Chromalox HVH-04-83, HVH-02-21, HVH-04-21, HVH-04-23, HVH-04-71 Installation, Operation And Maintenance Manual

...
Page 1
Chromalox
®
SERVICE REFERENCE
Installation, Operation
and
MAINTENANCE
DIVISION 4 SECTION HVH
SALES
REFERENCE
(Supersedes PF203-5)
161-305679-001
JANUARY, 2012
DATE
Type HVH Horizontal/Vertical Unit Heater
GENERAL
Heater Location Instructions: Arrange units so their discharge air streams: A. Are subjected to a minimum of interference from columns,
machinery and partitions. B. Wipe exposed walls without blowing directly at them. C. Are directed away from room occupants in comfort heating. D. Are directed along the windward side when installed in a build-
ing exposed to a prevailing wind. E. See additional mounting limitations in Table D.
Locate thermostat on interior partition walls or posts away from cold drafts, internal heat sources and away from heater discharge air streams.
Small rooms can be heated by one unit heater. Where two walls are exposed, the heater should be mounted as shown in Figure 1.
WARNING
Failure to understand and follow these installation instructions and the “WARNING” notes therein may result in serious personal injury from electrical shock, or from the heater falling due to faulty installation.
This heater is not intended for use in hazardous atmo­spheres where flammable vapors, gases, liquids or other combustible atmospheres are present as defined in the National Electric Code. Failure to comply can result in explosion or fire. For these applications see PDS CXH-A­EP (PF490).
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could re­sult in personal injury or property damage. Heater must be installed or serviced by a qualified person in accor­dance with the National Electrical Code, NFPA 70.
Large rooms require multi-unit installation. Number and capacity of units will be determined by volume of building and square feet of floor area to be heated. Arrange units to provide perimeter air circula­tion where each unit supports the air stream from another.
Exposed
Exposed
Exposed
Figure 1 - Single and Multi Unit Mounting
This heater is not intended for use in exposed outdoor, marine, or wash-down environments or in areas where corrosive liquids or fumes exist under normal conditions.
ELECTRIC SHOCK HAZARD. Any installation involving electric heaters must be performed by a qualified person and must be effectivley grounded in accordance with the National Electrical Code to eliminate shock hazard.
Do not mount mercury type thermostat directly on unit. Vibration could cause heater to malfunction.
The heater must be mounted at least 7’ above the floor to prevent accidental contact with the heating elements or fan blade which could cause injury.
Keep at least 5’ clearance in front of the heater. Refer to Table D for side, top and back clearance requirements.
Exposed
Exposed
Exposed
© 2012 Chromalox®, Inc.
Page 2
WARNING (cont’d.)
The ceiling mounting structure and the anchoring provisions must be of sufficient strength to support the combined weight of the heater and mounting bracket. (Refer to Table B for weights of heater and bracket.)
The wall or mounting surface, and the anchoring provisions must be capable of supporting the combined weight of the heater and mounting brackets cantilevered from the mounting surface. (Refer to Table B for weights of heater and brackets and for cantilevered force expressed in foot-pounds.)
Fan blade rotation must be checked. If airflow is not moving out through the louvers, interchange any two of the three customer power leads on three-phase units only.
