Chromalox ITASC1D2-EXT Installation Manual

Installation Manual & Set-Up Guide
Ordinary Area
ITAS Ambient Sensing Control Panel
ITAS-EXT Ambient Sensing Extender Control Panel
ITLS Line Sensing Control Panel
ITLS-EXT Line Sensing Extender Control Panel
Hazardous Area
ITASC1D2-EXT Ambient Sensing Extender Control Panel
ITLS C1D2 Line Sensing Control Panel
ITLS C1D2-EXT Line Sensing Extender Control Panel
PK497-5
0037-75514
June 2018
1
Safety Precautions
IMPORTANT SAFEGUARDS
Throughout the IntelliTrace® Setup Guide, these sym­bols will alert you to potential hazards. Safety precau­tions should always be followed to reduce the risk of fire, electrical shock, injury and even death to persons.
Please read all instructions before operating your IntelliTrace® ITLS, ITAS, ITLS-EXT or ITAS-EXT Control Panel.
WARNING
HIGH VOLTAGE is used in the opera­tion of this equipment; DEATH ON CONTACT may result if personnel fail to observe safety precautions.
Learn the areas containing high-volt­age connections when installing or operating this equipment.
To avoid electrical shock or injury, always remove pow­er before servicing a circuit. Personnel working with or near high voltages should be familiar with modern methods of resuscitation. Contact an area supervisor or safety personnel for more information.
WARNING
ELECTRIC SHOCK HAZARD
Any installation involving control equipment must be performed by a qualified person and must be effec­tively grounded in accordance with the National Electrical Code to elimi­nate shock hazard.
Be careful not to contact high-volt­age connections when installing or operating this equipment.
Before working inside the equipment, turn power off and ground all points of high potential before touching them.
ii
Table of Contents
Contents Page Number
Safety Precautions .................................................................................................................................................ii
Table of Contents .................................................................................................................................................iii
Introduction ............................................................................................................................................................ 1
Model Overview ..................................................................................................................................................... 2
Theory of Operation .............................................................................................................................................. 3
Types of Sensing Control ..................................................................................................................................... 4
Pre-Service Storage .............................................................................................................................................. 5
Before Powering Up ............................................................................................................................................. 5
General Panel Notes ............................................................................................................................................ 6
Installation ............................................................................................................................................................. 7
Main Menu Screen ............................................................................................................................................... 8
Temp Setup Menu.. .............................................................................................................................................. 9
Security Levels & Password Screen ................................................................................................................. 10
Temp Setup Menu (Cont.) ................................................................................................................................. 11
Apply Settings Globally .................................................................................................................................... 13
Soft Start Feature .............................................................................................................................................. 13
Load Setup Menu .............................................................................................................................................. 14
Tuning Menu ......................................................................................................................................................... 16
Control Modes: ON/OFF, Autotune & PID ......................................................................................................... 17
Sensor Mapping ................................................................................................................................................ 18
System Properties ............................................................................................................................................. 19
Auto Cycle Feature ............................................................................................................................................ 20
Communications ............................................................................................................................................... 21
Remote Monitoring & System Management ................................................................................................... 21
Alarm Log ........................................................................................................................................................... 22
Active Alarms ..................................................................................................................................................... 23
Clearing Alarms ................................................................................................................................................ 23
Alarm Troubleshooting ..................................................................................................................................... 24
Extension Panels – Connection & Considerations ......................................................................................... 25
Connecting the Extension panel to the Main Panel ......................................................................................... 25
Extension Panel Considerations ....................................................................................................................... 25
Wireless Temperature Sensing ......................................................................................................................... 26
Appendix A ......................................................................................................................................................... 37
Panel Specifications ......................................................................................................................................... 37
Default Settings ................................................................................................................................................ 38
Appendix B ......................................................................................................................................................... 44
ModBus Specification ...................................................................................................................................... 44
Service Contact Information .......................................................................................................................... 106
iii
Introduction
For nearly 100 years, customers have relied upon Chromalox for premiere quality and innovative solutions for industrial heating applications. Chromalox manufactures the world’s largest and broadest line of electric heat and control products.
The IntelliTrace® ITLS & ITAS Series Multiple Circuit Panels and Extender Panels are a complete temperature control and system management solution for electrical heat trace applications. They are designed for industrial applications in Hazardous (Class I, Division 2) or Non-Hazardous environments.
IntelliTrace® provides the user with an easy to navigate touch-screen interface, system parameter monitoring, off duty preventative maintenance, application flexibility and system customization.
The ITAS and ITASC1D2 provide Ambient Sensing control while the ITLS and ITLSC1D2 provide either Line Sens­ing control or a hybrid of both Line and Ambient Sensing control.
IntelliTrace® Features:
• 40 Amps/Circuit @ 100 – 600 VAC
• SSR Output Power Control
• 2 to 72 Circuit
• Large Touch Screen HMI
• Integral Control Panel and Circuit Breaker Distribution (non-hazardous areas)
• 1-pole or 2-pole Designs
• Soft Start, On/Off, PID and Manual (Hand) Control
• Modbus RTU/RS485 or TCP/Ethernet Communications
• Full Monitoring & Alarms (Lo/Hi Current & Temperature, Sensor, Transmitter Battery, Communications & GFEP)
• Hazardous (Class I, Division 2) and Non Hazardous Environments
• NEMA 4 Enclosure (Optional NEMA 4X 304 SS)
• UL, cUL Listing (CE available)
Touch Screen Computer:
• 10” on 6 – 72 Circuit Systems and 7” On 2 – 8 Circuit Systems
• 2 or 6 Circuit Circuit Detail Displayed at a Time
• Quick Launch to any 2 or 6 Circuit Group Display
• Remote Desktop Monitoring
• Extremely Intuitive Navigation, User Setting and Operation
• Fully Customizable Circuit Naming and Parameter Programming
Options:
• Powerful and Flexible Sensor Mapping (ITLS, ITLSC1D2 only)
• Enclosure Heater
• Fully Integrated Wireless Temperature Sensing
• IntelliTrace® Supervisory Control (ISC) for Central Command of Multiple Systems
1
Model Overview
The Chromalox line of IntelliTrace® Heat Trace Control Panels provides a significant amount of application and feature flexibility.
