4. WIRING - LOAD, LINE, INPUT SIGNAL AND OPTIONAL ALARM
5. SPECIFICATIONS
General
Category of use: ...................................................................................AC51, AC53a
Switching Mode: ......................................................................................Zero Cross
Input/Output Isolation Voltage: ........................................................ 4,000 VAC RMS
Operational Voltage Range
• 480 VAC models: ............................................................................ 24 - 530 VAC
• 600 VAC models: ............................................................................ 24 - 660 VAC
Nominal Frequency: .................................................................................50 - 60 Hz
Non-repetitive peak voltage
• 480 VAC models: .................................................................................... 1200 Vp
• 600 VAC models: .................................................................................... 1200 Vp
Zero Voltage Turn-on: ..................................................................................... ≤ 20V
Activation time: ...........................................................................................1/2 cycle
Deactivation time: .......................................................................................1/2 cycle
Potential drop at rated current: ............................................................... < 1.4 Vrms
Power factor: ........................................................................................................... 1
Protection: ........................................................................................................ IP20
Inputs
VDC Input (Type “1”)
Control voltage: ....................................................................................... 5 - 32 VDC
Maximum input: .................................................< 18 mA @5 VDC to 22 mA @ 32 V
Maximum reverse voltage: ...........................................................................36 VDC
Activation voltage: .....................................................................................> 4.5 VDC
Deactivation voltage: ...........................................................................< 3 VDC VAC
Input (Type “2”)
Control voltage: .............................................................................20 - 260 VAC/DC
Activation voltage: ................................................................................> 15 VAC/DC
Deactivation voltage: ..............................................................................< 6 VAC/DC
Current draw: ................................................................≤ 8 mAac/dc @ 260 VAC/DC
Integrated Thermal Protection
The SSR temperature is constantly monitored. If the maximum temperature limit
(230°F/110°C) is exceeded, current to the load is interrupted and the YELLOW
over-temperature condition LED illuminates.
Alarm Output Option
The Alarm Output is a solid state switch which actuates a wired device during an
alarm event, such as a horn or light. This output alarm requires an external 24 VAC/
DC power supply.
Alarm Output Ratings: Imax ........................................................................ 150 mA
Vmax .................................................................32 VAC/DC
Z close (impedance) ................................................ < 15 Ω
For Models with 24 VDC Input Control Signal
The alarm output function closes the isolated solid state output switch when it
detects the following fault condition:
The control signal is active, but:
• The internal temperature limit of the SSR has been exceeded (Code 1)
For Models with 20 - 260 VAC/DC Input Control Signal
The alarm output function closes the isolated solid state output switch when it
detects any of the following fault conditions:
The control signal is active, but:
• The internal temperature limit of the SSR has been exceeded (Code 1)
• There is no current on the load (Alarm Option Code 2)
• There is no line voltage power supply (Alarm Option Code 2)
Environment Conditions
Operating Temperature Range: .............................................................-20˚C to 80˚C
Max. Relative Humidity: ..........................................................................50% @ 40˚C
Max. Installation Altitude: ...................................................... 2000m above sea level
Pollution Level: ..........................................................................................................2
Storage Temperature: ............................................................................-20˚C to 85˚C
Junction Temperature: .......................................................................................125˚C
This device conforms to ECC 2004/108/CE and 2006/95/CE and subsequent
modifications including with reference to product standard EN 60947-4-3 (Lowvoltage switchgear and control gear – AC contactors and semiconductor motor
starters). The product is designed for type A environments. Use of the product in
type B environments may cause undesired electromagnetic noise. In this case, the
user should take appropriate steps for improvement.
PK528
0037-75554
July 2015
© 2015 Chromalox, Inc.
RR
R
R
RR
F1 F2 F3
5-32 VDC
Control
Signal
Output
RRR
LOAD LOAD
Optional Over Temperature
Alarm Output Feature
1/L1 3/L2 5/L3
AC51: 40A
AC53a: 8A
CS3-04060-221
On
135 A1+
246 A2-
B1
B2
A1
A2
2/T1 4/T2 6/T3
20-260
VAC/VDC
600 VAC
50/60 Hz
fan: 230 VAC
nc
nc
Out
AI
Outputs
Specification CS3-025 CS3-040 CS3-055
Rated Current (@ 40˚C continuous service)
AC51 AC53 AC51 AC53 AC51 AC53
3 X 25A 3 X 5A 3 X 40A 3 X 8A 3 X 55A 3 X 15A
Maximum Surge Current (t=20 ms) 400 A 600 A 1,150 A
Maximum I
2
t for fusing (blowout) 645 A2s
1,010 A2s 6,600 A2s
Critical dV/dt Off-state (minimum)
1,000 V/μs
Off-state Leakage Current (@ Rated Voltage)
< 3 mA
CS3-025, CS3-040 & CS-055 Derating Curves
Rated Current versus Ambient Temperature
Note: Models as tested with approved heat sinks and
fans, if applicable.
25
40
55
0
20
40
60
04