Chromalox 1603 User Manual

Page 1
1603
Issue Date June 1999
USER’S MANUAL
0037-75214
Temperature Controller
Page 2
Chromalox 1603 User's Manual i
Model Identification..................................Page ii
Dimensions and Panel Cut Out ........................ 1
Wiring.........................................................................2
Thermocouple Inputs.................................... 2
RTD Inputs........................................................ 3
Relay Outputs .................................................. 3
Voltage Outpus ............................................... 5
Power Line and Grounding ........................ 6
Configuration Procedure.....................................7
Advanced Configuration ...................................10
Operator Mode .....................................................12
Pushbutton Functions ........................................13
Manual Reset of Alarms ...................................13
SMART Function..................................................14
Direct Access to Setpoint Modification ......15
Output Power OFF...............................................15
Lamp Test ...............................................................15
1603 Operator Parameters ...............................16
Error Messages ....................................................18
Error Descriptions................................................19
Calibration Procedure ........................................21
Warranty and Return..........................................26
Contents
Page 3
ii Chromalox 1603 User's Manual
Model Identification
Model
1603 1/16 DIN Temperature Controller, Dual Display
Code Output 1 - Heat or Cool
1 Relay, 3 Amps at 250 Vac (Resistive) 6 SSR Drive, 14 Vdc at 20 mA
Code Output 2 - Cool or Alarm
1 Relay, 1 Amp at 250 Vac (Resistive Load)
Code
0 Add to complete model number
Code Instrument Power
3 100-240 Vac 5 24 Vac/dc
Code
0 Add to complete model number
1603 - 61030Typical Model Number
Page 4
Chromalox 1603 User's Manual 1
1600
SMART
SMART
FUNC
ALM
OUT
˚F
Figure 1
Dimensions and P anel Cut Out
3.0
(75)
2.4
(60)
1.9
(48)
1.77 (45)
1.9
(48)
3.9
(100)
Dimensions in inches (mm in parenthesis)
1.77 (45)
Page 5
2 Chromalox 1603 User's Manual
Figure 2
Wiring
6
7
8
8
9
10
8
1
2
3
4
5
INST . PWR.
T/C
RTD
+
-
OUT 2
+
-
SSR (Output Code 6 only)
MAIN RELA Y (Output Code 1 only)
NO C NC
"C" "NO"
Sensor Inputs
Note:
Any external components (like Zener diodes, etc.) connected between sensor and input terminals may cause errors in measurement due to excessive and/or not balanced line resistance or possible leakage currents.
TC Input
Figure 3
Thermocouple Input W iring
Wiring Guidelines
3
2
+
-
3
2
+
-
Page 6
Chromalox 1603 User's Manual 3
Notes:
1.Do not run input wires with power cables.
2.For TC wiring use proper compensating cable (use type J TC extension wire with type J TC connections), preferably shielded.
3.Shielded cable should be grounded at one end only.
RTD Input
Figure 4
RTD Input Wiring
Notes:
1.Do not run input wires together with power cables.
2.Observe the line resistance; a high line resistance may cause measurement errors.
3.When shielded cable is used, it should be grounded at one end only to avoid ground loop currents.
4.The resistance of the 3 wires must be the same.
TC Inputs (continued)
Relay Outputs
Figure 5
Relay Outputs
123 123
RTD RTD
OUT 1
6
7
8
5
4
OUT 2
NC
C
NO
C
NO
Page 7
4 Chromalox 1603 User's Manual
Relay Outputs (continued)
The OUT 1 NO contact and the OUT 2 contact are protected by varistor against inductive loads with inductive components up to 0.5 A.
OUT 1 contact rating is 3A/250Vac resistive load. OUT 2 contact rating is 1A/250Vac resistive load. The number of operations is 1 x 10
5
at specified rating.
Notes:
1.To avoid electric shock, connect power line at the end of the wiring procedure.
2.For power connections use No 16 AWG or larger wires rated for at last 75 °C.
3.Use copper conductors only.
4.Do not run input wires together with power cables.
Inductive Loads
Employing the following recommendations will help avoid serious problems that may occur when relay outputs are used with inductive loads.
High voltage transients may occur when switching inductive loads. Through the internal contacts these transients may introduce disturbances that can affect the performance of the controller.
For all the outputs, the internal protection (varistor) assures a correct protection up to 0.5 A of inductive component.
The same problem may occur when a switch is used in series with the internal contacts as shown in Figure 8.
Figure 6
External Switch in Series with the Internal Contact
C
R
Load
Power
Line
Page 8
Chromalox 1603 User's Manual 5
The SSR Drive Output is a time proportioning output.
