Insulation Resistance (Megger) Test .................................................................................. 34
Stabilized Current Test ...................................................................................................... 34
End of Current Voltage Test ............................................................................................... 34
Installation and Maintenance Log........................................................................................ 35
Page 3
Important Safeguards and Warnings
• Never use tie-wire or pipe straps to secure Selfregulating or Constant Wattage heating cables,
FIRE HAZARD. Failure to follow these guidelines
could result in property damage or personal injury.
• Disconnect all power sources before installing or
servicing heating cable. Failure to do so could
result in personal injury or property damage.
• Heating cable must be installed by a qualified
person in accordance with the National Electrical Code, NFPA 70.
• Each heating cable branch circuit must be effectively grounded in accordance with the National
Electrical Code to eliminate shock hazard.
• Never attempt to use damaged heating cables or
connection kits. If cable damage is observed, either replace the complete heating cable, or cut
out the damaged section and replace using the
proper splice connection kit. Do not attempt to
repair damaged heating cable.
• Never energize the cable when it is coiled or on a
reel. Test only when it is laid out straight.
• Handle coils and reels utilizing equipment designed for that purpose.
• Do not drop coils or reels, especially from transporting equipment.
• Lift or handle reels so that the lifting/handling
device does not come in contact with the cable
or it’s protective covering. Coils should be placed
on a skid.
• Handle reels so that the deterioration or physical
damage of cable is prevented.
• Do not install heating cable on equipment which
could become hotter than the heating cable’s
maximum exposure temperature.
• Do not install heating cable in an area or on
equipment which contains potentially corrosive
materials without having a suitable protective
jacket on the cable. Observe all published specifications.
• Do not expose cables to temperatures above
their specified maximums. Do not run cables longer than specified maximum circuit lengths. See
tables provided in this installation manual for details.
as this may damage the cable.
• Keep bus wires separated to avoid shorting the
cable.
• Keep cable ends and connection kits dry before
and during installation.
• Be careful not to break bus wire strands when
preparing the cable, as damaged bus wires can
overheat and short.
• The presence of heating devices must be evident
by the posting of caution signs or markings at appropriate locations and/or at frequent intervals
along the circuit.
• Users should install adequate controls and safety devices with their electric heating equipment.
Where the consequences of failure may be severe, back-up controls are essential. Although
the safety of the installation is responsibility of
the user, Chromalox will be glad to assist in making equipment recommendations
• Insulate the pipe immediately after installing the
heating cable, using only fire-resistant insulation
materials.
• Ground fault equipment protection is required for
each circuit
• Heating cables require a Class A ground-fault circuit-interrupter and any metallic components in
contact with the heating device shall be bonded
to ground.
A ground fault protection device must be used with
this heating device.
Ce produit doit être utilisé avec une protection de
mise à la terre.
3
Page 4
System Components
A complete electric heat trace system includes the following system components – See the figure below for a typical
system.
1. Electric Heat Tracing (Self-regulating, Constant Wattage)
2. Termination Accessories
A. Power Connection
B. Splice/Tee
C. End Seal (under insulation, above insulation or signal
light type)
D. Control Thermostat or RTD Sensor
E. Attachments
i. Fiberglass tape
ii. Aluminum tape for plastic pipe install
iii. Pipe clamps for termination accessories
iv. Electric Trace Caution Label
3. Controls
A. Thermostats
B. Digital Thermostats
C. Single/Dual Loop Panels
D. Weather Trace Panels
E. IntelliTrace Panels
4. Thermal Insulation
5. Weather Barrier for Insulation
4
Page 5
Chromalox Cable Types
Table 1 – Cable Type Overview
Self-Regulating
Wattage
Hazardous ratings availableYesYesYesYes
Usable on plastic pipeYes*NoNoNo
Can be cut to length in eldYe sYes**NoYes
Can be single overlappedYesNoNoNo
Constant
* SRL only on plastic pipe.
** Must be cut at module point to avoid cold leads.
Table 2 – Maximum Temperatures
Cable Type
Max. Maintain
(Power On)
Max. Exposure
(Power Off)Voltage Rating
SRL150˚F185˚F120, 208-277
SRP230˚F275˚F 120, 208-277
SRM/E302˚F420˚F120, 208-277
CWM320˚F*392˚F120, 208-277, 480
SLL302˚F450˚F120, 208-277, 480, 600
MI1112˚F1200˚F120-600
* See Table 15 for maximum maintenance temperatures at each output.
Mineral
Insulated
Long Line
Series
Overcoat Over
Braid (Optional)
Buss Wires
Self-Regulating
Alloy 825 Sheath
Mineral Insulation
Mineral Insulated
Densely
Compacted
Tinned Copper
Braid (Optional)
Jacket
Conductive Matrix
Twin (Shown) or Single
Resistance Wires
Resistance Wire
Binder
Buss Wires
Constant Wattage
High Temperature
Fluoropolymer
Overjacket
16, 14, 12,10 AWG
Copper Buss Wires
SLL Long Line
Module Point
Primary Insulation
Tinned Copper Braid (Optional)
Overcoat Over Braid (Optional)
Metallic Braid
High Temperature
Fluoropolymer Jacket
High Temperature
Fluoropolymer Core Matrix
Approvals
Chromalox heating cables and components approved for use
in hazardous and nonhazardous locations. Refer to the specific product data sheets for details.
5
Page 6
General Information
Use of Manual
These instructions are to be followed when installing Chromalox heating cables on pipes in ordinary locations. Consult
factory for installation of braided cable in hazardous locations. This manual discusses the installation of two types of
heating cables: parallel cables (SRL, SRP, SRM/E) and series
cables (CWM, MI, SLL). Although they are all resistance type
cables, they have different operating characteristics. These
characteristics may make one type of cable more suitable
for a particular application than another. This manual, however, is not intended as a product selection manual. Refer
to appropriate application design guide for product selection
guidelines. A chart high-lighting certain characteristics for
Chromalox heating cables can be found on page 5.
For customer support, design assistance, or information regarding any other Chromalox products, please contact your
local Chromalox representative or use the information below.
Chromalox, Inc.
103 Gamma Drive
Pittsburgh, PA 15238
Tel: +1 (412) 967-3800
Fax: +1 (412) 967-5148
Email: is@chromalox.com
www.chromalox.com
Storage
The heating cables should be stored in their shipping cartons
or on reels in a dry atmosphere until they are ready to be installed. They should be stored in a clean location, where they
are protected from mechanical damage.
Storage temperature range: 0°F(-18°C) to 140°F(60°C).
Important Installation Notes
The following notes should be reviewed prior to installation.
• Always install tracing at the 4 or 8 o’clock position on a
pipe.
• Do not attempt to heat trace any piece of equipment
which will not be insulated.
• Allow a minimum of 2” between cable runs.
• Always install heat tracing on the outside radius of elbows.
• Never install heat tracing over expansion joints without
leaving slack in the cable.
• Pumps and small vessels should be heat traced and controlled with the piping on the inflow end. The cable on the
pump or vessel should be physically separate to permit
disconnection during maintenance or removal.
