Chromalox 1020, 1030 Installation & Operation Manual

Page 1
Installation & Operation Manual
1020 & 1030
Temperature Controllers
PK552
0037-75578
August 2018
i
Page 2
Page 3
Safety and Warranty Information
Products covered in this issue of the manual: 1020 & 1030 Process and Over-Temperature Controllers.
This manual supplements the Quick Start Product manual supplied with each instrument at the time of shipment. Information in this installation, wiring and operation manual is subject to change without notice. Copyright © August 2015, Chromalox Corporation, all rights reserved. No part of this publication may be re­produced, transmitted, transcribed or stored in a re­trieval system, or translated into any language in any form by any means without the written permission of Chromalox.
Copies of this manual are available in electronic format on the Chromalox web site (www.chromalox.com) .
THE INTERNATIONAL HAZARD SYMBOL IS IN­SCRIBED ADJACENT TO THE REAR CONNEC­TION TERMINALS
IT IS IMPORTANT TO READ THIS MANUAL BE­FORE INSTALLING OR COMMISSIONING THE UNIT.
WARNING: PRODUCTS COVERED BY THIS MAN­UAL ARE SUITABLE FOR INDOOR USE, INSTAL­LATION CATEGORY II, POLLUTION CATEGORY
2 ENVIRONMENTS
THIS SYMBOL MEANS THE EQUIP­MENT IS PROTECTED THROUGHOUT BY DOUBLE INSULATION.
Warranty and Returns Statement
These products are sold by Chromalox under the war­ranties set forth in the following paragraphs. Such war­ranties are extended only with respect to a purchase of these products, as new merchandise, directly from Chromalox or from a Chromalox distributor, represen­tative, or reseller and are extended only to the first buyer thereof who purchases them other than for the purpose of resale.
Warranty
These products are warranted to be free from function­al defects in material and workmanship at the time the products leave Chromalox factory and to conform at that time to the specifications set forth in the relevant Chromalox instruction manuals sheet or sheets, for such products for a period of three years.
THERE ARE NO EXPRESSED OR IMPLIED WAR­RANTIES, WHICH EXTEND BEYOND THE WARRAN­TIES HEREIN AND ABOVE SET FORTH. CHROMAL­OX MAKES NO WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE PRODUCTS.
Limitations
Chromalox shall not be liable for any incidental damag­es, consequential damages, special damages, or any other damages, costs or expenses excepting only the cost or expense of repair or replacement as described above. Products must be installed and maintained in accordance with Chromalox instructions. There is no warranty against damage to the product resulting from corrosion. Users are responsible for the suitability of the products to their application. For a valid warranty claim, the product must be returned carriage paid to the supplier within the warranty period. The product must be properly packaged to avoid damage from Electrostatic Discharge or other forms of harm during transit.
Page 4
Table of Contents
Contents Page Number
Safety & Warranty .................................................................................................................................................. iii
Chapter 1 Installation ............................................................................................................................................. 1
1.1 Unpacking .................................................................................................................................................... 1
1.2 Cleaning ....................................................................................................................................................... 1
1.3 Installation .................................................................................................................................................... 1
Chapter 2 Electrical Installation ............................................................................................................................ 2
2.1 Installation Considerations .......................................................................................................................... 2
2.2 AC Power Wiring .......................................................................................................................................... 2
2.3 Wire Installation ............................................................................................................................................ 2
2.4 Use of Shielded Cable ................................................................................................................................. 2
2.5 Noise Suppression at Source ...................................................................................................................... 2
2.6 Sensor Placement ........................................................................................................................................ 3
2.7 Panel Wiring ................................................................................................................................................. 3
2.8 Terminal Wiring ............................................................................................................................................ 4
2.9 Power Connection ....................................................................................................................................... 4
Chapter 3 Powering Up .......................................................................................................................................... 7
3.1 Powering Up Procedure ............................................................................................................................... 7
3.2 First Power Up or Factory Default ............................................................................................................... 7
3.3 Auto-Tune .................................................................................................................................................... 7
3.4 Front Panel ................................................................................................................................................... 7
3.5 General Navigation & Editing ....................................................................................................................... 8
3.6 Mode (or Menu) Structure ............................................................................................................................ 8
3.7 Returning to Perator Mode .......................................................................................................................... 8
3.8 Mode and Access and Lock Codes ............................................................................................................. 8
3.9 Use of the Controller for Non-Temperature Applications.............................................................................8
3.10 Controller Transmitter Function ................................................................................................................. 8
3.11 User Mode & Screens on Standard & Extruction models .......................................................................... 9
3.12 Warnings & Messages ............................................................................................................................ 10
Chapter 4 Initial Default Settings ........................................................................................................................ 12
4.1 Factory Reset Procedure ........................................................................................................................... 12
Chapter 5 Setup Mode ......................................................................................................................................... 13
5.1 Navigating the Setup Screens ................................................................................................................... 13
Chapter 6 Advanced Configuration Mode ......................................................................................................... 15
Chapter 7 User Mode ........................................................................................................................................... 16
7.1 User Menu ................................................................................................................................................. 16
7.2 Input Menu ................................................................................................................................................. 17
7.3 User Calibration Menu ............................................................................................................................... 18
7.4 Outputs Menu ............................................................................................................................................ 18
7.5 Control Menu (Standard Model) ................................................................................................................. 19
7.6 Control Menu (Extrusion Model) ................................................................................................................ 20
7.7 Setpoint Menu (Standard Model) ............................................................................................................... 21
7.8 Setpoint Menu (Extrusion Model) .............................................................................................................. 21
7.9 Alarm Menu ................................................................................................................................................ 22
7.10 Communications Menu ............................................................................................................................ 22
7.11 Display Menu ........................................................................................................................................... 23
7.12 Operator Screens Menu ........................................................................................................................... 23
7.13 Information Menu ..................................................................................................................................... 23
7.14 Exiting the Advanced Configuration Mode .............................................................................................. 23
iviv
Page 5
Contents Page Number
Chapter 8 Calibration Mode ................................................................................................................................ 24
8.1 Single Point Calibration (PV Offset) ........................................................................................................... 24
8.2 Two Point Calibration ................................................................................................................................. 24
8.3 Base Input Calibration ............................................................................................................................... 25
8.4 Calibration Check ...................................................................................................................................... 25
8.5 Base Calibration Procedure ....................................................................................................................... 26
8.6 Calibrating the mV Input ............................................................................................................................ 25
8.7 Calibrating Other Input Types .................................................................................................................... 26
8.8 Calibration Input States ............................................................................................................................. 26
8.9 Calibration Progress .................................................................................................................................. 26
8.10 Calibration Modbus Addresses ............................................................................................................... 26
Chapter 9 Automatic Tuning ................................................................................................................................ 27
9.1 Running the Pre-Tune ................................................................................................................................ 27
9.2 Running Tune at SP ................................................................................................................................... 27
9.3 Tuning at SP Troubleshooting .................................................................................................................... 27
9.4 Tuning at SP for Heat and Cool ................................................................................................................. 28
Chapter 10 Digital Input Operation ..................................................................................................................... 29
Chapter 11 Timer Feature .................................................................................................................................... 31
11.1 Timer Feature ........................................................................................................................................... 31
11.2 Delay, Ramp & Timer Diagram ................................................................................................................. 31
Chapter 12 Extrusion Model Only Features ....................................................................................................... 32
12.1 Non-Linear Cooling Function ................................................................................................................... 32
12.2 Method ..................................................................................................................................................... 32
12.3 Parameter Adjustment ............................................................................................................................. 34
12.4 Soft Start Function ................................................................................................................................... 34
12.5 Extrusion Only Parameters in the Control Menu...................................................................................... 35
Chapter 13 Limiter Models .................................................................................................................................. 36
13.1 Introduction to the Limiter Model ............................................................................................................ 36
13.2 Limiter Modbus Communications ............................................................................................................ 36
13.3 Limiter Digital Input .................................................................................................................................. 36
13.4 Limiter Operator Mode & Screens ........................................................................................................... 37
13.5 Limiter Output Latching ........................................................................................................................... 37
13.6 Limiter Setup Mode Parameters .............................................................................................................. 37
13.7 Limiter Advanced Configuration Parameters ........................................................................................... 40
13.8 Limiter Input Menu ................................................................................................................................... 40
13.9 Limiter User Calibration Menu ................................................................................................................. 40
13.10 Limiter Outputs Menu ............................................................................................................................ 41
13.11 Limiter Communications Menu .............................................................................................................. 43
13.12 Limiter Display Menu ............................................................................................................................. 43
13.13 Limiter Information Menu ....................................................................................................................... 43
13.14 Limiter Exiting from Advanced Configuration Mode .............................................................................. 43
Chapter 14 Configuration Software .................................................................................................................... 44
14.1 Introduction .............................................................................................................................................. 44
14.2 Connectivity Requirements ...................................................................................................................... 44
14.3 Installing & Accessing the Configuration Program .................................................................................. 45
14.4 Getting Started ........................................................................................................................................ 45
14.5 Troubleshooting the Series 20 Configurator ............................................................................................ 46
14.6 Getting Started (continued) ...................................................................................................................... 47
14.7 Navigating the Configurator ..................................................................................................................... 48
vv
Page 6
Contents Page Number
Chapter 15 Serial Communications .................................................................................................................... 51
15.1 Supported Protocol ................................................................................................................................. 51
15.2 RS485 Configuration ................................................................................................................................ 51
15.3 RS485 Device Addressing ....................................................................................................................... 51
15.4 Link Layer ................................................................................................................................................. 51
15.5 Supported Modbus Functions ................................................................................................................. 52
15.6 Function Descriptions .............................................................................................................................. 52
15.7 Function 03/04 Read Holding/Input Registers ........................................................................................ 52
Chapter 16 Modbus Addresses ........................................................................................................................... 54
16.1 Input Parameters ..................................................................................................................................... 54
16.2 Standard Extrusion Modbus Addresses .................................................................................................. 55
16.3 Limiter Modbus Addresses ...................................................................................................................... 63
Chapter 17 Specifications ................................................................................................................................... 68
Chapter 18 Glossary ............................................................................................................................................. 70
Chapter 19 Order Tables ...................................................................................................................................... 78
vi
Page 7
1 Installation
)
4.76”
1.1 Unpacking
Carefully remove the product from its packing. Please retain the packing for future use.
A single sheet concise manual is also supplied in one or more languages. Examine the delivered items for damage or defects. If any are found, contact your sup­plier immediately.
1.2 Cleaning
Clean the front panel by wiping down with a dry cloth. Never allow water or any other substances to ingress into the instrument.
1.3 Installation
Installation should only be performed by tech­nically competent personnel. It is the respon­sibility of the installing engineer to ensure that the configuration is safe. Local regulations regarding electrical installation & safety must be observed (e.g. US National Electrical Code (NEC) or Canadian Electrical Code.
This instrument is designed for indoor back of panel use.
(121 mm)
3.90”
(99 mm)
4.84”
(123 mm)
This equipment is protected throughout by double insulation, when installed properly. This type of installation does not need an earth connection, but it is vital for safety reasons, that the instrument is replaced if the instru­ment housing is broken.
The optional bus connection should be slid onto the DIN Rail before fitting the 1020/1030 Rail.
The connectors must be pushed together to share the bus.
0.89”
(22.5 mm)
4.21”
(107 mm
This bus connection links up the optional RS485 com­munications connections without extra wiring but does not supply power.
Ensure there is adequate air flow inside the panel to prevent overheating.
11
Page 8
2 Electrical Installation
The installation should be only performed by technically competent personnel.
It is the responsibility of the installing engineer to ensure that the configuration is safe.
Local Regulations regarding electrical installa­tion & safety must be observed (e.g. US Nation­al Electrical Code (NEC) or Canadian Electrical Code).
2.1 Installation Considerations
Ignition transformers, arc welders, motor drives, me­chanical contact relays and solenoids are examples of devices that generate electrical noise in typical indus­trial environments.
The following guidelines MUST be followed to mini­mise their effects.
If the instrument is being installed in existing equip­ment, the wiring in the area should be checked to en­sure that good wiring practices have been followed. Noise-generating devices such as those listed above should be mounted in a separate enclosure.
If this is not possible, separate them from the instru­ment, by the largest distance possible.
If possible, eliminate mechanical contact relays and replace with solid-state relays. If a mechanical relay cannot be replaced, a solid-state relay can be used to isolate the instrument.
A separate isolation transformer to feed only the in­strumentation should be considered. The transformer can isolate the instrument from noise found on the AC power input.
2.2 AC Power Wiring - Neutral (for 100 to 240V AC versions)
It is good practice to ensure that the AC neutral is at or near ground (earth) potential. A proper neutral will help ensure maximum performance from the instrument.
2.3 Wire Isolation
Four voltage levels of input and output wiring may be used with the unit:
• Analogue input (for example thermocouple, RTD, VDC, mVDC or mADC)
• Relays outputs
• SSR Driver outputs
• AC power
The only wires that should run together are those of the same category.
If any wires need to run parallel with any other lines, maintain a minimum space of 6” between them. If wires MUST cross each other, ensure they do so at 90 de­grees to minimize interference.
2.4 Use of Shielded Cable
All analog signals must use shielded cable. This will help eliminate electrical noise induction on the wires. Connection lead length must be kept as short as pos­sible keeping the wires protected by the shielding. The shield should be grounded at one end only. The pre­ferred grounding location is at the sensor, transmitter or transducer.
2.5 Noise Suppression at Source
Usually when good wiring practices are followed, no further noise protection is necessary. Sometimes in severe electrical environments, the amount of noise is so great that it must be suppressed at source. Many manufacturers of relays, contactors, etc. will supply ‘surge suppressors’ which mount on the noise source. For those devices that do not have surge suppressors supplied, Resistance-Capacitance (RC) networks and/ or Metal Oxide Varistors (MOV) may be added.
2
Page 9
Inductive coils: - MOVs are recommended for tran­sient suppression in inductive coils, connected in par­allel and as close as possible to the coil. Additional protection may be provided by adding an RC network across the MOV.
Figure 5. Contacts: - Arcing may occur across con­tacts when they open and close. This results in electri­cal noise as well as damage to the contacts. Connect­ing a properly sized RC network can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm resistor and 0.1 microfarad capacitor (1000 volts) is recommended. For circuits from 3 to 5 amps, connect two of these in parallel.
2.6 Sensor Placement (Thermocouple or
RTD)
If the temperature probe is to be subjected to corrosive or abrasive conditions, it must be protected by an ap­propriate thermowell. The probe must be positioned to reflect true process temperature: In a liquid media, the most agitated area. In air, the best circulated area.
The placement of probes into pipe work some distance from the heating vessel leads to trans­port delay, which results in poor control.
For a two wire RTD a wire link should be used in place of the third wire. Two wire RTDs must only be used with lead lengths less than 3 meters (10 ft.). Use of three wire RTDs is strongly recommended.
2.7 Panel Wiring
In general, all wiring connections are made to the in­strument after it is installed. Copper wires must be used for all connections (except thermocouple signal wires).
To avoid electrical shock, AC power wiring must not be connected to the source distribu­tion panel until all wiring procedures are com­pleted.
