Chromalox CAF-12, CCAS-12 User Manual

(Supersedes PF423-1)
PF493-1
CAF-12 CCAS-12
161-506171-001
JULY, 2002
4
and
MAINTENANCE
(Supersedes PF493)
Architectural Convection Heaters
Type CAF-12 and CCAS-12
© 2010 Chromalox, Inc.
TABLE 1Specifications
CAF-12 CCAS-12
Dimensions (In.)
ModelModel VoltsPhase WattsAmps BTUH Height Length Depth Weight (Lbs.)
CAF-12F211 CCAS-12F211 208 1 1125 5.4 3,838 12 24.3 5.75 19 CAF-12F211 CCAS-12F211 208 3 1125 3.1 3,838 12 24.3 5.75 19 CAF-12F211 CCAS-12F211 240 1 1125 4.7 3,838 12 24.3 5.75 19 CAF-12F211 CCAS-12F211 277 1 1125 4.1 3,838 12 24.3 5.75 19 CAF-12F215 CCAS-12F215 208 1 1500 7.2 5,118 12 24.3 5.75 19 CAF-12F215 CCAS-12F215 208 3 1500 4.2 5,118 12 24.3 5.75 19 CAF-12F215 CCAS-12F215 240 1 1500 6.3 5,118 12 24.3 5.75 19 CAF-12F215 CCAS-12F215 277 1 1500 5.4 5,118 12 24.3 5.75 19 CAF-12F215 CCAS-12F215 480 3 1500 1.8 5,118 12 24.3 5.75 19 CAF-12F316 CCAS-12F316 208 1 1687 8.1 5,756 12 36.3 5.75 24 CAF-12F316 CCAS-12F316 208 3 1687 4.7 5,756 12 36.3 5.75 24 CAF-12F316 CCAS-12F316 240 1 1687 7 5,756 12 36.3 5.75 24 CAF-12F316 CCAS-12F316 277 1 1687 6.1 5,756 12 36.3 5.75 24 CAF-12F316 CCAS-12F316 480 3 1687 2 5,756 12 36.3 5.75 24 CAF-12F422 CCAS-12F422 208 1 2250 10.8 7,677 12 48.3 5.75 29 CAF-12F422 CCAS-12F422 208 3 2250 6.3 7,677 12 48.3 5.75 29 CAF-12F422 CCAS-12F422 240 1 2250 9.3 7,677 12 48.3 5.75 29 CAF-12F422 CCAS-12F422 277 1 2250 8.1 7,677 12 48.3 5.75 29 CAF-12F422 CCAS-12F422 480 3 2250 2.7 7,677 12 48.3 5.75 29 CAF-12F430 CCAS-12F430 208 1 3000 14.4 10,236 12 48.3 5.75 29 CAF-12F430 CCAS-12F430 208 3 3000 8.3 10,236 12 48.3 5.75 29 CAF-12F430 CCAS-12F430 240 1 3000 12.5 10,236 12 48.3 5.75 29 CAF-12F430 CCAS-12F430 277 1 3000 10.8 10,236 12 48.3 5.75 29 CAF-12F430 CCAS-12F430 480 3 3000 3.6 10,236 12 48.3 5.75 29 CAF-12F633 CCAS-12F633 208 1 3375 16.2 11,515 12 72.3 5.75 39 CAF-12F633 CCAS-12F633 208 3 3375 9.4 11,515 12 72.3 5.75 39 CAF-12F633 CCAS-12F633 240 1 3375 14.1 11,515 12 72.3 5.75 39 CAF-12F633 CCAS-12F633 277 1 3375 12.2 11,515 12 72.3 5.75 39 CAF-12F633 CCAS-12F633 480 3 3375 4.1 11,515 12 72.3 5.75 39 CAF-12F645 CCAS-12F645 208 1 4500 21.6 15,354 12 72.3 5.75 39 CAF-12F645 CCAS-12F645 208 3 4500 12.5 15,354 12 72.3 5.75 39 CAF-12F645 CCAS-12F645 240 1 4500 18.8 15,354 12 72.3 5.75 39 CAF-12F645 CCAS-12F645 277 1 4500 16.2 15,354 12 72.3 5.75 39 CAF-12F645 CCAS-12F645 480 3 4500 5.4 15,354 12 72.3 5.75 39 CAF-12F845 CCAS-12F845 208 1 4500 21.6 15,354 12 96.3 5.75 49 CAF-12F845 CCAS-12F845 208 3 4500 12.5 15,354 12 96.3 5.75 49 CAF-12F845 CCAS-12F845 240 1 4500 18.8 15,354 12 96.3 5.75 49 CAF-12F845 CCAS-12F845 277 1 4500 16.2 15,354 12 96.3 5.75 49 CAF-12F845 CCAS-12F845 480 3 4500 5.4 15,354 12 96.3 5.75 49 CAF-12F860 CCAS-12F860 208 1 6000 28.8 20,472 12 96.3 5.75 49 CAF-12F860 CCAS-12F860 208 3 6000 16.7 20,472 12 96.3 5.75 49 CAF-12F860 CCAS-12F860 240 1 6000 25 20,472 12 96.3 5.75 49 CAF-12F860 CCAS-12F860 277 1 6000 21.7 20,472 12 96.3 5.75 49 CAF-12F860 CCAS-12F860 480 3 6000 7.2 20,472 12 96.3 5.75 49
MODEL NUMBER DESCRIPTION
This document explains the correct procedure for the installa­tion and safe operation of all models of Draft Barrier and Pedestal Mounted Heaters.