Logic Level 0:Vout < 0-5 Vdc Logic Level 1:14V ± 20% @ 17mA
+24V ± 20% @ 1mA
Maximum = 17mA
Notes:
1.This output is not isolated. An external solid state relay with 2600V isolation must be used to isolate the controller output and power supply for CE compliance. The Chromalox Series 4115, 7710, 4001, and 4003 meet these isolation requirements.
2.To determine Output #1 output type, check the tag on your controller and compare it to the model identification table on page ii.
Inductive Loads (continued) Warnings:
When a relay output is used to drive an inductive load, it is suggested that you connect an external snubber network (RC) across the terminals using Chromalox P/N 0149-01305.
Voltage Outputs for SSR Drive
Figure 7
SSR Drive Output Wiring
8
7
+
-
+
-
˜
Page 9
6 Chromalox 1603 User's Manual
Power Line and Grounding
Figure 8
Power Supply
10
9
N
Power Supply 100 to 240 Vac or 24 Vac/Vdc
Notes:
1. Before connecting the power line, check that the voltage is correct (see Model Identification, pg. ii).
2. For supply connections use 16 AWG or larger wires rated for at least 75 °C.
3. Use copper conductors only.
4. Do not run input wires with power cables.
5. Polarity does not matter for 24 Vdc wiring.
6. The power supply input is NOT fuse protected. Please provide external fusing.
When the fuse is damaged, it is advisable to verify the power supply circuit. Return the controller to Chromalox for test and verification.
7. Safety requirements for permanently connected equipment:
• Include a switch or circuit-breaker in the
installation.
• Place the switch in close proximity to the
equipment and within easy reach of the operator.
• Mark the switch as the disconnecting device for
the equipment.
Note:
A single switch or circuit-breaker can drive more
than one controller.
8. When the NEUTRAL line is present, connect it to terminal 10.
9. To avoid shock and possible controller damage, connect power last.
Power supply Type Current Voltage 24 V AC/DC T 500 mA 250 V 100/240 V AC T 125 mA 250 V
Page 10
Chromalox 1603 User's Manual 7
General Operation
There are two setup modes for the 1603:
• Configuration Mode
• Operator Mode In general, the Configuration Mode is the initial setup of the controller when first installed. Input type and alarm setup are examples of Configuration Mode settings. The Operator Mode includes settings that might be adjusted frequently with daily control operations such as setpoints and PID parameters.
Pushbutton Functionality During Configuration Procedure
FUNC = Must be pressed to store the new value of a
selected parameter and increments to the next parameter.
SMART= In configuration Mode, scrolls parameters
back (in reverse order) without storing the new parameter value.
= Increases the value of the selected parameter .= Decreases the value of the selected parameter.
Configuration Procedure
1. Remove the controller from its case.
2. Set the internal switch V2 (see Fig. 9) in open condition.
3. Reinsert the controller in the case.
4. Switch the controller “ON”. Note: If “CAL” indication is immediately displayed, press the pushbutton to return to the configuration mode “CnF.”
5. Push the FUNC pushbutton. The lower display will show the parameter alphanumeric and the upper display will show the parameter value.
+
+
1
3
4
2
PZ3
PZ4
PZ5
V2
B
L4
C6
C10
C5
C8
L3
L2
C7
R7
R8
J6
J5
2
C14
C2
R4
R5
R11
Q2
R3
PZ2
PZ1
C15
K2
C9
Figure 9
V2
Page 11
8 Chromalox 1603 User's Manual
P1 - Input Type and Standard Range
0 = TC type L range 0 / +800 °C 1 = TC type J range 0 / +800 °C 2 = TC type K range 0 / +999 °C 3 = TC type N range 0 / +999 °C 4 = RTD type P t 100 range -199 / +500 °C 5 = RTD type P t 100 range -19.9 / +99.9 °C 6 = TC type T range 0 / +400 °C 8 = TC type L range 0 / +999 °F 9 = TC type J range 0 / +999 °F 1 0 = TC type K range 0 / +999 °F 1 1 = TC type N range 0 / +999 °F 1 2 = RTD type Pt 100 range -199 / +999 °F 1 3 = TC type T range 0/+752 °F
Note: To set the display for °C engineering units, place the °C sticker label on the controller faceplate. The label is located in the shipping box.
P2 = Initial Scale Value
Not present when P1 = 5 Enter the initial and full scale values which are going to be used by the PID algorithm to calculate the input span.
When this parameter is modified, rL (setpoint lower limit) is automatically modified to the same value.
P3 = Full Scale Value
Not present when P1 = 5 When this parameter is modified, rH (setpoint upper limit) is automatically modified to the same value. The initial and full scale values determine the input span which is used by the PID algorithm, the SMART and the alarm functions.
Note: The minimum input span (P3 - P2) is 600°F (300°C) for TC input and 200°F (100°C) for RTD input.
