HDS-1 Power Disconnect Switch Kit
for Field Installation in an HVH Series Air Heater
Electrical Data (60 Hz) Standard
Contactor
Model Volts Watts Phase Amps Rating (Qty.)
HVH-02-81 208 2,667 1 12.8
HVH-02-21 208/240 2000/2,667 1 11.1* ——
HVH-02-71 277 2,667 1 9.6
HVH-04-81†
208 4,000
1 19.2 ——
HVH-04-83† 3 11.2 30A (1)
HVH-04-21†
208/240 3,000/4,000
1 16.7* ——
HVH-04-23† 3 9.6* 30A (1)
HVH-04-71 277 4,000 1 14.5 ——
HVH-04-43 480 4,000 3 4.8 30A (1)
HVH-05-81†
208 5,000
1 24.0 ——
HVH-05-83† 3 13.8 30A (1)
HVH-05-21†
208/240 3,750/5,000
1 20.8* ——
HVH-05-23† 3 12.1* 30A (1)
HVH-05-71 277 5,000 1 18.2 ——
HVH-05-43 480 5,000 3 6.0 30A (1)
HVH-07-81†
208 7,500
1 36.1 50A (1)
HVH-07-83 3 20.9 30A (1)
HVH-07-21†
208/240 5,625/7,500
1 31.1* 30A (1)
HVH-07-23 3 18.1* 30A (1)
HVH-07-71 277 7,500 1 27.2 30A (1)
HVH-07-43 480 7,500 3 9.0 30A (1)
HVH-10-81†
208 10,000
1 48.0 50A (1)
HVH-10-83 3 27.8 30A (1)
HVH-10-21†
208/240 7,500/10,000
1 41.7* 30A (1)
HVH-10-23 3 24.0* 30A (1)
HVH-10-43 480 10,000 3 12.0 30A (1)
HVH-12-83 208 12,500 3 34.8 50A (1)
HVH-12-23 208/240 9,375/12,500 3 30.1* 50A (1)
HVH-12-43 480 12,500 3 15.1 30A (1)
HVH-15-83 208 15,000 3 41.8 50A (1)
HVH-15-23 208/240 11,250/13,000 3 36.2* 50A (1)
HVH-15-43 480 15,000 3 18.1 30A (1)
This instruction sheet provides information for field installing an
HDS-1 Power Disconnect Switch in an HVH Series air heater.
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do
so could result in personal injury or property damage. Power Disconnect Switch must be installed by
a qualified person in accordance with the National
Electrical Code, NFPA 70.