Chromalox CVEP-C User Manual

Chromalox
®
DIVISION 4 SECTION
CVEP
SALES
DATE
SERVICE REFERENCE
Installation, Operation
and
RENEWAL PARTS IDENTIFICATION
PF457-8
JUNE, 2010
(Supersedes PF457-7)
161-302639-001
GENERAL
INSTALLATION
NOTICE: Carefully remove heater from carton and check for shipping damage. Any damage claims should be entered immediately with the carrier.
Type CVEP Convection Heaters are designed for use in Class I, Div I hazardous environments. Units without control options are suitable for areas classified as Groups B, C & D. Units with built-in controls can be supplied for groups C and D or B, C and D. Refer to classification stamped on heater nameplate.
FIRE/EXPLOSION HAZARD.
To prevent ignition of haz­ardous atmospheres, this heater should not be installed in areas where vapors or gases having an ignition tempera­ture less than 280˚C (536˚F)(T2A) at 1.8kW, 3.6kW, 4.5kW,
7.6kW, 9.0kW or 180˚C (356˚F)(T3A) at 1.6kW, 3.2kW,
4.0kW are present. These heaters must not be operated in ambient tempera­tures exceeding 40˚C (104˚F).
1.
Connect air heaters to the same line voltage as on heater nameplate.
2. Heaters can be mounted individually end to end.
3. Heaters can be mounted directly on any type of surface masonry,
concrete, block, plastered walls, metal framework, etc.-using appropriate hardware.
4. All controls such as thermostat and contactor, when required must
have the same explosion-proof rating as heater.
5. Do not install one unit above the other.
6. Units are mounted a minimum of 8” above the floor.
7. Heaters are mounted on wall in a horizontal position with termi- nal end at right. Never recess heater into wall.
8. NOTE: Article 500 of the National Electric Code (NEC) out-
lines requirements for installation of electrical equipment in haz­ardous (Classified) locations.
9. All unit electrical installation fittings, conduit, wiring and seals must meet NEC and local codes for hazardous locations. External line fusing or circuit breaker protection is required.
10. Failure to understand and follow these installation instructions and the “WARNING” notes contained therein may result in severe personal injury, death or substantial property damage.
ELECTRIC SHOCK HAZARD. Any installation involving electric heaters must be performed by a qualified person and must be effectively grounded in accordance with the National Electrical Code to eliminate shock hazard.
ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could result in personal injury or property damage. Heater must be installed by a qualified person in accor­dance with the National Electrical Code, NFPA 70.
1. Remove front panel by removing screws.
2. Locate desired heater position on wall.
3. Locate mounting holes for rear panel. Rear panel must be a mini-
mum of 8” from the floor.
4. Refer to Figure 1A, 1B or 1C for mounting hole layout for each
cabinet size.
5. Drill a pilot hole in wall mounting surface at each mounting hole location. Use a convenient small size drill.
6. Drill the mounting holes in accordance with size in Table 1. Insert anchors where applicable.
7. Fasten rear panel to wall with screws noted in Table 1.
8. Replace front panel and screws.
FIRE HAZARD. Never operate heater with front panel off. Adequate air flow across heating elements requires the front panel to be in place. The heating elements could overheat causing equipment damage or personal injury.
Type CVEP-C
Convection Air Heater for Hazardous Locations
© 2010 Chromalox, Inc.
kW A B C D
1.6
1.8 34 20 7
3.6
3.2 58 32 16 13
7.6
4.0
4.5 70 48 24 11
9.0
10
INSTALLATION
Dimensions (In.)
CVEP MODELS WITHOUT CONTROLS — GROUPS B, C AND D
Dimensions (In.)
CVEP MODELS WITH BUILT-IN CONTROLS — GROUPS B, C AND D
Dimensions (In.)
CVEP MODELS WITH THERMOSTAT ONLY — GROUPS C AND D
2
Type of Mounting ** Accessory Screw Size to Fit
Surface Hardware Screw Type Drill Size and Type Mtg Hole Size
Concrete Block
Ackerman Rd. Hd. Mach. Steel 1/2” Masonry † 1/4” x 20 x.............lg
Masonry
Lead Anchor
Rd. Hd. Mach Steel or Pan Hd.