P4 = Main Output Action
The 1603 skips this parameter when P5 = 5 (cooling) r = reverse action (heating) d = direct action (cooling)
P5 = Output 2 Functions
0 = None 1 = Process alarm (absolute) 2 = Band alarm (+ and - deviation) 3 = Deviation alarm (+ or - deviation) 4 = Controller failure indicator (under- or over-range,
CJC or A-D converter failure)
5 = Cooling output Note: When P5 = 5, the P4 parameter is forced to “r”.
Page 12
Chromalox 1603 User's Manual 9
P6 = Output 2 Operative Mode
P6 is available only when P5 is different from 0. When P5 = 1, 2, or 3: H.A. = high alarm (outside boand) with automatic reset L.A. = low alarm (inside band) with automatic reset H.L. = high alarm (outside band) with manual reset L.L = low alarm (inside band) with manual reset When p5 = 4, the selections H.A. and L.A. are controller failure indicator alarms with automatic reset. The H.L. and L.L. selections are controller failure indicator alarms with manual reset. When P5 = 5, this parameter selects the cooling medium:
AIr= Air OIL = Oil H
2
0 = Water Note: Different set of cooling medium produces the automatic modification of the relative cooling gain and of the cooling cycle time.
P7 = Alarm Action
Present only when P5 is different from 0 or 5.
r = reverse (relay de-energized in alarm condition) d = direct (relay energized in alarm condition)
P8 = Alarm Inhibit
Present only when P5 is different from 0,4 or 5.
OFF = Inhibit disabled ON = Inhibit enabled
Note: If the alarm is programmed as band or deviation alarm, this function disables the alarm condition after a setpoint change or at the controller startup until the process variable passes the alarm setpoint plus or minus hysteresis. If the alarm is programmed as a process alarm, this function disables the alarm condition at controller startup until the process variable passes the alarm setpoint plus hysteresis.
P9 = OFFSET Applied to the Measured Temperature
This OFFSET is applied along the whole range. When P1 = 5 P9 is programmable from -19.9 to
19.9 °C.
When P1 5 P9 is programmable from -199 to
199 °C or °F.
P10 = Threshold of the “Soft Start” Function
Enter the Threshold value, in °C or °F, for the automatic start of the “Soft Start” function (limiting output power). If the unit powers up below the Threshold value, the “Soft Start” function is enabled and limits the power output to “OLH” for “tOL” minutes. “OLH” and “tOL” are set in the Operator Mode.
P6 C (cycle time) rC (cool gain)
Air 10(s) 1 Oil 4(s) 0.8
H
2
O 2(s) 0.4
Page 13
10 Chromalox 1603 User's Manual
P11 = User Defined Security Code
0 = Security lock disabled. All Operator Mode
parameters can be modified.
1 = Security lock enabled. No parameters can be
modified except the setpoint.
2 to 499 = Select the security code (to be stored).
During the “Operator Mode” the security code setting will display:
a. The controller is “Unlocked”
and all parameters can be modified. To make the device Locked,” insert a number different from the security code. Now none of the parameters can be modified except the SP.
b. The controller is “locked” and
none of the parameters can be modified except the SP. To “Unlock” the device, insert the security code.
500 to 999 = Selecting a security code between these two numbers, everything will occur as explained above except that when the device is “Locked” the only parameters that can be modified are the setpoint and the alarm setpoint.
P12 = Control Output Maximum Rate of Rise
Programmable from 1% to 10% of the output per second. The ramp is applied when the controller changes the percent of output desired. Above 10%, the display will show “InF”, meaning that no ramp is imposed and the output immediately changes to the PID calculated value. P12 not used if ON/OFF control selected.
Advanced Configuration
When the standard configuration procedure is completed, the controller shows “-,-,-,-,” on both displays. When it is desired to end the configuration procedure, push the FUNC pushbutton. The display will show “COnF”.
To access the advanced configuration parameter, procede as follows:
1. using and pushbuttons, set the 219 code.
2. push the FUNC pushbutton.
Page 14
Chromalox 1603 User's Manual 11
P14 = Display of the Operator Parameters
This parameter is available only if P11 is different from 0. This parameter allows you to enable/disable the display of the operator parameters. OFF = parameter cannot be displayed ON = parameter can be displayed, but not changed
P15 = SMART Function Enabling/Disabling
0 = The SMART function is disabled 1 = The SMART function enabling/disabling is NOT
protected by the Security Code (P11).
2 = The SMART function enabling/disabling is
protected by the Security Code (P11).
P16 = Maximum Value of the Proportional Band by
the SMART Function
This parameter may be programmed from P17 or P18 value to 99.9.
P17 = Minimum Value of the Proportional Band Set
by the SMART Function in Heating Control Only
This parameter is present only if P5 is different from 5. It may be programmed from 1.0% to P16 value.