Specifications – Table A
Model Volts Watts Phase Amps BTU
HVH-02-81 208 2,667 1 12.8 8,850 16-1/8 13 10 —— 10 HVH-02-21 208/240 2000/2,667 1 11.1* 8,850 16-1/8 13 10 —— 10 HVH-02-71 277 2,667 1 9.6 8,850 16-1/8 13 10 —— 10 HVH-04-81† 208 4,000 1 19.2 13,661 16-1/8 13 10 —— 10 HVH-04-83† 208 4,000 3 11.2 13,661 16-1/8 13 10 30A (1) 12 HVH-04-21† 208/240 3,000/4,000 1 16.7* 13,661 16-1/8 13 10 —— 10 HVH-04-23† 208/240 3,000/4,000 3 9.6* 13,661 16-1/8 13 10 30A (1) 12 HVH-04-71 277 4,000 1 14.5 13,661 16-1/8 13 10 —— 10 HVH-04-43 480 4,000 3 4.8 13,661 16-1/8 13 10 30A (1) 11 HVH-05-81† 208 5,000 1 24.0 17,076 16-1/8 13 10 —— 10 HVH-05-83† 208 5,000 3 13.8 17,076 16-1/8 13 10 30A (1) 12 HVH-05-21† 208/240 3,750/5,000 1 20.8* 17,076 16-1/8 13 10 —— 10 HVH-05-23† 208/240 3,750/5,000 3 12.1* 17,076 16-1/8 13 10 30A (1) 12 HVH-05-71 277 5,000 1 18.2 17,076 16-1/8 13 10 —— 10 HVH-05-43 480 5,000 3 6.0 17,076 16-1/8 13 10 30A (1) 13 HVH-07-81† 208 7,500 1 36.1 25,598 20-5/8 17-1/8 12-3/4 50A (1) 12 HVH-07-83 208 7,500 3 20.9 25,598 20-5/8 17-1/8 12-3/4 30A (1) 12 HVH-07-21† 208/240 5,625/7,500 1 31.1* 25,598 20-5/8 17-1/8 12-3/4 30A (1) 12 HVH-07-23 208/240 5,625/7,500 3 18.1* 25,598 20-5/8 17-1/8 12-3/4 30A (1) 12 HVH-07-71 277 7,500 1 27.2 25,598 20-5/8 17-1/8 12-3/4 30A (1) 12 HVH-07-43 480 7,500 3 9.0 25,598 20-5/8 17-1/8 12-3/4 30A (1) 13 HVH-10-81† 208 10,000 1 48.0 34,130 20-5/8 17-1/8 12-3/4 50A (1) 12 HVH-10-83 208 10,000 3 27.8 34,130 20-5/8 17-1/8 12-3/4 30A (1) 12 HVH-10-21† 208/240 7,500/10,000 1 41.7* 34,130 20-5/8 17-1/8 12-3/4 30A (1) 12 HVH-10-23 208/240 7,500/10,000 3 24.0* 34,130 20-5/8 17-1/8 12-3/4 30A (1) 12 HVH-10-43 480 10,000 3 12.0 34,130 20-5/8 17-1/8 12-3/4 30A (1) 13 HVH-12-83 208 12,500 3 34.8 42,663 20-5/8 17-1/8 12-3/4 50A (1) 12 HVH-12-23 208/240 9,375/12,500 3 30.1* 42,663 20-5/8 17-1/8 12-3/4 50A (1) 12 HVH-12-43 480 12,500 3 15.1 42,663 20-5/8 17-1/8 12-3/4 30A (1) 13 HVH-15-83 208 15,000 3 41.8 51,195 20-5/8 17-1/8 12-3/4 50A (1) 12 HVH-15-23 208/240 11,250/13,000 3 36.2* 51,195 20-5/8 17-1/8 12-3/4 50A (1) 12 HVH-15-43 480 15,000 3 18.1 51,195 20-5/8 17-1/8 12-3/4 30A (1) 13 HVH-20-23 208/240 14,758/19,500 3 47.0 66,534 20-5/8 17-1/8 14-1/16 50A (2) 15 HVH-20-43 480 19,500 3 23.5 66,534 20-5/8 17-1/8 14-1/16 50A (1) 14 HVH-20-63 600 19,500 3 18.8 66,534 20-5/8 17-1/8 14-1/16 HVH-25-23 208/240 18,720/24,900 3 60.0 84,959 29-3/16 26-1/16 14-5/8 50A (2) 15 HVH-25-43 480 25,000 3 30.2 85,300 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-25-63 600 25,000 3 24.1 85,300 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-30-23 208/240 22,400/29,900 3 72.1 102,019 29-3/16 26-1/16 14-5/8 50A (2) 15 HVH-30-43 480 30,000 3 36.2 102,360 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-30-63 600 30,000 3 29 102,360 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-35-23 208/240 25,600/34,000 3 81.9 116,008 29-3/16 26-1/16 14-5/8 50A (3) 15 HVH-35-43 480 34,000 3 41 116,008 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-35-63 600 34,200 3 33 116,690 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-40-23 208/240 28,000/37,400 3 90.1 127,609 29-3/16 26-1/16 14-5/8 50A (3) 16 HVH-40-43 480 37,400 3 45.1 127,609 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-40-63 600 37,500 3 36.2 127,950 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-45-23 208/240 33,700/44,800 3 107.9 152,858 29-3/16 26-1/16 14-5/8 50A (3) 16 HVH-45-43 480 44,800 3 54 152,858 29-3/16 26-1/16 14-5/8 50A (2) 15 HVH-45-63 600 45,200 3 43.6 154,222 29-3/16 26-1/16 14-5/8 50A (1) 14 HVH-50-23 208/240 38,400/50,000 3 123.1 174,353 29-3/16 26-1/16 14-5/8 50A (3) 16 HVH-50-43 480 50,000 3 61.6 174,353 29-3/16 26-1/16 14-5/8 50A (2) 15 HVH-50-63 600 50,000 3 49.5 175,036 29-3/16 26-1/16 14-5/8 50A (2) 15
* Note: 208V amperage is 86% of 240V value. † These models can be field changed from single phase to three phase or three phase to single phase.