5/16” Masonry † # 1/4” x .................lg
Metal (Self Tapping)
Wood Studs — — Wood or Metal (Self Tapping) — — † # 1/4” x .................lg
Plaster wall Hollow or
— — Toggle Bolt #7 Twist † # 1/4” x .................lg
Similar Type
* Metal Beam, Nuts
Rd. Hd. Mach. Steel #7 Twist † 1/4” x 20 x.............lg
Channel, etc. Washers
Table 1 — Suggested Heater Mounting Screws — Types and Sizes
*If clearance permits use washer, lockwasher and nut; otherwise drill and tap to these lengths add thickness of beam, washers, nut, etc. **If mounting structure permits. Except plastered hollow walls explosive type anchors can be used. Suggested size noted in Table and/or sketches be used to determine size of anchors. †Select overall length of screw to provide a minimum penetration of 1 inch into base wall material.
1/2
7/8
5/16
Mounting Hole
Detail “A”
Figure 1A
Figure 1B
Figure 1C
kW A B C D
1.6
1.8 34 20 7
3.6
3.2 58 32 16 13
7.6
4.0
4.5 70 48 24 11
9.0
10
kW A B C D
1.6
1.8 34 20 7
3.6
3.2 58 32 16 13
7.6
4.0
4.5 70 48 24 11
9.0
10
7/8
3/4" Conduit Entrance
7
D
See Detail "A"
8-15/16
D
C
C
B
19
20-1/16
A
2-3/8
5-1/16
3-3/8
1" Conduit Entrance
8-7/8
D
See Detail "A"
C
C
D
19
20-1/16
8-15/16
A
B
Feet are Optional Primarily Used to Protect Thermowell During Shipping and Installation
3/4" Conduit Entrance
7
D
See Detai "A"
C
C
D
19
20-1/16
8-15/16
5-1/16
3-3/8
A
2-3/8
WIRING
ELECTRIC SHOCK HAZARD. Any installation involving electric heaters must be performed by a qualified person and must be effectively grounded in accordance with the National Electrical Code to eliminate shock hazard.
1. All wiring should be done in accordance with local codes and
the National Electrical Code by a qualified person as defined in the NEC.
CAUTION: Use copper conductors only.
2. Rough-in-line-wiring to unit in manner approved for hazardous
locations. (See warning below.)
3.
Wire per diagrams 1 through 6 based on the rating and control options listed in table 2. Refer to table 3 for amperage specifications.
4. Remove cover of conduit box for connections. Use either opening
and plug the other with the plug provided.
5. In single phase units the heaters must be wired in parallel, com-
bining L1 to L1, L2 to L2 and for 3 phase unit, L3 to L3.
6. Re-assemble cover with a minimum of 7 turns.
FIRE/EXPLOSION HAZARD.
(Group B atmospheres) To prevent ignition of Group B atmospheres, conduit runs must not exceed 3/4” in size and all conduit runs 1/2” size and larger must have a sealing fitting connected within 2”, 6” or 18” of the terminal enclo­sure depending on the exact model. For correct placement, refer to data located on the enclosure label.
OPERATION
The system designer is responsible for the safety of this equipment and should install adequate back-up controls and safety devices with their electric heating equipment. Where the conse­quences of failure could result in personal injury or
property damage, back-up controls are essential.
1. Do not operate heater at voltages in excess of that stamped on
the heater since excess voltage will shorten heater life and cause high element temperatures which may exceed allowable temperatures of operation in a hazardous atmosphere.
3
Elements
Optional Thermostat
Built-In or Ext. Supplied
Single Phase — No Controls, 120-277V
& Heater Amps < 22A
Diagram 1
Diagram 3
Diagram 5
Diagram 2
Diagram 4
Diagram 6
Elements
Optional Thermostat Built-In or Ext. Supplied
Single Phase — No Controls, Volts > 277V & 120–277V When Heater Amps > 22A
External
Contactor
Control Voltage
Elements
Optional Thermostat Built-In or Ext. Supplied
External
Contactor
Control Voltage
Three Phase – No Controls
Optional Thermostat Built-In or Ext. Supplied
Contactor
Transformer
Element Wiring 1 PH or 3 PH Single or Double Element
Single or Three Phase With Controls — Contactor & Transformer
Optional Thermostat Built-In or Ext. Supplied
Contactor
Line Voltage Control Voltage
Element Wiring 1 PH or 3 PH Single or Double Element
Single or Three Phase With Controls — Contactor & Line Voltage Control
Optional Thermostat Built-In or Ext. Supplied
Contactor
Element Wiring 1 PH or 3 PH Single or Double Element
Single or Three Phase With Controls — Contactor & External Supplied Control Voltage
Terminal
Block
External Supplied Control Voltage
Loading...
+ 5 hidden pages