vide the flexibility for the owner to meet their process expansion needs. Simply connect the Extension Panel to its matching ITLS, ITLSC1D2 or ITAS, ITASC1D2 Base Panel and circuit capacity is seamlessly in-
The ITAS and ITASC1D2 are designed for Ambient Sensing applications while the ITLS and ITLSC1D2 are
creased. The Extension Panels do not have a HMI, but otherwise are identical.
designed for Line Sensing applications. Additionally, the ITLS and ITLSC1D2 have the capability to function as both a Line Sensing control panel and an Ambient Sensing control panel should the Customizable Sensor
These panels are UL and cUL Listed for Ordinary (Non Hazardous ITLS/ITAS) and Hazardous (Class I, Division 2 ITLS/ITAS C1D2) Environments. CE is available.
Mapping feature be selected.
Please see Table 1 below for applicable features and
The IntelliTrace® matching ITAS-EXT, ITASC1D2-EXT
capabilities by model type.
and ITLS-EXT, ITLSC1D2-EXT Extension Panels pro-
Table 1
ITLS
Standard Features/Capabilities
Ordinary, Non-Hazardous Area X n/a X n/a X n/a X n/a
Hazardous Area (Class I, Division 2) n/a X n/a X n/a X n/a X
7" Touch Screen HMI (2-4 Loop Versions) X X X X n/a n/a n/a n/a 10" Touch Screen HMI (6-48 Loop Versions) 40 Amps/Loop @ 100-600 VAC X X X X X X X X
Circuits 2, 4, 6, 8, 12, 18, 24, 30, 36, 42, 48 (Expandable to 72 with -EXT Panel)
SCR Control X X X X X X X X NEMA 4 Enclosure X X X X X X X X Integral Circuit Panel with Circuit Breakers X n/a X n/a X n/a X n/a Soft Start Feature X X X X 1 1 1 1 Full Communications X X X X 1 1 1 1 Full Alarm Capabilities X X X X 1 1 1 1 Complete GFEP Monitoring & Alarms X X X X 1 1 1 1 Load Monitoring & Alarms X X X X 1 1 1 1 Sensor Mapping X X X X 1 1 1 1 UL, cUL Listing X X X X X X X X
ITLS
C1D2 ITAS
X X X X n/a n/a n/a n/a
Options
Enclosure Heater X X X X X X X X Wireless Temperature Sensing X X X X 1 1 1 1 Main Breaker/Disconnect X n/a X n/a X n/a X n/a Nema 4X 304 SS Enclosure X X X X X X X X HMI Sunshield X X X X n/a n/a n/a n/a Panel Weathersheild X X X X X X X X Heater Power and RTD Terminal Blocks X X X X X X X X Z-purge system X n/a X n/a X n/a X n/a Panel Light (on separate breaker) X X X X X X X X Powered Receptacle (on separate breaker) X X X X X X X X Copper Ground Bar X X X X X X X X
CE available X X X X X X X X
X - Available as a standard or option for this model 1 - This feature is enabled when paired with matching base panel n/a - This feature is not available for this model
ITAS
C1D2 ITLS-EXT
ITLS
C1D2-EXT ITAS-EXT
ITAS
C1D2-EXT
2
Theory of Operation
The set-up of the individual and global circuit parameters is explained in the Temp/Load Set-up sections of this manual. This Theory of Operation overview is intended to give a quick summary of how it all works together.
• Each circuit of the system may be enabled (active) or disabled (inactive). A disabled loop will have no output and will not map into the common alarm. It will display “Circuit #” and “Disabled” text above the process temperature. Alarms for disabled circuit will not be monitored or displayed on the screen.
• Each circuit of the system may use unique individual control parameters or the control parameters may be alike. The Global Settings function facilitates this action.
The GFEP and Load current are automatically and continuously being calculated. The horizontal orange bar indicates the average output current for that circuit. The GFEP current value is not displayed on the screen but its value is compared to the GFEP setpoint. A GFEP alarm condition will occur when the GFEP current value exceeds the GFEP setpoint value.
If a ground fault that exceeds the GFEP setpoint value is detected during normal operation and “Trip” button on the Load Setpoints screen is checked, the output of the defective circuit is set to 0% and that circuit goes into an alarm condition. If “Trip” button is not selected, the operation of that circuit continues and that circuit goes into alarm condition. The GFEP alarm may be either Latching or Non­Latching.
• During extended periods of time where the output of all circuits are off, such as during warmer sea­sons, the Auto Cycle feature may be engaged. This feature initiates power to each circuit and checks for alarms. Each output is tested for one minute within the desired Auto Cycle Interval. The Auto Cycle feature may be disabled by setting the Auto Cycle Interval time to “0 Hours”.
