Chromalox PF450-5 User Manual

© 2010 Chromalox®, Inc.
VUH Vertical Unit Heater
Specifications — Table 1
* Based on 60˚F entering air. ** For use with drop ceiling only. Installation in a drop ceiling should be in accordance with NFPA-90A and Article 300-22 of (NEC). *** For instructions on VUH units rated 15-25 kW refer to Bulletin PF451; VUH units rated 30-50 refer to Bulletin PF452.
A
B
C
4-11/16" Dia.
Mounting
Holes
Note:
Knockout Location See Table 2 For Recommended Conduit Size.
Figure 1
Figure 2
F
Approx.
H
D
E
12" Min.
30" Min.
M
7' Min.
To Floor
C
L
Position With Junction Box Facing Away From Walls For Easy Access
Warm Air
Discharge
4-11/16" Dia.
Mounting Holes
Heating Capacity Volts Air Delivery Data
Max.
Dimensions (In.)
Mtg.
Model
1 3 Outlet
Mtg. Weight
kW BTUH
Phase Phase
CFM FPM
Temp.˚F*
Height
ABCD EFHM
(Lbs.)
(Ft.)
208 208
VUH-C-05 5 17,000 240 240 450 703 102 10 14 13-1/2 26 3-1/4 6-5/8 4 7-1/4 10-5/8 48
277 480
208 208
VUH-C-07 7.5 25,500 240 240 550 880 102 12 14 13-1/2 26 3-1/4 6-5/8 4 7-1/4 10-5/8 48
277 480
9.8 208 208
VUH-C-10
10
34,000
240 240
712 1160 104 14 14 13-1/2 26 3-1/4 6-5/8 4 7-1/4 10-5/8 48
277 480
DIVISION 4 SECTION
VUH
SALES
REFERENCE
DATE
SERVICE REFERENCE
PF450-5
161-057822-001
JULY, 2002
Installation Instructions
and
RENEWAL PARTS IDENTIFICATION
(Supersedes PF450-4)
IMPORTANT
Failure to understand and follow these installation instructions and the “WARNING” notes therein may result in serious per­sonal injury from electrical shock, or from the heater falling due to faulty installation.
FIRE/EXPLOSION HAZARD. This heater is not intended for use in hazardous atmospheres where flammable vapors, gases, liquids or other com­bustible atmospheres are present as defined in the National Electrical Code. Failure to comply can result in personal injury or property damage.
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could result in personal injury or property dam­age. Heater must be installed by a qualified per-
sonal in accordance with the National Electrical Code, NFPA 70.
The heater must be mounted at least 7’ above the floor to prevent accidental contact with the heating elements or fan blade which could cause injury.
The ceiling structure, the brackets, hangers or chains used to sus­pend the heater, and the anchoring provisions must be of sufficient strength to support the combined weight of the heater installation (48 pounds for VUH-C-05, 07, 10 plus the weight of the supports).
Prior to operating the heater verify that the fan hub setscrews are tightened and the push-on clip is secured to assure that the fan blade is securely fastened to the motor shaft.
On models connected to three-phase power, fan blade rotation must be checked. If airflow is not downward, interchange any two of the three customer power leads.
First stage of thermostat must be connected to terminals C1 and C2 to insure proper operation of overheat protective devices.
INSTALLATION
ELECTRIC SHOCK HAZARD. Any installation involving electric heaters must be performed by a qualified person and must be effectively grounded in accordance with the National Electrical Code to eliminate shock hazard.
1. Heater should be positioned with the junction box facing away
from walls to provide easy access for servicing relay(s) mounted within. See Figure 1.
Mount the heater for down discharge only. Failure to comply may result in personal injury or property damage.
2. It is important that the 12” minimum dimension shown in
Figure 1 be maintained to make it possible for a serviceman to remove the fan motor, if necessary, without moving the heater from its mounting.
The heater must be mounted at least 7’ above the floor to prevent accidental contact with the heating elements or fan blade which could cause personal injury.
The ceiling structure, the brackets, hangers or chains used to sus­pend the heater and the anchoring provisions must be of sufficient strength to support the total weight of the heater installation (48 pounds for VUH-C-05, 07, 10 plus the weight of the supports).
3. The heater to be mounted to the ceiling by attaching rigid
angle brackets, hangers, or chains to the four mounting holes on the top of the heater case using four 5/8” bolts (by others). See Figures 1 and 2.
Note: Brackets, hangers, or chains to support the heater are supplied by the customer.
4. All wiring should be done in accordance with local codes and
the National Electrical Code by a qualified person.
Power Supply Circuit
Contactor
Holding Coil
Motor
Model
Minimum Volt Ampheres
kW Volts Phase
Line Line
No.
Conduit (Note 3)Amps Wire Size
Circuits
Size †(Note 1) (Note 2)
Inrush Sealed
Volts H.P. Phase
208 1 25 8 1 3/4” 208/240 208 3 15 12 1 1/2” 280/240 240 1 22 10 1 1/2” 208/240
VUH-C-05 5
240 3 13 12 1 1/2”
60 9
208/240
1/25 1
277 1 19 10 1 1/2” 277 480 3 7 14 1 1/2” 480
208 1 37 6 1 3/4” 208/240 208 3 22 10 1 1/2” 208/240 240 1 32 8 1 3/4” 208/240
VUH-C-07 7.5
240 3 19 10 1 1/2”
60 9
208/240
1/25 1
277 1 28 8 1 3/4” 277 480 3 10 14 1 1/2” 480
9.8
208 1 48 6 1 3/4” 208/240 208 3 29 8 1 3/4” 208/240
240 1 43 6 1 3/4” 208/240
VUH-C-10 10
240 3 25 8 1 3/4”
60 9
208/240
1/25 1
277 1 37 6 1 3/4” 277 480 3 13 12 1 1/2” 480
Table 2 - Electrical Data
Notes:
1. Includes Fan Motor Amps.
2. Use 75˚C Wire - Copper Conductors only.
3. Standard units have one contactor. Units with separate fan
motor control use two contactors.
Conduit knockout location - top of Junction Box.
Loading...
+ 2 hidden pages