Table B – Weights of Heater & Bracket
WEIGHT (Lbs.) Heater and Brackets
Ceiling
Model
Weight
Weight Ft.-Lbs.
HVH-02 to HVH-05 27 25-1/2 48
HVH-15 to HVH-20 55 67-1/4 112
HVH-25, 30, 35 108 105 126.3
HVH-40, 45, 50 118 115 138.4
A
Height
2
B
Width
C
Depth
Std. Contactor
Rating (Qty.)
50A (1) 14
Wall
Wiring
Dia. Figure
Page 3
INSTALLATION
NOTICE – These heaters are designed for wall and ceiling mount. Other modes of mounting void factory warranty.
Vertical Air Flow
1. Height above floor
A. It is recommended that the heater only be used with ceiling
heights of 12 feet or greater. Minimum spacing to ceiling is 6 inches, use 3/8-18” thread stock (supplied by others) as shown in Figure 3.
B. Mimimum mounting height is 10 feet from floor to bottom of
heater.
2. Spacing to walls. A. Side of case to wall 6”. Top or bottom of case to back wall is
10-1/4” (HVH-02 to HVH-05), 13” (HVH-15 to HVH-20) and 15-1/2” (HVH-25 to HVH-50).
CEILING (Vertical Airflow):
A. The heater can be rod mounted to the ceiling by installing four
(4) threaded mounting rods in the threaded holes located on the top of the heater as shown in Figure 3. (Refer to Table C for mounting rod thread size.)
B. Securely attach the four (4) mounting rods to the ceiling. (Re-
fer to Table D for wall and ceiling clearances, and Figure 2 for mounting spacing specifications.)
ADDITIONAL THREADED
3/8-18 THREADED MOUNTING HOLES
MOUNTING HOLES FOR HVH-25 TO HVH-50
Figure 2 - Wall and Ceiling Clearance
XX
L2
CL
CL
TERMINAL BOX ACCESS DOOR
Back Wall
Figure 3 - Rod Spacing
Table C — Rod Thread Type and Spacing Dimensions (inches) for
Vertical Discharge.
Rod
Unit
Thread Type
L1 L2 X
2-5 kW 3/8-16 2-7/8 7-1/8 3-3/4 7-1/2 - 20 kW 3/8-16 4-5/16 9-3/8 5-1/2 25 - 50 kW 3/8-16 8-15/16 14 9-15/16
Table D — Clearance Requirements (Vertical Discharge)
Mounting Limitations (In.)
Model
Back to Wall Side to Wall Top to Ceiling
HVH-02 Thru HVH-05 10-1/4 6 6
HVH-07 Thru HVH-20 13 6 6
HVH-25 Thru HVH-50 15-1/2 6 6
Horizontal Air Flow
1. Height above floor
A.
In areas where ceiling height is more that 12 feet, recommended mounting height is approximately 10 feet to underside of heater.
Side Wall
L1
Dimensions – (In.)
TERMINAL BOX ACCESS DOOR
Figure 4 - Heater Back View
KO FOR POWER WIRING
KO FOR CONTROL WIRING
Knockout Sizes
HVH-02 - 05 1/2” 3/4” (1) HVH-07 - 20 1/2” 1” (1) HVH-25 - 50 1-1/4” 2” (1)
B. For ceiling heights of 12 feet or less, maximum mounting
height is detemined by the use of the mounting bracket offered for these heaters. Minimum spacing to ceiling is 7-3/4”. (See Figure 5)
C. In either case, the mimimum mounting height is 7 feet from
floor to bottom of heater.
