Chromalox PE414-3 User Manual

Chromalox
®
(Supersedes PE414-2)
PE414-3
NWH
161-304777-001
MAY, 2007
RENEWAL PARTS IDENTIFICATION
Installation, Operation
and
Circulation
Heaters for Oil or Water Heating
© 2010 Chromalox, Inc.
Specifications – Table A
GENERAL
READ ALL INSTRUCTIONS BEFORE USE
FIRE/EXPLOSION HAZARD. Ordinary location heaters (designated E1) are not intended for use in hazardous atmospheres where flammable vapors, gases, liquids or other combustible atmospheres are present as defined in the National Electrical Code. Failure to comply can result in personal injury or property damage.
This design has the versatility of field adjustments of voltage
kW through various wiring combinations.
The NWHSRG model is a general purpose water circulation heater intended for indoor use. E2 designs have a Moisture Resistant/Explosion Resistant enclosure. Designs are up to 40kW
- DO NOT USE THE NWHSRG MODEL FOR OIL.
The NWHOSR model is a general-purpose regular and fuel oil solution circulation heater intended for use indoors. E2 designs have a Moisture Resistant/Explosion Resistant enclosure. Designs are up to 10kW - DO NOT USE THE NWHOSR MODEL FOR WATER. Ensure the wiring guide for oil is used for the correct wiring diagram.
Both the NWHSRG and NWHOSR use six INCOLOY
®
sheath elements welded to a steel 2.5” screw plug. The vessel is cast iron and is surrounded by 1.5” insulation and a sheet metal jacket. For water applications, the vessel has a galvanized coating. A J-type thermocouple in a thermowell is standard. These
versaTHERM
TM
heaters
are designed for 150 psig max. at 35°F min. to 300°F max.
IMPORTANT: It is the responsibility of the purchaser of the heater to make the ultimate choice of sheath material based upon his knowledge of the chemical composition of the corrosive solution, character of the materials entering the solution, and controls which he maintains on the process.
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could result in personal injury or property dam­age. Heater must be installed or serviced by a qualified person in accordance with the National Electrical Code. NFPA 70.
The system designer is responsible for the safety of this equipment and should install adequate back-up controls and safety devices with their electric heating equipment. Where the conse­quences of failure could result in personal injury or property damage, back-up controls are essential.
If foreign material is to be carried by the liquid flow, install
suitable filters in the inlet pipe to the heater.
Ensure the temperature/pressure is controlled below the vapor point of the liquid at all times and is within the temperature/pres­sure ratings for this heater.
Heating elements must be completely immersed in liquid when energized.
Dim. (In.)
A B Model PCN
Cast Iron Body / Oil .5 to 10 kW
29 19 NWHOSR-06-04P5-E1 100108 29 19 NWHOSR-06-04P5-E1 100116 41 30
3
/4 NWHOSR-06-005P-E1 100124 29 19 NWHOSR-06-006P-E1 100132 29 19 NWHOSR-06-006P-E1 100140 41 30
3
/4 NWHOSR-06-010P-E1 100159
Galvanized Body / Water .5 to 40 kW
29 19 NWHSRG-06-018P-E1 100010 29 19 NWHSRG-06-018P-E1 100028 41 30
3
/4 NWHSRG-06-020P-E1 100036 29 19 NWHSRG-06-024P-E1 100044 29 19 NWHSRG-06-024P-E1 100079 41 30
3
/4 NWHSRG-06-040P-E1 100095
A
B
6"
Rotatable Terminal Cover
1" Conduit Opening
Outlet 1" FNPT
Inlet 1" FNPT
1" FNPT Pipe Plug (or Inlet)
8 / "
1
2
4"
2 Mtg. Lugs / "-13 x / " Deep
1
1
2
2
Specifications – Table B
Dim. (In.)
A B Model PCN
Cast Iron Body / Oil .5 to 10 kW
32 19 NWHOSR-06-04P5-E2 100255 32 19 NWHOSR-06-04P5-E2 100263 44 30
3
/4 NWHOSR-06-005P-E2 100271 32 19 NWHOSR-06-006P-E2 100280 32 19 NWHOSR-06-006P-E2 100298 44 30
3
/4 NWHOSR-06-010P-E2 100300
Galvanized Body / Water .5 to 40 kW
32 19 NWHSRG-06-018P-E2 100327 32 19 NWHSRG-06-018P-E2 100343 44 30
3
/4 NWHSRG-06-020P-E2 100351 32 19 NWHSRG-06-024P-E2 100360 32 19 NWHSRG-06-024P-E2 100378 44 30
3
/4 NWHSRG-06-040P-E2 100386
Dimensions (Inches)
A
B
11"
7-7/8"
6"
E1
E2
TM
INSTALLATION
ELECTRIC SHOCK HAZARD. Disconnect all power before installing heater. Failure to do so could result in personal injury or property damage. Heater must be installed by a qualified person in accordance with the National Electrical Code. NFPA 70.