P18 = Minimum Value of the Proportional Band Set
by the SMART Function in Heating/Cooling Control Only
This parameter is present only when P5 is equal to 5. This parameter may be programmed from 1.5% to P17.
P19 = Automatic Modification of Relative Cooling
Gain
This parameter is present only when P5 is equal to 5. OFF = The SMART function does not modify the
“relative cooling gain” parameter.
ON = The SMART function modifies the “relative
cooling gain” parameter (rC).
P20 = Minimum Value of Integral Time Set by
SMART Function
P20 is programmable from 00.1 (10 seconds) to 02.0 (2 minutes).
P21 = Extension of the Anti-Reset-Windup
Range: from -30 to +30% of the proportional band Note: A positive value increases the high limit of the anti-reset-windup (over setpoint), while a negative value decreases the low limit of the anti-reset-windup (under setpoint).
End of Advanced Configuration
When the advanced configuration procedure is completed, the controller displays “CnF”.
To restart Configuration
Push FUNC to begin the Configuration Mode.
Page 15
12 Chromalox 1603 User's Manual
+
+
1
3
4
2
PZ3
PZ4
PZ5
V2
B
L4
C6
C10
C5
C8
L3
L2
C7
R7
R8
J6
J5
2
C14
C2
R4
R5
R11
Q2
R3
PZ2
PZ1
C15
K2
C9
Operator Mode
1. Remove the controller from its case.
2. Set the internal switch V2 in closed condition.
3. Reinsert the controller in its case.
4. If, during the configuration procedure, a display in °C
has been selected, it is necessary to put the °C sticker label on the front of the controller. The additional label is located in the shipping box.
5. The 1603 displays the measured temperature on the upper display and the programmed set point on the lower display. This display is known as the “normal display mode.” If error 400 message is displayed, press
the or simultaneously until normal display mode appears.
V2
°C
Closed Position
Indicators
SMART= Flashes when the first part of the SMART
algorithm is active. Lit when the second part of the SMART algorithm is active.
OUT = Lit when OUT 1 is in ON condition. ALM = Lit when Alarm 1 is in alarm condition or
when this output is used as a time proportioning cooling control output.
Figure 10
Page 16
Chromalox 1603 User's Manual 13
Pushbutton Functions
FUNC = Must be pressed to store the new value of a
selected parameter and increments to the next parameter. Parameter values are displayed on the upper display; parameter name is displayed on the lower display.
SMART= Enables or Disables the SMART function,
when held for 1.5 seconds. Scrolls operator parameters back (in reverse order).
= Increases the value of the selected parameter.= Decreases the value of the selected parameter.+ FUNC = Press together to perform an LED/
indicator test. Press both again to turn LED/ indicator test “off”.
Note: A 10 second time out occurs during parameter modification. If, during parameter modification, no pushbutton is pressed for more than 10 seconds, the controller automatically reverts to the “normal display mode”. The new setting of the last parameter modified is stored, prior to the time out, only if the FUNC pushbutton was depressed.
Manual Reset of Alarms
If the alarm has been configured as a latching alarm, the alarm status persists after the alarm condition disappears until the alarm is reset. To reset the alarm, press the FUNC pushbutton to select the “n.rS” parameter. The displays will show “n.rS” and “OFF”. Using and , select “ON” and push the FUNC pushbutton again. The alarm reset action will only occur if the alarm condition no longer exists.
Page 17
14 Chromalox 1603 User's Manual
SMART Function
The SMART function automatically calculates the optimum PID control parameters. To enable the SMART function, push and hold the SMART pushbutton for more than 1.5 seconds, when the controller is in normal display mode. The SMART LED will light or flash according to the algorithm automatically selected. When the SMART function is enabled, it is possible to display but not to modify the control parameters (PB, TI, TD and rC). When the traditional control (PID) is desired, push and hold the SMART pushbutton for more than 1.5 seconds again to turn the “SMART” OFF. The controller maintains the last set of SMART calculated control parameters and allows parameters to be adjusted.
Notes:
1. During the SMART function operation, the relative cooling gain (if present and controlled by SMART) is limited within the following ranges:
Cooling Medium Range
Air 0.85 to 1.00 Oil 0.80 to 0.90 H2O 0.30 to 0.60
2. The SMART function uses a derivative time equal to 1/4 of the integral time.
3. The limits of the proportional band set by the SMART function are programmed by P16, P17, and P18 parameters.
4. The lower limit of the integral time set by SMART function is programmed by P20 parameter.
5. When ON/OFF control is programmed (PB = 0), the SMART function is disabled.
6. The SMART enabling/disabling can be protected by the safety lock (see P15 parameter).
Page 18
Chromalox 1603 User's Manual 15
Direct Access to Setpoint Modification
When direct access to setpoint modification is required, proceed as follow:
1. Push, for more than 3 seconds, the or pushbutton; the set point value, shown on the lower display, will start to change.