• Use aluminum foil tape to cover the heating cable whenever the cable is not in good contact with the pipe (i.e. at
supports, valves, pumps, etc.).
• Separately controlled circuits should be provided on dead
end legs and closed bypasses.
• No heat tracing circuit should extend more than two feet
beyond a point where two or more pipes join when such
junctions permit optional flow paths. In such cases, separately controlled traces should be used.
• The minimum installation temperature for all Chromalox
heating cables is -76˚F (-60˚C).
• Chromalox Type SRL heating cables are well suited for
heat tracing plastic pipes. Consult “Chromalox Design
Guide for Heat Tracing Products” for design recommendations. Installation details apply for plastic pipe only
when Type SRL heating cable is used. Consult factory for
applications involving other products.
• Always ensure that the heating cable load is compatible
with the rating of the selected control systems.
• Only install control devices where the electrical conduit
has a low-point drain that prevents condensation from
entering the thermostat enclosure.
NOTICE
STORE IN DRY AREA
These products may be become damaged by moisture. Damage to electrical components,
electrical properties, corrosion or other damage may occur if equipment is not stored
in a dry location. Visual inspection and electrical checks must be performed prior to
installation to ensure safety and proper operation. See equipment installation manual
or contact the factory for more information. 800-443-2640 or www.chromalox.com.
6
Page 7
Installation
Pre-Installation Guidelines
Before attempting to install the heating cable, read this instruction sheet and those enclosed with the accessories to
familiarize yourself with the products. Complete the following
pre-installation steps:
• Verify that the selection of heating cable type and rating
is in accordance with the procedures located in the applicable application design guide.
• Ensure that the voltage rating of the heating cable is acceptable for the available service voltage.
• Walk along the pipe segment that is to be traced and plan
out the path for the heating cable on the pipe.
• Remove any obstacles or sharp edges that are present
along the pipe segment.
• Open package and visually check for breaks or nicks in
the cable jacket. File claim with carrier if any damage is
found.
• After removing the cable from the carton or wrapping,
measure the insulation resistance of the unit from buss
wires to braid at 2,500 VDC to assure the cables have not
been damaged during shipping and handling. If the cable
has no braid, uncoil the cable onto a metal surface and
check resistance between the buss wires and the metal
surface. See Table 4 for acceptable minimum insulation
resistance readings and page 32 for a detailed explanation on how to conduct the insulation resistance test.
ELECTRIC SHOCK HAZARD. Any cable with an insulation resistance reading less than 20 megohms
before installation should not be installed. Contact
your local Chromalox representative.
• Ensure all pipes, tanks etc. have been hydrostatically
tested prior to the installation of the heating cable.
• Ensure all cable ends, connections, and surfaces are dry
prior to installation.
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heating cable. Failure
to do so could result in personal injury or property
damage. Heaters must be installed by a qualified
person in accordance with IEC 62086-2:2001.
Any installation involving electric heating must be
effectively grounded in accordance with IEC 620862:2001 to eliminate shock hazard.
7
Page 8
Installation Guide: Single Run of Cable
If installing a single run of heating cable on a pipe, follow the
steps below:
1. Mount the reel of cable on a holder and place near one
end of the pipe run to be traced. Choose the end from
which it will be the easiest to pay out the cable.
2. Pay out the cable from the reel and loosely string along
the piping, making sure the cable is always next to the
pipe when crossing obstacles. For example, if the heater
is on the wrong side of a crossing pipe, you will have to
restring the cable or cut and splice it.
To prevent damage to cable, avoid such things as:
— Pulling the cable over sharp edges.
— Forcibly pulling the cable free if it snags while
being paid out.
— Walking on or subjecting the cable to other abuse
which could cause mechanical damage.
3. When you reach the end of the circuit, secure the heating
cable to the pipe using glass tape or plastic cable tie with
a temperature rating compatible with the heater cable.
If this end is to have an end seal installed, remember to
leave about a foot of extra cable. If it is a power connection, leave about two feet of extra heater cable.
4. If the heater cable is to be spiraled, go to step 4a.
Begin attaching the cable to the pipe about every foot (0.3
meters).
Place the cable on the bottom half of the pipe at the 4 or
8 o’clock position. Refer to installation detail AD1. Go to
step 5.
a. Note the path of the heater cable and the spiral factor
of the design. A simple way to think about spiral factor
is: A 1.1 spiral factor means install 11 feet of heating
cable on every 10 feet of pipe, etc. At about every 10
feet of pipe, pull the required amount of cable and let
hang in a loop, and attach the cable to the pipe.
b. Rotate the loops around the pipe until all the slack has
been taken up. Even out the spirals of the heater cable
and secure to the pipe as necessary to obtain good
contact. The entire circuit can be installed with hanging loops with the spiraling on the pipe being done
when you trace the heat sinks. Refer to installation detail AD3.
5. At a heat sink (pipe supports, valves, pumps, reducers,
gauges, bucket strainers, etc.), attach the heater cable
to the pipe just before the heat sink. Refer to the design
specs or Table 3 to determine the amount of heater cable
you need to install on the heat sink. Pull this amount of
cable into a loop, attach the heater cable on the other
side of the heat sink and continue attaching the cable
down the pipe as before.
6. When you reach the heater cable reel, you should have
the heater cable attached all along the pipe, with the correct amount of heater cable pulled in loops at all heat
sinks. Attach the cable to the pipe, (leave an extra foot if
at an end seal, two feet if at a power connection) and cut
the heater cable from the reel.
7. Install the heater cable loops on the heat sinks. Refer to
the proper installation detail AD5-AD12 for a general idea
of how to install the cable, but remember:
• It is important to get the proper amount of heater ca-
ble on the heat sink, rather than exactly as the detail
shows. The detail is just a guide.
• Self-regulating heater cables are very flexible and can
be single overlapped for installation ease. Feel free to
use this feature when you can.
• By having the cable installed this way, it can be re-
moved easily from the heat sink without cutting of access to, or removal of the heat sink is required.
Note: If a tee is designed into the system, or if you are using
two or more short cable lengths to complete a circuit, allow
two or three feet of each cable to overlap. This will allow flexibility in assembling the connection kit and locating it on the
pipe.
FIRE HAZARD. Do not overlap constant wattage
heating cables.
8
Page 9
Installation Guide: Multiple Cable Runs
There are two cases where you will need to install more than
one heater cable on a pipe:
• When the design calls for more than one cable.
• When the lines being heat traced are considered important enough to install a backup (redundant) heat tracing
system.
The installation requirements are different for these cases.
Installing Multiple Heater Cables for
Design Requirement
The most common multiple cable requirement is two cables
on a pipe. Below are the recommended techniques for the
two cable systems. They also apply to installations where
three or more cables are to be installed on a pipe.
There are two ways of paying out two heater cables along
a pipe. The first is to locate two reels of heater cable and
supply one cable from each. This method works for all types
of piping runs. However, it may increase material waste by
leaving unusable lengths from two reels. The second way is
to supply both cables from one reel. This method is generally the easiest for relatively straight, simple piping runs. For
each circuit, decide which method to use and then go to the
appropriate part below.