• To limit inrush current on the overall system, a proprietary Soft Start algorithm is applied during sys­tem start-up. This will ONLY occur while the operation mode is set to AUTO. The Soft Start program will increment output % by 1% every 1 second until the desired temperature is reached or the output % achieves 100%. After the Soft Start program completes its cycle, the Control Mode of the system will either be PID or ON/OFF Control Mode, depending what was selected by the user. The Soft Start Program will not function if the control mode is set to Manual.
Centralized control of multiple ITAS or ITLS panels is accomplished via the ISC-IntelliTrace Supervisory Controller.
3
Types of Sensing Control
Ambient Sensing Control
Strict ambient-sensing control utilizes a thermostat or a simple electronic controller which senses the ambient tem­perature via an RTD, Thermocouple or Bulb & Capillary sensor. This is the simplest type of control as the heating circuit is energized only when the ambient temperature drops below the setpoint of the controlling device. This is also known as On/Off control. A relatively large temperature variation around the setpoint is anticipated. Mechani­cal thermostats are often employed due to their low cost and acceptable accuracy. Multiple heater circuits are controlled by a singular ambient sensed temperature. This is the least efficient type of control and it is typically limited to freeze-protection applications.
PASC - Proportional Ambient Sensing Control
Proportional ambient sensing control (PASC) utilizes an electronic controller which continuously compares ambient temperature and the rate of the change of the ambient temperature to the desired temperature setpoint and regulates the heater output power accordingly. The result is a smaller temperature variation around the desired setpoint and a much smoother response to changing weather conditions. Like ambient sensing control, multiple heater circuits are controlled by a singular ambient sensed temperature. PASC control is therefore significantly more energy ef­ficient than ambient sensing control. PASC control can be employed in a variety of heat trace temperature control applications but is typically used for freeze protection.
Line Sensing Control
Line sensing control is where each heated section of pipe (or heated surface area) is controlled independently of other sections of pipe and therefore must have its own controller. Multiple sections of pipe may also be independently controlled by an electronic multiple circuit control system. The control method may be either proportional or On/ Off control. Each section may have different setpoints and different allowances around the setpoint temperature. Line sensing control is typically found in process temperature maintenance applications. These applications are typically more critical and thus demand tighter temperature control. Electronic control is highly recommended over thermostat control. Like PASC, the pipe surface temperature and the rate at which it is changing is continuously compared to the setpoint temperature. The controller responds to these variations and regulates the heater output power accordingly. Mission critical applications should only be managed by controllers which monitor all parameters and present alarms both locally and remotely via communications or supervisory control means.
4
Pre-Service Storage
If this equipment cannot be placed into service upon receipt, prevent damage caused by impact, harsh environmental conditions, condensation or liquid ingress. Preferably store in a clean, dry, air conditioned, or ventilated building. During storage, assemblies should be placed on a firm, level surface to prevent distortion.
Outdoor storage of indoor equipment is not recommended. The covering provided during shipment of indoor as­semblies is NOT adequate for outdoor storage.
Cover the equipment to keep it free from dust, dirt, and corrosive elements. The covering must protect the assembly, but permit adequate ventilation. Blocking placed between the roof of the equipment and the cover will help keep covering material from restricting the air flow.
If the storage area is subject to humidity and significant temperature changes, energize the anti-condensation heat­ers provided in the equipment, or add heat from a separate source to prevent condensation inside the equipment. The internal temperature must be at least 5˚C (9˚F) above the ambient.
If storage temperatures fall below 0°C (32°F), energize the internal equipment heaters provided, or add sufficient heat from a separate source to keep the internal temperature of the panel to at least 0°C (32°F).
In areas with high humidity, inspect the equipment regularly, and add additional heat if necessary to keep the equipment dry.
Remove all loose packing, documents, and flammable materials before energizing heating elements.
Heat from a separate source must be removed before the equipment is put into service.
WARNING: Care must be taken that integral control power transformers are not accidentally back-fed from the heater circuits. Disconnect primary and secondary fuses.
Summer Standby Operation
If equipment is switched off during warm periods, and they are subject to humidity and significant temperature changes, energize the anti-condensation heaters provided in the equipment, or add heat from a separate source to
prevent condensation inside the equipment. The internal temperature must be at least 5˚C (9˚F) above the ambient.
Before Powering Up
Chromalox takes great pride in knowing that we have provided to you a product of premium quality and workman­ship. We have taken every precaution to ensure that your equipment arrives safe and secure.
However, vibration and temperature changes during shipping can cause some components to become loose. Additionally, throughout the life span of this product, other environmental and application conditions may have affected the mechanical and electrical continuity of several internal components. Therefore, for your safety and overall product performance, please take the time to familiarize yourself with the MAINTENANCE, OPERATION, AND INSTALLATION INSTRUCTIONS technical manual that was shipped with your panel.
Since it is not uncommon for electrical wiring and mechanical connections to become slightly loosened during shipment, we ask that you pay particular attention to section 4-5.3 Wiring and Connections:
4-5.3 WIRING AND CONNECTIONS. Check wiring and connections as follows:
a. Inspect wiring for wear, fraying, chipping, nicks, and evidence of over-
heating. Repair minor defects with a good grade of electrical tape, or replace if needed.
b. Inspect for loose electrical and mechanical connections. Tighten or
replace defective crimp-style lugs. Re-solder loose solder connections. Tighten or replace all loose or missing hardware.
5
General Panel Notes
1. This panel is designed to UL508A to facilitate NEC and CEC compliance, However it is the responsibility of installer(s) and end user(s) to make sure that the installation wiring and all equipment, including this panel, fulfill appropriate national and local electrical code requirements.