2. Using the and pushbuttons, set the desired value.
3. When the desired value is reached, do not push any pushbutton for more than 3 seconds. The new setpoint will become operative 3 seconds after the pushbutton is released.
If, during this procedure, there is no interest in memorizing the new value, push the FUNC pushbutton; the controller returns automatically to the normal display mode without having memorized the new setpoint.
Output Power OFF
To turn the output signal OFF, press and hold the pushbutton then push FUNC.
Pressing both pushbuttons for more than 3 seconds, will cause the controller will show “OFF” instead of the set point value.
In the output power OFF condition, the parameters can always be viewed and modified. When control is disabled (output power off), the alarms are not in an alarm condition. The alarm output status depends on the type of alarm action.
When the output is OFF, all parameters can be reviewed and modified. The SMART function will be disabled during the OFF condition. If power is lost, the unit will power-up in the OFF condition.
To return to normal control, press and hold the and then push FUNC for more than 3 seconds. The controller then automatically goes to the NORMAL DISPLAY MODE.
The alarm inhibit function, if configured, will be activated as if it were a powerup.
Lamp Test
To verify operation of the display LED, push and FUNC together. The instrument LEDs will flash until the Lamp Test is turned off.
To turn off the Lamp Test, press and FUNC together. No pushbutton functions are operable during the Lamp
Test.
Page 19
16 Chromalox 1603 User's Manual
1603 Operator Parameters
Push the FUNC pushbutton. The lower display will show the cue while the upper display will show the value of the selected parameter. Not all parameters will be displayed due to specific unit configuration.
Cue Description SP Setpoint—range set at P1-Sensor Selection. May
be limited by setting low and high limits at P2 and P3 (see configuration parameters).
n.rS Manual reset of latching alarms. Press to set
ON, then press FUNC to reset the alarm.
nnn Security code for parameter protection.
ON=the controller is in LOCK condition OFF=the controller is in UNLOCK condition When it is desired to switch from LOCK to UNLOCK condition, set a value equal to P11 parameter. When it is desired to switch from UNLOCK to LOCK condition, set a value different from P11 parameter.
Cue Description AL Alarm setpoint—range for a process alarm set
at P1-Sensor Selection and may be limited by setting low and high limits at P2 and P3 (see Configuration Parameters). Range for a band alarm 0-500, range for a deviation alarm
-199 to 500. HSA Alarm hysteresis—deadband range from 0.1 to10.0 %. Pb Proportional band—range from 1.0 to 99.9 % of
span (P3-P2) for heat or cool control and 1.5 to
99.9% of span (P3-P2) for heat/cool control. When
Pb = 0 the controller performs as an ON/OFF control and ti, td, C, C2, rC, OLP, OLh and tOL parameters are skipped.
HS Hysteresis (deadband for ON/OFF control action
(Pb = 0)—range from 0.1 to 10 % of input span (P3-P2).
ti Integral time—range from 0 minutes and 10
seconds to 20 minutes and 0 seconds (minutes. seconds); above the upper limit the display blanks out and the integral action is excluded.
td Derivative time—range from 0.00 to 9.59
Page 20
Chromalox 1603 User's Manual 17
1603 Operator Parameters (continued)
(minutes. seconds). td = 0, turns off derivative
action. Cue Description IP Integral PreLoad—range 0 to 100% for one
control output, -100 to 100% for two control
outputs (P5 =5). This parameter does not
appear when Pb (Proportional Band) = 0. C Heating cycle time—range from 1 to 200 seconds (30
seconds or greater recommended for relay outputs). C2 Cooling cycle time—range from 1 to 200
seconds (30 seconds or greater recommended
for relay outputs). Available if P5 = 5. rC Relative cooling gain—range from 0.20 to 1.00.
This parameter does not appear if P5 5 or
PB = 0. OLP Dead zone/Overlap—range from -20% to + 50%
of the proportional band. A negative value is a
dead zone and a positive value creates an
overlap. Available if P5 = 5 and PB 0. rL SP low limit—range from the initial scale value
(P2) to rH value.
Cue Description rH SP high limit—range from the rL value to the full
scale value (P3).
OLH Output power maximum value—range 0 to 100%
heating, -100 to 100% heat/cool, limits power continuously (tOL = Inf) or on start up per tOL setting. PB 0.
tOL Time interval for OLH power output limit, range
1 to 100 minutes or if “Inf” infinite. The timer starts on power up if the actual temperature is less than P10 (threshold value). A new TOL value will not become active until the unit is powered up. If PB = 0, this parameter will not be displayed.