1. Supplying cable from two reels
The general procedure here is the same as given earlier,
but there are a few things to do to make sure the system
is correctly done.
a. At each heat sink, the easiest thing to do is supply the
extra heater called for by the design drawing from only
one heater cable. This avoids having to measure out
half of the requirement from each cable.
b. When doing the previous step, leave a small loop in
the other cable at equipment which may be serviced,
such as pumps, valves, instruments, etc. This is so
both heater cables may be removed enough for future
access.
2. Supplying cable from one reel
The general procedure is the same as given earlier, but
there are a few things to do to make sure the system is
correctly done.
a. With this method, a loop is pulled for the entire circuit.
To do this, attach the end of the heater cable to the
pipe near the heater cable reel. Remember to leave
enough extra cable for the type of connection to be
installed.
b. Begin pulling the cable off the reel in a large loop down
the piping run. Be sure to keep the cable next to the
pipe. Moving down the run, continue attaching the cable to the pipe, leaving the side of the loop going back
to the reel unattached.
c. You will want both sides of the loop to be about the
same length to avoid future problems. Also, it is easier
to install the extra cable required at each heat sink
from only one cable. Therefore, pull the right amount
of extra heater cable needed at every second heat
sink from the side of the loop you are attaching to the
pipe. At the remaining serviceable heat sinks (pumps,
valves, instruments, etc.) do not forget to leave a short
loop of cable for slack when access to the equipment
is needed.
d. When the end of the piping run is reached, pull the
proper amount of extra cable for the connection to be
installed.
e. Now, begin working the remaining side of the loop
back toward the reel, installing it on the pipe and heat
sinks as required.
Installing Backup (Redundant)
Systems
The purpose of a backup system is to provide the proper
amount of heat from the second heater cable if there are
problems with the first. Therefore, each cable must be installed so it can do the job alone. The simplest way to do this
is to install the first heater cable as described in the Installation Guide: Single Run of Cable section. Then, go back and
install the backup heater cable the same way.
There are several things to keep in mind:
• The power connections and end seals for the two cables
are often designed to be at opposite ends of the run in a
redundant system. Remember to leave the proper amount
of extra cable for the connection to be installed on each
cable at that end.
• On piping one inch IPS or smaller, it can be difficult to
apply both heater cables with good contact at all places.
The main thing is to get the correct amount of cable installed. However, try to get as much contact with the piping and heat sinks from both cables as possible.
9
Page 10
Supplementary Instructions:
ATEX and IECEx Applications
SRL and SRM/E Self-Regulating Heating Cables, U Series
Connection Accessories Type DTS-HAZ, UPC, UMC, UES
and RTES
• Do not bend the cable for a length of 300mm from the
cable gland inlet.
• Connection and termination of Chromalolx ATEX and
IECEx certified cable must be carried out by using the U
Series of certified cable connection kits as supplied by
Chromalox, Inc. These are only to be used for the operations for which they were designed.
• The supply circuit to the heating cables must be protected by a safety differential device or equivalent ground
fault protection.
• The earthing braid of the heat trace cable must be bond-
• The minimum cable installation temperature for SRL and
• The certified minimum cable exposure temperature for
ed to a suitable earth terminal.
SRM/E cable is -40˚C (-40˚F).
SRL and SRM/E cable is -60˚C (-76˚F).
10
Page 11
Other Installation Considerations
Bending the Heating Cable
Pipe Hanger
When using a pipe hanger, ensure that the heating cable is
not pinched between the pipe and the hanger. Damage to
the cable can result in electrical arcing, arc faults, and arc
flashes.
Slab Penetrations
Before installing heating cables on a pipe that penetrates a
concrete floor or wall, be sure that the hole comfortably fits
both the pipe, cable, and insulation. Do not damage or cut
the heating cable during installation. Make sure that the cable
is not pinched between the pipe and the concrete floor and
wall when the hole is sealed. When fire stopping around floor
and wall penetrations, aviod damaging or cutting the heating
cable. The heating cable should be protected by a tube or
conduit and should not be installed directly into the sealing
material.
Do not attempt to bend the heating cable in the flat plane,
as it may be damaged. The minimum bending radius for all
Chromalox heating cables is six times the minor diameter.
Heat Sinks
Refer to the design specs or Table 3 to determine the amount
of heater cable you need to install on each heat sink. Install
the heater cable on the heat sinks as explained in installation
details AD5-AD12. However, remember that the detail is just
a guide. It is important to get the proper amount of heater cable on the heat sink, rather than exactly as the detail shows.
11
Page 12
Table 3 – Additional Cable Lengths Required for In-Line Components (Based on Iron Pipe Size)
Piping Size Gate Valve
1/2 in.1.001.001.001.001.001.001.000.30
3/4 in.1.501.001.001.001.501.001.000.30
1 in.2.001.001.001.001.501.001.000.30
1-1/2 in.2.501.501.501.502.002.002.000.30
2 in.2.502.002.002.002.002.002.000.30
2-1/2 in.2.502.002.002.002.002.002.000.30
3 in.3.002.502.502.502.002.002.000.50
4 in.4.003.003.003.002.502.502.500.50
6 in.5.003.503.503.502.502.502.500.80
8 in.7.004.004.004.002.502.502.500.80
10 in.8.004.504.504.503.003.003.000.80
12 in.9.005.005.005.003.003.003.000.80
14 in.10.005.505.505.503.003.003.001.00
16 in.11.006.006.006.003.503.503.501.00
18 in.12.007.007.007.003.503.503.501.00
20 in.13.007.507.507.503.503.503.501.00
22 in.13.007.507.507.503.503.503.501.00
24 in.15.008.008.008.004.004.004.001.00
Globe
ValveBall Valve
Butterfly
Valve
Dimensions in Feet (Ft.)
Support
Shoe
Hanger
Support
Sleeper
Support
Flange
Pair
Typical Installation Detail
AD1 - One Run of CableAD2 - Two Runs of Cable
12
Page 13
AD3 - One Cable-Spiralling Method
AD4 - One Run of Cable at Pipe Elbow
AD5 - Orifice Flange
AD6 - Expansion Joint
AD7 - Welded SupportAD8 - Shoe Support
13
Page 14
AD9 - Valve
AD10 - Pressure Gauge
AD11 - Diaphragm Pressure Gauge
AD13 - U Series Power Connection
AD12 - Level Gauge
AD14 - U Series Splice & Tee Connection
14
Page 15
AD15 - EL Series Splice and Tee Kit
AD16- DL Series Below Insulation End Seal
AD17 - DL Series Power ConnectionAD16-2 U Series Above Insulation End Seal
15
AD19 - Sensor PlacementAD18 - DL Series Splice & Tee Connection
Page 16
Wiring
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heating cable. Failure
to do so could result in personal injury or property
damage. Heater must be installed by a qualified person in accordance with the National Electrical Code,
NFPA 70.
