INSTALLATION
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing heater. Failure to do so could
result in personal injury or property damage.
Heater must be installed by a qualified person in
accordance with the National Electrical Code.
NFPA 70.
1. Vertical Mounting (Preferred) —
When the heater is vertically mounted, the electrical enclosure
will be at the top of the heater. The inlet pipe will be located on
the side near the bottom of the heater and the outlet pipe at the
top.
The axis of the chamber will be in a vertical position as in
Figure A.
2. Horizontal Mounting (Optional) —
When mounting heater horizontally, inlet and outlet pipes must
be up. In any other position, heater cannot be purged of air, and
elements may be seriously damaged. (See Figure B.)
Note: Heater cannot be completely drained in the horizontal position. When mounting the heater, allow adequate spacing for draining the heater.
3. Whether vertical or horizontal, the heater should be rigidly
mounted so that vibration is at a minimum since excessive
vibration will result in erratic thermostat operation (if thermostat is used instead of thermocouple). The NWHOSR/NWHSRG is provided with mounting lugs to support the heating
chamber. (See drawing on front page.)
FIRE HAZARD. An integral thermostat, if used, is
designed for temperature control service only.
Because the thermostat is not fail safe, it should
not be used for temperature limiting duty. Wiring to
this device is the responsibility of the user.
FIRE HAZARD. Since heaters are capable of developing high temperatures, extreme care should be
taken to:
A. Provide minimum of 6” spacing from chamber
and related piping to nearest combustible material.
B. Do not operate near combustible fluids or in
combustible vapor or gas laden atmosphere.
4. Ensure clearance is available to allow removal of the heating
assembly from the chamber. Generally this is a space extending from the electrical enclosure equal to the length of the
entire unit. Otherwise, removing the entire heater may be
required to service the heater.
5. Standard side inlet can be changed to the end connection for
ease of piping.
6. Mount heaters to permit unrestrained expansion of the chamber
due to temperature. This may be accomplished by using a slotted mounting assembly on either of the mounting lugs.
7. If two or more heaters are required to provide the heating
capacity, pipe units in series or parallel.
EXPLOSION HAZARD. When heating in closed vessels, controls and back-up controls must be used
to regulate build-up of temperature and/or pressure.
8. A pressure relief valve should be provided by customer at out-
let of vessel. There should be no other valving between vessel
and relief valve.
9. Install adequate collection/drainage below the heater to prevent
damage to other materials and property at your location.
Figure B — Horizontal Mounting
Figure A — Vertical Mounting
Correct
Correct
Incorrect
Incorrect
2