Check the information label on the case to de­termine the correct voltage before connecting to a live supply.
3
Page 10
2.8 Terminal Wiring
The diagram shows all possible option combinations. Please check the product configuration before wiring. Dedicated Configuration Socket (on bottom of the in­strument)
The wiring label shows the power requirements, con­nector positions and terminal number.
This example is:
TOP 1 & 2 Rear = RS485 Comms 3 & 3 Rear = Linear Out 3 5 & 6 Front = SSR Driver Out 2 7 & 8 Front = 100-240VAC power.
BOTTOM 9 & 10 Rear = Digital Input 11, 12 Rear & 16 Front = Relay Out 1 13, 14 & 15 Front = Process Input
2.9 Power Connection
To avoid damaging your instrument it is critical the power connection is made to the correct terminals
Power is connected to pins 7 & 8. Top, rear connector on the right-hand side. (front connector omitted from picture for clarity)
The green LED shows when power is correctly con­nected.
NEVER DIRECTLY CONNECT THIS SOCKET TO A USB PORT.
A configuration socket to USB adaptor can be obtained from your supplier.
4
Page 11
1020/1030 Rail Isolation Chart
Universal
PSU
PSU
Input Relay SSR Linear
RS485
Comms
Non-
Isolated
Digital
Input
Isolated
Digital
Input
Configuration
Port
Universal Input
Relay
SSR
Linear
RS485 Comms
Non-Isolated Digital Input
Isolated Digital Input
Configuration Port
Not Applicable
No Isolation
Reinforced Isolation
5
Page 12
1020/1030 Input & Output Map
Relay COM / Linear +
Relay COM / Linear +
Relay NO / Linear -
-
+
Relay COM / Linear +
Relay NO / Linear -
Relay COM / SSR -
Relay NO / SSR+
L +
N -
Relay COM / Linear +
Relay NO / Linear -
Relay COM / SSR -
Relay NO / SSR+
L +
N -
Relay COM / Linear +
Relay NO / Linear -
+
-
Volt-free or TTL compatible
Relay COM / SSR -
Relay NO / SSR+
Relay NC
L +
N -
Relay COM / Linear +
Relay NO / Linear -
+
-
Volt-free or TTL compatible
Relay COM / SSR -
Relay NO / SSR+
Relay COM / SSR -
Relay NO / SSR+
Relay NC
Use cables with 80°C minimum temperature rating, conductor sizes 30-12 AWG
1
2
3
4
5
6
7
8
9
10
16
11
12
RS485 A (Rx/Tx+)
RS485 B (Rx/Tx-)
Relay NO / Linear -
Relay COM / SSR
Relay NO / SSR+
+
Volt-free or TTL compatible
-
Relay COM / SSR -
Relay NO / SSR+
Output 3 – Standard & Extrusion
models
Output 2 – Standard & Extrusion
models
L
Power – low power or mains (hardware dependent)
N -
Output 1 – Standard and
Extrusion models
Communications
Output 3 (Alarm 2 or Retx PV) –
Limiter model
Alarm 1 output – Limiter model
Digital Input
Limit output – Limiter model
(Relay only)
13
14
15
RTD
TC / RTD / Linear
TC / RTD / Linear
Input – thermocouple, RTD or linear
6
Page 13
3 Powering Up
ENSURE SAFE WIRING PRACTICES HAVE BEEN FOLLOWED. WHEN POWERING UP FOR THE FIRST TIME, DISCONNECT THE OUTPUT CON­NECTIONS.
3.2 First Power Up or Factory De-
fault
When the unit is initially powered up or the user restores the factory defaults to the device, it immediately enters the Setup menu without requiring an unlock code. The user must then cycle through every parameter, to either view or adjust the value, and then exit the menu.
Check carefully the supply voltage and connec­tions before applying power.
The instrument must be powered from a supply accord­ing to the wiring label on the side of the unit. (100vac to 240Vac, or 24 Vac/dc depending upon the model purchased.)
3.1 Powering Up Procedure
At power-up, a self-test procedure is run, during which a product logo screen is displayed.
When powering up for the first time the instrument starts up in the Setup Mode after the product logo screen is displayed.
You must complete the Setup by cycling through all of the parameters before using the device for the first time.
1. Use or to review every parameter.
2. Change value if necessary using , then use or to adjust the value, then to save.
3. Exit Setup by pressing & together.
If the above steps are not followed the Setup has not been completed so the device will go into Setup, again, on every subsequent power up.
3.3 Auto-Tune
The controller can be auto-tuned from the Setup Mode.
1. Pre-tune
2. Auto-tune at setpoint
Auto-Tuning will not engage if:
• Controller is set to On/Off Control
• Setpoint is ramping
• PV is within 5% of the input range from setpoint
3.4 Front Panel
Display shows PV (process variable), units, SP (setpoint), alarm/latch statuses, error & warning messages.
By default, the display turns off after 5 minutes without any key presses.
3 navigation keys:
Ok/Select
Up
Down
This is configurable in the Advanced Configuration, in the Display sub­menu, parameter Screen Timeout. Any key press turns the display back on.
Standard: 3 Output Status LEDs
1 2 3
Extrusion: 3 Status LEDs for: Heat Cool Alarm
7
Limiter: 3 Status LEDs for
LM EX AL
Page 14
3.5 General Navigation & Editing
• Press or keys to navigate between param­eters or menu items.
• Press to highlight a parameter value, ready for editing.
• Press or to change the parameter val­ue, then press within 60 seconds to confirm change.
3.6 Mode (or Menu) Structure
There are 3 main modes (or menus) on the device – Setup and Advanced Configuration Mode.
• User Mode - the live screen used for normal op­eration. The process variable can always be seen in this mode
• Setup Mode – allows access to the most important parameters
• Advanced Configuration Mode - access all param­eters via sub-menus
Setup Mode - press & .
Advanced Configuration - press & .
Never connect the instrument’s configuration socket directly to a USB port as it will damage the controller.
3.7 Returning to Operator Mode
3.9 Use of the Controller for Non­Temperature Applications
In the majority of applications this controller will be used for temperature sensing, either via a sensor or a linear DC input, which use heat and cool. However this controller can be used for other types of processes.
If your process is not a temperature then the param­eters labelled as “HEAT”refer to reverse acting outputs used to increase the process value and “COOL” to de­crease the process value.
As an example you may have a system that reads and controls humidity. The “HEAT” output drives the hu­midifier and the “COOL” output drives the de-humidifi­er. Use the “HEAT” parameters to control the humidifier and the “COOL” parameters to control the de-humid­ifier.
Often the “HEAT” and “COOL” is referred to as “Pri­mary” and “Secondary” on other controllers.
3.10 Controller Transmitter Function
The Standard 1020 & 1030 model can be used as a “transmitter” to retransmit the process value or con­troller setpoint via Output 3, if the linear option is fitted. The parameter Usage in the Linear Output sub-menu can be set to PV Retransmit or SP Retransmit.
In the Display menu, the parameter Transmitter can be used to enable Transmitter view. This hides the Set­point from view.
Control functions will remain active if they have been configured.
Press & to move back one level
From a sub-menu you will need to do this twice; once to return to Advanced Configuration Mode then again to exit. After 120 seconds without key presses the unit returns automatically to the first Operator mode screen.
3.8 Mode Access and Lock Codes
Separate lock codes can be set for the Setup mode and for the Advanced Configuration mode.
• Setup mode lock code – default 10.
• Advanced Configuration mode lock code – default
20.
Hold the button while powering up for a read-only view of lock codes.
8
Page 15
3.11 User Mode & Screens on Standard & Extrusion models
User Screen Temperature Unit.
PV – process variable (e.g. process temperature) SP - Setpoint
Manual control
Transmitter screen is present on Standard model only.
Important: The following parameters are only displayed if set to “Show” in the User sub-menu.
Alarm State
Latch State
PV – process variable (e.g. process temperature) Manual Power is shown as P%.
Transmitter parameter = Enable, SP is hidden.
The device still functions as a controller
To act as a PV transmitter the parameter Usage in the Linear Output sub-menu needs to be set to PV Re­transmit.
Alarm triggered
Alarm configured, but not triggered
– Alarm not set
Output Latched
Latch configured, but
output not Latched
using the local Setpoint.
To clear press
to select Yes.
Press to accept.
then
– Latch not set
Maximum PV
Minimum PV
Screens show the Maximum & Minimum PV reached.
Control Enable OFF - Control output(s) disabled. (Ignored when in manual mode).
ON - Control output(s) enabled.
Manual Control Enable OFF - Automatic control, PID or On-Off control available.
ON - Manual control, Manual Power shown as P% xxx
Time On Remaining On Timer Visible when On Timer is active.
See Ramp & Timers diagram.
Delay Time Remaining Delay Timer Visible when Delay Timer is active.
See Ramp & Timers diagram.
9
To clear press then
to select Yes.
Press
to accept.
Page 16
3.12 Warnings & Messages
Pop-Up Alerts
Pop-up alerts appear in front of the current screen. They must be acknowledged before you can access other screens.
Pop-Up Alert List
Message Description
Press
& together to clear the pop-up alert.
Alarm 1
Alarm 2
Alarm 1 & 2
Control Enabled
Calibration Pass
Calibration Fail
Tuning in Progress
Setup not completed
Offset in use
Limit Exceeded
Tune Error
PV within 5% of SP
Tune Error
Setpoint is ramping
Tune Error
Control is ON/OFF
Tune Error
Control is manual
Tune Error
Tune at Setpoint not able to run
Tune Error
Sensor Break
Tune Error
Timer Running
Alarm 1 is active.
Alarm 2 is active.
Alarm 1 and 2 are active.
Alerts user that the control is re-enabled. (not Limiter.)
Factory calibration (Full Input Calibration has passed.)
Factory calibration (Full Input Calibration has failed.)
Tune at Setpoint or Pre-Tune is running. (Not Limiter.)
Please refer to First Power Up or Factory Default section.
SP offset is being used in Setpoint sub-menu.
Limiter only, indicates when the limit value has been exceeded.
PV within 5% of the scale range input from SP (for Pre-Tune). Try a different setpoint or narrow the scale range input.
Setpoint is ramping. Turn off ramping and try again.
Control is not set to PID, i.e. the proportional band = 0. Set the proportional band to any other value and try again.
Manual control enabled. Set Manual Control Enable to OFF and try again.
Tune at setpoint has timed out or cannot run.
Check your sensor.
Timer Running. Set the Enable Timer parameter to Disabled.
10
Page 17
Message List
Message Description
ALARM
LATCH
LIMIT
HIGH
LOW
OPEN
ERROR
TUNE
P%
Ramp
Alternates with PV and shows one, or both, Alarms are active.
Alternates with PV, one or more outputs are latched on & no alarm is active.
On Limiter model, alternates with PV to show Limit is active.
Process variable input >5% over-range. Check for possible issues with sensor or connections. Also, check that Scale Range Maximum is high enough for your application.
Process variable input >5% under-range. Check for possible issues with sensor or connections. Also, check that Scale Range Minimum is low enough for your application.
Break detected in process variable input sensor, wiring or wrong input type selected. Shows OPEN until resolved, Control is disabled on Standard or Extrusion models), or Limit state set until resolved on Limiter model.
Selected input range is not calibrated. Shows ERROR until resolved. Control is disabled on Standard or Extrusion models), or Limit state set until resolved on Limiter model.
Alternating with SP shows Auto-tuning is in progress.
Manual power value replaces setpoint, shows P% xxx of power.
Setpoint ramp is active (alternates with actual setpoint).
Control is disabled. Control output(s) are off.
OFF
Enable control by setting Control Enable to ON or check state of the Digital Input if Digital I/P Action is set to Ctrl Enable/Disable.
DELAY
Shows when Delay Timer is active, control is off until the timer finishes.
The Automatic Tuning parameter must be changed to Off to clear any tuning message. Display alternates between the tuning code & setpoint
tErr1
tErr2
tErr3
tErr4
tErr5
tErr6
tErr7
tErr8
PV within 5% of the scale range input from SP (for Pre-Tune). Try a different setpoint or narrow the scale range input.
Setpoint is ramping.
Control is ON/OFF. Control is not set to PID, i.e. the proportional band = 0.
Control is manual. Set Manual Control Enable to OFF.
Tune at Setpoint not able to run.
Sensor Break.
Timer Running. Set the Enable Timer parameter to Disabled before attempting to run tuning again.
Control is disabled. Please check it is safe to enable control and then go to the User menu to change Control Enable to ON.
11
Page 18
4 Initial Default Settings
Your 1020 & 1030 Process and Over-temperature Con­troller will arrive with specific factory settings. If at any point the factory default process is performed, all the parameters will be returned to the values shown below.
4.1 Factory Reset Procedure
Press to highlight NO.
Press to move highlight to YES.
Press to accept.
A confirmation screen appears.
If you are sure press to show YES (leave as NO to cancel).
Press to confirm your choice.
The instrument shows the default for the Input Type and its default value.
The Reset to Defaults can be found in the sub-menu Display in the Advanced Configuration on all models.
The user must review all parameters in the Set-up menu before exiting.
12
Page 19
5 Setup Mode
5.1 Navigating the Setup Screens
To access the Setup Mode from User Mode, press & together. Enter code for Setup Lock (default = 10) using & , then press .
Lock Code 10 Lock code to enter Setup Mode. Default is 10
Parameter Name Description Meaning & Visibility
Input Type
-200 to 1200ºC
-328 to 2192ºF
-240 to 1373ºC
-400 to 2503ºF
-199 to 800ºC
-328 to 1472ºF
100 to 1824ºC 211 to 3315ºF B Thermocouple
0 to 2320ºC 32 to 4208ºF C Thermocouple
0 to 762ºC
32 to 1403ºF
0 to 1399ºC 32 to 2551ºF N Thermocouple
0 to 1795ºC 32 to 3198ºF R Thermocouple
0 to 1762ºC 32 to 3204ºF S Thermocouple
-240 to 400ºC
-400 to 752ºF
0 – 50mV** 0 – 50mV**
10 – 50mV 10 – 50mV
-128.8 to 537.7ºC
-199.9 to 999.9ºF
-128.8 to 537.7ºC
-199.9 to 999.9ºF
-128.8 to 537.7ºC
-199.9 to 999.9ºF
0.0 to 537.7ºC
32.0 to 999.9ºF
-128.8 to 400.0ºC
-199.9 to 752.0ºF
0 – 20mA 0 – 20mA
4 – 20mA 4 – 20mA
0 – 5V 0 – 5V
1 – 5V 1 – 5V
0 – 10V 0 – 10V
2 – 10V 2 – 10V
J Thermocouple
K Thermocouple
PT100
L Thermocouple
T Thermocouple
** 0 – 50mV is only linear dc input available on Extrusion models.
Input Units ˚C ˚F Select °C or °F temperature units – Default is °C
Units parameter hidden when linear input is used and units are not shown on the display
Input Decimal Place
0000 00.00 Number of decimal resolution. (2 or 3 decimal
000.0 0.000
places only available.
