Controls
CX224
12-Channel
Temperature Monitor
(cont’d.)
Stocked Items
Part Number PCN
CX224-A1A 309913
CX224-A1B 309921
Ordering Information
Complete the model number using the matrix
provided.
Accessories
Part
Number Description
AC102734 Communications package.
Includes isoated RS232 to RS485
converter, power supply for converter, 6' (1.8 m) serial cable and
DB25 to DB9 Adapter
TI241 8-Channel thermocouple isolator.
Electrically isolates grounded thermocouples for use with CX224
Specifications
Input:
Standard Input Types:
(Platinum/100 W/0.00392 W/W/°C)
-200 to 700°C: PB
(Platinum/100 W/0.00391 W/W/°C)
-200 to 850°C: PD/PE
(Platinum/100 W/0.00385 W/W/°C)
-200 to 600°C: PF
(Platinum/1000 W/0.00385 W/W/°C)
-80 to 260°C: NA
(Nickel/120 W/0.00672 W/W/°C)
-100 to 260°C: CA
(Copper/10 W/0.00427 W/W/°C)
-270 to 1000°C: Type E
-200 to 1200°C: Type J
-270 to 1150°C: Type K
-270 to 400°C: Type T
4 to 20 mA current loop: Pressure (PSI, Bar),
Humidity (%), Temperature (°F, °C), Vibration
(G),andprocessvariable(mA,VDC)
Note: 4 to 20 mA inputs must be linear with
respect to the measured variable.
Input Scan Rate: 1.5 seconds maximum.
Input Fault Detection:
Options for ignoring, sounding
Output:
Relays: Form C, SPDT 10 A @ 250 VAC/24
CX224 12-Temperature Monitor
Code Power supply
A 85-240 VAC @ 50/60 Hz / 110-370 VDC
Code Output
1 Relays
2 Logic (5 VDC)
Code Interface
A RS232
B RS485
CX224 - A 1 A Typical Model Number
The CX224 monitor comes complete with CX224 software.
1 to 12 RTDs (2 or 3-wire), thermocouples, or 4 to 20 mA current loops.
Accepts any combination of input types.
RTD: -200 to 700°C: PA
Thermocouple (grounded models require TI241):
alarm, or tripping relays associated with the failed sensor. Other
zones are unaffected.
24 independent trip points (2 per
channel): 5 relays, one relay is
intended for use as an alarm func
tion (but can be configured as a
trip point), and one internal audible
alarm. Alarm may be programmed
to sound when selected relays trip.
Logic output option is available for
controlling external SSRs or send
ing a signal to another devic
VDC resistive load; 10 A make
current; 2500 VA breaking capacity, ¼ HP at 120 VAC motor load.
e.
Trip point Hysteresis (deadband):
Display: 20×4 line backlit LCD. 0.1°C or
Accuracy: 2°C (3°F) in 0 to 60°C (32 to
Supply Power:
Power Loss Protection:
Trip points and program pa-
Keyboard: 4 membrane type keys with
Serial Interface:
Programming:
Firmware Fault Protection:
Watchdog resets microproces-
Enclosure: Steel case; NEMA 4 front panel
Connections:
-
Leadwire Resistance Compensation:
Dimensions:
Mounting: Panel mount enclosure. Cutout
-
Weight: 3.8 lbs. (1.72 kg.)
Agency Approvals: UL: 508
Programmable from 0 to 20 (°C or °F).
0.1°F resolution. Front panel LEDs
indicate relay and alarm status
158°F) ambient, over entire range
of the input
85 to 240 VAC @ 50/60 Hz. or
110 to 370 VDC, 5 watts max.
rameters stored in non-volatile
memory. Normal operation
resumes when power is restored.
audible feedback.
RS485 or RS232 (Modbus protocol).
Programmable from front panel
or via RS485 or RS232 interface
using Modbus protocol. PC soft
ware is included for data logging,
commissioning, and configuration. Program settings may be
password protected
sor if it fails to perform program
sequence
Ambient Temperature Rating:
0 to 60°C (32 to 158°F)
Terminal blocks at rear accept
wirestoAWG12
Up to 30 W per leadwire for RTDs,
with no effect on reading
7.5×11.5×2” (191×292×51 mm)
size of 6.8×10.6” (173×269 mm)
-
H-27
multi-loop