Page 21
18 Chromalox 1603 User's Manual
Error Messages
OVERRANGE, UNDERRANGE, and BURN-OUT INDICATIONS
The controller shows the OVERRANGE and UNDERRANGE conditions with the following
UnderrangeOverrange
indications: The sensor leads break can be signalled as:
• for TC input: OVERRANGE
• for RTD input: OVERRANGE
Sensor leads short circuit detection: On RTD input, a special test is provided to signal OVERRANGE when input resistance is less than 15 ohm (short circuit sensor detection).
Note;
• When the controller is set for one output only, and an OVERRANGE is detected, the OUT 1 turns OFF (if reverse action) or ON (if direct action).
• When the controller is set for heating/cooling action, an and OVERRANGE is detected, OUT 1 turns OFF and OUT 2 turns ON.
• When the controller is set for one output only, and an UNDERRANGE is detected, the OUT 1 turns ON (if reverse action) or OFF ( if direct action).
• When the controller is set for heating/cooling action, and an UNDERRANGE is detected, OUT 1 turns ON and OUT 2 turns OFF.
• When an OVERRANGE or UNDERRANGE is detected, the alarms operate as in the presence of the maximum or the minimum measurable value respectively.
To eliminate the OUT OF RANGE condition, proceed as follows:
1. Check the input signal source and the connecting line.
2. Make sure that the input signal is in accordance with controller configuration; otherwise, modify the input configuration. See P1.
Page 22
Chromalox 1603 User's Manual 19
ERRORS
Diagnostics are made at controller power-up and during normal mode of operation. If a fault condition (error) is detected, the lower display will show the message “Err” while the upper display shows the error code.
10 0 EEPROM memory writing error.
After 2 seconds the controller restarts automatically. If this error persists, send the controller back to your supplier.
1 50 General hardware error on the CPU card.
If this error persists, send the controller back to your supplier.
20 0 Protect register memory error.
The controller remakes this check every 2 seconds. Set the switch V2 in open condition. Switch on the controller. Set the switch V2 in closed condition, and power the controller. If this error persists, send the controller back to your supplier.
201-219 Wrong configuration parameter value (2xx,
where xx is the Configuration Code). The two least significant digits show the number of the wrong configuration parameter. Return to the configuration procedure and check the values.
30 1 RTD calibration error.
Go to calibration procedure and check the P1 and PH calibrations. See RTD calibration check.
30 5 Thermocouple input calibration error.
Go to calibration procedure and check the tl and tH calibrations. See Thermocouple Calibration Check.
30 7 Reference junction calibration error.
Go to calibration procedure and check the tJ calibration. See Cold Junction Calibration specs.
ERROR Descriptions
ERROR Descriptions
Page 23
20 Chromalox 1603 User's Manual
4 00 One or more control parameters are out of
range with respect to the allowed values. It may appear at controller power-up after configuration changes. Push and hold and pushbuttons simultaneously and load all the default parameters.
500 Autozero error.
The controller measures an internal autozero value too negative or too positive. The controller checks this condition every 30 seconds. If this error persists, send the controller back to your supplier.
50 2 Cold junction measurement errors.
The controller cannot perform cold junction compensation. Check the ambient temperature and, if necessary, re-calibrate the cold junction. If this error persists, send the controller back to your supplier.
ERROR Descriptions ERROR Descriptions
51 0 Incorrect measured value during calibration
procedure. Check the input value and, if necessary, calibrate the controller. If this error persists, send the controller back to your supplier.
Figure 11
Dip Switch Location: To start calibration, V2 must be OPEN.
+
+
1
3
4
2
PZ3
PZ4
PZ5
V2
B
L4
C6
C10
C5
C8
L3
L2
C7
R7
R8
J6
J5
2
C14
C2
R4
R5
R11
Q2
R3
PZ2
PZ1
C15
K2
C9
V2
Open Position
Calibration
Page 24
Chromalox 1603 User's Manual 21
Note: All 1603s are calibrated at the manufacturing plant. It is not necessary to calibrate the 1603 on receipt.
For a good calibration, it is necessary to proceed as follows:
1. The controller under calibration should be mounted in its case in order to keep the internal temperature constant.
2. The ambient temperature should be stable. Avoid any draft due to air conditioning, etc.
3. The relative humidity should not exceed 70%.
4. Minimum warm-up time must be 20 minutes.
5. If possible, operate in a noise free environment.
6. During calibration, connect one input at a time to the rear terminal block.
WARNING: Do not attempt calibration without the recommended simulators or calibrators.
General Guide Lines for Calibration
Calibration Procedure
Calibration parameters are logically divided in groups of two parameters each (initial and final scale value). After each group, the calibration check is provided but it is also possible to do the check without calibrating.