13
Page 20
Parameter Name Description Meaning & Visibility
Scale Range Up­per Limit
1000 Upper limit of scaled input range. (Only visible in
Setup Mode when a DC linear type is selected). Default is input max.
Scale Range Lower Limit
0 Lower limit of scaled input range. (Only visible in
Setup Mode when a DC linear type is selected). Default is input min.
Input Digital I/P Action
None None, Alarm Reset (clears latched alarms), Ctrl
Enable/Disable (disables control), Ctrl Auto/ Manual, Pre-Tune Start/Stop, Tune at SP Start/ Stop
Output 1 Usage Heat Heat, Cool, Non Linear Cooling (on Extrusion
model only), Alarm 1, Alarm 2, Alm. 1 or 2 (logi­cal ‘OR’ of Alarm 1 & 2), Loop Alarm
Output 2 Usage Alarm 1 Same options as Output 1 Usage
Output 3 Usage Alarm 2 Same options as Output 1 Usage
If a Relay or SSR drive is fitted in Output 3 you will see >Output 3.
If the Linear option is fitted in Output 3 you will see the >Linear Output menus instead.
Linear Output
PV Retx Heat, Cool, PV Retx, SP Retx
Usage
Linear Output Type 0-10V 0-10V, 2-10V, 0-20mA, 4-20mA, 0-5V, 1-5V
Linear Output Scale Range Max.
>Linear Output Scale Range Min.
1373 Maximum PV or SP value corresponding to
maximum linear output for retransmission.
-240 Minimum PV or SP value corresponding to mini­mum linear output for retransmission.
Alarm 1 Adjust 1373 Sets the Alarm 1 value. (Range minimum to
range maximum) OFF disables the alarm. (De­fault alarm type is high alarm)
Alarm 2 Adjust -240 Sets the Alarm 1 value. (Range minimum to
range maximum) OFF disables the alarm. (De­fault alarm type is low alarm)
Setpoint Adjust 0 Target setpoint. Adjustable between setpoint
upper and lower limits Default is 0
Coms Unit
1 Modbus address from 1 to 255
Address
Coms Baud Rate 9600 1200, 2400, 4800, 9600, 19200 & 38400 bps
1. The Start Tune at SP function is not available for
Heat & Cool processes.
2. If the Input Type is changed, input scaling and
alarm values are set to new values based on the maximum and minimum of the new input type. If necessary, review these settings.
3. If necessary, press
& to clear the “Control is
Enabled” Pop Up Alert then press & to exit the Setup mode.
14
Page 21
6 Advanced Configuration Mode
The Advanced Configuration mode gives access to all the parameters accessible from the front panel; how­ever, the device hides parameters that are not relevant to your exact model code specification & configuration.
It may be faster to access some parameters from the Setup Mode.
Lock Code 20
Menu Name Meaning & Visibility
User
Input Set up input sensor and range.
Calibration For entering calibration points.
Outputs Set functions for up to 3 outputs.
Control Control settings for PID, or ON/OFF control, and Auto-tune.
Provides access to User parameters including Control Enabled and Manual Control Enabled parameters.
Press Operator screen.
Enter Advanced Lock-code using & , then press .
& to enter Advanced Configuration from
Lock code to enter Advanced Configuration Mode. Default is 20.
Setpoint Setpoint and timer settings.
Alarm All alarm settings including sensor break alarm.
Comms Modbus address, baud rate and parity - only shown if RS485 option is fitted.
Display Lock code set up and Basic Setpoint Control enable/disable.
Operator Visibility setting for parameters that can be made visible in the User Mode.
Info
Revision level, Firmware version, Serial number and Manufactured date.
15
Page 22
7 User Mode
The normal, live screen showing the PV (process variable) or temperature is called the User Mode.
7.1 User Menu (Applicable to Standard and Extrusion Models)
Parameter Description Default Value
Alarm State
Alarm triggered
Alarm configured, but not triggered – Alarm not set
N/A
Latch State
To clear any latched outputs, press
Maximum PV
Minimum PV
Control Enable OFF - Control output(s) disabled. (Ignored when in man-
Manual Control Enable OFF - Automatic control, PID or On-Off control available.
To clear the stored value, press Yes.
Press to accept.
ual mode). ON - Control output(s) enabled.
ON - Manual control, Manual Power shown as P% xxx
then to select Yes. Press to accept.
Output Latched
Latch configured, but output
not Latched
– Latch not set
then to select
N/A
Screens show the Maximum & Minimum PV reached.
ON
OFF
16
Page 23
7.2 Input Menu (Applicable to Standard and Extrusion Models)
Parameter Description Default Value
Input Type Refer to Input types in the table in the Setup menu sec-
tion for a full list of inputs available.
Units Display Units either °C or °F.
This parameter is hidden when input is a linear type and °C or °F are hidden from the display.
Units hidden when linear input is used and no unit is shown on the display
Decimal Place 0000
000.0
00.00 (not for temperature)
0.000 (not for temperature)
For temperature inputs, enter the maximum working
Scale Range Maximum
Scale Range Minimum
Filter Time
CJC Enable Enable Enables the internal thermocouple CJC (Cold Junc-
Digital I/P Action None
range. For linear inputs, enter the display value for the maximum input level
For temperature inputs, enter the minimum working range. For linear inputs, enter the display value for the minimum input level.
Input filter time value to reduce noise. OFF or 0.5 to 100.0 seconds in 0.5 increments
tion Compensation). Disable Disables the internal CJC. If disabled, external compensation must be provided.
Alarm Reset (clears latched alarms) Ctrl Enable/Disable (disables control) Ctrl Auto/Manual Pre-Tune Start/Stop Tune at SP Start/Stop
K thermocouple
°C
0000
Maximum allowed for
Input Type
Minimum allowed for
Input Type
2.0
Enable
None
The input scale range, consisting of Scale Range Maximum & Scale Range Minimum above, is used to narrow the working range of the controller.
If the measured value is more than 5% above or below the scaled range PV display is replaced by HIGH (over-range) or LOW (under-range).
The scale range also affects if Pre-Tune will run. If the PV is <5% of the scaled range from setpoint Pre-Tune cannot be used.
17
Page 24
7.3 User Calibration Menu (Applicable to Standard and Extrusion Models)
Parameter Description Default Value
Offset Shifts the input value up or down by this offset value,
across the entire range.
Low Point Enter value at which the low point error was measured. Lower Limit
Low Offset Enter equal, but opposite offset value to the observed
low point error.
High Point Enter value at which the high point error was measured. Upper Limit
High Offset
Enter an equal, but opposite offset value to the observed high point error.
0
0
0
7.4 Outputs Menu (Applicable to Standard and Extrusion Models)
Parameter Description Default Value
Output 1 Sub-menu
Heat (Reverse acting control) Cool (Direct acting control) Non Linear Cooling (Extrusion model only)
Usage
Alarm Action
Latching
LED Indicator Direct - LED Indicator lit when output is active
Output 2 Sub-menu
Usage Same options as Output 1 - Usage Alarm 1
Alarm Action Same options as Output 1 - Alarm Action Direct
Latching Same options as Output 1 - Alarm Latching Off
LED Indicator Same options as Output 1 - LED Indicator Direct
Output 3 Sub-menu
If a Relay or SSR drive is fitted in Output 3, this sub-menu is visible.
Usage Same options as Output 1 Usage Alarm 2
Alarm Action Same options as Output 1 - Alarm Action Direct
Alarm Latching Same options as Output 1 - Alarm Latching Off
LED Indicator Same options as Output 1 - LED Indicator Direct
Alarm 1 Alarm 2 Alarm 1 or 2 (i.e. logical ‘OR’ of Alarm 1 & 2) Loop Alarm
Direct - Output active when alarm triggers Reverse - Output active when alarm is not triggered
Off - Alarm doesn’t latch On – Alarm latches (remains in active state until cleared)
Reverse - LED Indicator lit when output is inactive
Heat
Direct
Off
Direct
18
Page 25
Parameter Description Default Value
Linear Output Sub-menu
If the Linear option is fitted in Output 3, this sub-menu is visible.
Heat (Reverse acting control)
Usage
Type
Scale Range Maximum
Scale Range Minimum
Retransmission of PV or SP: PV Retx, SP Retx
Display value at which retransmission output is at its maximum value ( -1999 to 9999)
Display value at which retransmission output is at its minimum value ( -1999 to 9999)
Cool (Direct acting control)
0-10V 2-10V
0-20mA
7.5 Control Menu (For Standard Model only)
Parameter Description Default Value
4-20mA
0-5V 1-5V
PV Retx
0-10V
1000
0
Proportion Heat Band The Proportional Bands for heating and cooling control,
Proportion Cool Band
Auto Reset (Integral) 0.01 to 99.59. and OFF (0.00) (minutes & seconds). 5.00
Overlap/Deadband In display units, range -20 to +20% of Heat & Cool Pro-
Differential (On/Off) Visible when using On-Off control.
Loop Alarm Time Visible when On/Off control & Loop Alarm assigned to an
Manual Reset (Bias) Manual Reset. Biasing of the control working point, 0 to
Heat Cycle Time 0.1 to 512.0 seconds
Cool Cycle Time 32.0
Output Interlock Prevents simultaneous activation of both heat & cool
Heat Power Limit % heating and cooling power upper limits
Cool Power Limit 100%
Power Up Action
Automatic Tuning
in display units. Set to ON/OFF (0) or PID control:
1 to 9999 - 0 decimal places
0.1 to 999.9 - 1 decimal place
0.01 to 99.99 - 2 decimal places
0.001 to 9.999 - 3 decimal places
Possible values/resolution depends on values display
resolution.
portional Band
In display units centred about the setpoint. Range: 0.1% to 10.0% of input span
output. Sets time before the loop alarm triggers. (minutes & seconds)
100%. (-100% to 100% if heat/cool control)
Relay/SSR control output cycle times
outputs. Choose from On or Off. Do not use if PB ‘overlap’ has been set
0 to 100%
Last - Powers up with control enable/disable in the same state as on power off or power failure. On - Always powers up with control enabled.
Off Start Pre-Tune Start Tune at SP
(Not available for Heat & Cool processes.)
161
161
0
8
99.59
25%
32.0
Off
100%
Last
Off
19
Page 26
7.6 Control Menu (For Extrusion Model only)
Parameter Description Default Value
Proportion Heat Band The Proportional Bands for heating and cooling control,
Proportion Cool Band
Auto Reset (Integral) 0.01 to 99.59. (minutes & seconds) and OFF (0.00). 5.00
Overlap/Deadband In display units, range -20 to +20% of Heat & Cool
Differential (On/Off) Visible when using On-Off control.
Loop Alarm Time Visible with On-Off control & Loop Alarm assigned to an
Manual Reset (Bias) Manual Reset. Biasing of the control working point, 0 to
Soft Start Time 0:01 to 60:00 or OFF (0:00) (hours & minutes) OFF
Soft Start Setpoint The setpoint used by the Soft Start.
Heat Cycle Time
Cool Cycle Time 32.0
Output Interlock
Heat Power Limit
Cool Power Limit 100%
Minimum Cooling
Impulse Length
Minimum Off Time
Non Linear Adjust
Power Up Action
Automatic Tuning
in display units. Set to ON/OFF (0) or PID control:
1 to 9999 - 0 decimal places
0.1 to 999.9 - 1 decimal place
0.01 to 99.99 - 2 decimal places
0.001 to 9.999 - 3 decimal places
Possible values/resolution depends on values display
resolution.
Proportional Band. -ve values=Deadband.
In display units centred about the setpoint. Range: 0.1% to 10.0% of input span
output. Sets time before the loop alarm triggers. (minutes & seconds)
100%. (-100% to 100% if heat/cool control)
See Soft Start function section.
0.1 to 512.0 seconds Relay/SSR control output cycle times
Prevents simultaneous activation of both heat & cool outputs. Choose from On or Off. Do not use if PB ‘overlap’ has been set
% heating and cooling power upper limits, adjustable from 0 to 100%
Sets the minimum temperature at which water cooling will activate.
Non-linear cooling pulse time.
0.01 to 99.99 (seconds)
Minimum non-linear cooling pulse time.
0.01 to 99.99 (seconds)
Attenuates effective cooling vs PID cooling power. From 1 to 999.9
Last - Powers up with control enable/disable in the same state as at power off. On - Always powers up with control enabled.
Off Start Pre-Tune Start Tune at SP (Not available for dual Heat & Cool)
161
161
0
8
99.59
25%
-240
32.0
Off
100%
120
10
20
5
Last
Off
20
Page 27
7.7 Setpoint Menu (For Standard Model only)
Parameter Description Default Value
Enabled - Enables the Delay and On Timers. Applies at
Enable Timer
Delayed Start Time
Ramp Rate
On Time
Upper Limit Used to limit the Maximum setpoint value. Scale Range Maximum
Lower Limit Used to limit Minimum setpoint value. Scale Range Minimum
Offset
next power-up or next control enable. Disabled - Delay and On Timers are ignored. (Setpoint ramping still functions.)
Time from power-up or control enable before control be­gins from 00.01 to 99.59 (hours & minutes) or OFF (0.00). If delay is OFF control starts immediately.
Rate the actual setpoint changes from current PV to tar­get setpoint following power-up or control enable. From 0.001 to 9999 (Units / hr) or OFF (10000). Any changes in the setpoint value also follow this rate.
The time the target setpoint will be maintained once reached, from 00.01 to 99.59 (hours & minutes) or Off (00.00) Set to >99.59 for Infinite - control remains on indefinitely.
For use in multi-zone setpoint slave applications. Offsets the setpoint from -1999 to 9999. Effective SP = SP+Offset. NOTE: effective SP is not limited by setpoint
limits.
‘Offset in use’ pop-up appears when SP is changed.
Disabled
OFF
OFF
Infinite
0
7.8 Setpoint Menu (For Extrusion Model only)
Parameter Description Default Value
Rate the actual setpoint changes from current PV to tar-
Ramp Rate
Upper Limit Used to limit the Maximum setpoint value. Scale Range Maximum
Lower Limit Used to limit Minimum setpoint value. Scale Range Minimum
Offset
get setpoint following power-up or control enable. From 0.001 to 9999 (Units / hr) or OFF (10000). Any changes in the setpoint value also follow this rate.
For use in multi-zone setpoint slave applications. Offsets the setpoint from -1999 to 9999. Effective SP = SP+Offset. NOTE: effective SP is not limited by setpoint
limits.
‘Offset in use’ pop-up appears when SP is changed.
OFF
0
21
Page 28
7.9 Alarm Menu (Applicable to Standard and Extrusion Models)
Parameter Description Default Value
Alarm 1 Sub-menu
None
Type
Value Value for the alarm, from Range minimum to range maxi-
mum, or OFF (maximum +1). OFF disables the alarm.
Hysteresis Sets the alarm switching differential from 1 display unit to
the full input span.
Alarm 2 Sub-menu
Type
Value
Hysteresis
Options Sub-menu
Inhibiting of ‘active alarms’ at power-on, control enable
Alarm Inhibit
Alarm Notification
On - activates both alarms, if configured, when a sen-
Sensor Break Alarm
sor break is detected. If Off, alarms activate only break condition is an alarm condition.
