Chromalox DH, DHOC Installation Instructions Manual

Installation Instructions
DH and DHOC
Electric Duct Heaters
PF503
161-562766-001
1
February 2015
Table of Contents
General ...............................................................................................................................3
Installation .......................................................................................................................... 3
Mounting ............................................................................................................................6
Wiring ................................................................................................................................10
Operation .........................................................................................................................11
Maintenance ....................................................................................................................11
Heater Bundle Removal and Replacement ................................................................... 11
Replacement Parts .......................................................................................................... 12
Troubleshooting ............................................................................................................... 13
2
DH and DHOC Electric Duct Heaters
General
Read and understand all instructions before in­stalling, servicing or operating product. Failure to do so could result in personal injury or prop­erty damage.
These heaters are designed to be installed in either a horizontal or vertical duct in one of the six positions shown in figure 12. The heater is constructed with in­dividual metal sheath fintube elements mounted to a heavy gauge metal terminal box.
Due to the various options and materials available, check the nameplate attached to the heater terminal box with the catalog number designation system be­fore installing to insure the heater you received con­forms to your specification.
Please read these directions carefully to insure all limi­tations are properly observed and all wiring and con­trols are properly installed and connected.
IMPORTANT - Observe at least one complete heat­ing cycle operation before leaving the installation.
FIRE/EXPLOSION HAZARD. This heater is not intended for use in hazardous atmospheres where flammable vapors, gases, liquids or other combustible atmospheres are present as defined in the National Electrical Code. Failure to comply can result in personal injury or prop­erty damage.
ELECTRIC SHOCK HAZARD. Any installation involving electric heaters must be performed by a qualified person and must be effective­ly grounded in accordance with the National Electrical Code to eliminate shock hazard.
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could result in personal injury or property damage. Heater must be installed or serviced by a qualified person in accordance with the National Electrical Code, NFPA 70.
Installation
Limitations: Must be in accordance with one of the
following: Standards of the National Fire Protection Association for the installation of Air Conditioning and Ventilating Systems of other than Resident Type (Pam­phlet 90A) or Residential Type Warm Air Heating and Air Conditioning Systems (Pamphlet 90B).
NOTE: The minimum distances shown are limitations. Wherever possible, locate as far away from these lim­its as practical. In any case, this distance with any re­quired airflow correction must be sufficient to accom­plish even air flow at a velocity equal to, at least, the minimum stated on the heater nameplate.
1. Installation near heat pump, central air conditioner, filters or humidifier. (Refer to Figure 1).
Duct Heater
Air
Flow
4 Ft. Min.
Heat Pump, Central Air Conditioner, Filters or Humidifier
Figure 1
3
2.
Installation near air handler discharge. (Refer to Fig. 2).
Duct Heater
Air
Flow
5. Installation with duct transitions in some air distri­bution systems, the duct heater may be consid­erably larger than the ductwork and the duct area must be increased by a sheet metal transition. The slope of the transformation piece on the upstream side of the equipment is limited to 30° as indicated in Fig. 5. On the leaving side, the slope should not be more than 45°.
4 Ft. Min.
Air Handler
Figure 2
3. Installation in branch duct take-off. (Refer to Fig. 3).
Air Flow
4 Ft. Min. Straight Section
Duct Heater
Figure 3
4.
Installation near turns. (Refer to Fig. 4). If heater must be installed closer than 4 feet from the downstream side of a turn, turning vanes must be installed in the turn. The turning vanes will straighten out the air flow so it will be uniform over the face of the heater.
2 Ft. Min.
30"
Air Flow
Max.
30°
4 Ft. Min.
45°
Duct Heater
45°
Max.
4 Ft. Min.
Figure 5
6.
Do not insulate control or terminal box. (Refer to Fig. 6).
External Insulation
Top of Duct
Duct Heater
Leave Control Box Uninsulated
Figure 6
7. Installation in duct larger than heater. For installa-
tion where the duct dimensions exceed the insert type heater dimensions, the area beyond the heater dimensions must be filled with wire mesh, expand­ed or perforated sheet metal of 50% open area as shown in Figure 7. This will maintain a uniform air velocity across the face of the duct.
Duct Heater Here or Here
Air Flow
4 Ft. Min.
Figure 4
4
Inner Baffle
Insert Type Duct Heater
Perforated Metal (50% Open Area)
Flexible Duct
(Must be suitable
for 195°F)
Air
Flow
4 Ft. Min.
Figure 8
Duct Heater
Remove Bracket and Use Sheetmetal Screws Thru Same Holes into Duct.
Oversized Duct
Figure 7
8. Installation with flexible duct. Where a duct heater
must be installed near a flexible duct connection, be certain that a 4’ minimum distance between the duct heater and the flexible connector exists and that the connector is suitable for 195°F tempera­ture. (Refer to Fig. 8).
9. Do not install duct heater outdoors. Duct heaters cannot be installed with rooftop equipment where they are exposed to the weather.
10.
Installation with dampers or filters. Maintain at least 4’ distance between duct heater and damper, filter frames, or other similar obstructions. (Refer to Fig. 9).
4 Ft. Min.
Damper
Duct
Heater
Air Flow
Top of Duct
Figure 9
Clearance: Zero clearance between duct heater and
combustible materials such as wood is permissible. However, adequate clearance must be provided around terminal box for proper ventilation and future service ac­cessibility.
5
Loading...
+ 9 hidden pages