2. Spacing to adjacent walls. A. Rear of case to back wall 2” minimum. B. Side of case to side wall 6” minimum.
CEILING – Horizontal Airflow (See Figure 5): The ceiling mounting bracket is fastened to the top of the heater using the four (4) bolts supplied with the mounting bracket. The bracket is then mounted to the ceiling using a 5/8” bolt (by others).
WALL – Horizontal Airflow (See Figure 6): Wall mounting necessitates the use of both an adaptor mounting bracket and a wall mounting bracket. First, attach the ceiling mounting bracket to the heater. Then, attach the wall mounting bracket to the wall using four 5/16” bolts and six 3/8” bolts (by others). Attach the ceiling mounting bracket on the heater to the wall mounting bracket using the 5/8” bolt provided.
3
Page 4
INSTALLATION (cont’d.)
The heater may be rotated to discharge in the desired direction. Open and adjust louvers to desired position. See Figure 5 and 6 for additional mounting details.
CEILING
V
CL OF BOLT
A
BACK OF HEATER
B
W= MINIMUM DISTANCE FROM WALL TO ALLOW FOR FULL 180˚ SWIVEL
Bracket
Model No.
HVC-1 16-1/8 13 10 8-3/8 5-3/4 7-3/4 9-3/4 12 4 HVH-02, 04, 05 HVC-2 20-5/8 17-1/8 12-3/4 10-3/4 6-3/4 7-3/4 13 12 8 HVH-07, 10, 12, 15 HVC-3 20-5/8 17-1/8 14-1/16 12-1/16 8-1/16 7-3/4 13-5/16 8 7 HVH-15 (600V), HVH-20 HVC-4 29-13/16 26-1/16 14-5/8 11-3/4 8-3/16 7-3/4 22-5/16 8-7/16 17 HVH-25, 30, 35, 40, 45, 50
N
C
Dimensions (in.)
CEILING
M
U
FOR SWIVEL MOUNTING TO CEILING, USE ONE 5/8" LAG BOLT. FOR FIXED MOUNTING TO CEILING, USE FOUR 3/8" LAG BOLTS
WALL
W
Wt.
(Lbs.) Use WithA B C M N U V W
Figure 5 - Optional Ceiling Swivel Mounting Bracket
ADAPTOR BRACKET
Figure 6 - Optional Wall Swivel Mounting Bracket
R
S
P
Q
T
Bracket
Model
No.
HVW1 16-1/16 18-7/8 7 5 17-5/8 3-3/4 HVH-02, 04, 05 HVW2 16-1/16 23-1/4 7 5 18-5/8 6-1/2 HVH-07, 10, 12, 15 HVW3 6 23-7/16 6-7/8 4-15/16 20-1/16 9 HVH-15 (600V), HVH-20 HVW4 8 32-13/16 10-3/8 8-1/2 22-7/16 14 HVH-25, 30, 35, 40, 45, 50
Dimensions (in.)
Bracket Weight
(Lbs.) Use WithP Q R S T
4
Page 5
WIRING
ELECTRIC SHOCK HAZARD. Be sure electricity is turned off at main switch first before wiring. Any in­stallation involving electric heaters must be effective­ly grounded in accordance with the National Electrical Code to eliminate shock hazard.
1. Use heater only on the voltage and frequency specified on the name­plate.
2. All wiring should be done in accordance with local codes and the National Electrical Code by a qualified person as defined in the NEC.
3. Two knockouts are provided on the back of the heater for wire entry. See Figure 4 for location of knockouts.
4. Branch circuit wire for connection to heater must be at least 60˚C wire.
5. The bottom access door is hinged. There are two screws that must be removed to gain access (Figure 3).
6. A ground wire or ground lug is provided near the power connection point (ground Wire on HVH-02 to HVH-20 and ground lug on HVH­25 to HVH-50).
7. Terminals on contactor or on line voltage terminal block are supplied to be connected to accept the correct size power supply wire. Copper rated at 600V and 60˚C is satisfactory for the heater branch circuit.