PV High PV Low
Same options as Alarm 1 sub-menu.
or controller setpoint change.
None • Alarm 1 • Alarm 2
Alarm 1 & 2 (both alarms are inhibited)
Alternates ‘Alarm’ with PV value if selected alarm(s)
are active. Red alarm output LEDs are not affected
by this parameter.
None • Alarm 1 • Alarm 2
Alarm 1 and 2 (Alarm 1 OR 2)
Deviation
Band
PV High
1373
1
PV Low
-240
1
None
Alarm 1 and 2
Off
7.10 Communications Menu (Applicable to Standard and Extrusion Models)
Parameter Description Default Value
Unit Address Modbus address from 1 to 255 1
Baud Rate Coms data rate in kbps
1200, 2400, 4800, 9600, 19200 & 38400 bps.
Parity Parity checking: Odd, Even or None
9600
None
22
Page 29
7.11 Display Menu (Applicable to Standard and Extrusion Models)
Parameter Description Default Value
Setup Unlock Code
Advanced Unlock Code
Screen Timeout Screensaver time. Display turns off after 5, 15 or 30 mins.
Selected language
Transmitter
Reset to Defaults
View & adjust Setup lock code. From 1 to 9999 or Off for no lock code
View & adjust Advanced lock code. From 1 to 9999 or Off for no lock code.
Choose the display language (English plus one other). From: English & German / English & French. The second language offered can be changed via the configuration software.
‘Enable’ hides the setpoint, SP.
Important: The device still functions as a con­troller even though the SP is hidden.
Used to reset all parameters back to the factory defaults, as shown on the right in parameter lists. See the Default Value column in the Setup and Advanced menu tables.
10
20
English
Disable
7.12 Operator Screens Menu (Applicable to Standard and Extrusion Models)
Parameter Description Default Value
Control Enabled Manual Ctrl Enabled Hide Alarm State Hide Latch State Show Maximum PV Hide Minimum PV Hide Remaining On Time
(Standard model only) Remaining Delay Time
(Standard model only)
Hide or Show parameters in Operator Mode.
For security, or to simplify the operator screens, hide any
that you do not need to allow access to.
Hide
Hide
Hide
5
7.13 Information Menu (Applicable to Standard and Extrusion Models, Read Only menu)
Parameter Description
PRL DOM
FW Version / FW Type Display of the units’ firmware version & code type numbers. Serial Display of the Serial Number.
Out1 Out2 Out3
Comm DI
The hardware/software revision level, used for internal quality control. The Date of manufacture in mmyy format
Shows the outputs types fitted. These cannot be changed after manufacture. Options are: – SSR (SSR driver) or Relay SSR (SSR driver) or Relay None, SSR (SSR driver), Relay or Linear
Shows other options fitted. These cannot be changed after manufacture. Options are: – RS485 communications - Fitted or None. Digital Input is isolated or not - Iso or NonIs
7.14 Exiting the Advanced Configuration mode
If necessary, press & to clear any Pop-Up Alerts.
Press & to move up one menu level. Some menus have sub-menus so it may be necessary to press this key combination more than once to exit.
23
Page 30
8 Calibration Mode
Low Process Value
Original Displayed Value
It is possible to calibrate the controller to compensate for sensor errors and other tolerance errors in the sys­tem. This is achieved using the calibration mode. The calibration mode allows an offset to be applied in one of two ways. The method used will be dependent on the process application.
These methods do not alter the internal instrument calibration. Set the offset values back to zero to restore standard measured values. Re-calibration of the internal base calibration is also possible, but should only be attempted by qualified personnel as it overwrites the factory calibration – see Base Input Calibration below.
8.1 Single Point Calibration (PV Off­set)
This is a ‘zero offset’ applied to the process variable across the entire span. Positive values are added to the reading, negative values are subtracted. It can be used if the error is constant across the range, or the user is only interested in a single critical value. To use, se­lect Single Point Calibration from the input calibration menu, and simply enter a value equal, but opposite to the observed error to correct the reading.
This example shows a positive offset value.
8.2 Two Point Calibration
This method is used where an error is not constant across the range to change the calibration slop. Sepa­rate offsets are applied at two points in the range to eliminate both “zero” and “span” errors.
1. Measure and record the error at a low point in the process.
2. Measure and record the error at a high point in the process.
3. Go to the first two-point input calibration screen.
a. Enter the desired low point value as the Calibra-
tion Low PV value.
b. Enter an equal, but opposite value to the ob-
served error as the Calibration Low Offset to cor­rect the error at the low point.
4. Go to the second two-point input calibration screen.
a. Enter the desired high point as the Calibration
High PV value.
b. Enter an equal, but opposite value to the ob-
served error as the Calibration High Offset to correct the error at the high point.
Calibration High Offset
Single Point ‘Offset Calibration’ value
New Displayed Value
Original Displayed Value
For example: If the process displays 27.8 when it should read 30, The error is -2.2 so an applied offset of +2.2 would change the displayed value to 30. The same offset is applied to all values, so at 100.0 the new displayed value would be 102.2.
New Displayed Value
Calibration Low Offset
Calibration
Choose values as near as possible to the bot­tom and top of your usable span to achieve maximum calibration accuracy. The effect of any error can grow at values beyond the cho­sen calibration points.
The single and two-point calibration methods can be used together, if you need to change the calibration slope and offset the zero point simultaneously.
Calibration High
Process Value
24
Page 31
8.3 Base Input Calibration
Calibration of the input is carried out during manufac­ture, and for most applications, re-calibration is not required during the lifetime of the instrument. User 1-point and 2-point calibration can be carried from the User Calibration menu.
Re-calibration of the internal base values is possible, but should only be attempted by qualified personnel as it overwrites the factory calibration.
A suitable calibration signal source is required for each input type. To verify the accuracy of the instrument or carry out re-calibration, the input sources listed below are required, with better than ±0.05% of the reading accuracy:
1. DC linear inputs: 0 to 50mV dc, 0 to 10V dc & 0 to 20mA dc.
2. Thermocouple inputs - complete with 0ºC reference facility, appropriate thermocouple functions and compensating leads (or equivalent).
3. RTD inputs: decade resistance box with connec­tions for three-wire input (or equivalent).
8.5 Base Calibration Procedure
Input calibration is carried out in five phases as shown below, each phase corresponds to an input range of the instrument.
The 50mV phase must be calibrated first be­fore any other range(s).
Calibration phases: i. mV for 50 mV ii. V for 10 V iii. mA for 20 mA iv. RTD input (200Ω ohm resistance source) v. CJC (K type thermocouple source at 0ºC required) For Extrusion models phase ii and iii (V & mA) are omit­ted.
8.6 Calibrating the mV Input
1. Check your calibration source is connected to the correct terminals on the 1020 Rail. For 50mV, con­nect your mV source +ve to pin 14 and -ve to pin 15 located on the bottom rear connector – see wiring section.
8.4 Calibration Check
1. Set up the instrument to the required input type.
2. Note down, then remove any single or two-point calibration values by setting them to zero.
3. Power up the instrument and connect the correct input leads, to the correct terminals.
4. Leave powered up for at least five minutes for RTD and DC linear inputs, or at least 30 minutes for ther­mocouple inputs.
5. After the appropriate delay for stabilization has elapsed, check the calibration by connecting the appropriate input source and checking a small number of cardinal points.
6. Repeat the test for all required input types.
7. Check the results against the specification stated for the required input type.
8. Reinstate the calibration values removed at step if they are still appropriate.
Make the connections using the correct ther­mocouple cable type. For all other input types use copper cable. Using the wrong type of ca­ble will cause incorrect readings. This is espe­cially important with thermocouple sensors.
2. Press and hold the button, whilst the instrument is powering up, until the display shows the screen starting with mV. Be patient, may take approximate­ly 30 seconds.
3. In the calibration phase menu displayed, highlight mV from the list.
4. With mV selected, press . The following screen will appear:
>mV Input userCAL Press enter to start
5. Press . You should see the messages Starting Calibration, followed by Calibration in Progress.
A dot moves across the display to show the prog­ress.
6. If the input is wrongly connected or an incorrect sig­nal is applied the calibration will be aborted and the display will show Calibration FAIL. The previous calibration value will be retained.
25
Page 32
7. If the calibration was successful, the display shows
Calibration PASS.
8. To clear the Pass or Fail pop-up press and .
9. Now press and to return to the calibration menu. From here either select another calibration phase,
or press & again to return to the operator screen.
When you have completed the required phases, press
& to exit back to the operator screen.
The Calibration Mode automatically exits if there is no button activity for five minutes.
8.8 Calibration Input States
8.7 Calibrating Other Input Types
The 50mV calibration must be carried out first. After this, you can select the other types in turn. The oth­er calibration phase procedures are similar to the mV phase above, but ensure that the correct input signal and connections are used – see the wiring section for connection details.
Note: When calibrating the RTD input type, connect an accurate 200Ω resistance source across pin 14 and pin 15, and link between pin 13 and pin 14 to replicate the 3-wire compensating lead.
8.10 Calibration Modbus Addresses
Each input can have one of three states:
Description State Shown
Input not calibrated noCAL
Factory calibrated factCAL
User calibrated userCAL
8.9 Calibration Progress
Description Popup
Initial popup Starting calibration
During calibration Calibration in progress
Calibration succeeded Calibration PASS
Calibration failed Calibration FAIL
The following Modbus addresses can be used to initiate the calibration phases and read back the status.
Description Comment Dec Hex
50mV Calibration
10V Calibration
20mA Calibration
RTD Calibration
CJC Calibration
Calibration Status
Write 0xCAFE to start the
calibration for the selected input.
0x0000 - Calibration Failed
0xCAFE - Calibration Busy
0xFFFF - Calibration Successful
Write Only
Read Only
1700
1701
1702
1703
1704
1770
6A4
6A5
6A6
6A7
6A8
6EA
26
Page 33
9 Automatic Tuning
To avoid process time-lags that can make effective tuning difficult or even impossible, ensure correct sen­sor and heat source positioning in your application be­fore use.
There are two automatic tuning methods on the 1020 and 1030 controllers. Pre-Tune and Tune at SP.
The Pre-Tune is a ‘start-up disturbance’ tuning meth­od. It usually gives better results than Tune at SP. However, a minimum 5% of span distance between the process value and setpoint is required for Pre-Tune to run. This means it cannot be used if the setpoint is close to ambient temperature. In this case, use Tune at SP. A full description of Pre-tune and Tune at SP is in the Glossary.
Refer to the Warnings & Messages section for information on the Tuning Error messages.
9.1 Running the Pre-Tune
1. For best results, before running the Pre-Tune adjust the input span (Scale Range Maximum and Scale Range Minimum) to suit your process, allowing a small tolerance beyond the operating range. e.g. if operating from ambient to 180°C, perhaps set the range 0 to 200.
2. Run from cool. Ideally the process should to be cool before running Pre-Tune. Disable control, or tempo­rarily lower the setpoint, until the PV is a least 5% of the input span difference between the current SP and PV. A larger gap is better if this is possible.
3. Allow for overshoot and undershoot. Please be aware that when the Pre-Tune is run, full power is applied to the process for some time. Although the controller cuts power before the setpoint is reached, some process over/undershoot should be expected. The overshoot might exceed the setpoint value. If exceeding SP might cause a problem, run your first Pre-Tune with a lower SP. If required and safe to do so, you can run another Pre-Tune closer to the required SP.
4. The Pre-Tune can be activated via the Automatic Tuning parameter in the Setup menu or the Ad­vanced Configuration menu. It may also be activat­ed via a Modbus command.
The message ‘TUNE’ is displayed whilst Pre-Tune is
running.
Pre-Tune will not engage, and a Tune Error message
will be displayed under the following conditions: 1) There is a sensor break, 2) The PV is <5% of span from SP, 3) A setpoint ramp has been set, 4) A Timer is running, 5) The current control mode is On-OFF
6). The controller is in Manual mode. 7) Control is Disabled*. Resolve the displayed problem then run
Tune at SP again if required. *Note: If control is dis­abled, running Pre-Tune at First Power-up (or imme­diately after a Reset to Default) automatically sets the control to enabled.
5. Once Pre-Tune is complete it will disengage, and the ‘TUNE’ notification ends. The length of time the tuning takes to complete will vary from process to process.
9.2 Running Tune at SP
1. Initial PID values. Tune at SP needs a reasonable level of process stability to run. It is therefore rec­ommended to set the initial PID values in the Con­trol menu back to their default values: Proportional
Band to 10% of your chosen input range, Auto Re­set (Integral) to 5.00 and Rate (Derivative) to 1.15
before using Tune at SP.
2. The Tune at SP can be activated via the Automatic Tuning parameter in the Setup menu or the Ad­vanced Configuration menu. It may also be activat­ed via a Modbus command.
The message ‘TUNE’ is displayed whilst Tune at SP
is running.
3. Once Tune at SP is complete it will disengage, and the ‘TUNE’ notification ends. The length of time the tuning takes to complete will vary from process to process
9.3 Tuning at SP Troubleshooting
Tune at SP will not engage, and a Tune Error message will be displayed under the following conditions: 1) There is a sensor break, 2) A setpoint ramp has been set, 3) A Timer is running, 4) Control is Disabled. 5) The current control mode is On-OFF 6) The controller is in Manual mode.
Resolve the displayed problem then run Tune at SP again if required.
If Tune at SP starts, but remains running indefinitely, the cause is either the process value not achieving rea­sonable stability (±1% of span), or the control power variation is too great (±10%).
To resolve this:
1. Check the PID values in the control menu were at the defaults values (see above). If they were correct, go to step 2. Otherwise, correct them and run Tune at SP again.
2. If step 1 has not resolved the issue, observe the displayed process value for >5minutes and noting the highest and lowest values seen. Subtract the lowest value from the highest to find the peak-to-
27
Page 34
peak deviation. Check the input span (Scale Range Maximum minus the Scale Range Minimum) to see if the it is >100 x the peak-to-peak deviation. If not, increase the input span to more than this value, and run Tune at SP again.
3. If this has not resolved the issue, double the current
PID terms (Proportional Band, Auto Reset and Rate values), then run Tune at SP again.
4. In the unlikely event that the tuning still does not complete continue from step 3.
9.4 Tuning at SP for Heat and Cool
Tuning at SP is possible for Heating or Cooling applica­tions, but not for both Heat and Cool together. If you have defined outputs for heating and cooling, Tune at SP is not offered in the tuning menu. Instead use Pre­Tune.
28
Page 35
10 Digital Input Operation
Depending on your model, the digital input can be used to perform one of the available functions as shown in the table below.
High = Open contacts (and 2 to 24Vdc for the isolated digital input).
Low = Closed contacts (and <0.8Vdc for the isolated digital input).
Digital Input
Controller
Functions
Reset Latched Alarm(s) No Action Reset*
Control Enable/Disable Disable Enable
Auto/Manual Manual Automatic
Pre-Tune Start/Stop Stop Start*
Tune at SP Start/Stop Stop Start*
*Alarm outputs only reset if the alarm condition is no­longer present and tuning will only start if the settings and current process conditions allow (see tuning sec­tion for more details)
Limiter
Function
Reset Latched Limit &
Alarm(s)
*Limit and Alarm outputs only reset if the limit exceed and/or alarm conditions are no longer present.
