Chromalox SRP Catalog Page

Self-Regulating Process Temperatures
• Self- Regulating, Energy
Efcient
• 16 AWG Buss Wire
• Circuit Lengths to 750 ft.
• Process Temperature Maintenance to 230°F (110°C)
Heating Cable
E C B A
Cut to Length
in Field
Can be Single
Overlapped
D
Maintains up to
230°F
Withstands up to
275°F
Low Tempera-
ture
Output
Temperature
Self Regulating
Output
• Maximum Continuous Exposure Temperature, Power Off, 275°F (135°C)
• Available in 5, 10, and 15 Watts per Foot
• 120 and 208-277 Volts Available from Stock
• Industrial Process Maintenance Applications
• Approximate Size 3/8"W x 1/8"H
• Min. Bend Radius 1-1/8"
• For use on Metallic Pipes
• Consult Facotory for use on Plastic Piping
Description
Chromalox SRP self-regulating heating cable provides safe, reliable heat tracing for process maintenance applications to 230°F (110°C) or freeze protection of pipes / tank with high heat losses. Constructed of industrial grade 16 AWG buss wire with a tinned copper braid and optional overjacketing, SRP ensures operating integrity most hostile industrial environments.
Features
• Energy efficient, self-regulating SRP uses less energy when less heat is required.
• Easy to install, SRP can be cut to any length (up to max circuit length) in the field.
• SRP features lower installed cost than steam tracing, less maintenance expense and less down time.
• SRP can be single overlapped without burn­out, which simplifies heat tracing of in-line process equipment such as valves, elbows and pumps.
• Because SRP is self-regulating, overtem­perature conditions are minimized.
• Chromalox U-Series Connection Kits reduce installation time.
Construction
A
Twin 16 AWG Copper Buss Wires – Pro-
vide reliable electric current capability.
B
Semiconductive Polymer Core Matrix
“Self-Regulating” component of the cable its electrical resistance varies with temperature. As process temperature drops,the core’s heat output increases; as process temperature rises, the heat output decreases.
C
Fluoropolymer Jacket – Flame retardant,
electrically insulates the matrix and buss wires and provides corrosion resistance.
D
Tinned Copper Braid – Provides addition-
al mechanical protection in any environ­ment and a positive ground path.
E
High Temperature Fluoropolymer
Overjacket – Corrosion resistant, flame
retardant overjacket is highly effective in many environments. Protects against exposure to organic or corrosive solu­tions. The overjacket also protects against abrasion and impact damage.
Approvals
Factory Mutual (FM) approved for ordinary areas. FM approved for hazardous (classi­fied) areas when used with U Series and DL accessories
FM Approved:
• Class I, Division 2, Groups B, C, D (Gases, vapors)
• Class II, Divisions 1*&2, Groups F, G (Comubustible dust)
• Class III, Division 2 (Easily ignitable fibers and fillings)
• Class I, Zone 1, AEx e II
• 3,5,8 and 10 Watt Rated T4 Temperature Class
SELF-REGULATING
WARNING A ground fault protection device is required by NEC to minimize the danger of fire if the heating cable is damaged or improp­erly installed. A minimum trip level of 30mA is recommended to minimize nuisance tripping.
G-13
Heating Cable
Self-Regulating Process Temperatures
(cont’d.)
Thermal Output Ratings on Insulated Metal Pipes
21
20
19
18
17
16
15
14
13
12
11
10
9
8
Heat Output (W/Ft.)
7
6
5
4
3
2
Cable Output vs.
1
Temperature
5 W/Ft.
15 W/Ft.
10 W/Ft.
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230
Pipe Temperature (°F)
Note 1 — Thermal output is determined per IEEE 515-2011 Standard for testing, design,
installation and maintenance of electrical resistance heat tracing section 4.1.11 Method C.
Output Wattage at Alternate Voltages (W/Ft.)
Model 208V
SRP 5 3.85 -20 4.25 -13 6.45 +15 SRP 10 8.3 -18 8.80 -10 12.50 +13 SRP 15 12.75 -14 13.50 -9 18.45 +12
% Change
In Output 220V
% Change
In Output 277V
% Change
In Output
Circuit Breaker Selection (Max. Circuit Lengths in Ft.)
Cable
Rating
SRP5-1CT 145 195 295 390 490 110 145 215 295 360 70 90 135 180 225 SRP5-2CT 295 385 580 750 750 220 290 430 580 720 135 180 270 360 450 SRP10-1CT 100 135 200 270 330 70 95 145 190 240 65 85 130 175 215 SRP10-2CT 200 270 400 530 665 145 190 290 380 480 130 175 260 350 440 SRP15-1CT 75 100 150 200 250 60 80 120 160 200 55 70 110 145 180 SRP15-2CT 150 195 295 390 500 120 160 235 320 400 110 145 220 290 360
NR = Not Required. Maximum circuit length has been reached in a smaller breaker size.
15A 20A 30A 40A 50A 15A 20A 30A 40A 50A 15A 20A 30A 40A 50A
50°F Start-Up (Ft.) 0°F Start-Up (Ft.) -20°F Start-Up (Ft.)