8. Electrical accessories, either kits or factory-installed options, are shown connected by a dash line on the heater wiring diagram.
9. Wiring connections are to be made on designated wire leads as shown in the wiring diagrams located inside the access door.
10. Louver adjustment (Do not attempt to adjust while heater is op­erational): Louvers have been preset at factory with the minimum
open angle. Decreasing the 45˚ angle may result in high tempera­tures and functioning of the over temperature control. To increase the opening angle, grasp the left end of louver with the left hand using the index finger and thumb. Grasp right end of louver with right hand in the same manner. Twist louver to the desired position.
REMOTE SUMMER FAN SWITCH
(MANUAL SWITCH-LINE VOLTAGE). The wall switch is packed in the wiring compartment. The remote fan switch is mounted external and remote from the HVH unit heater. The voltage of the re­mote fan switch is the same as the supply voltage to the HVH heater.
1. Use 14 gauge copper, NEC Class 1, 600V rated insulated wire.
Wiring must meet all Local and NEC requirements for 480-volt service.
2. Install the remote fan switch in standard wall box in any conve-
nient location that is protected from traffic or other accidental dam­age.
3. Connect the 14 gauge copper field wire to the switch lead wires
with suitable connectors.
Power Disconnect Switch
To Power Supply
See Note 2
Notes:
1. This illustration shows wiring hook up for three phase service. Remove lead wires marked L3 and S3 when using single phase power service.
2. For units without contactors, disconnect switch is to be wired to terminal block on heater power.
3. Use copper supply wire only with this switch.
L1
L2
L3
Contactor or Terminal Block
S1
S2
S3
See Notes
Figure 8 - Power Disconnect Switch Wiring Diagram
Top of Heater
45˚ Min.
All Louvers
Figure 7 - Louver Adjustment
POWER DISCONNECT SWITCH
(Available as a kit or factory installed option). This switch discon­nects the power to the power leads when the handle is turned to its off position. Refer to Instruction Sheet PF207.
1. Use copper conductor supply wire only when connecting to the
power line. (See Figure 8.)
2. Connection to the switch pigtails should be made with compres-
sion connectors and the joint should be then well insulated.
3. Consult the local wiring code in your area.
SUMMER FAN SWITCH - Refer to Instruction sheet PF205 with­out relay, PF206 with relay.
(MOUNTED ON FRONT OF HEATER). When the switch handle is pointing toward the Summer (Fan ON) position, the fan will run continu­ously. When the switch handle is pointing toward the WINTER (HEAT) position, the fan will run only when the heating elements are hot.
REMOTE FAN SWITCH
480V + Heaters require an additional fan relay. (Available as a kit or factory installed option and standard on heaters 20kW and above). The wall switch is packed in the wiring compartment.
1. Use 18 gauge (min.) NEC Class 1, 600V wiring that meets all Lo-
cal and NEC requirements.
2. Install the wall switch in a standard wall box in any convenient
location that is protected from traffic or other accidental damage.
3. Connect the field wire to the switch lead wires with suitable con-
nectors.
OPTIONAL THERMOSTAT (HVH-TK) Refer to Instruction Sheet PF204.
Heaters can be equipped with an optional thermostat of the Bulb and Capillary type for automatic temperature control (Figure 8). The thermostat controls the heating elements and fan simultaneously to achieve set temperature.
The “Lo” setting of the thermostat is approximately 40˚F, and the “Hi” setting is approximately 90˚F.
Chromalox
Figure 9 — Thermostat Location, Front View
5
Page 6
WIRING (cont’d.)
CONTROL VOLTAGE WIRING — EXTERNAL REMOTE THERMOSTATS AND FAN SWITCHES
ELECTRIC SHOCK HAZARD. Be sure electricity is turned off at main switch first before wiring. Any in­stallation involving electric heaters must be effective­ly grounded in accordance with the National Electrical Code to eliminate shock hazard.
1. Use 600 volt, NEC Class 1 insulated wiring with a minimum gage
of 18 for thermostats and minimum gauge of 14 for line voltage motor switch (remote fan switch without relay).
2. The thermostat should be located in the area to be heated on an in­side wall. The thermostat should not be exposed to drafts, sunlight, radiation from hot objects, or in a direct line with the discharge from the unit heater.