State Transition
High to
Low
Digital Input State
Transition
High to
Low
No Action Reset*
Low to
High
Low to
High
When the instrument is turned on, a change in the digi­tal input signal from High Low, or Low to High will cause the function to change (unless it is already in the state dictated by the signal change).
The keypad can also be used to change the status of the same function via the relevant menu. The most
recent digital input or keypad instruction will be implemented.
The digital input is “edge sensitive”, which means that it only reacts to a detected transition in the input state. The device cannot detect a status change made when it is turned off. It also means that if it is in the “ON” state, but the current condition of the unit is the “OFF” state (either because a keypad instruction or it has powered up that way) the digital input would first have to be set first to OFF and then ON again before it would set the function ON.
However, on the Limiter model if the Digital Input is in an “ON” state at power-up it gives a Reset signal. Once powered up the Limiter model behaves the same way to a transition.
29
Page 36
Below is an illustration of digital input and keypad use. The example is for the Control Enable function. Other func­tions behave in a similar way.
Unit
Start-Up
Control Function
Control Enabled
Control Disabled
Digital Input
Signal High
Signal Low
HMI
Menu – “ON”
Menu – “OFF”
1. On start-up, the unit uses the Power-Up Action for its initial control state. In this example, it starts in the disabled condition.
2. Digital input signal changes from Low to High; therefore, control becomes enabled. The Control Enable parameter will say ON, when viewed from the HMI (front panel).
3. The keypad on the HMI (front panel) menu is used to change the control back to disabled, Control En- able parameter = OFF.
4. The digital input changes state, going from High to Low, but as the control is already disabled no change is made.
5. Then the digital input goes from Low to High again, re-enabling the control. The Control Enable param­eter in the HMI also shows control is ON again.
30
Page 37
11 Timer Feature
11.1 Timer Feature
The timer feature is only available on the Standard model. It consists of a Delay Timer and an On Timer.
When the Timer Enable parameter is set to Disabled the timer will not be used and the delayed start time and on time are ignored. Note: If the setpoint has been set to ramp, this will still be active, even if the timer is Disabled.
The timer, control power down state and the power-up action have the following relationship:
When Enabled the timer will take control of the Set­point as defined by the Delayed Start Time and On Time parameters. Enabling the timer has no effect until the controller is power cycled or the control is disabled then re-enabled.
Power-up
Control state
at power down
Enabled Last Disabled N/A Control Enabled
Disabled Last Disabled N/A Control Disabled
Enabled On Disabled N/A Control Enabled
Disabled On Disabled N/A Control Enabled
Enabled Last Enabled Off Control Enabled
Disabled Last Enabled Off Control Disabled
Enabled On Enabled Off Control Enabled
Disabled On Enabled Off Control Enabled
Enabled Last Enabled Time Set Control Disabled until Delay timer expires
Disabled Last Enabled Time Set Control Disabled
Enabled On Enabled Time Set Control Disabled until Delay timer expires
Disabled On Enabled Time Set Control Disabled until Delay timer expires
Action
setting
Timer Enable
parameter
setting
Delayed
Start Value Control state at power-up
11.2 Delay, Ramp & Timer Diagram
The delay, ramp and soak is only available on the stan­dard model.
1. From power-up, if control is in the enabled state, or whenever control is changed from disabled to en­abled, the unit delays process control (i.e. control is still disabled) until the Delay Timer expires (time as set by Delayed Start Time). If this is OFF, step 1 is omitted.
2. Setpoint ramps from the current PV to the target setpoint at Ramp Rate (‘RAMP’ alternating with the current effective SP value indicates it is still ramp­ing). If Ramp Rate is OFF the effective setpoint steps directly to target setpoint.
3. After any Delay and/or Ramp completes, the set­point ‘Dwells’ at the target value while the On-Timer counts down (time set by On Time).
4. When the On Timer finishes the control switches off (i.e. control is disabled). If the On Timer has been set to OFF, step 4 is omitted, and control is main­tained at the setpoint indefinitely.
31
Page 38
12 Extrusion Model Only Features
12.1 Non-Linear Cooling Function
The initial cooling effect with water cooling can be very strong when water first flows into a hot process. Evaporation extracts significant amounts of heat en­ergy making the effective cooling power dispropor­tionally high at nominally low levels of cooling output. This makes process control more difficult, particularly if “over-cooling” during the transition from heating to cooling causes the heating to be reactivated. Non-Lin­ear Cooling can be used to counteract these effects by applying the cooling more gradually at first.
To enable the Non-Linear Cooling function the Output 1, Output 2 or Output 3 Usage parameter needs to be set to Non Linear Cooling.
Heat Power
Cool Power >Output 1 Usage
This table lists the Control sub-menu parameters re­lated to non-linear cooling.
Title Description
Minimum Cooling
Impulse Length
Minimum Off Time
Non-Linear Adjust
Non Linear Cooling
Alarm 1
Alarm 2 Alarm 1 or 2
Loop Alarm
The minimum temperature for non­linear cooling to operate
The fixed “On” pulse duration with non-linear cooling
The minimum “Off” duration with non-linear cooling
Adaptation of characteristics of the non-linear cooling
Heat Power
12.2 Method
The cooling characteristic is altered so that the control­ler output is weak until approximately 70% of nominal cooling demand. Beyond this level, the correcting vari­able rapidly rises to the maximum cooling allowed.
Cooling is inhibited entirely until the Minimum Cool­ing temperature has been exceeded. After that it turns ON with fixed duration pulses (adjustable with Impulse Length parameter). The OFF time between pulses is varied to adjust the cooling effort, but is never off for less than Minimum Off Time value whenever cooling is active. This ratio limits the maximum effective cooling.
The maximum effective cooling is calculated as fol­lows:
Impulse Length
Max Cooling= x 100%
Impulse Length + Minimum Off Time
The Non-Linear Adjust parameter can be reduced if the corrective action is too severe by reducing the non-lin­earity of the effective output. See the examples below.
32
Page 39
Non Linear Adjust = 900
Non Linear Adjust = 1
33
Page 40
12.3 Parameter Adjustment
Minimum Cooling
Cooling is enabled only above the temperature set be­cause evaporation, with its associated cooling effect, is not possible at temperatures below 100°C. Set this >100, but it should be well below the normal operating setpoint.
Note: In manual mode cooling is still possible below this temperature.
Impulse Length
A fixed length for cooling pulses set by this parameter. The ON pulses are this length for all cooling output val­ues above 1% nominal cooling demand.
Relatively low values should be used, but remember that the ratio of the Minimum Off Time vs Impulse Length affects the maximum effective cooling (see above). Do not allow this to limit cooling to the extent that insuf­ficient cooling effect is available for the process.
The impulse length is also limited by the hardware (e.g. the response time of your valve). Valves and electro­mechanical relays should not be switched to quickly. Consult the device manual or check with your supplier for suitable minimum settings.
Using these settings, and observe the transition
from heating to cooling. If there is a noticeable over-reaction, where the cooling is still too strong, increase the Non-Linear Adjust value until the ef­fect is reduced to acceptable levels. If the transition becomes too slow, with effective cooling unaccept­ably delayed, reduce the value set.
12.4 Soft Start Function
Soft Start is primarily intended to allow heaters to dry out gradually at start-up condensation which can form when the heaters are cold can cause damage if it evap­orates too quickly.
Soft Start has its own setpoint, allowing a pre-defined low-temperature dwell period which reduces the power demand from the heaters, allowing moisture to evapo­rate more slowly before going to full working tempera­ture. During this period, it also minimizes the heater-on times by reducing the cycle time and limiting the PID power demand.
Note: Soft Start does not limit the instantaneous cur­rent to the heaters when the output is on.
Activated by setting the parameters Soft Start Time and Soft Start Setpoint.
Minimum Off Time
The “off” time between pulses is varied dependent upon the PID cooling demand. The Minimum Off Time is the minimum allowed “off” time (but note that below 1% of cooling demand, the output is disabled).
The time set is hardware-dependent (e.g. the response time of your valve). Generally, it is best set to the lowest value compatible with the output switching device, but remember that valves and electromechanical relays should not be switched to quickly. Consult the device manual or check with your supplier for suitable mini­mum settings.
Remember that the ratio of the Minimum Off Time vs Impulse Length affects the maximum effective cooling (see above). Do not allow this to limit cooling to the extent that insufficient cooling effect is available for the process.
Non-Linear Adjust
This attenuates the cooling curve, and altering where the output rate begins to increase more rapidly. The val­ue can be reduced if the corrective action is too severe, this reduces the non-linearity of the effective output.
To find an appropriate Non-Linear Adjust setting: First set Minimum Cooling, Impulse Length and
Minimum Off Time to appropriate values (see above), and initially set Non-Linear Adjust to 5. Use Pre-Tune or manual tuning to adjust the controllers PID settings to your process.
1. When powered up the unit will control to the Soft Start Setpoint. The control cycle time is 1/4 of the
value entered (subject to the minimum possible value of 0.5s) and the maximum power demand is limited to the Heat Power Limit value (set in the Control menu). The reduced cycle time is used dur­ing the soft start phase.
2. After reaching the Soft Start Setpoint the Soft Start Time begins. The timer starts as soon as the PV is equal to Soft Start Setpoint – 1. The Soft Start Set­point is maintained until this time has elapsed.
3. When Soft Start Timer expires, the unit returns to normal operation. It controls to the normal set­point, the cycle time reverts to the value set and the
Heat Power Limit is no longer used.
Remember, when using the Soft Start feature the Heat Power Limit is only active from power-on and during the Soft Start Time. It remains in use until the Soft Start timer expires or all the time if no Soft Start time is OFF.
34
Page 41
12.5 Extrusion Only Parameters in the Control menu
Soft Start Parameters
Non-Linear Cooling parameters
35
Page 42
13 Limiter Models
13.1 Introduction to the Limiter Model
LM EX AL
The Limiter model has fixed output functions.
Depending upon which option is fitted in Output 3 it is Alarm 2 or Retransmit PV.
Refer to the Information menu or check the product label identify your version.
Output 1. = Limit Output 2. = Alarm 1 Output 3. If Relay or SSR = Alarm 2 / If Linear = Re-
transmit PV
The Limiter LEDs have fixed functions: Limit, Exceed & Alarm.
When the PV enters the Exceed condition both the Lim­it and Exceed LEDs turn ON. Going from the Exceed condition back into the Safe condition the Exceed LED will turn off but the Limit LED will stay latched until it is reset. Remember the Limit output itself is energized in Safe condition but de-energizes when in the Limit condition.
Navigating is the same as the Standard and Extrusion versions, see General Navigation & Editing, but for se­curity, users cannot change parameter values such as the Limit Setpoint in the Operator mode on the Limiter model. These can only change values via the lock code protected Setup or Advanced Configuration modes.
Warning & Error messages on the Limiter model are similar to the Standard and Extrusion versions, with the exclusion of control or tuning related messages. On the Limiter, there is the additional pop-up alert Limit Exceeded message if the process is beyond the limit value set.
Please refer to the Warnings & Messages section.
The Annunciator alarm type, which can be selected for Alarm 1 or Alarm 2, cannot be inhibited.
13.2 Limiter Modbus Communica-
tions
Please refer to the Commonly Used Modbus Address­es and the Limiter Modbus Addresses for the Modbus register addresses.
See the Serial Communications for general communi­cations information.
13.3 Limiter Digital Input
The Digital Input has only one function on the Limiter model. There is no need for a configuration parameter because it is always a Limit & Alarm Reset. Refer to the Digital Input Operation section. However, in addition on the Limiter model, if the Digital Input is in an Open state at power-up it gives a Reset signal.
36
Page 43
13.4 Limiter Operator Mode & Screens
User Screen PV – top
Temperature & Unit – centre & right. LIM & Limit Setpoint - bottom
IMPORTANT: Visibility for parameters below must be set to Show in the Operator menu.
Alarm State
Alarm triggered
Alarm configured, but not triggered
– Alarm not set
Latch State
Maximum PV
Screens show the Maximum & Minimum PV reached.
Minimum PV
13.5 Limiter Output Latching
When an SSR drive or Relay output is configured to ‘latch’ it will remain on after the limit or alarm condi­tion has cleared. The latch enable parameter, Output Latching, needs to be ON for outputs you want to latch.
Limiter Clearing Latched Outputs
The latch condition, shown by in the Latch State screen, needs to be cleared either via a Modbus com­mand, digital input or from the front panel.
To clear latches from the front panel, in the Latch State screen, press then to select Yes.
Press to accept.
Limiter Start-up Latch
The parameter Startup Latch, is only present on the limiter model. It determines how latching outputs be­have when the unit is powered up. It is set individually for each of the outputs (limit and/or the 2 alarms). The three possible modes are as follows:
Reset Latch: The latch state is not remembered
when the unit is powered off. The latch becomes active again only if the associated limit / alarm state is present at or after power-on.
Output Latched
Latch set, but output
not Latched
– Latch not set
Always Latch: The instrument will always power on
with the chosen output in the latched state, even if the associated limit or alarm is not active.
Last Latch: The latch state is remembered on
power down. Any output that was latched on power down it will still be latched when power is restored, even if that limit or alarm is no longer active.
Note: If a limit or alarm state exists at power-up, previously unlatched outputs always activate im­mediately, no matter how the Start-up Latch has been set.
Limiter Sensor Break Detection
If a “Sensor break” is detected on the Limiter model, this always triggers the Limit exceed condition, place the process into a safe state. Correct the input prob­lem, then unlatch the limit output to resolve this.
Limiter Output 3 – Linear, Relay or SSR drive
• If the linear output is fitted to Output 3 on the Limiter model, it can only be used for a PV re-transmit func­tion.
• If a relay or SSR drive is fitted in Output 3 then it is fixed as Alarm 2.
To clear press
to select Yes.
Press to accept.
To clear press
to select Yes.
Press to accept.
then
then
37
Page 44
13.6 Limiter Setup Mode Parameters
If necessary, press & to enter Setup from Op­erator mode.
Enter Setup Lock-code (default of 10) using and
, then press .
The parameters are shown in the following table
Parameter Description Default Value
* Maximum of 1 decimal place for temperature inputs, in the blue square.
J Thermocouple *
-200 to 1200ºC
-328 to 2192ºF
K Thermocouple *
-240 to 1373ºC
-400 to 2503ºF
-199 to 800ºC
-328 to 1472ºF
B Thermocouple
100 to 1824ºC 211 to 3315ºF
C Thermocouple
0 to 2320ºC 32 to 4208ºF
L Thermocouple *
>Input Type
> Input Units °C or °F (not available for Linear dc inputs)
>Input Decimal Place
Scale Range maximum & minimum are only visible when input is a linear dc type.