ELECTRIC SHOCK HAZARD. Any installation involving electric heating cables must be performed by a
qualified person and must be effectively grounded
in accordance with the National Electrical Code to
eliminate shock hazard.
ACCESSORIES:
• Selection of installation accessories should be in accordance with ChromaTrace 4 design software program. Ensure accessories are rated for the area where they are located. If Chromalox accessories are not used with cable,
all third-party approvals are voided.
• Only use Chromalox installation kits and use them only for
the operations for which they are designed.
• The instructions included in the Chromalox installation
accessories must be followed for the third-party approvals (UL, FM, CSA, ATEX, IECEx, etc.) to apply.
• Junction boxes must be in accordance with the requirements of the area classification.
• All outdoor junction boxes must be located above grade
level. Covers should be kept on the boxes at all time when
not being worked in.
• All terminations must be protected from the weather and
from physical damage by locating them either under the
weather-proof insulation or inside an appropriate junction
box.
• All equipment must be properly grounded.
• Install installation accessories according to the instructions included in the kits and per installation details AD13
through AD19.
To prevent equipment damage, Circuits fed from
overhead lines should be protected by secondary
lighting arrestors.
CONTROLS:
• All heating circuits should have temperature controls.
Temperature control of the pipeline can be obtained
through various Chromalox temperature controls.
• Contactors must be used when load currents exceed the
rating of the thermostat contacts. Equipment protection
ground fault (30 mA EPD) thermal breakers are recommended with types SRL, SRP, SRM/E, SLL, and CWM.
• The temperature control should be mounted in a location
where it will not be subjected to excessive shock or vibration.
• Line sensing temperature sensors should be mounted in
accordance with installation detail AD19.
• Ambient sensing temperature sensors should be located
at a point where the lowest ambient temperature is expected.
To prevent equipment damage, handle and secure
temperature sensors, especially thermostat bulbs
and capillaries with care to avoid distortion or
crimping which might impair control accuracy.
• Exposed thermostat capillaries should have mechanical
protection.
End Cap
Buss Wire
Heat Generating Matrix
End Cap
Buss Wire
Heat Generating Matrix
Thermostat
Contactor
Thermostat
I. Self-Regulating
L2
Power Supply
L1
L2
L1
Control
Circuit
Power
Supply
Heat Resistance Wire
End Cap
16
End Cap
Buss Wire
Heat Resistance Wire
Thermostat
Contactor
Buss Wire
Thermostat
II. Constant Wattage
L2
Power Supply
L1
L2
L1
Control
Circuit
Power
Supply
Page 17
End Cap
Cold Lead
OR
Heat Resistance Wire
Thermostat
L2
Power Supply
L1
Heat Resistance Wire
End Cap
Contactor
L2
Power
Supply
L1
Control
Circuit
L2
L1
Thermostat
III. Mineral Insulated / Series Long Line
Installation Testing
To identify potential damage, installation testing should be
completed at the following times:
• Prior to installing the heating cable
• Prior to installing the connection kits
• Prior to insulating the pipe
• After insulating the pipe
• Prior to energizing the cable
• During periodic system check-ups
• After maintenance/repair work
As part of the installation testing, complete the following
steps:
1. Visually inspect the heater cable and temperature controls for signs of mechanical damage. If damage is seen,
either replace the complete heater cable, or cut out the
damaged section and replace using the proper splice
connection for the area and cable you are using.
Thermostat
2. Inspect all connections to be sure they are correctly assembled. Be sure each heater cable entry to a connection
has a grommet and the compression plates and caps are
properly tightened.
3. Determine the insulation resistance of the circuit using at
least 1,000 VDC. It is strongly recommended that higher
test voltages be used. Polymeric cables (SR, SLL, and
CWM) should be tested at 2,500 VDC. Always perform
this test at the power connection. See Table 4 for minimum insulation resistance readings. Any cable with an insulation resistance below the recommended value should
be removed and factory should be contacted. See page
31 for a detailed explanation on how to conduct the insulation resistance test.
4. Check voltage at the end of circuit and record in the log
on page 33. See page 31 for information on how to complete the end of circuit voltage test.
Table 4 – Minimum Insulation Resistance Readings
Delivery
Chromalox SRL20 MΩ20 MΩ5 MΩ5 MΩ
Chromalox SRP20 MΩ20 MΩ5 MΩ5 MΩ
Chromalox SRM/E20 MΩ20 MΩ5 MΩ5 MΩ
Chromalox CWM20 MΩ20 MΩ5 MΩ5 MΩ
Chromalox MI
Chromalox SLL20 MΩ20 MΩ5 MΩ5 MΩ
20 MΩ20 MΩ5 MΩ5 MΩ
Installation
Pre-Insulation
17
Installation
Post-InsulationMaintenance
Page 18
Heating Cable Components
Connection Kits
Table 5 – U Series Connection Kits Overview
Catalog NumberDescription
NEMA 4X rated junction box designed to connect
cables to customer supplied power wiring. This
kit provides water-resistant cable entry for one
UPC
Power Connection
Box
UMC
Multiple Entry Power
Connection Box
UES
Above Insulation End
Seal Kit
cable, enclosure support, terminal block, and a
water-resistant corrosion-resistant wiring enclosure with a 3/4” opening to accept a conduit hub
(CCH-2 or equal)
NEMA 4X rated junction box designed to connect
two or three cables. This kit provides waterresistant cable entry, enclosure support, terminal
block, and a water-resistant, corrosion-resistant
wiring enclosure. In addition to splicing or teeing
cables, this model can be used to provide power
connection to up to three cables from one connection kit.
NEMA 4X rated end seal designed to terminate
cables. This kit provides water-resistant cable
entry for one cable. It has a corrosion-resistant
pipe support that brings the cable end outside of
the insulation for easy access.
Installation
Manual
PJ495
PJ497
PJ496
UESL
End Seal Signal
Light Kit
USL
Power/End Seal
Signal Light Kit
SSK
Single Entry
Sealing Kit
NEMA 4X rated end seal designed to seal one
cable and indicate power on with universal voltage 120-277 LED indicator light. This model
provides water-resistant cable entry, enclosure
support, terminal block, and corrosion-resistant
wiring enclosure. Available in red and green.
NEMA 4X rated end seal designed to power or
seal one cable and indicate power on with universal voltage 120-277 LED indicator light. This
model provides water-resistant cable entry,
enclosure support, terminal block, and corrosion-resistant wiring enclosure.
This kit provides water-resistant cable entry for
one cable. It has a corrosion-resistant pipe support that brings the cable end outside of the
insulation for easy connection to power.
PJ448
PJ937
PJ498
18
Page 19
Table 6 – U Long Line Series Connection Kits Overview
Catalog NumberDescription
NEMA 4X rated junction box designed to connect
SLL heating cables to customer supplied power wir-
UPC LL
Power Connection
Kit
UMC LL
Multiple Entry Power
Connection Box
UES LL
End Seal
Connection Kit
ing. This kit provides water-resistant cable entry for
one cable, enclosure support, crimp connections,
cold leads, and a water-resistant corrosion-resistant
wiring enclosure with an opening to accept a 3/4"
conduit hub.