Note:
Pushing the SMART pushbutton goes back to the previous parameter without modifying the calibration.
For this calibration procedure it is necessary to use calibrators with the following accuracy and resolution:
Accuracy
1. For TC input: +0.005% output +0.001% range + 5 µV
2. For RTD Input: ±0.02% ±0.0025 /decade.
3. For cold junction compensation: better than 0.1°C.
Resolution
1. For TC input: 1 µV.
2. For RTD input: 10 m
3. For cold junction compensation: better than 0.1°C.
Page 25
22 Chromalox 1603 User's Manual
Calibration Procedure (continued)
All the controllers are originally calibrated at the factory by means of calibrators with high accuracy and resolution. The following is a complete list of calibration symbols:
Code Parameter
tL TC input initial scale value (0 mV) tH TC input full scale value (50 mV) t. TC input check rJ Cold junction compensation rJ. Cold junction compensation check PL RTD input initial scale value (0 ) PH RTD input full scale value (300.00) P. RTD input check
How to Proceed
1.To start calibration, V2 must be OPEN (see Figure 11).
2.Switch on the controller. The display will show CnF.
3.Push pushbutton. The display will show CAL.
4.Push the FUNC pushbutton to display the first calibration code.
5.Depress FUNC pushbutton in sequence until the desired calibration code is reached.
TC Input Initial Scale Value
1.Provide connections between calibrator and controller under test as shown in Figure 12.
2.“OFF” will show on the upper display, while “tL” will appear on the lower display.
3.Set calibrator to 0.000 mV. Push pushbutton. The upper display will change to “ON”.
4.After 30 seconds, start calibration by pushing FUNC pushbutton. Only the decimal point of the last significant digit will light to indicate that the controller is performing the calibration routine. At the end of this calibration routine, the controller will go to the next parameter.
Figure 12
3
2
+
-
RTD Calibration only:
If only calibrating RTDs, press FUNC until the “PL” parameter is displayed and proceed to page 24 (PL) for further instructions.
Page 26
Chromalox 1603 User's Manual 23
tH-TC Input—Full Scale Value
1. After “tL” is calibrated, the 1603 will display “tH” for the full scale value.
2. Set the calibrator to 50.000 mV (full scale value).
3. Push pushbutton. The upper display will show “ON”.
4. After 30 seconds, start calibration by pushing the FUNC pushbutton. Only the decimal point of the last significant digit will light to indicate that the controller is performing the calibration routine. At the end of this calibration routine, the controller will go the next step.
TC Input Check
000 t. 3 0
1. Check the zero calibration by setting the calibrator to
0.000 mV. The readout must be t.00 000 ± 10 counts.
2. Check linearity at half scale by setting 25.000 mV on the calibrator. The readout must be “t 15 000” ± 10 counts.
3. If linearity is incorrect, repeat thermocouple calibration.
4. Push the FUNC pushbutton. “OFF” and “rJ” will appear on the display.
RJ—Cold Junction Compensation Note:
Make sure that tL and tH parameters are correctly calibrated before rJ calibration.
1. Measure the temperature close to terminals 1 and 3 using an instrument with accuracy better than 0.1°C (see Figure 13).
2. Wait a few minutes to allow the temperature to stabilize over the entire system.
3. “rJ” and “OFF” are being displayed. Using and pushbuttons, set a value equal to the temperature measured by the measuring device in a tenth of °C.
The display will show “t” followed by a number showing the measured value in counts.
With the calibrator set to 50.000 mV, the calibration is correct if the indication is “t.30 000” ± 10 counts.
Page 27
24 Chromalox 1603 User's Manual
RJ—Cold Junction Compensation (continued)
4.Start calibration by pushing the FUNC pushbutton. Only the decimal point of the last significant digit will light to indicate that the controller is performing the calibration routine. At the end of this calibration routine, the controller will go to the next calibration step.
Figure 13
1
3
+
Measuring
Device
Cold Junction Compensation Check
The display will show “rJ.” and the temperature, in tenths of °C, measured by the CJ compensator. Make sure that the display readout is equal to the value read on the measuring device. Push the FUNC pushbutton. The controller will go to the next parameter.
PL—RTD Input Initial Scale Value
1.Connect a resistor box as shown in Figure 14.
2.Set 0.00 on the resistor box.
3.Push pushbutton. The upper display will show “ON”.
4.After 30 seconds, start calibration by pushing FUNC pushbutton. Only the decimal point of the last significant digit will light to indicate that the controller is performing the calibration routine. At the end of this calibration routine, the controller will go to the next parameter.
Figure 14
1
2
3
TC Calibration only:
Thermocouple calibration is now complete, if RTD calibration is not needed. Press FUNC until “CAL” is displayed. See Step 5 on page 25.