0000 – no decimal point
000.0 – one decimal point
00.00 – two decimal points (linear dc only)
0.000 – three decimal points (linear dc only)
0 to 762ºC
32 to 1403ºF
N Thermocouple
0 to 1399ºC 32 to 2551ºF
R Thermocouple
0 to 1795ºC 32 to 3198ºF
S Thermocouple
0 to 1762ºC 32 to 3204ºF
T Thermocouple *
240 to 400ºC
-400 to 752ºF
Linear dc
0 – 20mA 0 – 50mV
0 – 5V
0 – 10V
1. Some parameters may be hidden depending upon configuration & hardware.
2.
Note the permissible ranges for each temperature sensor type, below. For example, the B type thermo­couple readings cannot have a decimal point, and it cannot measure below 100ºC or above 1824ºC.
3. The number of decimal points is set by the Decimal Place parameter.
-128.8 to 537.7ºC
-199.9 to 999.9ºF
-128.8 to 537.7ºC
-199.9 to 999.9ºF
PT100 *
-128.8 to 537.7ºC
-199.9 to 999.9ºF
0.0 to 537.7ºC
32.0 to 999.9ºF
-128.8 to 400.0ºC
-199.9 to 752.0ºF
4 – 20mA
10 – 50mV
1 – 5V
2 – 10V
K Thermocouple
˚C
0000
38
Page 45
Parameter Description Default Value
>Input Scale Range Maximum
>Input Scale Range Minimum
>Limit Type
>Limit Value
> PV Retrans Type
>PV Retrans Scale Range Maximum
> PV Retrans Scale Range Minimum
>Alarm 1 Value
>Alarm 2 Value
The scaling value for the input range maximum.
The scaling value for the input range minimum.
High – device will limit when PV is greater than the Limit value. (Exceed condition if PV>Limit Value). Low - device will limit when PV is less than the Limit value. (Exceed condition if PV<Limit value).
The exceed condition value at which the Limit output will trip.
PV Retrans parameters are only visible if Output 3 is Linear.
0-10V 2-10V
0-20mA
4-20mA
0-5V 1-5V
Displayed PV value corresponding to maximum linear output.
Displayed PV value corresponding to minimum linear out­put.
Range minimum to range maximum, or OFF (maximum +1) where OFF disables alarm. Default alarm type is PV High.
If a Relay or SSR drive is fitted in Output 3 you will see Alarm 2.
Same options as Alarm 1. Default alarm type is PV Low.
1000
0
High
-240
0-10V
1373
-240
1373
-240
>Coms Unit Address
>Coms Baud Rate
Modbus address from 1 to 255
1200, 2400, 4800, 9600, 19200 & 38400
>Coms Parity Odd, Even or None
If the Input Type is changed the relevant values from the table above are used for the Scale Range Maximum and Scale Range Minimum. Review and change if required.
1
9600
None
If necessary, press & to clear any Pop Up Alerts.
Press & to exit the Setup mode.
39
Page 46
13.7 Limiter Advanced Configuration Parameters
Sub-menu Name
1. Input
2. User Calibration
3. Outputs
4. Communication
5. Display
6. Information
If necessary, press figuration mode from Operator mode.
Enter Advanced Lock-code (default of 20) using and , then press .
13.8 Limiter - Input Menu
Parameter Description Default Value
Input Type
Units Display Units either °C or °F.
Decimal Place 0000
Scale Range Maximum The scaling value for the input range maximum.
Scale Range Minimum The scaling value for the input range minimum.
Filter Time OFF or 0.5 to 100.0 seconds in 0.5 increments
CJC Enable Enable – Enables the internal thermocouple CJC (Cold
Possible Input types are as listed in the Limiter Setup mode parameters above
This parameter is hidden when input is a linear type and °C or °F are hidden from the display.
000.0
00.00 (not for temperature)
0.000 (not for temperature)
Junction Compensation). Disable – Disables the internal CJC. External compensation must be provided for thermo­couples.
& to enter Advanced Con-
K thermocouple
°C
0000
Maximum allowed for
Input Type.
Minimum allowed for
Input Type.
2.0
Enable
The input scale range, consisting of Scale Range Maximum & Scale Range Minimum above, is used to narrow the working range (input span) of the controller
At 5% beyond the scaled range the controller with give over-range or under-range warnings.
For example, a range 0 to 100 gives a span of 100c, so when the PV is >105c the display will show HIGH.
13.9 Limiter - User Calibration Menu
Parameter Description Default Value
Offset
Low Point Enter value at which the low point error was measured.
Low Offset
High Point Enter value at which the high point error was measured.
High Offset
Shifts the input value up or down by a single offset amount across the entire range.
Enter equal, but opposite offset value to the observed low point error.
Enter an equal, but opposite offset value to the observed high point error.
40
0
Lower Limit
0
Upper Limit
0
Page 47
13.10 Limiter - Outputs Menu
Parameter Description Default Value
Limit Output
High – device will limit when PV is greater than the Limit
Type
value. (Exceed condition if PV>Limit Value). Low - device will limit when PV is less than the Limit value. (Exceed condition if PV<Limit value).
High
Value
Output Latching
Startup latch
Alarm 1
Type
Value
Hysteresis
Action
Output Latching
Startup latch
The exceed condition value at which the Limit output will trip. Adjustable within the Scaled Range set in Input.
ON – Limit output latches & needs to be cleared OFF- Limit output doesn’t latch
Valid only if limit output latching is set to ON
Reset Latch (resets at power on) Always Latch (latches at power on) Last Latch (keeps last state at power on)
None
PV High
PV Low
Deviation
Annunciator
Adjustable within the Scaled Range set in In-put. Range minimum to range maximum, or OFF (maximum +1) where OFF disables alarm
Sets the alarm switching differential from 0 to full span, on the “safe” side of the alarm point.
Direct - Output active when alarm is active. Reverse - Output active when alarm is not active.
ON – Alarm 1 output latches. Reset to continue OFF – Alarm 1 output doesn’t latch
Valid only if Alarm 1 output latching is set to ON
Reset Latch (resets at power on) Always Latch (latches at power on) Last Latch (keeps last state at power on)
-240
ON
Last Latch
PV High
1373
1
Direct
ON
Last Latch
41
Page 48
Parameter Description Default Value
Alarm 2 menu is only shown if Output 3 is Relay or SSR drive
Alarm 2
None
PV High
Type
PV Low
Deviation
Annunciator
Adjustable within the Scaled Range set in In-put.
Value
Range minimum to range maximum, or OFF (maximum +1) where OFF disables alarm.
Hysteresis
Action
Output Latching
Sets the alarm switching differential from 0 to full span, on the “safe” side of the alarm point
Direct - Output active when alarm is active. Reverse - Output active when alarm not active
ON – Alarm 2 output latches. Reset to continue OFF – Alarm 2 output doesn’t latch
Valid only if Alarm 2 output latching is set to ON
Startup latch
Reset Latch (resets at power on) Always Latch (latches at power on) Last Latch (keeps last state at power on)
PV Retrans menu is only shown if Output 3 is Linear
PV Low
-240
Off
Direct
PV Retrans
Output Type
0-10V 2-10V
0-20mA
4-20mA
0-5V 1-5V
Scale Range Maximum Display value for maximum output -1999 to 9999
Scale Range Minimum Display value for minimum output -1999 to 9999
Alarm Options
Inhibit the alarm(s) on Start up :-
None
Start-up Inhibit
Alarm 1 Alarm 2
Alarm 1 & 2
Either OFF or ON.
Sensor Break
ON - triggers Alarm output(s) when sensor break is detected.
0-10V
1000
0
None
ON
42
Page 49
13.11 Limiter - Communications Menu
Parameter Description Default Value
Unit Address Modbus address from 1 to 255
Baud Rate
Parity Parity checking: Odd, Even or None.
Coms data rate in kbps 1200, 2400, 4800, 9600, 19200 & 38400.
1
9600
None
13.12 Limiter - Display Menu
Parameter Description Default Value
Setup Unlock Code
Advanced Unlock Code
Screen Timeout Screensaver time. Display turns off after 5, 15 or 30 mins. 5
Selected language Display language – English, German or French. English
Reset to Defaults
View & adjust Setup mode lock code (password). From 1 to 9999 or Off for no lock code.
View & adjust Advanced mode lock code (password). From 1 to 9999 or Off for no lock code.
Used to reset all parameters back to the factory defaults. See 1020 Controller Factory Defaults.
10
20
13.13 Limiter - Information Menu
Parameter Description
PRL DOM
FW Version FW Type
Serial Serial Number of unit.
Out1 Out2 Out3
Comm DI
The hardware/software revision level. Shows the product update status. Date of manufacture in the form of month and year, mmyy.
The firmware version number & code type.
Shows factory fitted hardware options – Output 1 can be: SSR (SSR driver) or Relay Output 2 can be: SSR (SSR driver) or Relay Output 3 can be: None, SSR (SSR driver), Relay or Linear
RS485 communications option - Fitted or None. Digital Input is isolated or not - Iso or NonIs – see the Isolation Chart
13.14 Limiter - Exiting from Advanced Configuration Mode
If necessary, press & to clear any Pop-Up Alerts.
Press & to exit up one menu level. Repeat if required.
Some menus have sub-menus so it may be necessary to press this key combination more than once. For ex­ample, to go back to the Operator screen from inside the Output 2 sub-menu you need to go up 3 levels and
then press tion mode.
& to exit the Advanced Configura-
43
Page 50
14 Configuration Software
14.1 Introduction
The ChromaTemp Configurator Software Program is available at no charge from the Chromalox website: www.chromalox.com. It facilitates the cloning of mul­tiple controllers and fast parameter file uploads and downloads to and from the controller or PC. It also comes with a Setup Wizard which covers the most ba­sic wiring, input type and programming requirements.
14.2 Connectivity Requirements
In order to use the ChromaTemp Configuration Soft­ware, you must connect to a PC in one of two ways:
1. Use the RS485 control terminals and PC connection
(controller must have the RTU/RS485 feature) or 2. Use the Chromalox Universal Converter & ChromaTemp Configurator Cable.
1. The Universal converter comes with a cable which connects to the USB port on your PC.
2. The ChromaTemp Cable connects to a dedicated port on the bottom of your DIN Controller. (See con­nection details below)
The ChromaTemp dedicated configuration port is very similar to a micro USB socket. It should never be directly connected to a standard USB port or USB charger. Use of this socket re­quires the Universal Converter to ChromaTemp Controller cable which is available from Chro­malox. See the Accessories on the DIN Control­ler Order Table.
44
Page 51
14.3 Installing & Accessing the Configuration Program
Locate the program on the Chromalox website and install it to a known location on your PC. You may choose to have a quick launch icon located on your desktop for fast access. After the program is loaded, locate the quick launch icon and open the program.
14.4 Getting Started
You will be presented with the ChromaTemp Configu­rator Option Selection window. You may accept the model that is presented to you or modify the outputs, options and supply voltage or Read (upload) the op-
To read the settings from a DIN controller, the unit must be powered up and properly connected to your compter via the Universal Converter. (See 12.2 above)
tions and settings from an existing DIN controller. If you wish to accept the Model presented to you, sim­ply select [ OK ] to and proceed to the Section 12.7 Navigating The Configurator.
45
Page 52
14.5 Troubleshooting the ChromaTemp Configurator
When connecting the controller to the PC for the first time, Windows will attempt to load the device drivers. In some cases, you may need to direct this Windows function to the file location of your ChromaTemp Con­figuration Program.
When attempting to run the program the first time, you may need to shut down/restart the Configuration Pro­gram.
You may receive this Timeout Error message if:
A. The connection is not correct or,
B. The device files have not been loaded or,
C. The USB connection tree has not yet been popu-
lated.
You may receive this USB Device Not Recognized window. This occurs when your controller is connected but the computer has not completed the installation of the necessary device drivers or it has not completed populating the USB connection tree.
Be patient. Verification of the drivers and populating the COM ports and USB connection tree may take sev­eral minutes.
If you are still having connectivity/program recognition errors, you may wish to investigate your Windows De- vice Manager. Ensure that you have no warning sym­bols.
In this example, the COM7 is the Communications Port to which the Universal Converter is attached. Select [OK].
46
Page 53
14.6 Getting Started
14.6 Getting Started (continued)
We are back at attempting to Read all Parameter Set­tings and Model Features from an existing device.
The controller is properly connected and the converter is recognized by your PC.
(See 12.5 for troubleshooting suggestions).
From the Confirm Settings to Connect window, choose which communication port (Configuration Port or RS485 Port) and the respective Port Settings (COM1 or COM7 for example). Select [ OK ]
The progress of the device reading will be displayed in the Communications Progress window. The device reading should take approximately 10 seconds.
Upon a successful reading from your device, you will see that the Outputs and Options displayed in the ChromaTemp Configurator Option Selection window are now the same as your controller.
Parameter value changes may be made within the Configuration Software program. These changes may be saved to a file, downloaded to the controller, or hard copy printed for review.
47
Page 54
Opens Settings window –Program language, communication settings & firmware update
14.7 Navigating the Configurator
File Toolbar
The File Toolbar contains several file-related function icons:
Open a previously saved configuration file via Windows Explorer
Save a new configuration file in Windows Explorer
Hard copy printout of all parameter settings
Opens the Option Selection window
Opens the Setup Wizard (See Section 12.8 below)
Read from a Controller, opens the Confirm Settings to Connect window
Write to a Controller, opens the Confirm Settings to Connect window
48
Page 55
Read in Your Hardware
If you are working online with your instrument, press
, then check and adjust Units’ Com­munication Port, the PC COM port number, and if using RS485, enter the correct Address, Baudrate, Databits and Parity (as currently setup in your instrument).
Then press to read in your 1020 Controller
hardware options.
This step reads in the hardware settings from the connected unit but not the param­eter settings.
Read in Parameter Configuration
Before reading in the parameters, first up­load the hardware options (see above).
Then press to read in the current settings from the unit.
Make Configuration Changes
Edit the configuration to your requirements.
Write to Unit
Press to download your new configuration to the unit.
Save Changes to File
Press to save any changes to a file if you wish to use it later.
Loading in Older Configuration Files
The ChromaTemp configurator may give a warning when loading in a file from older versions of the con­figurator.
If you open this file you need to consider that the Unit Information-Details section may not be complete or correct.
Opening files in older versions of the configurator will not give a warning message but can give misleading information in the Details.
For example, see screenshot where the DoM is July
2014.
Details
49
Page 56
Firmware and Language Updating
If advised by the factory or your authorized supplier, you
can upgrade the firmware in the connected instrument
by pressing . Set the communications parameters
(see above), then press the but-
ton.
Follow the on-screen instructions, ensuring you select the correct type and version of firmware file (*.s19) for your 1020 Controller type.
Model Firmware Name
Standard V227E_Encrypt.s19 Extrusion V227F_Encrypt.s19 Limiter V227G_Encrypt.s19
If you are uploading language files (1020 Controller only) the version needs to match the firmware.
50
Page 57
15 Serial Communications
MODBUS
SLAVE
INSTRUMENT
15.1 Supported Protocol
The unit supports Modbus RTU protocol through the RS485 interface.
For a complete description of the Modbus protocol refer to the description provided at http://www.modbus.org/
15.2 RS485 Configuration
The RS485 address, bit rate and character format are configured via the front panel from the Communica­tions Sub-menu.