NEMA 4X rated junction box designed to connect
two SLL heating cables to each other. This kit provides water-resistant cable entry for one cable,
enclosure support, crimp connections, and a water
resistant corrosion-resistant wiring enclosure with an
opening to accept a 3/4" conduit hub.
NEMA 4X rated junction box designed to terminate
SLL heating cables outside of the insulation. This kit
provides water-resistant cable entry for one cable,
enclosure support, crimp connections, and a waterresistant corrosion resistant wiring enclosure with an
opening to accept a 3/4" conduit hub.
Installation
Manual
PJ951
PJ949
PJ950
Table 7 – DL Series Connection Kits Overview
Catalog NumberDescription
RTES
End Seal Kit
RTPC
Power Connection
Kit
RTST
Slice & Tee Kit
NEMA 4X rated enclosure that provides waterproof
cable entry for one (1) cable. The fitting has two (2)
different mounting surfaces: one for pipes with a
diameter of 3” or more, and one for smaller pipes
NEMA 4X rated junction box that provides waterproof cable entry for up to three (3) cables with an
opening to accept a 3/4” conduit hub (Chromalox
CCH-2 or equal).
NEMA 4X rated junction box that provides waterproof cable entry for two (2) cables for a splice or
three (3) cables for a tee.
Installation
Manual
PJ450
PJ451
PJ452
19
Page 20
Table 8 – HL Series Connection Kit Overview
Catalog NumberDescription
HL-PC
Power Connection
Box for Hazardous
Locations
Splice Kit for
Hazardous Locations
Tee Kit for Hazardous
Locations
HL-S
HL-T
Division 1 certified junction box and seal
fitting. The kit is designed to connect selfregulating cables to customer supplied
power wiring. The pipe stand-off and seal
fitting combination provides a water resistant and explosion proof seal. The junction
box has a 3/4" opening with top or side
entry for the power connection.
Division 1 certified junction box and seal
fittings. The kit is designed to splice two
self-regulating cables. The cable entry fitting and seal fitting combination provides a
water-resistant and explosion proof seal.
Division 1 certified junction box and seal
fittings. The kit is designed to splice three
self-regulating cables. The cable entry fitting and seal fitting combination provides a
water-resistant and explosion proof seal.
Installation
Manual
PJ912
PJ920
PJ921
HL-ES
End Seal for
Hazardous Locations
Division 1 certified junction box and seal
fitting. The kit is designed to terminate a
run of self-regulating cable. The pipe
stand-off and seal fitting combination provides a water resistant and explosion proof
seal.
PJ918
20
Page 21
Table 9 – MI Series Connection Kit Overview
Catalog NumberDescription
JB-7-4
MI Cable Power
Connection Kit
JB-7-MB
MI Cable Pipe
Mounting Bracket
SSW-100
Stainless Steel Tie
Wire
SSP-1
Stainless Steel
Spacer Strip
Installation
Manual
NEMA 7 cast aluminum junction box for mineral insulated cable.
N/A
Pipe mounting bracket to be used with the
JB-7-4 power connection kit.
N/A
Stainless steel tie wire, 100ft roll.
N/A
Stainless steel spacer strip with 1” spaced
tabs, 50ft roll.
N/A
HTC
Heat Transfer
Cement
Heat transfer cement available in 1 and 5 gallon pails.
N/A
21
Page 22
Accessories
Table 10 – Accessories Overview
Catalog NumberDescription
180 ft roll of aluminum foil installation tape.
AT- 1
Aluminum Tape
FT-3
Fiberglass Tape
2-mil thickness with high tensile strength;
2-1/2” wide. 200°F (93°C) rating. Minimum
application temperatures 40°F (5°C).
66 ft roll of glass cloth installation tape. 3/8”
wide. 500°F (260°C) rating. Strap at one-foot
intervals. Minimum application temperature
40°F (5°C).
Installation
Manual
N/A
N/A
PS
Stainless Steel Pipe
Straps
CL-1
Caution Labels
SSP-1
Stainless Steel
Spacer Strip
SSW-100
Stainless Steel Tie
Wire
HTC
Heat Transfer
Cement
One (1) pipe strap used to attach kits to pipe.
Available for pipe sizes 1/2” to 3/4”, 1” to
3-1/2”, 2-1/2” to 9”, and 9” to 19.5”.
Pack of five (5) weather resistant electric heat
tracing caution labels.
Stainless steel spacer strip with 1” spaced
tabs, 50ft roll.
Stainless steel tie wire, 100ft roll.
Heat transfer cement available in 1 and 5 gallon pails.
N/A
N/A
N/A
N/A
N/A
22
Page 23
Control Systems
Ambient Sensing
The ambient sensing control systems activate the heating cable when the ambient temperature falls below the thermostat set
point. It is important that these devices are installed above ground at the pipe segment that is subject to the lowest temperatures and fastest wind speeds. The device should be placed out of direct sunlight.
Table 11 – Sensors
Installation
Manual
N/A
Installation
Manual
-
N/A
Table 12 – Thermostats
Catalog NumberDescription
Measures the ambient air temperature to prevent
GIC-AMB
Ambient Heat Trace
Sensor
Catalog NumberDescription
B-100
Freeze Protection
Thermostat
freeze-up of process piping that is carrying products whose temperature must be kept above
freezing. The RTD sensor element is made up
with a Copper sheath and can be installed directly to a controller or junction box using the 1/2”
NPT conduit fitting.
The B100 direct mount thermostats feature liquidfilled thermal assemblies and sense air tempera
tures from 15 to 140°F. The thermostats are epoxy
coated to seal from moisture and contaminants in
compliance with NEMA 4X requirements.
THL
Freeze Protection
Thermostat
TXL
Freeze Protection
Thermostats
Table 13 – Thermostats with Power Connection
Catalog NumberDescription
UAS
Ambient Sensing
Thermostat and
Power Connection
Kit
RTA S
Ambient Sensing
Thermostat and
Power Connection
Kit
The THL direct mount thermostats feature liquidfilled thermal assemblies and sense air temperatures from 15 to 140˚F. The thermostats are
epoxy coated to seal from moisture and contaminants in compliance with NEMA 4X requirements.
The TXL direct mount thermostats feature liquidfilled thermal assemblies and sense air tempera
tures from 15 to 140˚F. The thermostats are epoxy
coated to seal from moisture and contaminants in
compliance with NEMA 4X requirements.
NEMA 4X rated junction box designed to connect
a single cable run to power and control cable out
put via ambient air temperature in non-hazardous
areas. This kit provides water-resistant cable entry
with a 3/4” opening to accept a conduit hub
(CCH-2 or equal). Temperature set point 0° to
225°F (-81°C to 107°C) with 10°F scale divisions.
-
-
NEMA 4X rated junction box with ambient
sens-ing thermostat. Provides temperature
control and termination for one (1) cable. One
(1) addi-tional cable can be connected upon
purchase of additional grommet.