2. Incoming and outgoing branch circuit conductors may not be protected by fuses or breakers in this panel. Consult appropriate national and local electrical codes and device specifications for selective coordination.
3. Protection relays must be set on site according to the requirements of the site engineer’s protection study. Low-level ground fault protection, if required, should be provided.
4. Consult all applicable instruction manuals.
5. Customer interlocks are provided for use of external shutdown device(s). Interlocks require contacts that open to trip or shutdown.
6. Contacts are shown in the de-energized state. Controller contacts shown on electrical schematics are internal to the controller. Most of these contacts are programmable to suit the mode of operation. Consult the appro­priate user manual(s).
7. Dashed lines indicate user field wiring connections.
8. The panel installer must ground the panel according to appropriate national and local electrical code require­ments.
9. Conduit openings in enclosure are to be user installed, sized and located as required. Hubs or fittings must be of the same environmental rating as the enclosure to maintain integrity.
10. Unless fitted with an HMI sun sheild, do not place this equipment in direct sunlight.
11. Unless panel is properlly equipped with an enclosure heater for ambient temps below 0°C (32°F), the ambient temperature outside this panel must be between 0°C (32°F) and 40°C (104°F).
12. If the panel cannot be placed into service upon receipt, an anticondensation heater must be used to prevent condensation from forming inside the panel. This heater can be user supplied or factory supplied but must be used to prevent damage to the panel.
13. Dimensions are for reference only, and are nominal unless otherwise specified.
6
Installation
Heat Sink Considerations – Heat Dissipation
The Chromalox ITLS, ITLSC1D2, ITAS & ITASC1D2 Multiple Loop Heat Trace panels employ SSRs (Solid State Relays) as a means to switch the heating load power. Inherently, SSRs produce heat when operating. This heat is dissipated through the heat sinks which are typically mounted on the sides of the enclosures. These heat sinks must be mounted such that the fins are vertically orientation in order to allow the heat sink to properly dissipate the heat from the controller. The air flow around these heat sinks must in no way become restricted.
To maintain UL/cUL listing, the heat sinks must be inspected prior to and during every season, or no more than every 12 months, to confirm that no debris or objects are in contact with the heat sink. All debris must be removed from the heat sink fins. High pressure blasts of clean, dry air or other means which will not damage the fins are to be used to dislodge all debris from the fins.
Servicing Heat Sinks
Adjacent Panel
or Wall
In the rare occurrence that the Power Board assembly, which includes the Heat Sink, needs to be removed or inspected, a minimum of 7 inches (18 cm) of clearance is needed to externally withdraw the assembly from the enclosure.
7 Inches
(18 cm)
Outdoor Applications
Equipment protection from the environment must be carefully considered when installing these systems outdoors. Both Solar Loading and UV Rays from the sun can impact the performance of these systems.
Solar Loading The panel ratings, per UL/cUL, are based on operating the panel within the listed Ambient Environmental tempera­tures and under NO SOLAR LOAD (exposure to direct sunlight).
Therefore, it is highly recommended to install an adequately designed Solar Shield to provide shade across the entire top of the panel so no solar load is realized. This Shield will also provide some protection to the HMI Touchscreen.
See the appendix for Solar Shield design options offered by Chromalox.
UV Rays The IntelliTrace® Heat Trace Panels employ an HMI Touch Screen with LED backlit technology. UV Rays are known to be damaging to these types of HMI touch screens. Chromalox insists on installing HMI Sunscreens in all outdoor applications to protect the HMI Touch screen from these harmful rays. See the appendix for HMI Sunscreen design options offered by Chromalox.
Please note that warranties will only be honored if all of the following conditions are met:
1. Suggested options are adequately designed are properly employed
2. These designs must either meet or exceed the designs suggested by Chromalox
3. This Optional Equipment must be installed prior to initial equipment commissioning
7
Main Menu Screen
Circuit Number and Circuit Identification
(1-6, 7-12 for 5 Cir
Sensor Mapping Menu
Active Alarms Menu
Alarm Log Menu
The ITAS/ITLS Touch Screen Computer is extremely user friendly and quite intuitive. Navigation to any other screens or any 2 or 6 circuit grouping of circuts is accomplished by selecting the blue labeled buttons along the bottom of the screen or in the upper right or left hand corners.
The main menu screen displays alarm status, circuit number, circuit name, process and set point temperatures, current load demand, manual/auto control state and output percentage for 2-6 circuits at a time. See Figure 1.
Figure 1
Alarm Status & Type
2-6 Circuit
Navigation
Buttoon (x2)
Process
Temperature
Alarm Status by
2-6 Circuit Grouping
and up Systems
or 1-2, 3-4 for 2-4
Circuit Systems
up to 72 Circuits)
cuit
Temperature
Setpoint
Current Load
Control State
& Output %
Quick Launch to
Temperature Menu
Quick Launch to
Load Setup Menu
Quick Launch to
Tuning Menu
Quick Launch to
Quick Launch to
SystemMenu
Quick Launch to
Quick Launch to
8
Temp Setup Menu
The Temp Setup button at the bottom of the screen is a quick launch to the Temperature Property Sheet which is simply a series of tabaulated screens. See Figure 2.
Figure 2
Each block contains input cells for the panel operation. For example, temperature and overide controls are located within the Temp Setup Screen.
Navigation notes:
1. Each screen illustrates 2 or 6 circuits at a time. To make setting changes to circuits beyond the current screen
within the menus, one must select the Circuit Navigation buttons in the upper right or left of screen.
2. For most screens, to save your settings and exit back to the mail screen, select the “X” button in the lower right
corner of the screen.