1. Vertical Mounting (Preferred) —
When the heater is vertically mounted, the electrical enclosure will be at the top of the heater. The inlet pipe will be located on the side near the bottom of the heater and the outlet pipe at the top.
The axis of the chamber will be in a vertical position as in Figure A.
2. Horizontal Mounting (Optional) — When mounting heater horizontally, inlet and outlet pipes must be up. In any other position, heater cannot be purged of air, and elements may be seriously damaged. (See Figure B.)
Note: Heater cannot be completely drained in the horizontal posi­tion. When mounting the heater, allow adequate spacing for drain­ing the heater.
3. Whether vertical or horizontal, the heater should be rigidly mounted so that vibration is at a minimum since excessive vibration will result in erratic thermostat operation (if thermo­stat is used instead of thermocouple). The NWHOSR/NWH­SRG is provided with mounting lugs to support the heating chamber. (See drawing on front page.)
FIRE HAZARD. An integral thermostat, if used, is designed for temperature control service only. Because the thermostat is not fail safe, it should not be used for temperature limiting duty. Wiring to this device is the responsibility of the user.
FIRE HAZARD. Since heaters are capable of devel­oping high temperatures, extreme care should be taken to:
A. Provide minimum of 6” spacing from chamber
and related piping to nearest combustible mate­rial.
B. Do not operate near combustible fluids or in
combustible vapor or gas laden atmosphere.
4. Ensure clearance is available to allow removal of the heating
assembly from the chamber. Generally this is a space extend­ing from the electrical enclosure equal to the length of the entire unit. Otherwise, removing the entire heater may be required to service the heater.
5. Standard side inlet can be changed to the end connection for
ease of piping.
6. Mount heaters to permit unrestrained expansion of the chamber
due to temperature. This may be accomplished by using a slot­ted mounting assembly on either of the mounting lugs.
7. If two or more heaters are required to provide the heating
capacity, pipe units in series or parallel.
EXPLOSION HAZARD. When heating in closed ves­sels, controls and back-up controls must be used to regulate build-up of temperature and/or pres­sure.
8. A pressure relief valve should be provided by customer at out-
let of vessel. There should be no other valving between vessel and relief valve.
9. Install adequate collection/drainage below the heater to prevent
damage to other materials and property at your location.
Figure B — Horizontal Mounting
Figure A — Vertical Mounting
Correct
Correct
Incorrect
Incorrect
2
3
WIRING
ELECTRIC SHOCK HAZARD. Any installation involv­ing electric heaters must be performed by a quali­fied person and must be effectively grounded in accordance with the National Electrical Code to eliminate shock hazard.
Ensure the correct Wiring Guide is used for your heated medium and model type, and ensure the correct wiring diagram is used. Miswiring could result in an unsafe wattage.
1. Be sure line voltage matches your intended voltage and does
not exceed the max voltage on the nameplate.
2. Electric wiring to heater must be installed in accordance with
local and National Electrical Codes by a qualified person as defined in the NEC.
3. Power controllers must be used with this product.
4. Electrical wiring to heater should be with rigid conduit or flex-
ible conduit to keep corrosive vapors and liquids out of the electrical enclosure. If high humidity is encountered, the con­duit should slope down away from the heater.
5. Refer to appropriate wiring diagram for your model heater
from the Wiring Guide (on next two pages).
The specific Wiring Guide provides easy to follow steps to determine the appropriate wiring diagram for your heater instal­lation. Figure 1 may be referenced as a general diagram of how a contactor and temperature control are used in conjunction with the specific wiring diagrams.
6. Use ground fault protection equipment where electrical insula-
tion failure can cause process problems.
7. When element wattages are not equal, heaters must not be con-
nected in series.
8. If flexible cord is employed, a watertight connector should be
used for entry of the cord into the electrical enclosure. Outdoor applications require liquid-tight conduit and connectors.
9. If application uses a standard PCN at different voltages and
kWs from the Wiring Guide, refer to the Customer Wiring Guide Supplement if included with these instructions, or con­tact Customer Service at (800) 368-2493.
Note: Dotted lines indicate “customer furnished.” Complete power/temperature control panels or components are available. Contact Chromalox 1-800-443-2640
for more information and assistance.
Contactor
Thermostat
L1
L2
To equipment disconnect with overcurrent protection
L1 L2 L3
Heater
1Ø or 3Ø: Refer to wiring diagram designated from the the Wiring Guide for specific wiring directions to the heater.
or
Temperature control
L1
L2
Thermocouple
}}
Type "J" thermocouple is standard.
Control voltage
Figure 1
Loading...
+ 5 hidden pages