3. Install the thermostat approximately 5 feet above the floor line.
4. Install the remote fan switch in any convenient location that is pro-
tected from traffic or likely accidental damage.
5. Internal optional controls are shown on the unit heater wiring dia­grams by a dash line.
Optional thermostat
built-in or field
installed
Blue
Blue
Motor
T1 T2 T3
L1 L2 L3
Terminal Block
Figure 10
Optional disconnect switch built-in or field installed
Cutout
Power 60 Hz
1Ø Element wiring (Omit for 2 element heaters)
Elements
Optional
Disconnect
switch built-in or field
installed
Motor
T1 T2 T3
L1 L2 L3
Power 60 Hz
See Note #2
Optional Thermostat Built-in or Field Installed
3Ø Wiring
TO T1 TO T2 TO T3
Yellow
Blue
C1C2C3
Pink
Remove jumper wire when thermostat is used
NOTES:
1. Omit "L3" wiring for 1ø heaters
2. 3ø Motors used on all 480V, 7.5KV or higher
Black
Sec
Red
Figure 11
Cutout
Optional disconnect switch built-in or field installed
Motor
T1 T3T2
L2
L1 L3
Power 60 Hz
Optional thermostat built-in or field installed
TO T1 TO T1 TO T2 TO T3 TO T3 TO T2
C1C3C2
Pink
Remove jumper wire when thermostat is used
Notes: 1 Omit "L3" wiring for 1ø heaters
Figure 12
Purple
Orange
3Ø Wiring
Cutout
TO T1
TO T2
1Ø Wiring
TO T1
TO T2
TO T1
TO T2
Optional disconnect switch built-in or field installed
See Note #2
Motor
T2
T1
L1
L2
Power 60 Hz
Notes:
1. Omit "L3" wiring for 1ø heaters
2. 3Ø motors used on all 480V 7.5Kw or higher heaters. All other heaters use 1ø motors.
Optional thermostat built-in or field installed
TO T1 TO T1 TO T2 TO T3 TO T3 TO T2
T3
C1C3C2
L3
Remove jumper wire when thermostat is used
Yellow
Pink
Figure 13
Blue
Black
Black/Red
3Ø Wiring
SEC
Cutout
TO T1
TO T2
1Ø Wiring
TO T1
TO T2
TO T1
TO T2
6
Page 7
Figure 14
Elements
3 Phase Wiring
Line Fusing
Alternate 1PH Motor Wiring
Optional
Pliot Light
Built in or External Disconnect Switch
WIRING (cont’d.)
Capacitor
Fusing
Fusing
AR Cutout
Motor Contactor
Transformer
40VA
Time Delay
Refer to Nameplate for XFMR Primary (Input) and Seconday Control) Voltage.
Relay
Built In or Remote Thermostat
Termnal Block (Control)
Figure 15
Elements
3 Phase Wiring
Line Fusing
3 Phase Wiring
Optional
Line Fusing
Built in or External Disconnect Switch
Elements
Alternate 1PH Motor Wiring
Pliot Light
Capacitor
Fusing
Fusing
Motor Contactor
Transformer
Capacitor
Fusing
40VA
AR Cutout
Time Delay
Relay
Refer to Nameplate for XFMR Primary (Input) and Seconday Control) Voltage.
Built In or Remote Thermostat
Termnal Block (Control)
Line Fusing
Figure 16
Line Fusing
Built in or External Disconnect Switch
Optional
Pliot
Light
Line Fusing
Fusing
Built In or Remote Thermostat
Termnal Block (Control)
AR Cutout
Motor Contactor
Transformer
80VA
Time Delay
Relay
Refer to Nameplate for XFMR Primary (Input) and Seconday Control) Voltage.
7
Page 8
RENEWAL PARTS IDENTIFICATION
PRODUCT
TYPE KW VOLTS Ø CONTROL VOLTAGE
INTEGRAL
THERMOSTAT
INTEGRAL DISCONN.