9
Security Levels & Password Screen
After touching the Temp Setup button, but before the Temp Setup Menu is presented, a pop-up screen request­ing a password will appear. See Figure 3:
Figure 3
Initial factory set passwords for the below levels of Security are:
Level Title Code
4. Manager 999
3. Engineering 55
2. Supervisor 20
1. Operator 100
Enter the appropriate password and then hit ENT to continue to the setup screen.
Each of the above Security Levels has predefined accessibility and rights within the programming of the control panel. They include:
Level Title Accessibility/Rights
4. Manager All customer pages, all passwords and Setpoints editing
3. Engineering All customer pages, Engineering password and All Setpoints editing
2. Supervisor Setpoints, Tuning and Sensor Mapping Tabs & All Setpoints editing
1. Operator Setpoints Tab. Temperature Set Point editing
Changes to specific areas within the menus can only be made once the correct security level code has been selected.
10
Temp Setup Menu
The Temp Setup Menu tab (See Figure 4) contains input cells for the following settings for each circuit:
• Customized Naming of each Circuit
• Process Temperature Set Point
• High & Low Temperature Alarm Limits
• Maximum allowable GFEP (Ground Fault Equipment Protection) Alarm Limit
• Output behavior, whether Automatically or Manually
• Manual Output Load Percentage (if enabled)
• Circuit Output Override (Enable or Disable Each Circuit)
Additionally, there exists a “Global Setting” within the Circuit# 1 Grid
• Apply Globally Setting
Figure 4
11
Temp Setup Menu Navigation notes:
Apply T
1. Each screen illustrates 2 or 6 circuits at a time. To make setting changes to circuits beyond the current screen
within the Temp Setup Menu, one must select the Circuit Navigation buttons in the upper right or left of screen.
Figure 5 illustrates the input cell identification and location for a single circuit within the Temp Setup Menu:
Figure 5
Circuit Name
Temperature Setpoint
High Temperature Alarm Limit
Low Temperature Alarm Limit
emperature
Settings to all
Circuits
Manual Output Load Percentage
Soft Start Enable/Disable
Auto/Manual Output Operation
Enable/Disable
Circuit
12
Definitions for each of the Temp Setup Input Cells:
Name: Customize the Name of this individual circuit or loop
Temp STPT: Process Temperature Set Point (degrees F or C)
HI STPT: High Temperature Alarm Limit (degrees F or C)
LO STPT: Low Temperature Alarm Limit (degrees F or C)
Auto/Manual: Select Auto if you wish the Output behavior to be a function of a PID Algorithm or ON/OFF
Control (See Tuning Tab for selection)
Select Manual if you wish the Output to be driven by a pre-determined Output Percentage.
Enter the desired % output.
Disable Output: Select this check box if you wish to turn off or disable this circuit.
Apply Globally: This allows the user to copy all of the settings or Circuit Parameters from Circuit #1 to all other
available circuits.
Apply Settings Globally
The ITLS/ITAS has a feature which allows the user to apply settings from a single circuit to all of the remaining circuit within the system. Within Circuit #1 on the Load Setup Menu (See Figure 6), complete the input of the pa­rameters and select the “Apply Glob” button to mirror these settings across all circuits.
Soft Start Feature
These control panels are ideal for controlling heat trace cable. Certain heating cables exhibit inherent current inrush in colder temperatures. This inrush can cause nuisance breaker tripping. To limit inrush current on the overall system, a proprietary soft start algorithm is applied during system start-up. This will ONLY occur while the operation mode is set to AUTO.
The soft start program will increment output % by 1% every 1 second until the desired temperature is reached or the output % achieves 100%. After the soft start program completes its cycle, the control mode of the system will either be PID or ON/OFF Control Mode, depending what was selected by the user.
The soft start program will not function if the control mode is set to Manual.
The default setting of the proprietary soft start feature for each circuit is “enabled”. However, the soft start feature may be disabled if so desired by the owner. The owner has the option to manage the soft start feature on each circuit individually.
See Figure 5.
13
Load Setup Menu
The Load Setup Menu (See Figure 6) contains input cells for the following settings for each circuit:
• High & Low Load Alarm Limits
• Trip and/or Latch Enabled/Disabled (Output Permis-
sion) upon GFEP Violation
• Maximum allowable GFEP (Ground Fault Equipment
Protection) Alarm Limit
Figure 6
Additionally, there exists a “Global Setting” within the circuit# 1 Grid
• Apply Glob. Setting
14
Definitions for each of the Load Setup Menu Input Cells
Load HI Stpt ................. High Current Alarm Limit (Amps)
LoadLO Stpt ................. Low Current Alarm Limit (Amps)
GFEP: ........................... Maximum Allowable Leakage Current setpoint (milliamps)
Trip (GFEP): .................. Enabled: If the GFEP limit is met, the output will be 0%.
Disabled: If the GFEP limit is met, the output is unaffected.
Latch (GFEP): ............... Enabled: If the GFEP limit is met, the alarm condition will remain until it is manually cleared.
Disabled: If the GFEP limit is met, the alarm condition will be cleared once the GFEP vari-
able is less than the GFEP setpoint
Apply Globally: ............. This allows the user to copy all of the settings or Circuit Parameters from Circuit #1 to all
other available Circuits.
Apply Settings Globally
The ITLS/ITAS has a feature which allows the user to apply settings from a single loop to all of the remaining loops within the system. Within Loop #1 on the Setpoints Tab (See Figure 4), complete the input of the parameters and select the “Apply Globally” button to mirror these settings across all loops.
