4RS 485 Digital comm., Heater Break Down input, Out #3
CodeInstrument Power
3100 - 240 Vac
524 Vac/dc
Code
0Add to complete model number
1601 61030Typical Model Number
III
1604-7-0-AB.p655/16/00, 10:50 AM3
MOUNTING REQUIREMENTS
Select a mounting location where there is
minimum vibration and the ambient temperature
range between 0 and 50 °C.
The instrument can be mounted on a panel up to
15 mm thick with a square cutout of 45 x 45 mm.
For outline and cutout dimensions refer to Fig. 2.
The surface texture of the panel must be better
than 6,3 mm.
The instrument is shipped with rubber panel
gasket (50 to 60 Sh).
To assure the IP65 and NEMA 4 protection, insert
the panel gasket between the instrument and the
panel as shown in fig. 1.
While holding the instrument against the panel
proceed as follows:
1) insert the gasket in the instrument case;
2) insert the instrument in the panel cutout;
3) pushing the instrument against the panel,
insert the mounting bracket;
4) with a screwdriver, turn the screws with a
torque between 0.3 and 0.4 Nm.
Screw
bracket
Panel
Gasket
1604-7-1-AB.p655/16/00, 10:50 AM1
Fig. 1
1
OUTLINE AND CUT OUT
DIMENSIONS
3.0
(75)
2.4
(60)
1.77
(45)
1.9
(48)
2.2
(56)
Fig. 2OUTLINE AND CUT-OUT DIMENSIONS
1604-7-1-AB.p655/16/00, 10:50 AM2
1.77
(45)
4.8
(122)
2
CONNECTION DIAGRAMS
Connections are to be made with the instrument
housing installed in its proper location.
A) MEASURING INPUTS
NOTE: Any external components (like zener
barriers etc.) connected between sensor and
input terminals may cause errors in measurement
due to excessive and/or not balanced line
resistance or possible leakage currents.
TC INPUT
10
+
_
9
Shield
10
+
_
9
Fig. 3 .A
1604-7-1-AB.p655/16/00, 10:50 AM3
REAR TERMINAL BLOCK
Fig. 4
Shield
NOTE:
1) Don’t run input wires together with power
cables.
2) For TC wiring use proper compensating cable
preferable shielded.
3) when a shielded cable is used, it should be
connected at one point only.
3
RTD INPUT
RTD
RTD
LINEAR INPUT
10
9
+
_
Shield
mA,
mV
or
V
8
98
10
Fig. 5 RTD INPUT WIRING
NOTE:
1) Don’t run input wires together with power
cables.
2) Pay attention to the line resistance; a high line
resistance may cause measurement errors.
3) When shielded cable is used, it should be
grounded at one side only to avoid ground loop
currents.
4) The resistance of the 3 wires must be the
same.
1604-7-1-AB.p655/16/00, 10:50 AM4
9
10
10
9
Fig. 6 mA, mV AND V INPUTS WIRING
NOTE:
1) Don’t run input wires together with power
cables.
2) Pay attention to the line resistance; a high line
resistance may cause measurement errors.
3) When shielded cable is used, it should be
grounded at one side only to avoid ground loop
currents.
4) The input impedance is equal to:
< 5 W for 20 mA input
> 1 MW for 60 mV input
> 200 kW for 5 V input
> 400 kW for 10 V input
4
+
mA
mV
_
or
V
G
B) LOGIC INPUT
Safety note:
1) Do not run logic input wiring together with
power cables.
2) Use an external dry contact capable of
switching 0.5 mA, 5 V DC.
3) The instrument needs 100 ms to recognize a
contact status variation.
4) The logic inputs are NOT isolated by the
measuring input
C) RELAY OUTPUTS
OUT 2
OUT 3
1
3
2
NO - OUT 2
NO - OUT 3
C - OUT 2 and 3
SP / SP2
14
15
Fig. 7 - LOGIC INPUT WIRING
This logic input allows to select the operative set
point.
logic inputop. set point
openSP
closeSP2
1604-7-1-AB.p655/16/00, 10:50 AM5
Fig. 8 RELAY OUTPUTS WIRING
The contact rating of the OUT 2, 3 is 2A/250V AC
on resistive load.
The number of operations is 1 x 105 at specified
rating.
NOTES 1) To avoid electrical shock, connect
power line at the end of the wiring
procedure.
2) For power connections use No 16 AWG
or larger wires rated for at last 75 °C.
3) Use copper conductors only.
4) Don’t run input wires together with
power cables.
The relay contacts are protected by varistor against
inductive load with inductive component up to 0.5 A.
The following recommendations avoid serious
problems which may occur, when using relay
output for driving inductive loads.
5
INDUCTIVE LOADS
High voltage transients may occur switching
inductive loads.