SWITCH
FAN ONLY
SWITCH
TIME
DELAY
POWER
ON PILOT
LIGHT
OUTLET SCREEN
hhh – hh – h – h – hh – hh – h – hh – h – h – h
Code
No. kW Volts Phase
HVH-02-81 2.67 208 1 118-305631-001 193-302912-001 112-302997-001 HVH-02-21 2.67 208/240 1 118-305631-002 193-302912-001 112-302997-001 HVH-02-71 2.67 277 1 118-305631-003 193-302120-001 112-130367-001 HVH-04-81 4 208 1 118-305631-001 193-302912-001 112-302997-001 HVH-04-83 4 208 3 118-305631-001 193-302912-001 112-302997-001 HVH-04-21 3/4 208/240 1 118-305631-002 193-302912-001 112-302997-001 HVH-04-23 3/4 208/240 3 118-305631-002 193-302912-001 112-302997-001 HVH-04-71 4 277 1 118-305631-003 193-302120-001 112-130367-001 HVH-04-43 4 480 3 118-305631-003 193-302912-003 112-302997-001 HVH-05-81 5 208 1 118-305631-004 193-302912-001 112-302997-001 HVH-05-83 5 208 3 118-305631-004 193-302912-001 112-302997-001 HVH-05-21 3.75/5 208/240 1 118-305631-005 193-302912-001 112-302997-001 HVH-05-23 3.75/5 208/240 3 118-305631-005 193-302912-001 112-302997-001 HVH-05-71 5 277 1 118-305631-006 193-302120-001 112-130367-001 HVH-05-43 5 480 3 118-305631-007 193-302912-003 112-302997-001 HVH-07-81 7.5 208 1 118-305659-007 193-302912-004 112-130367-002 HVH-07-83 7.5 208 3 118-305659-007 193-302912-004 112-130367-002 HVH-07-21 5.6/7.5 208/240 1 118-305659-008 193-302912-004 112-130367-002 HVH-07-23 5.6/7.5 208/240 3 118-305659-008 193-302912-004 112-130367-002 HVH-07-71 7.5 277 1 118-305659-009 193-302120-004 112-130367-002 HVH-07-43 7.5 480 3 118-305659-010 193-302912-005 112-130367-002 HVH-10-81 10 208 1 118-305659-001 193-302912-004 112-130367-002 HVH-10-83 10 208 3 118-305659-001 193-302912-004 112-130367-002 HVH-10-21 7.5/10 208/240 1 118-305659-002 193-302912-004 112-130367-002 HVH-10-23 7.5/10 208/240 3 118-305659-002 193-302912-004 112-130367-002 HVH-10-43 10 480 3 118-305659-003 193-302912-005 112-130367-002 HVH-12-83 12.5 208 3 118-305659-004 193-302912-004 112-130367-002 HVH-12-23 9.4/12.5 208/240 3 118-305659-005 193-302912-004 112-130367-002 HVH-12-43 12.5 480 3 118-305659-006 193-302912-005 112-130367-002 HVH-15-83 15 208 3 118-305659-007 193-302912-004 112-130367-002 HVH-15-23 11.2/15 208/240 3 118-305659-008 193-302912-004 112-130367-002 HVH-15-43 15 480 3 118-305659-010 193-302912-005 112-130367-002 HVH-20-23 19.8 208/240 3 118-305762-019 193-302912-004 112-130367-002 HVH-20-43 19.8 480 3 118-305762-009 193-302912-005 112-130367-002 HVH-20-63 19.8 600 3 Check with Factory Check with Factory Check with Factory HVH-25-23 25.0 208/240 3 118-305762-017 193-302120-037 112-045422-016 HVH-25-43 25.0 480 3 118-305762-020 193-302120-011 112-045422-016 HVH-25-63 25.0 600 3 118-305762-016 193-302912-026 112-045422-016 HVH-30-23 30.0 208/240 3 118-305762-013 193-302120-037 112-045422-016 HVH-30-43 30.0 480 3 118-305762-014 193-302120-011 112-045422-016 HVH-30-63 30.0 600 3 118-305762-015 193-302912-026 112-045422-016 HVH-35-23 33.3 208/240 3 118-305762-011 193-302120-037 112-045422-013 HVH-35-43 33.3 480 3 118-305762-012 193-302120-011 112-045422-013 HVH-35-63 33.3 600 3 118-305762-010 193-302912-026 112-045422-013 HVH-40-23 37.5 208/240 3 118-305762-017 193-302120-037 112-045422-013 HVH-40-43 37.5 480 3 118-305762-020 193-302120-011 112-045422-013 HVH-40-63 37.5 600 3 118-305762-016 193-302912-026 112-045422-013 HVH-45-23 45.0 208/240 3 118-305762-013 193-302120-037 112-045422-013 HVH-45-43 45.0 480 3 118-305762-014 193-302120-011 112-045422-013 HVH-45-63 45.0 600 3 118-305762-015 193-302912-026 112-045422-013 HVH-50-23 50.0 208/240 3 118-305762-011 193-302120-037 112-045422-013 HVH-50-43 50.0 480 3 118-305762-010 193-302120-011 112-045422-013 HVH-50-63 50.0 600 3 118-305762-012 193-302912-026 112-045422-013
Element
Part No.