15
Tuning Menu
The owner has a choice of how the output is to be operated: Auto, Manual or Off. These selections are made within the Temp Setup Menu. If “Auto”, or Automatic Control Operation is desired, then the tuning of the automatic con­trol is accomplished via the Tuning Menu.
Figure 7
16
Control Modes: ON/OFF, PID & Autotune
ON/OFF
• Select ON/OFF if you wish the operation of the heat-
ers to be 100% ON when a demand for heat exists and 0% once the Set Point Temperature of the Pro­cess is achieved.
• The Deadband is enabled while in ON/OFF control
mode.
• The Deadband is the temperature range equally
divided above & below the temperature set point, where the controller will not take corrective action.
o Example: A setting of “10” for the deadband will
result in a deadband that is 5 degrees above and below the temperature setpoint.
• The deadband is adjustable in 2 degree increments.
It’s default is 10.
PID
• Select PID if you desire PID Control of the load.
• The Proportional Band (P), the Integral (I) & Deriva-
tive (D) are modes of control that work in union to bring the process variable to setpoint as smoothly and quickly as possible. They are enabled while in PID Control mode.
• The P, I & D will be automatically established during
the Autotune procedure (see above).
• Additionally, the P, I & D may all be manually estab-
lished by the user. Great care should be taken when manually establishing the P, I & D.
• Proportional Band: The temperature band expressed
in degrees within which the controller‘s proportion­ing action takes place. (Note: The wider the propor­tional band, the greater the area around the setpoint in which the proportional action takes place.) This is sometimes referred to as gain, which is the recipro­cal of proportional band.
Autotune
• If the Autotune Feature is selected, then the PID pa­rameters will be calculated and entered by the sys­tem once the Autotune function has completed its demand profile function.
• The Autotune function establishes the individual P, I & D (Proportional Band, Integral & Derivative) control modes. These modes help to bring the process vari­able to the setpoint temperature as quickly as pos­sible.
• In order to properly calculate the P, I & D modes, the Autotune program requires a 25 degree rise in sensed temperature after initiating the program. If within 30 minutes the temperature will not reach its setpoint, the Autotune algorithm will be canceled and old PID values will be used.
• Once the Autotune feature is activated, you must not change the menu page until the Autotune algorithm is completed. Changing the page will cause the Au­totune algorithm to shut down.
• The Autotune function is a one-time algorithm set up of the P, I & D control modes. Should your process variables change significantly, it is suggested to that the Autotune feature be turned off and then reiniti­ated.
Tuning Tab Navigation Notes:
1. Each screen illustrates 6 loops at a time. To make
setting changes to loops beyond the current screen within the Tuning tab, one must select the Loop Nav­igation buttons in the upper right or left of screen.
17
Sensor Mapping
The ITLS and ITLSC1D2 models provide the owner with customizable sensor mapping. This becomes a very powerful and desirable feature when the owner needs added flexibility in controlling the circuit outputs beyond the standard single sensor input.
1. Sensor Mapping is the assignment of one or more Sensor Inputs to one or more output circuits.
Sensor (Input) Mapping is accessed via the Sensor
Mapping Menu.
Sensor Mapping
Ambient or Line Sensing, Single Sensor A single sensor (RTD) may be mapped (or linked) to multiple output circuits. This allows several circuits to be controlled by a single sensor.
Minimum, Maximum, Averaging Several sensors may be mapped to a single output cir­cuit. This allows a single circuit to be controlled by the minimum, or the maximum or the average temperature of all of the sensors mapped to that output circuit. This may be desirable on long runs or zones which realize varying temperatures or weather conditions at different times of the day.
Multiple Sensor Mapping A single sensor may be used independently or com­bined with other sensors to control more than one cir­cuit.
For Example: The average temperature of Sensors 1, 3 and 5 is used to control Circuit 1 while simultaneously the maximum Temperature of Sensor 3, 4 and 5 is used to control Circuit 2.
Combining Sensing Types The owner may need to have multiple line and/or am­bient sensing control scenarios occurring simultane­ously.
For example, these may be occurring simultaneously:
1. Circuits 1, 2, 3, 4, and 5 are all controlled by a single RTD (Sensor 1) that is sensing the ambient temper­ature (Ambient Sensing)
2. Circuit 6 is controlled by Sensor Input 2 which is strapped to a process pipe. (Line Sensing)
Sensor mapping is accomplished within the Sensor Mapping Menu. See Figure 8.
This does not apply when only 1 Input/Circuit selection is made from the Order Table.
Figure 8
18
System Properties
Several informative items and general settings are available within the System Menu.
The System tab is only available to the two highest owner security levels: Manager and Engineer.
The Autocycle function is reviewed in the Autocycle Feature section.
Figure 9
Here, one can enter/revise the Facility Name, Date, Time, Temperature Units, Auto Cycle Interval and Se­curity Codes. The Manager has access to all security codes while the Engineer has access to only the Engi­neering Security Code. See Figure 9.
The Security Passwords and the respective rights for each security level are reviewed in the Security Level
and Password Screen Section.
System Page Definitions
Facility – name of the facility
Units – degree Celsius or Fahrenheit
Autocycle – Autocycle feature. Value of 0 disables it
Number of circuits – number of SSR circuits (not boards) installed in the panel
Number of RTD boards – Number of RTD boards in­stalled in the panel
Modbus – Modbus feature can be disabled or enabled to speed up processing and screen update current se­curity level password
Comm Settings – used to select correct Modbus com­munication parameters (baud rate, parity, stop bits, etc)
IP Address – present IP address of the HMI screen. IP address can be changed by pushing Comm Settings button.