N/A
N/A
Installation
Manual
PJ943
PJ453
RTAS-EP
Ambient Sensing
Thermostat and
Power Connection
Kit
Modified version of the RTAS which utilizes a
hermetically sealed switch. Class I, Division 2
approved.
23
PJ972
Page 24
Line Sensing
The line sensing control systems activate the heating cable when the pipe temperature drops below the desired setpoint. The
sensor must be secured to the pipe with aluminum tape and the insulation must be sealed where the capillary comes through.
The device should be mounted above ground in an area without heavy pedestrian or equipment traffic. To avoid thermal interference with the sensor, it is important that the sensor is installed at 90 degrees from the nearest heating cable or centered
equally between cables if more than one heating cable is used. The sensor should ideally be installed at the end of the circuit
but can be installed at any location that is at least 3 feet away from any heat sinks. See installation detail AD19.
Table 14 – Sensors
Catalog NumberDescription
The RBF sensor measures the surface temperature of process piping that is carrying products
whose temperatures must be controlled to pre-
RBF
Heat Trace or Pipe
Sensor
RBF-HT
RTD Heat
Trace Sensor
vent freeze-up, or to maintain a viscosity level so
that the inner medium will flow. The Thermocouple
or RTD Sensor Element is made up with a 316SS
sheath and has a stainless-steel mounting pad.
The RBF-HT sensor measures the surface temperature of process piping that is carrying products
whose temperature must be controlled. The RTD
sensor element is made up with a 316 SS sheath
and can be installed directly to a controller or junction box using the 1/2” conduit fitting.
Installation
Manual
N/A
N/A
Table 15 – Thermostats
Catalog NumberDescription
The E100 remote mount thermostats utilize a stain-
E-100
Line Sensing
Thermostat
THR
Line Sensing
Thermostat
TXR
Line Sensing
Thermostats
less-steel bulb and capillary design to accurately
sense temperature at key points along a pipe. The
thermostats are epoxy coated to seal from moisture
and contaminants in compliance with NEMA 4X
requirements.
The THR remote mount thermostats utilize a stainless-steel bulb and capillary design to accurately
sense temperature at key points along a pipe. The
thermostats are epoxy coated to seal from moisture
and contaminants in compliance with NEMA 4X
requirements.
The TXR remote mount thermostats utilize a stainless-steel bulb and capillary design to accurately
sense temperature at key points along a pipe. The
thermostats are epoxy coated to seal from moisture
and contaminants in compliance with NEMA 4X
requirements.
Installation
Manual
N/A
N/A
N/A
24
Page 25
Table 16 – Thermostats with Power Connection
Catalog NumberDescription
NEMA 4X rated junction box designed to connect a
UBC
Line Sensing
Thermostat and
Power Connection
Kit
RTBC
Line Sensing
Thermostat and
Power Connection
Kit
single cable run to power and control cable output
via pipe temperature in non-hazardous areas. This
kit provides water-resistant cable entry with a 3/4”
opening to accept a conduit hub (CCH-2 or equal).
Temperature set point 0° to 400°F (-81°C to 200°C)
with 10°F scale divisions.
NEMA 4X rated junction box with line sensing thermostat; 8” stainless steel capillary. Provides temperature control and termination for one (1) cable.
Modified version of the RTBC which utilizes a
RTBC-EP
Line Sensing
hermetically sealed switch. Class I, Division 2
approved.
Thermostat and
Power Connection
Kit
Installation
Manual
PJ942
PJ454
PJ973
25
Page 26
Table 17 – Controllers
Catalog NumberDescription
Microprocessor-based system with SSR power
control, full monitoring, and alarms. Single or
ITC1 & ITC2
Digital Heat Trace
dual point control. NEMA 4X Fiberglass and
stainless steel options available.
Controller
1 & 2 Circuits
Installation
Manual
PK509
ITAS 2-48
ITLS 2-48
Heat Tracing
Control Panel
ITASC1D2 2-48
ITLSC1D2 2-48
Heat Tracing
Control Panel
FPAS(M)
Freeze Protection
Ambient Sensing
(Monitoring) Series
FPLS(M)
Freeze Protection
Line Sensing
(Monitoring) Series
Microprocessor-based control/monitoring and
power management system for ambient sensing,
line sensing or a combination of both. Capacity
of 2-48 circuits but can be increased to 72 circuits with extension panels, ITAS-EXT 2-48 and
ITLS-EXT 2-48. User-friendly touch screen HMI.
NEMA 4/4X options available.
Microprocessor-based control/monitoring and
power management system for ambient sensing,
line sensing or a combination of both. Capacity
of 2-48 circuits but can be increased to 72 circuits with extension panels, ITASC1D2-EXT 2-48
and ITLSC1D2-EXT 2-48. User-friendly touch
screen HMI. NEMA 4/4X options available.
The FPAS series controls multiple heat trace circuits via an ambient sensing external thermostat,
external electronic controller or via an ambient
sensing, door mounted 6040 DIN controller.
Chromalox recommended controllers include:
RTAS, RTAS-EP, B100, E100 or the 6040 DIN
controller. NEMA 4/4X options available.
The FPLS series controls each heat trace line
with individual Chromalox RTBC, RTBC-EP,
E-100 or E121 line sensing controls. Each circuit
should be controlled by an individual sensor/
controller. Depending on the application, controllers can switch more than one circuit. NEMA
4/4X options available.
PK497
PK497
PK557
PK557
RSP
IntelliTrace Remote
Sensor Panel
DTS-HAZ
Heat Trace Digital
Thermostat
NEMA 4 Painted Steel, NEMA 4X Fiberglass or
NEMA 4X 305SS enclosure. Fully integrated
package that consolidates up to 252 temperature
sensor signals in a single enclosure. Works
seamlessly with the Chromalox IntelliTrace ITLS/
ITAS heat trace control panels.
The DTS-HAZ digital thermostat is a NEMA 4X
rated power connection kit and microprocessorbased temperature control. It is used for freeze
protection or process temperature maintenance
of pipes or tanks protected by heat tracing products.
*Not a standard offering.
**Not included in standard offering and only available for single circuit use.
120-
480
27
Page 28
Thermal Insulation
An installed heating circuit should be thermally insulated immediately to provide protection from damage from ongoing
work. Things to remember about insulating:
• Insulate the equipment being heat traced as soon as possible after the heating cable is installed. This will protect
the cable from possible physical damage.
• The type and thickness of thermal insulation specified on
the design drawing must be used. If you use another type
or thickness, the heater cable type or amount may have
to be changed.
• Never install wet insulation. Both the piping and the insulation must be dry when thermally insulating a circuit. Wet
insulation may cause start-up or operational problems.
• Properly weatherproof the thermal insulation. All places
where valve stems, conduits, pipe supports, connection
housing, thermal capillary tubes, etc. extend outside the
insulation jacketing must be sealed with a suitable compound to keep water out.
• Insulate valves fully up to, and including, the packing
gland.
• Heat trace and fully insulate the face of all non-diaphragm
pressure instruments.
Commission Testing
• Insulation must be covered by a weatherproof barrier,
such as an aluminum jacket.