Motor
Part No.
Fan
Part No.
8
Page 9
-0
-0
OUTLET SCREEN
OUTLET
SCREEN
-0
LIGHT
POWER
ON PILOT
PILOT LIGHT
TIME DELAY
-0
RENEWAL PARTS IDENTIFICATION
0 = No Pilot Light 0 = No Outlet Screen
P = 24V P/N 213-072380-029 S = 2-5 kW P/N 247-305642-001
TIME
DELAY
SWITCH
FAN ONLY
SWITCH
INTEGRAL
DISCONN.
INTEGRAL
THERMOSTAT
DISCONNECT
INTEGRAL
P = 120V P/N 213-072380-007 S = 7-20 kW P/N 247-305642-002
-0
SWITCH
-00
THERMOSTAT
00 = No Thermostat 0 = No Disconnect Switch
TL = SPST P/N 300-049197-003 D = 50A P/N 292-303472-007
TL = DPST P/N 300-049197-004 D = 80A P/N 168-303598-007
TH = SPST P/N 300-049197-001 D = 100A P/N 168-303598-008
TH = DPST P/N 300-049197-002
FAN ONLY SWITCH
D0 = No Disconnect Switch 0 = No Time Delay Relay
FI = 3PST Switch P/N 292-057673-001 R = 24V Relay P/N 072-071847-040
FE = 3PST Switch P/N 292-057673-001 R = 120V Relay P/N 072-071847-041
FI = 24V Motor Relay P/N 072-123534-075
FI = 120V Motor Relay P/N 072-123534-064
Miscellaneous Parts
Thermostat Knob 169-049278-001
Instruction Sheets
1. Internal Thermostat PF204
2. Internal/External Summer Fan Switch PF205
3. Internal/External Summer Fan Switch W/Relay PF206
4. Disconnect Switch PF207
Limited Warranty:
2150 N. RULON WHITE BLVD., OGDEN, UT 84404
Phone: 1-800-368-2493 www.chromalox.com
-00
TYPE KW VOLTS Ø CONTROL VOLTAGE
PRODUCT
hhh – hh – h – h – hh – hh – h – hh – h – h – h
CONTROL VOLTAGE
Ø
VOLTS
kW
0
-0
-00
7 30 = 24V Transformer P/N 315-304252-004
2, 4, 7, 8 00 = No Contactor
2, 4, 8 30 = 24V Transformer P/N 315-304252-002
2, 4, 7, 8 30,31 = 24V 35A Contactor P/N 072-306110-001
2, 4, 7, 8 30,31 = 24V 50A Contactor P/N 072-306110-002
2, 4, 7, 8 32,33 = 120V 35A Contactor P/N 072-306110-007
7 32 = Transformer P/N 315-304252-003
2, 8 34 = 208/240V 35A Contactor P/N 072-306110-013
2, 4, 8 32 = Transformer P/N 315-304252-001
2, 4, 7, 8 32,33 = 120V 50A Contactor P/N 072-306110-008
9
Please refer to the Chromalox limited warranty applicable to this product at
Cutout Switch
2.6 through 5 kW 300-024413-001
7.5 through 15 kW 300-024413-002
7 35 = 277V 35A Contactor P/N 072-306110-019
7 35 =277V 50A Contactor P/N 072-306110-020
2, 8 34 = 208/240V 50A Contactor P/N 072-306110-014
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.
Loading...