Line Frequency Capacitors 50/60Hz
ESTAprop®/ESTAdry® 200 - 1000V, SELF-COOLING, SINGLE-PHASE
DESIGN
• MKP-type wound elements in high-quality steel sheet or brass sheet welded casing;
• Casing varnish RAL 7033;
• IP00, indoor, - 25°C/+ 45° C (unless otherwise confi rmed);
• Self-healing, with overpressure switch (“DR”) or tear-off fuse (A)*,(*available only for a limited number of types!);
• Connection bolt M12, or M20 (depending on application current);
Grounding bolt M12;
Mounting in the upright position, or horizontally on the
narrow side.
Water-cooled capacitors can be supplied upon request.
Vishay ESTA
VERSION A/CIRCUITRY VI
35
M 12
345
50
40
60
50
383
405
VERSION B/CIRCUITRY VI
35
rating plate
2 x ø 9.8
50
11 x 15
rating plate
pressure monitoring device
H1
135
H
5
V I
pressure monitoring device
ADDITIONAL CIRTUITRY VERSIONS
III
III
V
IV
VII
M 12
40 50
60
Document Number: 13054 Revision 16-May-02
50
383 405
345
2 x ø 9.8
11 x 15
H1
IX
75
V I
50
H
5
www.vishay.com
9
Phmkp...-DR/Phmkpg...-DR
Vishay ESTA
Line Frequency Capacitors 50/60Hz
200 – 1000V, 50Hz (60Hz on request)
UN Q (V) (kVAr) .. x ..kVAr (µF) (A) CIRCUITRY mm Phmkp . . .
200 200 3 x 67 15915 1000 A / VI 900 M12 ..200/200/1 S-DR
200 200 3 x 67 15915 1000 B / VI 730 M 12 ..200/200/1 S-DR
250 250 3 x 83 12732 1000 A / VI 720 M 12 ..250/250/1 S-DR
250 250 3 x 83 12732 1000 B / VI 570 M 12 ..250/250/1 S-DR
400 400 3 x 133 7958 1000 A / VI 650 M 12 ..400/400/1 S-DR
400 400 3 x 133 7958 1000 B / VI 570 M 12 ..400/400/1 S-DR
440 440 3 x 147 7234 1000 A / VI 720 M 12 ..440/440/1 S-DR
440 440 3 x 147 7234 1000 B / VI 560 M 12 ..440/440/1 S-DR
500 500 3 x 167 6366 1000 A / VI 910 M 12 ..500/500/1 S-DR
N
SUBDIVISIONS
C
N
IN VERSION/ H BUSHING TYPE
500 500 3 x 167 6366 1000 B / VI 720 M 12 ..500/500/1 S-DR
550 510 3 x 170 5367 927 A / VI 970 M 12 ..550/510/1 S-DR
550 550 3 x 183 5787 1000 B / VI 800 M 12 ..550/550/1 S-DR
600 510 3 x 170 4509 850 A / VI 970 M 12 ..600/510/1 S-DR
600 550 3 x 183 4863 917 B / VI 820 M 12 ..600/550/1 S-DR
660 420 2 x 210 3069 636 A / V 960 M 12 ..660/420/1 S-DR
660 550 3 x 183 4019 833 B / VI 970 M 12 ..660/550/1 S-DR
750 550 3 x 183 3112 733 A / VI 970 M 12 ..750/550/1 S-DR
750 600 3 x 200 3395 800 B / VI 860 M 12 ..750/600/1 S-DR
800 600 3 x 200 2984 750 A / VI 950 M 12 ..800/600/1 S-DR
800 630 3 x 210 3133 788 B / VI 790 M 12 ..800/630/1 S-DR
900 630 3 x 210 2476 700 A / VI 910 M 12 ..900/630/1 S-DR
900 675 3 x 225 2653 750 B / VI 790 M 12 ..900/675/1 S-DR
1000 555 3 x 185 1767 555 A / VI 970 M 12 ..1/555/1 S-DR
1000 675 3 x 225 2149 675 B / VI 940 M 12 ..1/675/1 S-DR