Through the internal contacts these transients
may introduce disturbances which can affect the
performance of the instrument.
For the OUT 2 and OUT 3, the internal protection
(varistor) assures a correct protection up to 0.5 A
of inductive component.
The same problem may occur when a switch is
used in series with the internal contacts as shown
in Fig. 9.
C
R
LOAD
POWER
LINE
Fig. 9 EXTERNAL SWITCH IN SERIES WITH
THE INTERNAL CONTACT
In this case it is recommended to install an
additional RC network across the external contact
as show in Fig. 9
The value of capacitor (C) and resistor (R) are
shown in the following table.
LOAD
(mA)
<40 mA
<150 mA
<0.5 A
C
(mF)
0.047
0.1
0.33
R
(W)
100
22
47
P.
(W)
1/2
2
2
OPERATING
VOLTAGE
260 V AC
260 V AC
260 V AC
LINEAR OUTPUT
This instrument is equipped with one linear output
(OUT 1) programmable as:
- main output (heating or cooling)
- secondary output (cooling)
- analog retransmission of the measured value
- analog retransmission of the operative set point.
OUT 1
+
6
_
7
+
20 mA
_
Fig. 10 mA OUTPUT WIRING
It is an isolated analog output.
Maximum load: 500 W.
The cable involved in relay output wiring must be
as far away as possible from input or communication cables.
1604-7-1-AB.p655/16/00, 10:50 AM6
6
SERIAL INTERFACE
RS-485 interface allows to connect up to 30
devices with one remote master unit.
I
N
S
T
R
U
M
E
N
T
Fig. 11 - RS-485 WIRING
The cable length must not exceed 1.5 km at 9600
BAUD.
NOTE: The following report describes the signal
A/A'
11
B/B'
12
13
sense of the voltage appearing across the
interconnection cable as defined by EIA for
RS-485.
a) The ” A ” terminal of the generator shall
b) The ” A ” terminal of the generator shall
COMMON
be negative with respect to the ” B ”
terminal for a binary 1 (MARK or OFF)
state.
be positive with respect to the ” B ”
terminal for a binary 0 (SPACE or ON)
state.
A'/A
B'/B
M
A
S
T
E
R
D) POWER LINE WIRING
N
4
POWER LINE 100 V to 240 V A.C
5
R (S,T)
Fig. 12 POWER LINE WIRING
NOTES:
1) Before connecting the instrument to the power
line, make sure that line voltage corresponds to
the description on the identification label.
2) To avoid electrical shock, connect power line at
the end of the wiring procedure.
3) For supply connections use No 16 AWG or larger
wires rated for at last 75 °C.
4) Use copper conductors only.
5) Don’t run input wires together with power cables.
6) For 24 V DC the polarity is a do not care condition.
7) The power supply input is NOT fuse protected.
Please, provide it externally.
Power supplyType CurrentVoltage
24 V AC/DCT500 mA250 V
100/240 V ACT125 mA250 V
When fuse is damaged, it is advisable to verify
the power supply circuit, so that it is necessary to
send back the instrument to your supplier.
8) The safety requirements for Permanently Connected Equipment say:
- a switch or circuit-breaker shall be included in
the building installation;
- It shall be in close proximity to the equipment
and within easy reach of the operator;
- it shall be marked as the disconnecting device
for the equipment.
(50/60Hz)
or 24 V AC/DC
R (S,T)
N
1604-7-1-AB.p655/16/00, 10:50 AM7
7
NOTE: a single switch or circuit-breaker can drive
more than one instrument.
9) When the NEUTRAL line is present, connect it
to terminal 4.
1604-7-1-AB.p655/16/00, 10:50 AM8
8
PRELIMINARY HARDWARE
SETTINGS
1) Remove the instrument from its case.
2) It is necessary to set J106 according to the
desired input type as shown in the following figure.
INPUTJ106
TYPE1-23-45-67-89-10
TC-RTD openclose openopenopen
60 mVopenclose openopenopen
5 Vclose openclose openopen
10 Vopenopen close openopen
20 mAopenopen open closeclose
OPEN INPUT CIRCUIT
This instrument is able to identify the open circuit
for TC and RTD inputs.
The open input circuit condition for RTD input is
shown by an "overrange" indication.
For TC input, it is possible to select overrange
indication (standard) or underrange indication setting the CH101 and SH101 according to the following table:
Overrange (STD) CH101 = close SH101 = open
UnderrangeCH101 = open SH101 = close
Both pads are located on the soldering side of the
CPU card
NOTE : the not used jumper can be positioned on
pin 7-9
2 4 6 8 10
V101
1604-7-1-AB.p655/16/00, 10:50 AM9
J106
1 3 5 7 9
Fig. 13
9
Fig. 14
CH101
SH101
Loading...
+ 27 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.