Chromalox HVH-TK6, HVH-TK5 User Manual

The following procedure contains instructions for installing ther­mostat kits HVH-TK5 and HVH-TK6 in HVH-02 through HVH­15 Heaters.
ELECTRIC SHOCK HAZARD. Disconnect all power before installing thermostat kit. Failure to do so could result in personal injury or property damage. Thermostat kit must be installed by a qualified per­son in accordance with the National Electrical Code, NFPA 70.
© 2010 Chromalox, Inc.
Thermostat Kits
Model Number HVH-TK5 Model Number HVH-TK6
For field installation only in HVH-02 through HVH-15 heaters
SPECIFICATIONS
1. Temperature Range: 40˚F to 90˚F.
2. Differential: 5˚F.
3. Non-inductive Rating: 120V @ 25 Amperes 240V @ 25 Amperes 277V @ 22 Amperes
(Supersedes PF448-6)
PF204-1
LUH
161-305676-001
JANUARY, 2007
4
RENEWAL PARTS IDENTIFICATION
Installation, Operation
and
DATE
SALES
REFERENCE
DIVISION SECTION
Chromalox
®
LO HI
OFF
Ch romalo x
R
GENERAL
INSTALLATION
Step 1
1. Verify that the thermostat kit is compatible with your heater.
HVH-TK-6 is a DPST line voltage thermostat, it can be used on 1Ø, 240V max. up to 25A and 1Ø, 277V up to 22A heaters. HVH-TK-5 is a SPST is a thermostat used in conjunction with a contactor.
2. Peel off “Chromalox” label located on the bottom front corner of the heater. Removal of the label will reveal the holes for mounting the thermostat (See Figure 1).
3. Carefully remove the KO on the bottom side of heater.
KO
Nameplate
Figure 1
INSTALLATION (cont’d.)
Step 2 (Figure 2)
1. Remove (2) screws on cover and open cover.
2. Feed thermostat capillary (be careful not to kink or make any
sharp bends) out through the hole made in step 1.
3. Mount body of thermostat to front of heater case using the (2) 6-32 flat head screws (not location of leadwires shown in illus­tration). Attach new label and knob provided with TK kit.
Step 3 (Figure 3)
1. Attach thermostat bulb to case using the (2) clamps and
screws.
2. Make a slit in the rubber grommet and insert the grommet over the capillary.
3. Install the grommet into the hole in the case.
Step 4
1. For TK-6 Thermostat kits, wire one blue lead of thermostat to
terminal block pole “L1” and the other blue lead to terminal block pole “L2”. Connect incoming power wiring to the black leads with wire nuts provided by others. See figure 4 for line voltage thermostat. See figure 8 for control voltage thermostat.
For TK-5 thermostat kits with an internally provided control circuit, remove white jumper wire on terminal block between poles “C1” and “C2”. Connect blue wire of thermostat to pole “C1” and black wire to “C2”. See figures 5, 6 or 7.
For TK-5 thermostat kits with an externally provided control circuit, remove white jumper wire on terminal block between poles “C2” and “C3”. Connect blue wire of thermostat to pole “C2” and black wire to “C3”. See figure 7.
2. Inspect wiring to make sure it matches the appropriate wiring diagram.
3. Close heater cover and reattach screws.
SHEET METAL
SCREW
CLAMP
THERMOSTAT BULB
KNOB
LABEL FOR THERMOSTAT
6-32 FLAT HEAD SCREW
THERMOSTAT BODY
RUBBER GROMMET
LEADWIRES
Figure 2
Figure 3
}
Motor
Blue
Blue
Optional Thermostat Built in or field installed
Optional Disconnect Switch Built in or field installed
Power 60 Hz
Elements
1Ø Element Wiring (Omit for 2 Element Heaters)
Cutout
Terminal Block
T1
T3
T2
L1
L3
L2
Black
Black
Figure 4
208-277V 1Ø — 2.6 & 5 kW
WIRING DIAGRAMS