communication mode and bus number, all the parameters can be accessed in read and write modes.
Sensor fault
EN - 9
Options
Relay boards
Main board
Additional board
Remote control console
Console mounting
dimensions (mm)
The boards must be installed in a cabinet.
It has dry contacts for displaying three parameters: unit operation, sensor faults and fan stage faults.
For units with a motherboard and a daughterboard. It has dry contacts for displaying two parameters: sensor faults and fan stage faults.
Used to view and control the operation of the unit from a distance. Maximum distance of 1000 m. Must be installed indoors.
Height = 55
Electrical connections
General
Communication bus
connection
On/Off input connections
(automatic operation
control, manual override,
changeover of two
setpoints)
Analogue output
connections
Single-pair shielded cable required. Capacitance between wire and shield: 120 pF/m – Resistance of 56 /km.
Examples: Filotex FMA 2P or Filotex IBM 7 362 211. The shield must be connected at each end to the 0 V line (terminal 3 on J13 or
J12) on the units and the earth to the PLC end. The shielding braid must be as short as possible (2 cm max.).
The cables must be routed at a distance of at least 30 cm from the power cables. However, if a power cable intersects with a computer cable, they must do so at a right angle.
For distances of less than 30 metres, use a shielded cable and keep it at least 30 cm away cm from all lines that could generate interference. For distances of over 30 metres, install a relay for each input near the board.
Signal output of 0/10 V. Minimum VFD input impedance of 1 kΩ. Shielded cable connections. Shield connected at both ends to earth. Minimum cross-section of
0.32 mm
2
(1.5 mm2 max.).
On/Off output
connections
(General operation signal,
general fault signal)
Potential-free dry contacts. Maximum current of 10 A (AC1 load), minimum of 5 mA. Voltage of 12 to 230 V AC. Maximum connection cross-section of
2.5 mm
2
.
EN - 10
Loading...
+ 21 hidden pages