Chromalox DU-RAD-458 6.04 757 User Manual

(Supersedes PG423)
PG423-1
DU-RAD
161-057863-001
MARCH, 2004
4
and
RENEWAL PARTS IDENTIFICATION
Type DU-RAD Electric Radiant Heater
© 2010 Chromalox, Inc.
Specifications – Table A
Dimensions (In.)
BCD
A Total Center End
Model Volts kW Overall Heated Heated Heated
DU-RAD-458 6.04 75
7
/8 67 233/8 195/16 DU-RAD-466 6.42 797/8 71 323/8 195/16 DU-RAD-474 6.79 84 751/8 361/2 195/16 DU-RAD-482 7.17 881/16 791/8 409/16 195/16 DU-RAD-490 7.55 923/16 835/16 4411/16 195/16 DU-RAD-4102 208, 240, 8.12 983/16 895/16 5011/16 195/16 DU-RAD-4112 275 or 480 8.59 1035/16 947/16 5513/16 195/16 DU-RAD-4124 9.16 1091/2 1005/8 62 195/16 DU-RAD-4136 9.73 1151/2 1065/8 68 195/16 DU-RAD-4148 10.30 1215/8 1123/4 741/8 195/16 DU-RAD-4156 10.70 12511/16 11613/16 783/16 195/16 DU-RAD-4164 11.05 12913/16 12015/16 825/16 195/16 DU-RAD-4172 11.43 134 1251/8 861/2 195/16 DU-RAD-540 208, 240 6.60 815/8 723/4 191/4 263/4 DU-RAD-548 or 275 6.97 855/8 763/4 231/4 263/4 DU-RAD-558 7.44 903/4 817/8 283/8 263/4 DU-RAD-566 7.82 943/4 857/8 323/8 263/4 DU-RAD-574 8.19 987/8 90 361/2 263/4 DU-RAD-582 8.57 10215/16 941/16 409/16 263/4 DU-RAD-590 8.95 1071/16 983/16 4411/16 263/4 DU-RAD-5102 208, 240, 9.52 1131/16 1043/16 5011/16 263/4 DU-RAD-5112 275 or 480 9.99 1183/16 1095/16 5513/16 263/4 DU-RAD-5124 10.56 1243/8 1151/2 62 263/4 DU-RAD-5136 11.13 1303/8 1211/2 68 263/4 DU-RAD-5148 11.70 1361/2 1275/8 741/8 263/4 DU-RAD-5156 12.10 1409/16 13111/16 783/16 263/4 DU-RAD-5164 12.45 14411/16 13513/16 825/16 263/4 DU-RAD-5172 12.83 1487/8 140 861/2 263/4 DU-RAD-640 208, 240 7.60 933/4 847/8 191/4 3213/16 DU-RAD-648 or 275 7.97 973/4 887/8 231/4 3213/16 DU-RAD-658 8.44 1027/8 94 283/8 3213/16 DU-RAD-666 8.82 1067/8 98 323/8 3213/16 DU-RAD-674 9.19 111 1021/8 361/2 3213/16 DU-RAD-682 9.57 1151/16 1063/16 409/16 3213/16 DU-RAD-690 9.95 1193/16 1105/16 4411/16 3213/16 DU-RAD-6102 208, 240, 10.52 1253/16 1165/16 5011/16 3213/16 DU-RAD-6112 275 or 480 10.99 1305/16 1217/16 5513/16 3213/16 DU-RAD-6124 11.56 1361/2 1275/8 62 3213/16 DU-RAD-6136 12.13 1421/2 1335/8 68 3213/16 DU-RAD-6148 12.70 1485/8 1393/4 741/8 3213/16 DU-RAD-6156 13.10 15211/16 14313/16 783/16 3213/16 DU-RAD-6164 13.45 15613/16 14715/16 825/16 3213/16 DU-RAD-6172 13.83 161 1521/8 861/2 3213/16 DU-RAD-740 208, 240 8.80 106 971/8 191/4 3815/16 DU-RAD-748 or 275 9.17 110 1011/8 231/4 3815/16 DU-RAD-758 9.64 1151/8 1061/4 283/8 3815/16 DU-RAD-766 10.02 1191/8 1101/4 323/8 3815/16 DU-RAD-774 10.39 1231/4 1143/8 361/2 3815/16 DU-RAD-782 10.77 1275/16 1187/16 409/16 3815/16 DU-RAD-790 11.15 1317/16 1229/16 4411/16 3815/16 DU-RAD-7102 208, 240, 11.72 1377/16 1289/16 5011/16 3815/16 DU-RAD-7112 275 or 480 12.19 1429/16 13311/16 5513/16 3815/16 DU-RAD-7124 12.76 1483/4 1397/8 62 3815/16 DU-RAD-7136 13.33 1543/4 1457/8 68 3815/16 DU-RAD-7148 13.90 1607/8 152 741/8 3815/16 DU-RAD-7156 14.30 16415/16 1561/16 783/16 3815/16 DU-RAD-7164 14.65 1691/16 1603/16 825/16 3815/16 DU-RAD-7172 15.03 1731/4 1643/8 861/2 3815/16
Dimensions (In.)
