Chromalox RTBC, RTBC-EP Installation Instructions Manual

Chromalox
®
DIVISION 4 SECTION RT
SALES
REFERENCE
DATE
SERVICE REFERENCE
PJ454-6
161-562765-001
OCTOBER, 1998
(Supersedes PJ454-5)
© 1998 Wiegand Industrial Division, Emerson Electric Co.
GENERAL
WARNING: Hazard of Electric Shock. Disconnect all
power before starting. All installations must be effectively grounded in accordance with the National Electrical Code to eliminate shock hazard.
Note: All electrical wiring, including GFCI (Ground Fault Circuit Interrupters), must be done according to National Electrical or local codes by a qualified person.
These kits are designed to provide temperature control as well as power termination for one run of Rapid Trace Heating Cable. Select and purchase one grommet for terminating the cable. Please refer to the list below to insure that you purchase the proper grommet for the cable you are installing.
GR1 for SRL-C
GR2 for SRL-CR or SRL-CT
GR3 for CWM-C GR4 for CWM-CT GR5 for SRL-MC GR6 for SRL-MCR or SRL-MCT GR7 for SRM/E-C GR8 for SRM/E-CT
Each kit contains enough material to make one power connec­tion. Materials required for installation include: Standard electri­cal cutters, sharp utility knife, screwdriver and a pipestrap (Chromalox PS type or equal).
Wipe inside lip of cover with a clean cloth. Removing protec­tive backing from the gasket and affix it to the cover lip. Press firmly all around for proper adhesion.
RTBC and R TBC-EP
Power Connection Kit With Integral Thermostat
INSTALLATION
Note: These instructions are for all Self-Regulating and Constant Wattage Heating Cables in ordinary locations. Consult factory for installation of braided cable in hazardous locations. Not all instructions, however, are for all cases. Each step of the instruc­tions will have a heading in boldface stating which type of cable or connection each instruction is intended for.
1. FOR CONSTANT WATTAGE CABLE:
Cut the cable 12 inches past the last module point (indentation in cable). Note: Cutting the cable between module points cre­ates a non-heating cold lead. See Figure 1.
Figure 1
12”
Module Point
RTBC Kit Parts:
1 — Molded Enclosure consisting of Base — Box — Lid 1 — Three Position Terminal Block 1 — Mounting Screw for Terminal Block 1 — Uninsulated Barrel Connector (RTBC-EP Only) 1 — Eight Inch Length of 14AWG Insulated Wire with
Connector (RTBC Only)
1 — Ring Connector (RTBC Only) 1 — Thermostat with Mounting Screws (2) 1 — Capillary Grommet 1 — Cover Gasket 4 — Cover Screws, 5/8” Long 4 — Box Screws, 1” Long
NOTICE: These thermostats are designed for temperature control service only. Because they may not fail safe, they should not be used for temperature limiting duty.
WARNING: Users should install adequate back-up controls and safety devices with their electric heating equipment. Where the consequences of failure may be severe, back-up controls are essential. Although the safety of the installation is the respon­sibility of the user, Chromalox will be glad to make equipment recommendations.
RTBC
RTBC-EP
http://www.chromalox.com
INSTALLATION
2. FOR CABLE WITH EXPOSED METAL BRAID (-C):
Push the braid back 12 inches on the cable. See Figure 2.
3. FOR ALL CABLE:
Feed the end of the cable through the appropriate hole in the base. Allow 8 inches of cable to extend above the top of the base. See Figure 3.
4. FOR ALL CABLE:
Slide cable grommet over the end of the cable and insert it into the opening in the base. Attach the base to the pipe by threading the appropriate sized pipestrap through the slot in the mounting plate. Tighten the pipestrap until the base is loosely attached to the pipe. See Figure 4.
5. FOR OVERCOATED CABLES (-CR or -CT):
Score the outer insulation 1-1/2 inches from the end of the cable. Remove the jacket to expose the metal braid. See Figure 5. WARNING: Do not damage the braid or the base
cable insulation.
6. FOR ALL CABLE:
Punch out the knockouts on the bottom of the box which cor­respond to the openings in the base through which the heating cable passes. For these kits, the openings to be knocked out are the ones opposite the conduit entry and the one by the side of the box. Be careful to punch out only those knockouts to be used. If one is mistakenly punched, blank grommets can be ordered to re-establish the watertight seal. See Figure 6.
7. FOR ALL CABLE:
Feed the capillary of thermostat through the side hole of the box and side hole of the base. Slip the grommet over the capillary between the box and the base. See Figure 7.
8. FOR ALL CABLE:
Feed the cable through the end hole in the box. Allow 3/4 inch­es of stainless steel capillary to extend above the bottom of the box. Secure box to base using all four large (8-32) screws. See Figure 8.
9. FOR OVERCOATED CABLE:
Starting from the end of the cable. unravel 1-1/2 inches of the braid. Twist the strands together to form a pigtail. See Figure 9.
10.FOR SELF-REGULATING CABLE:
Using standard electrical cutters, cut a 3/4 inch long notch out of the cable between the conductor wires. Bare a 3/8 inch length of each conductor by stripping off the outside insula­tion and the inner black core material. See Figure 10.
11.FOR CONSTANT WATTAGE CABLE:
Score the outer jacket 3/4 inch from the end of the cable and remove the jacket. Cut off the exposed nichrome wire, pushing any remainder back under the jacket. Constant Wattage cables have an inner layer of insulation which is also to be removed as described above. Separate the buss wires and strip off the last 3/8 inch of insulation from both buss wires. See Figure 11.
Figure 2
12”
Figure 3
Figure 4
Figure 5
1-1/2”
8”
Figure 6
Figure 7
Figure 8
Figure 9
1-1/2”
Figure 10
Figure 11
1-1/2”
3/4”
3/8”
3/4”
http://www.chromalox.com
Loading...
+ 2 hidden pages