GENERAL
© 2010 Chromalox, Inc.
Titanium Over-the-Side Immersion Heater
Type PTHT
DANGER: This heater is not intended for use in haz-
ardous atmospheres where flammable vapors, gases, liquids or other combustible atmospheres are present as defined in the National Electrical Code. Failure to comply can result in explosion or fire.
Chromalox type PTHT over-the-side immersion heaters are especially suited for use in plating tanks, rinse tanks and other aqueous solutions.
WARNING: It is the responsibility of the purchaser of the heater to make the ultimate choice of sheath material based upon his knowledge of the chemical composition of the solution, and controls which he maintains on the process. Chromalox cannot warrant any electric immersion heater
against failure by sheath corrosion if such failure is the result of operating beyond our control.
1. Heater construction characteristics. A. High quality resistance wire held in place by compacted
magnesium oxide in titanium sheath.
B. Medium watt densities. C. Vapor tight junction box with 3’ PVC flexible conduit with
ground wire.
D. Spacer bar prevents elements from touching tank wall. E. Flat profile consumes little tank work area.
WARNING: Users should install adequate controls and safe-
ty devices with their electric heating equipment. Where the consequences of failure may be severe, back-up controls are essential. Although the safety of the installation is the responsibility of the user, Chromalox will be glad to make equipment recommendations.
Model
Volts
Dimensions (In.)
Approx.
Number
(Single
kW W/In
2
Wt.
Phase)
AB
(Lbs.)
PTHT-101 120
11913 6 6
PTHT-102 240
PTHT-202 240
2192112 7
PTHT-204 480
PTHT-302 240
3212617 8
PTHT-304 480
PTHT-402 240
4213122 9
PTHT-404 480
PTHT-602 240
6224233 12
PTHT-604 480
PTHT-802 240
8225344 14
PTHT-804 480
Specifications
INSTALLATION
WARNING:
Hazard of Electrical Shock. Disconnect all
power before installing heater.
1. Before installing the type PTHT heater, inspect it thoroughly for
possible damage which may have occured during shipment. Also check to insure that the line voltage is the same as that stamped on the heater nameplate.
2. Where work will pass over or near equipment, additional pro-
tection such as a metal guard may be needed.
3. To resist buoyancy and to keep the heater in close profile with
tank wall, a metal bracket with two mounting holes has been provided.
4. WARNING: Heated section (See Figure 1, “B” Dimension) must be totally immersed at all times. If the heater is not properly submerged, it will overheat and damage the heating element and create a possible fire hazard due to excessive sheath temperatures.
5. Heater must not be operated in sludge.
6. DANGER: Hazard of Fire. Since these heaters are capable
of developing high temperatures, extreme care should be taken to: A. Avoid installing heaters in an atmosphere containing com-
bustible gases and vapors.
B. Avoid contact between heater and combustible materials. C. Keep combustible materials for enough away to be free of
the effects of high temperatures.
Leadwires w/ Ground
Flexible PVC
Conduit
90˚ Bend
Mtg. Bracket
Terminal
Box
B
A
9-3/16”
4-3/4”
WIRING
WARNING: Hazard of Electric Shock. Any installa-
tion involving electric heaters must be effectively grounded in accordance with the National Electrical Code to eliminate shock hazard.
1. Electrical wiring to heater must be installed in accordance
with the National Electrical Code or local electrical codes by a qualified person.
2. When element wattages are not equal, heaters must not be
connected in series.
3. For single phase, apply power across two (2) black leads.
Green wire (ground) must be properly grounded.
4. For balanced 3 phase loads, three (3) heaters of the same volt-
age and wattage ratings are required. A six-step guide to wiring connections for 3 phase delta:
OPERATION
1. Do not operate heater at voltages in excess of that stamped on
the heater since excess voltage will shorten heater life.
2. WARNING: Always maintain a minimum of 2” of solution
above the heated portion of the element (See Figure 1, “B” Dimension) to prevent exposure of the effective heated length.
If the heater is not properly submerged, it may overheat and shorten heater life and create a fire hazard.
3. In an electroplating operation the heaters are not under any
circumstances to be placed between the electrodes and the work.
MAINTENANCE
WARNING: Hazard of Severe Shock. Disconnect all
power to heater before servicing or replacing heaters.
1. Heaters should be checked periodically for coatings and corro-
sion, and cleaned if necessary.
2. Tank should be checked regularly for sediment around the end
of heater as this sediment can act as an insulation and shorten heater life.
2150 N. RULON WHITE BLVD., OGDEN, UT 84404
Phone: 1-800-368-2493 www.chromalox.com
TA - Q0 - EF Litho in U.S.A.
A
A
A
A
#1#1
B
B
B
B
BBA A
#2
#2
#3
#3
A
A
A
A
#1
#1
#1
B
B
#2
#2
#2
#3
#3
#3
Step 1: Designate one black leadwire as “A” and one black leadwire as “B”.
Step 2: Assign designa­tions 1, 2, 3 to heaters.
Step 3: Connect leadwire “A” of Heater #1 to lead­wire “A” of Heater #2.
Step 4: Connect leadwire “B” of Heater #1 to lead­wire “B” of Heater #3.
Step 5: Connect leadwire “B” of Heater #2 to lead­wire “A” of Heater #3.
Step 6: Designate one 3 phase power line to each of the three connections.
Three Phase
Power
Note: Green wire (ground) of each heater must be properly grounded.
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.