• If you are using metal jacketing and sheet metal screws,
be sure the screws are not long enough to penetrate the
thermal insulation and damage the heater cable.
• Again, perform the megger test on the circuit immediately
after the thermal insulation is installed to detect if any mechanical damage may have occurred.
• When the insulation and the weatherproofing is complete,
attach “Electric Traced” labels on the outside of the insulation. These should be installed where they are visible from normal operations, usually on alternating sides
about every 10 feet. It is also useful to mark the location
of any connections buried under the insulation.
Additional requirements for rigid thermal insulations:
• In the standard single heater cable installation, rigid insulations do not need to be oversized. However, they should
be carved so there is no gap in the insulation.
• In case of redundant or multiple heater cables, rigid insulations which are 0.500 inches oversized should be used.
1. Again, visually inspect the piping, insulation, and connections for the heater cable to make sure no physical damage has occurred since the installation and start-up.
2. Megger the system again to determine if damage not
readily visible has occurred.
3. Turn all branch circuit breakers to the OFF position.
For systems controlled by ambient
sensing thermostats:
1. If the actual ambient temperature is higher than the desired thermostat setting, turn the thermostat setting up
high enough to turn the system ON or (some models) turn
the selector switch to the ON position.
2. Turn the main circuit breaker ON.
3. Turn the branch breakers ON one-by-one until all are on.
4. Allow system to run at least four hours in order to let all
pipes reach steady-state.
5. Measure the amperage draw, ambient temperature and
pipe temperature for each circuit and record in the installation log. This information may be needed for future
maintenance and troubleshooting.
6. When the system is completely checked out, reset the
thermostat to the proper temperature.
For systems controlled by line sensing thermostats:
1. Set the thermostat to the desired control temperature.
2. Turn the main circuit breaker ON.
3. Turn ON the branch circuit breakers controlled by the
thermostat.
4. Allow the pipe temperatures to be raised to the control
point. This may take up to four hours for most circuits
(large full pipes may take longer).
5. Measure the amperage draw, ambient temperature, and
pipe temperature for each circuit and record in the installation log. This information may be needed for future
maintenance and troubleshooting
For redundant systems:
Follow the procedure above for the type of control system
you have, but commission the systems one at a time. Start
up the primary system, qualify it and shut it down. Then start
up the backup system, qualify it and shut it down
28
Page 29
Specifications
Table 19 – CWM Cable Maximum Maintenance Temperatures
NR = Not Required. Maximum circuit length has been reached in a smaller breaker size.
Note — Thermal magnetic circuit breakers are recommended since magnetic circuit breakers could “nuisance trip” at low temperature.
NR = Not Required. Maximum circuit length has been reached in a smaller breaker size.
Note — Thermal magnetic circuit breakers are recommended since magnetic circuit breakers could “nuisance trip” at low temperature.
Reinstall thermostat on an appropriate pipe segment. Ensure thermocouple is fully contacting the
pipe.
Remove damaged or wet insulation and install
new, dry insulation. Ensure new insulation is
weatherproofed.
Additional heating cable can be added, as long
as the proper connection kits are used, and the
new heating cable length does not exceed the
maximum circuit length.
Contact a Chromalox representative and modify
design as needed.
Apply voltage as specied. Check/repair electrical
supply lines.
Replace damaged cable. Check pipe temperature
and cable power output.
Ensure length and heat trace path matches drawings.
Connect all splices and tees as per design speci-
cations.
Rewire to “Normally Closed” position
Lower pipe temperature if possible. Ensure
correct heater selection and design. Contact a
Chromalox representative and modify design if
pipe temperature cannot be reduced.
Apply voltage as specied. Check/repair electrical
supply lines.
Replace damaged cable using the proper splice
connection kits.
Ensure all connection kits are installed properly
and inspect them for damage. Replace if necessary.
For uninsulated heating cable: Check the heating
cable for damage, especially around heat sinks.
Replace damaged cable using the proper connection kits.
For insulated heating cable: Check the heating
cable for damage piecewise at each connection
kit to determine the damaged segment.
The Locating Faults section on page 30 can be
used to estimate fault location.
Excessive moisture on heating cable core or bus
wires: Replace cable.
Moisture on connection kits: Retest after drying
out all components. Ensure all conduit entries are
properly sealed during reinstallation.
Pipe temperature is too
low
Power output is too low
Insulation resistance is low
or inconsistent
Incorrect installation of thermostat/thermocouple
Damaged, missing, or wet insulation
Improper installation of heating cable on
heat sinks
Error in thermal design
Incorrect voltage applied
Damaged heating cable
Incorrect circuit length due to uninstalled
connections (splice/tee) or severed heating cable
High-resistant connection due to improper installation of connection kits
Thermostat is wired in “Normally Open”
position
The pipe temperature is too high
Incorrect voltage applied
Damaged heating cable
Shorted circuit
Moisture
Pipe temperature is too highRetest at ambient conditions
Test leads are in contact with junction box Retest after moving test leads
Undersized circuit breakerCheck design to ensure startup temperature,
Startup temperature is too lowStart up when temperature is higher than -76˚F
Damaged heating cableReplace damaged cable using the proper con-
Bus wires touching and shorting outCheck for proper termination at end seal. Note
MoistureExcessive moisture on heating cable core or bus
Undersized GFPD
current loads, and maximum circuit length are not
exceeded, and that the power wire size is compatible with the circuit breaker. Replace circuit
breaker if necessary.
(-60˚C).
nection kits.
that the heating cable could be permanently damaged and may need to be replaced.
wires: Replace cable.
Moisture on connection kits: Retest after drying
out all components. Ensure all conduit entries are
properly sealed during reinstallation.
Replace with appropriately sized GFPD.
Test Procedures
wire. To determine a low resistance ground fault, the resistance reading is taken between the bus wires and the braid
When testing any Chromalox heat trace product, always utilize the proper protective equipment and be
sure to comply with all applicable safety guidelines.
Before testing any Chromalox heat trace products,
ensure that all test equipment is working as intended and has been properly calibrated.
Only trained and qualified personnel should administer the test.
Locating Faults
The three most common test methods for finding the approximate location of a fault in a heating cable are:
• Ratio test
• Conductance test
• Capacitance test
with one lead on bus wire and one on the braid.
Example: There is a bus wire short at an unknown point on
a 100ft cable. The resistance reading between the bus wires
is 6Ω from the front end of the cable and 14Ω from the back
end.
The bus wire short is approximated to be 30ft (30% of 100ft)
from the front end of the cable.
Conductance Test
The conductance test can be used to find the fault location
of a severed heating cable. A standard ohmmeter is used to
take resistance readings between the bus wires from both
the front (F) and back (B) end of the cable. The fault location
(L) as a percentage of cable length measured from the front
end can be approximated by:
Ratio Test
The ratio test can be used to approximate the fault location
of a bus wire short or a fault from bus wire to ground braid. A
standard ohmmeter is used to take resistance readings from
both the front (F) and back (B) end of the cable. The fault location (L) as a percentage of cable length measured from the
front end can be approximated by:
To determine a bus wire short, the resistance reading is taken
between the bus wires with one lead placed on each bus
Example: A 100 ft long heating cable is severed at an unknown point. The bus-to-bus resistant reading is 10.0Ω from
the front end and 2.5Ω from the back end.