BCD
A Total Center End
Model Volts kW Overall Heated Heated Heated
One Double-Hairpin Element Models
DU-RAD-040 120, 208 1.60 20
3
/8 1815/16 DU-RAD-048 240 or 275 1.97 2325/32 2225/32 DU-RAD-058 120, 208 2.44 287/8 2725/32 DU-RAD-066 240, 275 2.82 331/4 3125/32 DU-RAD-074 or 480 3.19 371/4 3525/32 DU-RAD-082 3.57 411/8 397/8 DU-RAD-090
208,
3.95 453/16 437/8 DU-RAD-0102 4.52 517/8 497/8 DU-RAD-0112
240,
4.99 563/16 547/8 DU-RAD-0124 5.56 621/2 6015/16 DU-RAD-0136
275
6.13 689/16 6615/16 DU-RAD-0148 6.70 751/2 7215/16 DU-RAD-0156
or
7.10 7813/16 77 DU-RAD-0164 7.45 82
11
/16 81
DU-RAD-0172
480
7.83 87 85
1
/16
Three Hairpin Element Models
DU-RAD-240 3.20 44
3
/4 357/8 191/4 85/16
DU-RAD-248
120, 208
3.57 483/4 397/8 231/4 85/16 DU-RAD-258
240 or 275
4.04 537/8 45 283/8 85/16 DU-RAD-266 4.42 577/8 49 323/8 85/16 DU-RAD-274 4.79 62 531/8 361/2 85/16 DU-RAD-282 5.17 661/16 573/16 409/16 85/16 DU-RAD-290 5.55 703/16 615/16 4411/16 85/16 DU-RAD-2102 6.12 769/16 675/16 5011/16 85/16 DU-RAD-2112 6.59 815/16 727/16 5513/16 85/16 DU-RAD-2124 208, 240 7.16 871/2 785/8 62 85/16 DU-RAD-2136 or 275 7.73 931/2 845/8 68 85/16 DU-RAD-2148 8.30 995/8 903/4 741/8 85/16 DU-RAD-2156 8.70 10311/16 9413/16 783/16 85/16 DU-RAD-2164 9.05 10713/16 9815/16 825/16 85/16 DU-RAD-2172 9.43 112 1031/8 861/2 85/16 DU-RAD-340 3.80 51 421/8 191/4 117/16 DU-RAD-348
120, 208
4.17 55 461/8 231/4 117/16 DU-RAD-358
240 or 275
4.64 601/8 511/4 283/8 117/16 DU-RAD-366 5.02 641/8 551/4 323/8 117/16 DU-RAD-374 5.39 681/4 593/8 361/2 117/16 DU-RAD-382 5.77 725/16 637/16 409/16 117/16 DU-RAD-390 6.15 767/16 679/16 4411/16 117/16 DU-RAD-3102 6.72 827/16 739/16 5011/16 117/16 DU-RAD-3112 7.19 879/16 7811/16 5513/16 117/16 DU-RAD-3124 7.76 933/4 847/8 62 117/16 DU-RAD-3136 208, 240 8.33 993/4 907/8 68 117/16 DU-RAD-3148 or 275 8.90 1057/8 97 741/8 117/16 DU-RAD-3156 9.30 10915/16 1013/16 783/16 117/16 DU-RAD-3164 9.65 1141/16 1053/16 825/16 117/16 DU-RAD-3172 10.03 1181/4 1093/8 861/2 117/16 DU-RAD-440 5.20 663/4 577/8 191/4 195/16 DU-RAD-448 5.57 703/4 617/8 231/4 195/16
Single Element
Three Elements
2
INSTALLATION
MOUNTING
The system designer is responsible for the safety of this equipment and should install adequate back-up controls and safety devices with their electric heating equipment. Where the conse­quences of failure could result in personal injury or property damage, back-up controls are essential.
Before Installing
1. Open carton and remove heater at the place of installation.
Mounting clamps are in parts bag in carton.
2. Check nameplate volt and watt rating against your power supply
voltage and heating requirements of your installation. This name­plate of the complete assembly is located on the back of the heater housing. Note: Single element heaters have one nameplate. Three element heaters have four nameplates (one for each element and one for the complete assembly).
Housing
1 / "
7
8
Mounting Clamp
Assembly
Terminal
Cover
Terminal
Blocks
Polished Aluminum
Reflector
Element
Figure 1 — Heater Parts
and Dimensions
FIRE HAZARD. Since heaters are capable of devel­oping high temperatures, extreme care should be taken to maintain adequate spacing between heater and combustible materials. Failure to comply can result in personal injury or property damage.
Mounting
1. Clamps — Heaters are mounted by means of the mounting clamp
and 3/8” bolt assembly which is used as shown in Fig. 2. Clamp assembly may be attached to heater by sliding over end or by snap­ping over top of extruded frame section at any point along its length. (see Fig. 3) For proper heater support, the maximum dis­tance between clamps must not exceed 48”. On extra-long heaters, more than two clamps are furnished.
2. Mounting Holes — When heaters are mounted adjacent to each
other in the same plane, the minimum distance will depend on whether the wiring to the center element enters the terminal box through the connector furnished or through a right angle connector (not furnished).