Data rate: 4800, 9600 (default), 19200 or 38400 bps Parity: None (default), Even or Odd Device Address: 1 to 255 - See RS485 Device Ad-
dressing
For successful communication the master device must have matching communications settings.
15.3 RS485 Device Addressing
The instrument must be assigned a unique device ad­dress in the range 1 to 255. This address is used to rec­ognise Modbus queries intended for this instrument.
Except for globally addressed broadcast messages sent to device address 0, the instrument ignores Mod­bus queries from the master that do not match the address that has been assigned to it. These global queries are processed when received but no response messages are returned.
A message for either a QUERY or RESPONSE is made up of an inter-message gap followed by a sequence of data characters. The inter-message gap is at least
3.5 data character times - the transmitter must not start transmission until 3 character times have elapsed since reception of the last character in a message, and must release the transmission line within 3 character times of the last character in a message.
Three character times is approximately
0.75ms at 38400 bps, 1.5ms at 19200 bps, 3ms at 9600 bps and 6ms at 4800bps.
Data is encoded for each character as binary data, transmitted LSB first. For a QUERY the address field contains the address of the slave destination. The slave address is given together with the Function and Data fields by the Application layer. The CRC is generated from the given address, function and data characters.
For a RESPONSE the address field contains the ad­dress of the responding slave. The Function and Data fields are generated by the slave application. The CRC is generated from the address, function and data char­acters.
The standard MODBUS RTU CRC-16 calculation em­ploying the polynomial 216+215+22+1 is used.
Inter-message
gap
Address
1 char.
Function
1 char.
Data
n char.
CRC Check 2 char.
15.4 Link Layer
A Query (or command) is transmitted from the Modbus Master to the Modbus Slave. The slave instrument as­sembles the reply to the master.
MASTER
QUERY
RESPONSE
51
Page 58
15.5 Supported Modbus Functions
The following Modbus function types are supported by this instrument:
Function Code
decimal
(hexadecimal) Modbus Meaning Description
03 (0x03)
04 (0x04)
06 (0x06)
08 (0x08) Diagnostics Used for loopback test only to check the communications work.
16 (0x10)
Read Holding Registers
Read Input Registers
Write Single Holding
Register
Write Multiple Holding
Registers
Read current binary value of specified number of parameters at given address.
Up to 64 parameters can be accessed with one query.
Writes 2 bytes to a specified word address.
Writes up to 253 bytes of data to the specified address range.
15.6 Function Descriptions
The following is interpreted from the Modbus Protocol Description obtainable from http://www.modbus.org/.
In the function descriptions below, the preceding device address value is assumed, as is the correctly formed two­byte CRC value at the end of the QUERY and RESPONSE frames.
15.7 Function 03 / 04 - Read Holding/Input Registers
Reads the current binary value of data at the specified word addresses.
Query
Function Address of 1st Word Number of Words
03/04 HI LO HI LO
Response
Function Number of Bytes First Word Last Word
03/04 n HI LO HI LO
In the response, the “Number of Bytes” ‘n’, indicates the number of data bytes read from the instrument. E.g. if 5 words are read, the count will be 10 (A hex). The maximum number of words that can be read is 64. If a parameter does not exist at one of the addresses read, then a value of 0000h is returned for that word.
Function 06 – Write Single Register Query
Function Diagnostic Code Value
06 HI = 00 LO = 00 HI LO
Response
Function Sub-Function Value
06 HI = 00 LO = 00 HI LO
52
Page 59
Function 08 – Loopback Diagnostic Test Query
Function Diagnostic Code Value
08 HI = 00 LO = 00 HI LO
Response
Function Sub-Function Value
06 HI = 00 LO = 00 HI LO
The Response normally returns the same data as the loopback query itself and so can be used to test the communications. Other Diagnostic Codes are not supported.
Function 16 – (0x10 Hex) - Write Multiple Registers Query
Function
1st Write
Address
Number of
Words to Write
Number of
Query Bytes
1st Query
Byte
2nd Query
Byte
10 HI LO HI LO ----->
etc
Last Query
Byte
Response
Function 1st Word Address Number of Words
10 HI LO HI LO
The number of data bytes that can be written in one message is 253 bytes.
53
Page 60
16 Modbus Addresses
Register addresses are given in Decimal and Hexadecimal formats.
Parameter access can be Read Only (RO), Write Only (WO) or Read & Write (R/W)
16.1 Input Parameters
Parameter Name
Process Variable
Actual Setpoint
Setpoint
Limit Value
Limit Exceed Status
Alarm 1 Value
Alarm 2 Value
Alarm 1 Status
Alarm 2 Status
Output Latch Status
Latch Reset
Sensor Break Status
Control Enable/Dis­able
Control Enable State
Manual Power Enable
Combined Power (Manual Power in Manual Mode)
Heat Power Output (Primary)
Cool Power Output (Secondary)
Automatic Tuning
Modbus Address
(Dec)
1070
1270
1200
1481
1492
1402
1406
1470
1471
1170
1151
1072
1375
1376
1315
1316
1370
1371
1384
Modbus
Address
(Hex)
42E RO Read process variable value
4F6 RO
4B0 R/W
5C9 R/W
5D4 RO
57A R/W Alarm 1 value. Limited by the input span
57E R/W Alarm 2 value. Limited by the input span
5BE RO 0 = Alarm 1 inactive, 1 = Alarm 1 active
5BF RO 0 = Alarm 2 inactive, 1 = Alarm 2 active
47F RO
492 WO
430 RO 0 = Ok, 1 = Sensor Break
55F R/W
560 RO
523 R/W
524 RO/RW
55A RO 0-100% heating/primary power. Not applicable on Limiter
55B RO
568 R/W
Access
R/W Notes
Actual effective setpoint (e.g. instantaneous value when setpoint in ramping). Not applicable for limiter
Target controller Setpoint, settable within setpoint upper/ lower limit values. Not applicable for limiter
The ‘Exceed’ value at which the limit output will trip. Set­table within the input range. Limiter only.
0 = Limit value not exceeded 1 = Limit value exceeded
A bit mask where bit 1 = Output 1 latched, bit 2 = Output 2 latched, bit 3 = Output 3 latched. E.g. binary 00000101 = outputs 1 & 3 are latched
1 = Attempts to reset all latched outputs (effect is subject to process conditions)
0 = Control Disabled, 1 = Control Enabled Not applicable to Limiter model
0 = Control Disabled, 1 = Control Enabled Not applicable to Limiter model
0 = Automatic Control, 1 = Manual Control
Not applicable to Limiter model.
A read only combined heat/cool power level in automatic mode, or used to write the power level in manual mode.
-100 (max cooling) to 100 (max heating)
Not applicable to Limiter model.
0-100% cooling/secondary power. Not applicable on Lim­iter
Read: 0 = Inactive, 1 = PreTune Active 2 = Tune at SP Active Write: 0 = Stop Tune, 1 = Run PreTune 2 = Run Tune at SP
54
Page 61
16.1 Standard and Extrusion Modbus Addresses
Parameter Name HMI Mode
Process Variable Operator/User
Sensor Break Status Operator/User
Digital Input Status Operator/User
Alarm 1 Status Operator/User
Alarm 2 Status Operator/User
Latch Reset Operator/User
Output Latch Status Operator/User
Output 1 Latch Status Operator/User
Output 2 Latch Status Operator/User
Output 3 Latch Status Operator/User
Output 1 Status Operator/User
Modbus Address
(Dec)
1070
1072
1075
1470
1471
1151
1170
1171
1172
1173
1175
Modbus Address
(Hex)
42E RO Read process variable value
430 RO 0 = Ok, 1 = Sensor Break.
433 RO 0 = Off, 1 = On
5BE RO
5BF RO
492 WO
47F RO
47F RO 0 = Output 1 not latched, 1 = latched
47F RO 0 = Output 2 not latched, 2 = latched
47F RO 0 = Output 3 not latched, 3 = latched
47F RO 0 = Output 1 OFF, 1 = ON
Access
R/W Notes
0 = Alarm 1 inactive, 1 = Alarm 1 active
0 = Alarm 2 inactive, 1 = Alarm 2 active
1 = Attempts to reset all latched out­puts (effect is subject to process con­ditions)
A bit mask where bit 1 = Output 1 latched, bit 2 = Output 2 latched, bit 3 = Output 3 latched. E.g. binary 00000101 = outputs 1 & 3 are latched
Output 2 Status Operator/User
Output 3 Status Operator/User
Actual Setpoint Operator/User
Manual Power Enable Operator/User
Combined Power (or Manual mode power value)
Heat Power Output (Primary)
Cool Power Output (Secondary)
Control Enable/Dis­able
Control Enable State Operator/User
Operator/User
Operator/User
Operator/User
Operator/User
1178
1181
1270
1315
1316
1370
1371
1375
1376
47F RO 0 = Output 2 OFF, 1 = ON
47F RO 0 = Output 3 OFF, 1 = ON
Actual effective setpoint (e.g. instan-
4F6 RO
523 R/W 0 = Automatic, 1 = Manual Control
524
55A RO
55B RO
55F R/W
560 RO
RO
(RW)
taneous value when setpoint in ramp­ing). Not applicable for limiter,
A read only combined heat/cool power level in automatic mode (or used to write the power level in manual mode).
-100 (max cooling) to 100 (max heating)
Not applicable to Limiter model.
0-100% heating/primary power. Not applicable on Limiter
0-100% cooling/secondary power. Not applicable on Limiter
0 = Control Disable, 1 = Control En­able
0 = Control Disabled, 1 = Control Enabled
55
Page 62
Parameter Name HMI Mode
Digital Input Function Input
Cold Junction Compensation
Input
Filter Time Input
Scale Range Lower Limit
Scale Range Upper Limit
Decimal Point Position
Input
Input
Input
Input Units Input
Modbus Address
(Dec)
1007
1006
1004
1002
1001
1003
1005
Modbus Address
(Hex)
Access
R/W Notes
Sets the function digital input con­trols: 0 - No Action (Default) 1 - Alarm Reset (High) 2 - Control Enable (High) / Disable
3EF R/W
(Low) 3 - Control Auto (High) / Manual (Low) 4 - Pre-tune Stop (High) / Start (Low) 5 - Tune at SP Stop (High) / Start (Low)
3EE R/W
0 = Cold Junction Disabled, 1 = Enabled
0 (OFF) or 5 to 1000 = Input filter
3EC R/W
time OFF or 0.5 to 100.0 seconds, in
0.5s increments
3EA R/W
3E9 R/W
Max working temperature, or display value for the max linear input level
Min working temperature, or display value for the min linear input level
The number of decimal places dis­played:
3EB R/W
0 - XXXX 1 – XXX.X 2 – XX.XX (linear inputs only) 3 – X.XXX (linear inputs only)
3ED R/W 0 = Deg˚C, 1 = Deg˚F
56
Page 63
Parameter Name HMI Mode
Modbus Address
(Dec)
Modbus
Address
(Hex)
Access
R/W Notes
Value Range
Input Type Input
User High Calibration Offset
User High Calibration Point
User Low Calibration Offset
User Low Calibration Point
User Single Point Offset
User Calibration
User Calibration
User Calibration
User Calibration
User Calibration
1000
1605
1604
1603
1602
1601
3E8 R/W
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
J Thermocouple
K Thermocouple
PT100 B Thermocouple C Thermocouple L Thermocouple N Thermocouple R Thermocouple S Thermocouple T Thermocouple
0 – 20mA 4 – 20mA 0 – 50mA
10 – 50mA
0 – 5V
1 – 5V
0 – 10V 2 – 10V
645 R/W The required adjustment +/- Span
644 R/W
The adjustment point: Input range maximum to input range minimum
643 R/W The required adjustment +/- Span
642 R/W
The adjustment point: Input range maximum to input range minimum
641 R/W The required adjustment +/- Span
Linear Output 3 Type
Linear Out 3 Scale Max.
Linear Out 3 Scale Min.
Outputs
Outputs
Outputs
1140
1141
1142
474 R/W
475 R/W
476 R/W
57
Possible types. Valid if linear output fitted.
1 = 0-10V
2 = 2-10V 3 = 0-20mA 4 = 4-20mA
0 = 0-5V 5 = 1-5V
PV or SP value where retransmit out­put is at min level (e.g. 4mA if type is 4-20). Adjustable from -1999 to 9999
PV or SP value where retransmit out­put is at max level (e.g. 20mA if type is 4-20). Adjustable from -1999 to 9999
Page 64
Parameter Name HMI Mode
Output 3 Usage Outputs
Output 3 Indicator Invert
Output 3 Alarm Latching
Output 3 Alarm Action
Output 2 Indicator Invert
Output 2 Alarm Latching
Output 2 Alarm Action
Outputs
Outputs
Outputs
Outputs
Outputs
Outputs
Output 2 Usage Outputs
Output 1 Indicator Invert
Output 1 Alarm Latching
Output 1 Alarm Action
Outputs
Outputs
Outputs
Output 1 Usage Outputs
Modbus Address
(Dec)
1130
1131
1133
1132
1121
1123
1122
1120
1101
1103
1102
1100
Modbus Address
(Hex)
Access
R/W Notes
If Relay/SSR fitted: 0 = Heat Output 1 = Cool Output 2 = Non-Linear Cooling – Only Extrusion 3 = Alarm 1 4 = Alarm 2
46A R/W
5 = Alarm 1 or Alarm 2 6 = Loop Alarm
If Linear out fitted: 0 = Heat Output 1 = Cool Output 7 = Retransmit Setpoint 8 = Retransmit Process value
46B R/W
0 = Sync with output, 1 = Opposite to output (e.g. ON when output off)
46D R/W 0 = Off, 1 = On (will latch on when active)
46C R/W 0 = Direct, 1 = Reverse (off if alarm active)
461 R/W
0 = Sync with output, 1 = Opposite to output (e.g. ON when output off)
463 R/W 0 = Off, 1 = On (will latch on when active)
462 R/W 0 = Direct, 1 = Reverse (off if alarm active)
0 = Heat Output 1 = Cool Output 2 = Non-Linear Cooling – Only Extrusion
460 R/W
3 = Alarm 1 4 = Alarm 2 5 = Alarm 1 or Alarm 2 6 = Loop Alarm
44D R/W
0 = Sync with output, 1 = Opposite to output (e.g. ON when output off)
44F R/W 0 = Off, 1 = On (will latch on when active)
44E R/W 0 = Direct, 1 = Reverse (off if alarm active)
0 = Heat Output 1 = Cool Output 2 = Non-Linear Cooling – Only Extrusion
44C R/W
3 = Alarm 1 4 = Alarm 2 5 = Alarm 1 or Alarm 2 6 = Loop Alarm
58
Page 65
Parameter Name HMI Mode
Automatic Tuning Control
Tune Status / Error Messages
Control
Power Up Action Control
Modbus Address
(Dec)
1384
1378
1377
Modbus Address
(Hex)
568 R/W
562 RO
561 R/W
Access
R/W Notes
Read: 0 = Inactive, 1 = PreTune Active 2 = Tune at SP Active Write: 0 = Stop Tune, 1 = Run PreTune 2 = Run Tune at SP
0= No tuning active 1= Tuning active 2= PV within 5% of setpoint 3= Setpoint is Ramping 4= Control On/Off 5= Manual Control 6= Pulse Tune Error 7= Sensor Break 8= Timer running 9= Control disabled 10= Setup not completed
On power-up control enable/disable is: 0=Last State, 1=Always Enabled
Cool Power Limit Control
Heat Power Limit Control
Output Interlock Control
Cool Cycle Time Control
Heat Cycle Time Control
Bias (Manual Reset) Control
On/Off Differential Control
Overlap/Deadband Control
Loop Alarm Time Control
Derivative Time (Rate)
Integral Time (Automatic Reset)
Cool Proportional Band
Heat Proportional Band
Control
Control
Control
Control
1312
1311
1185
1318
1317
1307
1308
1306
1310
1305
1304
1303
1302
520 R/W Sets limit from 0-100% cooling
51F R/W Sets limit from 0-100% Heating
0=Interlock Off or 1=Interlock On (On pre-
4A1 R/W
vents simultaneous heating & cooling) Do not use if PB ‘overlap’ has been set
526 R/W
525 R/W
51B R/W
0 (OFF) or 1 to 5120 = Cycle time OFF or 0.1 to 512.0 seconds, in 0.1s increments
0 (OFF) or 1 to 5120 = Cycle time OFF or 0.1 to 512.0 seconds, in 0.1s increments
Biases the working point 0% to 100% or
-100 to +100% for dual control
51C R/W 0.1% to 10.0% of input span
In display unit, values from -20% to 20% of
51A R/W
combined primary and secondary propor­tional band values
51E R/W
1- 5999 seconds (used in manual mode if loop alarm has been configured
519 R/W 0 (Off) or 1 to 5999 seconds
518 R/W 0 (Off) or 1 to 5999 seconds
0 = On/Off control, or 1 to 9999 cooling
517 R/W
band, in display units (e.g. = 0.001 to 9.999 if display has 3 decimal places)
0 = On/Off control, or 1 to 9999 heating
516 R/W
band, in display units (e.g. = 0.001 to 9.999 if display has 3 decimal places)
59
Page 66
Parameter Name HMI Mode
Modbus Address
(Dec)
Modbus Address
(Hex)
Access
R/W Notes
Setpoint during Soft Start. Settable within
Soft Start Setpoint Control
1290
50A R/W
setpoint upper/lower limit values. Extrusion model only
Soft Start Time Control
Soft Start Time Remaining
Soft Start Time Remaining Secs
Control
Control
1291
1292
1293
50B R/W
50C RO Extrusion model only
50D RO Extrusion model only
0 = Soft Start Off, or 1 to 3600 minutes dura­tion. Extrusion model only
Soft Start Time Remaining = ( (Soft Start Time Remaining – 1) + Soft Start Time Remaining Secs)
Offset the entered SP by -1999 to 9999 Ef-
Setpoint Offset Setpoint
1205
4B5 R/W
fective SP = SP+Offset. NOTE: effective SP is not limited by the setpoint limits.