The cable is estimated to be severed at around 20ft (20% of
100ft) from the front of the cable.
32
Page 33
Capacitance Test
The capacitance test can be used to estimate the length of
an intact heating cable or the fault location of a severed cable
that has passed the insulation resistance testing. A capacitance reading is taken between the bus wires and the braid at
the end with the power connection. The bus wires should be
twisted together and connected to the positive lead, and the
braid should be connected to the negative lead. The fault location can be found by multiplying the recorded capacitance
with the capacitance factor found in Table 25.
Table 27 – Capacitance Factors
Example: A heating cable with a capacitance factor of 7 ft/
nF is severed at an unknown point. The capacitance reading
between the bus wires and the braid is 12 nF.
The cable is estimated to be severed at around 84ft from the
power connection.
Part
NumberDescription
Capacitance Factor
(ft/nF)
SRL3-1CR/CT3 W / FT @ 50˚F - 120V5.5
SRL3-2CR/CT3 W / FT @ 50˚F - 208-277V5.9
SRL5-1CR/CT5 W / FT @50˚F - 120V6.0
SRL5-2CR/CT5 W / FT @ 50˚F - 208-277V5.4
SRL8-1CR/CT8 W / FT @ 50˚F - 120V5.5
SRL8-2CR/CT8 W / FT @ 50˚F - 208-277V5.5
SRL10-1CR/CT10 W / FT @ 50˚F - 120V5.1
SRL10-2CR/CT10 W / FT @ 50˚F - 208-277V5.3
SRM/E5-1CT5 W / FT @50˚F - 120V7.5
SRM/E5-2CT5 W / FT @ 50˚F - 208-277V7.2
SRM/E8-1CT8 W / FT @ 50˚F - 120V7.5
SRM/E8-2CT8 W / FT @ 50˚F - 208-277V7.6
SRM/E10-1CT10 W / FT @ 50˚F - 120V7.4
SRM/E10-2CT10 W / FT @ 50˚F - 208-277V7.4
SRM/E15-1CT15 W / FT @ 50˚F - 120V7.9
SRM/E15-2CT15 W / FT @ 50˚F - 208-277V7.5
SRM/E20-1CT20W / FT @ 50˚F - 120V7.5
SRM/E20-2CT20 W / FT @ 50˚F - 208-277V7.2
33
Page 34
Insulation Resistance (Megger) Test
The insulation resistance test detects potential damage that
could result in the cable shorting out. A megohmmeter is used
to measure the insulation resistance between the conductive
core and the grounding braid, and the reading is compared
to the allowable minimum resistance reading (See Table 4).
The megohmmeter should be a minimum of 1000 Vdc, but
the use of 2500 Vdc is preferred. If possible, the meter should
be battery-operated, though digital or analog meters can also
be used.
1. De-energize the circuit.
2. Open the cover on the power termination kit.
3. Disconnect the bus wires and braid from the terminals.
4. Set the test voltage to 0 Vdc.
5. Connect the negative lead to the ground braid and the
positive lead to the bus wires.
6. Turn on the megohmmeter and perform insulation resistance test for one minute, until the needle on the meter
stops moving.
7. Check the reading and ensure it is above the allowable
minimum resistance reading.
8. Record the tested value in the log.
9. Turn off the megohmmeter and discharge it with an appropriate grounding rod (if the meter does not self-discharge).
10. Reconnect the wires and close the power termination kit.
5. Energize the circuit.
6. Allow the circuit to run for at least 20 minutes.
7. Take the current reading and record in the log.
8. De-energize the circuit.
9. Disconnect and turn off the meter.
10. Reconnect the bus wires and close the termination kit.
To determine the thermal output, complete the calculation
below:
Thermal output = (Current Reading / Circuit Length) x Voltage
Compare the result to the charted output temperature in the
“Chromalox Design Guide for Heat Tracing Products”.
For additional information about this test, please watch the
“Stabilized Current Test” video in the Chromalox video library:
This test determines the voltage at the end of the line, which
verifies the proper voltage. To perform the test, a standard
multimeter with auto-range up to 600V is required. If possible, the meter should be battery-operated, though digital or
analog meters can also be used.
For additional information about this test, please watch the
“Heat Trace Megger Testing Procedure” video in the Chromalox video library:
The stabilized current test determines the cable current at
full voltage. It ensures that the cable power output is correct
for design and that it is stable. To perform this test, a standard multimeter with an Amp clamp or an all-in-one unit is
required. Ensure the meter has an auto-range up to 100A. If
possible, the meter should be battery-operated, though digital or analog meters can also be used.
1. De-energize the circuit.
2. Open the cover on the power termination kit.
3. Disconnect the bus wires from the terminals.
4. Clamp the meter onto one bus wire.
Maintenance
Recommended maintenance for Chromalox heat tracing systems consists of performing the steps involved in the commission testing on a regular basis. For those systems controlled by line sensing thermostats, Chromalox recommends
checking the system at least twice per year. Systems controlled by an ambient-sensing thermostat should be checked
when the season requiring their use is approaching.
1. De-energize the circuit.
2. Remove the end cap.
3. Expose the bus wires.
4. Connect one test lead to each bus wire and energize the
circuit
5. Read the resulting voltage and compare it to the desired
value.
6. Record the reading in the test log.
7. De-energize the circuit.
8. Disconnect and turn off the multimeter.
9. Reconnect the end cap.
For additional information about this test, please watch the
“End of Current Voltage Test” video in the Chromalox video
library:
Repair or replace all damaged heater cable, connections,
thermal insulation and weatherproofing using only Chromalox connections and methods before testing the system.
Record all repairs made and measurements taken in the installation and maintenance log.
34
Page 35
Installation and Maintenance Log
Reference Information
Circuit Number
Circuit Breaker Number
Drawing Number
Circuit Length
Heat Tracing Visual Checks
No Signs of Moisture, Corrosion
or Damage
Proper Electrical Connection
Proper Grounding of the Braid
Heat Tracing Electrical Checks
Megger Test (500 VDC)
(Bypass Controls)
Amperage Draw Test
Compare to design Amperage
Draw
Voltage at end of Circuit*
Accessories/Control Checks
Temperature Control Properly Set
Initial
Date
Initial
Date
Initial
Date
Meg Ohms
Date
Amperage
Amp. Temp
Date
Voltage
Date
Setpoint
Date
Sensors Protected and
Undamaged
All Enclosures and Kits Closed
and Sealed
Thermal Insulation Checks
Location of Kits Visible on Outside
of Insulation
Insulation is Complete, Dry and
Weatherproof
* This test must be performed at installation or at any time the cable is cut or damaged in any way.
Initial
Date
Initial
Date
Initial
Date
Initial
Date
35
Page 36
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at