Draft Barrier Heating Systems are designed to be installed in accordance with the National Electrical Code and with local codes by a qualified person.
General Information —
Draft Barriers and Pedestal Mounted Heaters are intended for wall, sill or floor mounting.
The heaters are designed so that they may be used as an indi­vidual cabinet convector, in a wall-to-wall configuration or as an end-to-end continuous perimeter room heating system.
Draft Barrier heating systems are supported by a wide selec­tion of controls and accessories designed to solve any heating requirement.
Before You Unpack —
1. Make certain that the number of cartons received agrees with
the Bill of Lading, Packing List and original order. Also check
that the correct style (Model) and color have been shipped.
2. Every heater is carefully inspected and shipped with a clear
Bill of Lading.
Obvious external and/or concealed damage must be reported to
the carrier for remedy.
WARNING: — Hazard of Fire
1. DO NOT INSTALL HEATERS AGAINST ANY HIGH-
LY COMBUSTIBLE SURFACES SUCH AS LOW
DENSITY CELLULOSE FIBRE.
2. DO NOT LOCATE HEATER BELOW ELECTRICAL
CONVENIENCE RECEPTACLES.
3. DO NOT STORE OR USE GASOLINE OR FLAMMA-
BLE LIQUIDS IN THE VICINITY OF THE HEATERS.
WARNING: Hazard of Fire. The normal operating temperatures of cabinet convectors are relatively high and proper operation requires free circulation of room air through the heating element. Bottom
air inlet heaters must be mounted with minimum of 3” from finished floor.
WARNING: Hazard of Fire. Keep electrical cords, drapes, rugs and other furnishings away from the heater.
WARNING: Hazard of Fire. Furniture must be placed no closer than four inches from the heater (see Figure 1).
WARNING: Hazard of Fire. Drapes must clear the top of heater by at least twelve inches; or, if floor length drapes are used, they must clear the fin­ished floor by three inches and the minimum clear­ance from the back fold to the front cover should be at least four inches (see Figure 1).
WARNING: Hazard of Fire. When the floor is to be finished in carpet, allow clearance under the heaters and corners for carpet installation. Bottom air inlet heaters are to be mounted a minimum of 3” from the finished floor.
WARNING: Hazard of Fire. Rugs may be placed up to a heater provided that they are not of a thick­ness that would block the air-intake. Bottom air inlet heaters are to be mounted a minimum of 3” from the finished floor.
Figure 1: Furniture & Drapes
GENERAL
CAF-12B 2 1521 01A9 Refer to
or Wiring
CCAS-12 Code Control Options (Factory Installed) Diagram
00 = No Control Options A A9 = Built-in DP tamperproof hydraulic thermostat 208 - 277V E A3 = Built-in 3P tamperproof hydraulic thermostat for 3P voltages 208 - 480V G A4 = Built-in 24V low voltage relay for 1P voltages 208 - 277V B A5 = Built-in 24V low voltage relay and transformer for 1P voltages 208 - 277V D A6 = Built-in 24V contactor for 3P voltages 208 - 480V F A7 = Built-in 24V contactor and transformer for 3P voltages 208 - 480V H A8 = Built-in disconnect switch, rated 277V@20A I B9 = Built-in DP tamperproof thermostat and disconnect J B3 = Built-in 3P tamperproof thermostat and disconnect K
Code Finish Painted Anodized
68 = Almond 07 = Bronze 02 = White 10 = Clear
Code Voltage/Phase
21 = 208/1 23 = 208/3 31 = 240/1 41 = 277/1 73 = 480/3
Code Wattage (See Table)
Code Length
2 = 2 ft. 3 = 3 ft. 4 = 4 ft. 6 = 6 ft. 8 = 8 ft.
Code Inlet Location
F = Front B = Bottom
Type