Chromalox MOS Series Installation & Operation Manual

Installation & Operation Manual
MOS Series Hot Oil System
PQ448-1
161-123417-032
September 2018
1
MOS Series Hot Oil System
General Information
The Chromalox Heat Transfer Unit is a thoroughly engi­neered, pretested package, designed to give years of service, virtually maintenance free if properly installed. The MOS series can operate at 600˚F (315˚C) or 650˚F (343˚C) at atmospheric pressure (depending upon heat transfer fluid properties and unit configuration) with features that comply with the National Electrical Code.
Common to all models: electronic process controller, air-cooled mechanical seal, chamber insulation, dis­charge pressure gauge, steel heater sheath, cast iron, centrifugal pump; power requirements 240 to 600 volts, 3 phase, 60 cycles, 50 thru 500kW.
In hazardous areas, pipe surfaces could achieve temperatures high enough to cause auto-ignition of the hazardous material pres­ent. Consult Article 500 of the National Elec­tric Code for further information on the maxi­mum allowable temperature for a specific application.
H
H
D
W
W
D
MOS 50-150 kW Unit (Front View) MOS 175-500 kW Unit (Rear View)
Unit Proportions
2
TDH
Motor
(Ft.)
130 10
HP
Inlet/Outlet
Connection
3
ANSI
3”, 150#
System
Capacity
(Gal.)
3
Unit Size
Dry
Weight
(Lbs.)
Width
(In.)
Depth
(In.)
Height
(In.)
Flow
1
Rate
2
Pressure
GPM
50 & 75 kW 900 36 42 96 80 130 5 2”, 150# 24 100-150 kW 1400 36 42 96 120 130 7.5 3”, 150# 35 175-300 kW 2600 48 54 96 200 130 10 3”, 150# 65 350-500 kW 3500 48 54 96 200
1
650˚F Option will add 8” to overall height.
2
Refer to pump graph for full operating range
3
Option for 300 GPM 20HP pump with 4”, 150# inlet/outlet
3
85
2
Fluid Compatibility
This system is NOT for use with water, ethylene glycol and water mixture or some of the syn­thetic heat transfer fluids.
To avoid possible damage to the heaters do not energize the heater unless the system is filled with fluid.
Read manufacturer’s technical bulletins and instruc­tions carefully. Some heat transfer fluids may ignite or burn spontaneously if not properly used.
If you are not sure you are using an accepted heat transfer fluid, check with fluid manufacturer.
Unit Installation
Note: When installing system, allow sufficient room to
remove heating bundle.
Hydraulics
Note: The MOS systems should be mounted so the
control box does not fall in direct sunlight.
The bed plate should be mounted on a level, solid foundation and bolted down.
DO NOT mix heat transfer fluids unless authorized and approved by the fluid manufacturer. All heat transfer fluids are not compatible with each other, whether made by the same manufacturer or a different manu­facturer. If you plan to switch fluids, check with the fluid manufacturer to determine the following.
A. Is the new fluid compatible with the old?
B. What is the recommended cleaning method to re-
move the old fluid, its sludge, or any deposits re­maining in the system?
C. Does the fluid manufacturer have a reclaiming ser-
vice for used fluid? Do they have recommended procedure for disposal of used or old fluid?
1. Allow at least 1 foot or more around unit for proper maintenance,
2. Unit is designed for 104˚F (40˚C) maximum operat­ing environment.
3. Unit will be operating at elevated temperatures. Proper care must be provided to ensure personnel safety.
Piping Installation
1. The pipe size should be the same as the system
piping connections. All piping must be supported so the pump is not carrying any of the pipe weight. If these instructions are not followed, distortion in the pump may cause unnecessary wear and faulty operation.
2. The piping of the entire system should be arranged to minimize pockets where air may be trapped. Manual air vents or bleeder valves should be pro­vided in the system where air pockets may occur, or where the flow of fluid may drop.
3. Piping should be properly supported so pump can be removed without changing the position of the piping. If piping moves when the pump is removed, pump malfunction is probably due to stresses and twisting caused by the piping. These stresses will multiply where the system is hot due to thermal ex­pansion.
4. If there is a high differential pressure between the inlet and outlet of the heat transfer system at oper­ating temperature, this is probably due to a piping restriction. A continuing high differential pressure can cause excessive wear on the pump and pump stuffing box packing or mechanical seal and will eventually cause premature failure of the pump. The major causes of restrictions are:
a. Inlet and outlet pipes smaller than provided on
the system.
b. Piping many processes in series with one anoth-
er. To reduce the pressure drop of the system, equipment should be re-piped in balanced paral­lel flow.
DO provide for expansion and contraction of process piping and connections to the system. Piping strains can cause pump and motor misalignment, excessive wear on pump body, bearings and stuffing box packing or mechanical seal and will eventually cause failure of the pump and system.
DO provide sufficient cross sectional area in the pro­cess piping connections equivalent to the system pipes. In order to prevent undue pressure drop, maxi­mum velocity in all piping should be less than 10 feet per second.
DO check all vent tubes, purge valves, and bypass re­lief valves at least once a month. All heat transfer oils oxidize in the presence of air and sludge can block crit­ical piping. Blocked vent tubes may cause excessive system pressures and/or an explosion.
DO retighten all bolted connections and joints at oper­ating temperature. Joints will expand and leak as they get hot. Check all threaded connections on controls, gauges, etc. for leaks.
3
Loading...
+ 7 hidden pages