3. Framing — Where an extensive installation is being made, the use
of continuous slot metal framing manufactured by several con­cerns will be of assistance in saving time and money. The framing is reusable.
4. Reflector Spacer Sheets — Where heaters are not mounted side
by side (see Fig. 4), reflector spacer sheets can be used between heaters. These reflector spacer sheets and companion reflectors consisting of an extruded aluminum housing with reflector sheet and mounting clamps are available. Check factory or local Chromalox Sales and Application Engineers.
5. Insulation — Where unusually high work temperatures are
encountered, it may be desirable to insulate with high temperature insulation. Note: An air space should be left between backs of heaters and insulation. (see Figure 4)
6. Ventilation — Where solvents, water, etc. are being evaporated
from work in process, it is necessary to provide substantial quanti­ties of ventilation air to carry away the resulting vapors.
IMPORTANT –
In the case of solvents of an explosive nature, ventilation air must be in sufficient volume to dilute the solvent vapor so that explosive mixtures cannot occur. In order to comply with the standards of safety required by the insurance companies, ventilation protection and other facilities must be in accordance with NFPA Bulletin No. 86, entitled “Standard for Ovens and Furnaces”. This Bulletin may be obtained from the Association at 470 Atlantic Avenue, Boston Mass., 02110
FIRE/EXPLOSION HAZARD. This heater is not intended for use in hazardous atmospheres where flammable vapors, gases, liquids or other com­bustible atmospheres are present as defined in the National Electrical Code. Failure to comply can result in personal injury or property damage.
2 / "
15
16
2 / "
3
8
3 / "
11
16
Figure 2 Figure 3
Mounting Frame
Reflector Spacer Sheet
Insulation
Figure 4
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could result in personal injury or property dam­age. Heater must be installed by a qualified person in accordance with the National Electrical Code, NFPA 70.
ELECTRIC SHOCK HAZARD. Any installation involv­ing electric heaters must be performed by a quali­fied person and must be effectively grounded in accordance with the National Electrical Code to eliminate shock hazard.
1. The power supply voltage should be the voltage as specified on the
heater nameplate located on the heater housing.
2. Wiring should be run in flexible or rigid metal conduit and must be
installed in accordance with the requirements of the National Electrical Code and such other local requirements as may be applicable. Note: High temperatures will oxidize copper. Do not use copper wire in connecting this heater. Nickel-plated copper wire, insulated in accordance with requirements for temperature and voltage is recommended.
3. A sufficient length of this wire (not less than 12”) should be used
to extend from each heater terminal into a connection box location where the temperature does not exceed 300˚F.
4. ELECTRICAL CONNECTIONS A. End Elements
Electrical connection to the heater end elements is made through the 7/8” dia. opening in the end of the terminal cover of the element assembly. A 1/2” flexible conduit connector is provided with each element assembly for this purpose.
B. Center Elements
Electrical connection to the heater center element is made through the 7/8” dia. opening in the 4” octagon conduit box for the element assembly. A 1/2” flexible conduit connector is pro­vided with each element assembly for this purpose.
5. ACCESS TO TERMINALS A. End Elements
Access to the end element terminals is obtained by removing the mounting bolt, nut and spacer (see Figure 9, items 9, 16 and
18) and sliding the terminal end of the element assembly out of the housing.
B. Center Elements
Access to the center mounted element terminals is obtained by removing the terminal box cover.
6. END ELEMENT TERMINAL ASSEMBLY
Assemble end terminal, screw and wire as shown in Figure 5. Hold terminal with pliers and tighten the terminal screw securely with a screwdriver.
7. CENTER ELEMENT TERMINAL ASSEMBLY
Assemble center terminal, washers, nut and wire as shown in Figure 6. Hold terminal with pliers and tighten the terminal nut securely with a wrench.
CAUTION: Terminal clip is spot-welded to element terminal pin and over-tightening terminal screw may break the weld or shear off terminal pin. However, either the screw or nut should be suffi­ciently tightened to eliminate arcing.
8. SERIES CONNECTION of Radiant Heaters of equal volt and
watt rating is permitted in all line voltages up to 600 volts. In mak­ing such series connections it is necessary to observe the “right” (series-parallel) connection rather than the “wrong” (parallel­series) connection both shown in Figure 7. If heaters are connect­ed according to the “wrong” illustration, failure of any heater will cause progressive failure of other heaters still operating.
9. DELTA CONNECTIONS — When heaters occur in multiples of
three, they may be connected to, and balanced across, three-phase lines. The most commonly used connection is the delta connection illustrated in Figure 8.
Three phase Delta connections to minimize inductive effect in conduits are made per this diagram. The rule: run all 3 three-phase conductors in the same conduit as far as possible. For single-phase, run only two conductors and follow the same rule.
3
WIRING
Wrong
Right
L1
L2
L2
L1
Radiant Heaters
Wrong
Right
L1
L2
L2
L1
Radiant Heaters
Figure 5 — End Element Terminal Assembly
Figure 7
Figure 8
Figure 6 — Center Element Terminal Assembly
Loading...
+ 5 hidden pages