Log In – used to change current security level
Log Off – used to log off from the system
Change Password – used to change current security level password
19
Auto Cycle Feature
During prolonged down time periods, typically during the summer months, it advisable to intermittently exer­cise the loops. This exercising of the loops is accom­plished via the Autocycle feature.
To enable the Auto Cycle feature, select an Auto Cycle Interval greater than 0 hours within the System tab. See Figure 9. The Auto Cycle feature is disabled when the Auto Cycle Interval equals 0 hours.
Figure 10
On a sequential circuit basis, the Autocycle feature pe­riodically monitors system performance between 1-999 hours. The minimum and maximum values for Current Load, GFEP and Temperatures are stored. Once the new high or low value is attained the old value is over­written and displayed in the Autocycle tab text boxes. See Figure 10.
This provides a certain level of preventative mainte­nance of the system as Faults (Alarms) will present themselves accordingly. Problem areas can be ad­dressed during non-essential operating periods.
It is NOT advisable to engage the Auto Cycle feature during normal operating periods. The heating cables will become fully energized for approximately 2 minutes throughout the Auto Cycle Interval which could cause undesirable temperature overshoot.
WARNING:
20
Communications
All changes to the MODBUS settings are achieved via the COMMS screen. See Figure 11.
The Comms (Communications) screen may be ac­cessed by selecting the COMMS button located at the bottom of the System screen. The MODBUS Address, Communication Speed, Parity and Stop parameters are set within the Communications screen.
For complete communications specification details on ModBus messaging, Registers and Sensor Mapping, please reference our “ModBus Wiring and Registry Map Instructions Document A-60682-04. This is an ad­dendum to the PK497 manual. Go to the ITLS or ITAS product pages and search in the Technical Resources Tab at: www.chromalox.com.
Figure 11
Remote Monitoring & System Management
Users may monitor as well as adjust the System Pa­rameters settings of the panel remotely. The files re­quired for this feature are available to the owner. Due to the frequent program updates, we ask that you contact the factory for the most recent release version.
Communication Settings
To display the setting screen, touch (Device/ PLC Settings) from (Peripheral Equipment Set­tings) in offline mode.
Touch the External Device you want to set from the displayed list.
Setup Items Setup Description
SIO Type Select the SIO type for communicating with the External Device.
IMPORTANT
In the communications settings, set (SIO Type) correctly according to interface speci­fications of the Display.
If you select an SIO type that the serial interface does not support, proper operation cannot be guaranteed.
Refer to your Display Manual for details on the serial interface specifications.
Speed Select the communications speed between the External Drive and the Display
Data Length Select a data length
Parity Select how to check parity.
Stop Bit Select a stop bit length.
Flow Control Select the communications control methond to prevent overflow of transmission and
reception data
21
Alarm Log
The purpose of Alarm Log is to record every alarm condition with a date and time stamp. This log may be viewed via the ALARM LOG button at the bottom of the main screen. See Figure 12.
Alarm condition example: Sensor Error alarm on circuit 18 will be recorded as “11/08/12 – 13:38:48 SENSOR ALRAM CKT 18”. Every alarm event is saved into a text file (\Storage Card\log5.txt). Each event is appended to the file string on a new line.
This table holds up to 750 events (alarms). If the num­ber of entries exceeds 750 then the event that is last
Figure 12
on the list (by date) will be removed from the table. This process repeats indefinitely. Once an alarm has been recovered, it can be removed from the list by pushing the clear recovered alarm button.
To extract these files, one must:
1. Plug a USB flash drive into the USB port located on the back of the ITLS/ITAS computer. Go to Alarm Log Screen and push green button on the right of the screen labeled “Write Alarms to USB.”
Move Upward – moves cursor one position up
Move Downward – moves cursor one position down
Clear All Recovered Alarms – clears all recovered alarms from the alarm log
Clear Recovered Alarm – clears selected recovered alarm from the log
Acknowledge All – acknowledge all present alarms
Acknowledged – acknowledge selected alarm
Roll Up – move cursor one position up
Roll Down – move cursor one position down
Write Alarms to USB – saves alarm log into USB thumb drive
View USB – reads previously recorded alarm log from the USB thumb drive
22
Active Alarms
Alarms within any 6-circuit or 2-circuit grouping are in­dicted by RED squares in the left and right panels on any screen. If the square is GREEN, then no faults exist within that 6-circuit grouping. Once a fault is realized within any 6-circuit grouping, one may view the indi­vidual alarm circuit or circuits in two different ways:
1. When in the Main Display screen, one may navigate to the desired 6-circuit grouping via the Navigation buttons found in the upper right hand or upper left hand corner. Alarm conditions are illustrated within each circuit window. Up to three alarm conditions can be illustrated for any single circuit on the Main Menu screen.
2.
One may view the status of all fault conditions by se­lecting the ACTIVE ALARMS MENU button located at the bottom of the main display screen. To navigate to the desired 6-circuit grouping, one must press the Circuit Navigation but-tons found in the upper right or left corner of any screen. See Figure 13.
Figure 13
Clearing Alarms
Except for a Communications Alarm and a Latched GFEP Alarm, all other alarms are cleared once the ac­ceptable parameters are achieved.
23
Alarm Troubleshooting
The Alarm Condition, the resultant Output and the Design Behavior for each Alarm type can be found in Table 2 below.