Page 28
Chromalox 1603 User's Manual 25
PH—RTD Input Full Scale Value
1. Set the resistance box to 300.00 Ω.
2. Push pushbutton. The upper display will show “ON”.
3. Wait 30 seconds then push the FUNC pushbutton. Only the decimal point of the last significant digit will light to indicate that the controller is performing the calibration routine. At the end of this calibration routine. The controller will go to the next parameter.
P.—RTD Input Check
1. The display will show “P.” followed by a number showing the measured value in counts.
000 P. 3 0
Set the resistance box to 300.00 . The calibration is correct if the indication is “P. 30 000” ± 10 counts.
2. Check the zero calibration by setting 0.00 on the resistance box. The readout should be “P. 00 000” ± 10 counts.
3. Check linearity using the table below. The relationship between input signal and counts for
RTD input is not linear. The correct relationship is shown in the following table:
4. If linearity is incorrect, repeat RTD calibration.
5. Push the FUNC pushbutton. The calibration procedure is terminated and the display
will show “CAL”. When it is desired to go to the configuration procedure, depress the pushbutton and the display will show “CnF” and the controller is in configuration mode. If the previous configuration is correct, switch the controller OFF and set the switch V2.
Resistor Box Display
Counts
00 ± 10 counts 100 10 153 ± 10 counts 200 20 151 ± 10 counts 300 30 000 ± 10 counts
Page 29
26 Chromalox 1603 User's Manual
Warranty And Limitation Of Remedy And Reliability
Chromalox warrants only that the Products and parts manufactured by Chromalox, when shipped, and the work performed by Chromalox when performed, will meet all applicable specification and other specific product and work requirements (including those of performance), if any, and will be free from defects in material and workmanship under normal conditions of use. All claims for defective or nonconforming (both hereinafter called defective) Products, parts or work under this warranty must be made in writing immediately upon discovery, and in any event, within three (3) years from delivery, however all claims for defective Products and parts must be made in writing no later than three (3) years after shipment by Chromalox. Defective and nonconforming items must be held by Chromalox’s inspections and returned to the original f.o.b. point upon request. THE FOREGOING IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES WHATSOEVER, EXPRESS, IMPLIED AND STATUTORY, INCLUDING, WITHOUT LIMITATION, THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE.
Notwithstanding the provisions of this WARRANTY AND LIMITATIONS Clause, it is specifically understood that Products and parts not manufactured and work not performed by Chromalox are warranted only to the extent and in the manner that the same are warranted to Chromalox by Chromalox’s vendors, and then only to the extent that Chromalox is reasonably able to enforce such a warranty, it being understood Chromalox shall have no obligation to initiate litigation unless buyer undertakes to pay all cost and expenses therefore including but not limited to attorney’s fees, and indemnifies Chromalox against any liability to Chromalox’s vendors arising out of such litigation.
Upon buyer’s submission of a claim as provided above and in its substantiation, Chromalox shall at its option either (i) repair or replace its Products, parts or work at the original f.o.b. point of delivery or (ii) refund an equitable portion of the purchase price.
The foregoing is Chromalox’s only obligation and buyer’s exclusive remedy for breach of warranty, and is buyer’s exclusive remedy against Chromalox for all claims arising hereunder or relating hereto whether such claims are based on breach of contract, tort (including negligence and strict liability) or other theories, buyer’s failure to
Page 30
Chromalox 1603 User's Manual 27
submit a claim as provided above shall specifically waive all claims for damages or other relief, including but not limited to claims based on latent defects. In no event shall buyer be entitled to incidental or consequential damages and buyer should hold Chromalox harmless therefrom. Any action by buyer arising hereunder or relating hereto, whether based on breach of contract, tort (including negligence and strict liability) or other theories, must be commenced within three (3) years after the date of shipment or it shall be barred.
Returns
Items returned to Chromalox Instruments and Controls must be accompanied by a Return Authorization Number. This number may be obtained from Chromalox Instruments and Controls, Customer Service Department, Telephone Number (615) 793-3900. It should appear on the exterior of the shipping carton and on the shipping documents. Defective items will be repaired or replaced at our option, at no charge.
Return the defective part or product, freight prepaid, to:
Chromalox Instruments and Controls 1382 Heil-Quaker Blvd. LaVergne, TN 37086-3536
Page 31
28 Chromalox 1603 User's Manual
Page 32
Chromalox
®
INSTRUMENTS AND CONTROLS
1382 HE IL QUAKER BOULEVARD
LAVERGNE, TN 37086-3536
PHO NE (615) 793-3900
FAX (615) 793-356 3
WIEG AN D IN DU STRIAL D IVIS IO N
EM ERSON E LECTR I C CO.
®
Loading...