Table 2
Alarm Type Condition Output Design Behavior
HIGH TEMP
LOWTEMP
GFEP
HI CURRENT
(LOAD on Faults Screen)
LO CURRENT (LOAD on Faults Screen)
SENSOR
COMM
Sensed Temp => Hi Temp Setpoint
Sensed Temp <= Lo Temp Setpoint
Sensed GFEP Current => GFEP Setpoint
Sensed Load Current => Hi Current Setpoint
Sensed Load Current <= Lo Current Setpoint
Sensor Open, Sensor Shorted, Sensor Fault
Communication Error
No change Alarm will be cleared automatically when
Sensed Temp < Hi Temp Setpoint
No change Alarm will be cleared automatically when
Sensed Temp > Lo Temp Setpoint
Trip Latch
No No
Yes No
No Ye s
Yes Ye s
Output will switch to Manual Mode
No change Alarm will clear automatically when
Output will switch to Manual Mode
Output will switch to Manual Mode
Output will re­main at selected output %.
Output will go to 0% (OFF) while in alarm state
Output will re­main at selected output %.
Output will go to 0% (OFF) until alarm is reset
Alarm will be cleared automatically when sensed GFEP Current < GFEP Setpoint
The Alarm condition may only be cleared with a manual RESET of the GFEP Alarm.
Alarm will be cleared automatically when sensed Load Current < Hi Current Setpoint
Sensed Load Current > Lo Current Set­point. If your output is turned OFF, GFEP and Load values will not be updated.
Alarm will clear automatically when the RTD resistance is between 75.44W -
311.56W. Check if your sensor wire is not damaged and that it is properly connected to the Sensor board.
Make sure that the communication cable that connects the Touchscreen computer with boards inside enclosure is properly connected and/or not broken.
Press “RESET ALM” to reset this alarm.
24
Extension Panels
D
Connecting an Extension panel or a Remote Sensor Panel to the Main Panel
Below is the procedure to connect an Extension or a Remote Sensor Panel to the Main Panel. The Main Panel will manage the circuits in the Extension Panel and the inputs of the Remote Sensor Panel.
Procedure:
1. Turn off the power to the system.
2. In the main panel (the one with a touch screen com­puter) locate the distribution board (0113-10246) and verify that jumpers J.16 and J.17 are set in po­sitions 1 & 2.
3. Connect one end of the twisted pair cable into con­nectors J15.1 (RX+) and J15.2 (RX-) on the distribu­tion board of the Main Panel. Connect the other end of the twisted pair cable into connector J15.1 RX+ and J15.2 (RX-) on the distribution board of the Ex­tension panel.
Figure 14
Make sure that RX+ is connected to RX+ and RX- to RX-. (See Diagram Below)
4. Connect the metallic shielding material (see wire specification below) to the ground of the base panel Distribution Module. However, DO NOT connect the metallic shielding to the Extension Panel Distri­bution Module. (See Diagram Below)
5. If the number of loops needs to be changed, power up the system and login into the setup menu using 5731 as the password. Go to the “System” tab and select the desired number of loops and press “OK”.
6. Cycle power to the system.
**Note - a 2 or 4 Circuit Extension Panel may be added to a 6-48 Circuit system but not vice versa.
Remote Sensor Panel
Main Panel
2,500 FT
(775 M) Max
RX+
Main Panel Distribution
Module
RX-
GN
Extension Panel or Remote Sensor Panel Considerations
Environmental influences such as EMI/RFI can compro­mise the communication signal between the Extension or Remote Sensor Panel and the Main Pane. The use of properly designed cable will protect against and minimize these influences.
Here is a design guide for extension panel wiring:
RS-485 Max. total cable length ........... 2,500 ft (800 M)
RS-485 Wire specification .........T1/E1/DSL compatible
24-AWG shielded cable
Extension Panel
RX+
-
RX
GND
Chromalox uses the following vendor and cable item as a viable reference:
Example Vendor: ................................................L-com
Typical Specification: ...2 - 120 Ohm (E1) Shielded Pair
Vendor Item Number: .................................... TSC9928
Available at: .............................. http://www.l-com.com
Extension or Remote
Sensor Panel
Distribution Module
25
Wireless Temperature Sensing
No Maintenance Needed.
Overview
Chromalox now provides fully integrated Wireless Tem­perature Sensing Solutions for Heat Trace applications in ordinary and hazardous locations.
The components of the Chromalox Heat Trace Wireless Temperature Sensing system include the IntelliTrace ITLS or ITAS Series Heat Trace Control Panel and spe­cific industrial wireless transmitters which are paired with appropriate temperature sensors.
Control Panel
When the wireless temperature sensing feature is se­lected, the IntelliTrace Control Panel is properly con­figured at the factory and internally equipped with an industrial-duty WirelessHART® certified wireless gateway, antenna and the necessary communication accessories.
The panel facilitates both wired and wireless tempera­ture sensor inputs and the touchscreen computer HMI distinguishes wireless circuits from wired ones. Sev­eral of the IntelliTrace HMI screens are impacted when Wireless Temperature Sensing is ordered and enabled at the factory: The Main Screen and Sensor Mapping Menu.
Main Menu
On the main menu screen, the alarm status will appear as BATTERY when the transmitter battery of a wire­less circuit is due to be changed. Each wireless circuit has its own transmitter battery life meter. This provides three levels of remaining battery life so that you may properly plan service before it is needed.
Wirless Transmitter Battery Meter
BATTERY
Battery Life Good.
BATTERY
Battery Life Low. Plan for Maintenance.
BATTERY
Battery Life Very Low. Perform Maintenance Immediately.
26
Loading...
+ 80 hidden pages