Setpoint Setpoint
Setpoint Lower Limit
Setpoint Upper Limit
Setpoint
Setpoint
1200
1202
1201
4B0 R/W
4B2 R/W
4B1 R/W
Target controller Setpoint value, settable within setpoint upper/lower limit values
Minimum value for target Setpoint. Adjust­able within scale range. NOTE: does not limit effective SP with ‘Offset’
Maximum value for target Setpoint. Adjust­able within scale range. NOTE: does not limit effective SP with ‘Offset’
Time the setpoint is maintained (the ‘dwell’ after any delay or ramp). Set 1 to 5999 min-
Timer On-Time Setpoint
1277
4FD R/W
utes, 0 = No Dwell. Control is disabled when Dwell ends. 6000 = Infinite Dwell. Standard controller model only.
Setpoint Ramp Rate
Delayed Start Time Value
Setpoint
Setpoint
Timer Enable Setpoint
1204
1276
1275
4B4 R/W
4FC R/W
4FB R/W
The rate from 1 to 9999 display units for ‘ramping’ the setpoint. 10000 = Off (SP steps straight to the target value)
Time from power-up or control enable be­fore control actually begins. Set 1 to 5999 minutes, 0 = No Delay.
0 = Delay & On-Timer disabled, 1 = Enabled. Standard model only
Sensor Break Activate Alarm
Alarms
1409
581 R/W
60
0 = Off, 1 = Detected break always acti­vates both alarms (if configured). If Off, alarms only activate if break condition is also an alarm condition.
Page 67
Parameter Name HMI Mode
Alarm Notification Alarms
Alarm Inhibit Alarms
Alarm 2 Hysteresis Alarms
Modbus Address
(Dec)
1408
1410
1407
Modbus Address
(Hex)
580 R/W
582 R/W
57F R/W
Access
R/W Notes
While display is active, this alternates ‘Alarm’ with PV value if selected alarm(s) are active. Red alarm output LEDs are not affected. 0 = None, 1 = Alarm 1, 2 = Alarm 2, 3 = Alarm 1 or Alarm 2
Set alarms to Inhibit at power-up or controller setpoint change. 0 = None, 1 = Alarm 1, 2 = Alarm 2 3 = Both Alarms
Alarm 2 switching hysteresis. Limited by the input span
Alarm 2 Value Alarms
Alarm 2 Type Alarms
Alarm 1 Hysteresis Alarms
Alarm 1 Value Alarms
Alarm 1 Type Alarms
Parity
Baud Rate
Modbus Address
Communi-
cations
Communi-
cations
Communi-
cations
1406
1404
1403
1402
1400
1501
1502
1500
57E R/W Alarm 2 value. Limited by the input span
0 = None (alarm not used) 1 = High Alarm
57C R/W
2 = Low Alarm 3 = Deviation 4 = Band Alarm
57B R/W
Alarm 1 switching hysteresis. Limited by the input span
57A R/W Alarm 1 value. Limited by the input span
0 = None (alarm not used) 1 = High Alarm
578 R/W
2 = Low Alarm 3 = Deviation 4 = Band Alarm
5DD R/W 0 = None, 1 = Even, 2 = Odd
0 = 1200 bps 1 = 2400 bps
5DE R/W
2 = 4800 bps 3 = 9600 bps 4 = 19200 bps 5 = 38400 bps
5DC R/W
Unique instrument network address from 1 to 255
Selected Language Display
Alternative Language
Display
Screen Timeout Display
Transmitter View Enable
Display
1828
1808
1830
1806
724 R/W
710 RO
726 R/W
70E R/W
61
Language selection. 0 = English, 1 = The installed alternative language
The Installed alternative language. 00 = German, 01 = English, 02 = French
0 = 5mins, 1 = 15mins & 2 = 30mins without keypress before timeout
0 = Off, 1 = Hide setpoint on display, but control functions are still active.
Page 68
Parameter Name HMI Mode
Advanced Lock Code
Display
Setup Lock Code Display
Modbus Address
(Dec)
1803
1804
Modbus Address
(Hex)
70B R/W
70C R/W
Access
R/W Notes
The password to enter the Advanced Menu 0 = Off, or 1 to 9999
The password to enter the Setup Menu 0 = Off, or 1 to 9999
Unhide Delay Time Remaining
Unhide Time On Remaining
Unhide Manual Control Enable
Unhide Control Enable
Unhide Alarm Status
Operator
Operator
Operator
Operator
Operator
Unhide Alarm Latch Operator
Unhide PV Min Operator
Unhide PV Max Operator
Date of Manufacture
Information
2207
2206
2205
2204
2203
2202
2201
2200
505
89F R/W 0 = Hide, 1 = Show remaining time
89E R/W 0 = Hide, 1 = Show remaining time
89D R/W 0 = Hide, 1 = Show auto/manual select
89C R/W 0 = Hide, 1 = Show control enable/disable
89B R/W 0 = Hide, 1 = Show alarm status
89A R/W 0 = Hide, 1 = Show alarm latch screen
899 R/W 0 = Hide, 1 = Show stored minimum PV
898 R/W 0 = Hide, 1 = Show stored maximum PV
1F9 RO
Serial Number formed of aaaa bbbb cccc (12 BDC digits):
Serial Number High Information
Serial Number Mid Information
Serial Number Low Information
PRL Information
Firmware Type Low Information
504
503
502
506
65451
1F8 RO First four digits, aaaa, bits 32-47
1F7 RO Middle four digits, bbbb, bits 16-31
1F6 RO Last four digits, cccc, bits 0-15
1FA RO
FFAB RO (e.g. 227E). Returned as ascii
Encoding e.g. 0403 for April 2003 is re­turned as 193 hex.
Formatted as high byte hardware number as integer [0-99], low byte ascii character [A-Z] for software
Firmware Type High Information
Firmware Ver. High Information
Firmware Ver. Mid Information
Firmware Ver. Low Mid
Information
Firmware Ver. Low Information
Communications Option (RS485)
Information
Option 3 Information
Option 2 Information
Option 1 Information
Supply Voltage Information
Variant Information
Digital Input Information
65450
65458
65457
65456
65455
603
602
601
600
511
510
509
FFAA RO (e.g. 227E). Returned as ascii
FFB2 RO (e.g. 10p12). Returned as ascii
FFB1 RO (e.g. 10p12). Returned as ascii
FFB0 RO (e.g. 10p12). Returned as ascii
FFAF RO (e.g. 10p12). Returned as ascii
25B RO 0 = Not Fitted, 1 = Fitted.
25A RO 0= None, 1= Relay, 5= Linear
259 RO 0= None, 1= Relay, 3= SSR
258 RO 0= None, 1= Relay, 3= SSR
1FF RO 0= 240V, 1= Low Voltage
1FE RO 1= Standard, 0= Extrusion, 2= Limit
1FD RO 0= Non-isolated, 1= Isolated.
62
Page 69
16.3 Limiter Modbus Addresses
Modbus Address
Parameter Name HMI Mode
Process Variable Operator/User
Sensor Break Status Operator/User
Limit Exceed Status Operator/User
Alarm 1 Status Operator/User
Alarm 2 Status Operator/User
Parameter Name HMI Mode
Digital Input Function
Cold Junction Com­pensation
Filter Time Input 1004 3EC R/W
Scale Range Lower Limit
Scale Range Upper Limit
Decimal Point Position
Input 1007 3EF R/W
Input 1006 3EE R/W 0 = Cold Junction Disabled, 1 = Enabled
Input 1002 3EA R/W
Input 1001 3E9 R/W
Input 1003 3EB R/W
(Dec)
1070
1072
1492
1470
1471
Modbus Address
(Dec)
Modbus
Address
(Hex)
42E RO Read process variable value
430 RO 0 = Ok, 1 = Sensor Break.
5D4 RO
5BE RO 0 = Alarm 1 inactive, 1 = Alarm 1 active
5BF RO 0 = Alarm 2 inactive, 1 = Alarm 2 active
Modbus
Address
(Hex)
Access
R/W Notes
Access
R/W Notes
0 = Limit value not exceeded, 1 = Limit value exceeded
The function digital input controls: 0 - No Action 1 – Limit & Alarm Reset (High)
0 (OFF) or 5 to 1000 = Input filter time OFF or 0.5 to 100.0 seconds, in 0.5s increments
Max working temperature, or display value for the max linear input level.
Min working temperature, or display val­ue for the min linear input level.
The number of decimal places dis­played: 0 - XXXX 1 – XXX.X 2 – XX.XX (linear inputs only) 3 – X.XXX (linear inputs only)
Input Units Input 1005 3ED R/W 0 = Deg˚C, 1 = Deg˚F
63
Page 70
Parameter Name HMI Mode
Modbus
Address
(Dec)
Modbus Address
(Hex)
Access
R/W Notes
Value Range
Input Type Input
User High Calibration Offset
User High Calibration Point
User Low Calibration Offset
User Low Calibration Point
User Single Point Offset
User Calibration
User Calibration
User Calibration
User Calibration
User Calibration
1000
1605
1604
1603
1602
1601
3E8 R/W
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17
J Thermocouple
K Thermocouple
PT100 B Thermocouple C Thermocouple L Thermocouple N Thermocouple R Thermocouple S Thermocouple T Thermocouple
0 – 20mA 4 – 20mA 0 – 50mA
10 – 50mA
0 – 5V
1 – 5V 0 – 10V 2 – 10V
645 R/W The required adjustment +/- Span
644 R/W
The adjustment point: Input range maximum to input range minimum
643 R/W The required adjustment +/- Span
642 R/W
The adjustment point: Input range maximum to input range minimum
641 R/W The required adjustment +/- Span
Sensor Break Activate Alarm
Alarms
Alarm Inhibit Alarms
Alarm 2 Hysteresis Alarms
Alarm 2 Value Alarms
Alarm 2 Type Alarms
Alarm 1 Hysteresis Alarms
1409
1410
1407
1406
1404
1403
581 R/W
582 R/W
57F R/W
57E R/W
57C R/W
57B R/W
64
0 = Off, 1 = Detected break always activates both alarms (if configured). If Off, alarms only activate if break condition is also an alarm condition.
Set to inhibit alarms at power-up. 0 = None, 1 = Alarm 1, 2 = Alarm 2 3 = Both Alarms
Alarm 2 switching hysteresis. Limited by the input span
Alarm 2 value. Limited by the input span
0 = None (alarm not used) 1 = High Alarm 2 = Low Alarm 3 = Deviation 4 = Annunciator
Alarm 1 switching hysteresis. Limited by the input span
Page 71
Parameter Name HMI Mode
Alarm 1 Value Alarms
Alarm 1 Type Outputs
Limit Startup Latch Outputs
Limit Value Outputs
Limit Type Outputs
Linear Type Outputs
Linear Output 3 Scale Maximum
Linear Output 3 Scale Minimum
Output 3 Indicator Invert
Alarm 2 StartUp Latch
Output 3 Alarm Latching
Output 3 Alarm Action
Output 2 Indicator Invert
Alarm 1 Startup Latch
Outputs
Outputs
Outputs
Outputs
Outputs
Outputs
Outputs
Outputs
Modbus Address
(Dec)
1402
1400
1104
1481
1480
1140
1141
1142
1131
1134
1133
1132
1121
1124
Modbus Address
(Hex)
Access
R/W Notes
57A R/W Alarm 1 value. Limited by the input span
0 = None (alarm not used) 1 = High Alarm
578 R/W
2 = Low Alarm 3 = Deviation 4 = Annunciator
0 = Reset Latch (resets at power on)
450 R/W
1 = Always Latch (latches at power on) 2 = Last Latch (keep last state at power on)
5C9 R/W
The ‘Exceed’ value at which the limit output will trip. Settable within the input range.
5C8 R/W 0 = High Limit Action, 1 = Low Limit Action
PV Retransmit Possible types. Valid if linear output fitted.
0=0-5V
474 R/W
1=0-10V 2=2-10V 3=0-20mA 4=4-20mA 5=1-5V
PV value where retransmit output is at min
475 R/W
level (e.g. 4mA if type is 4-20). Adjustable from -1999 to 9999
PV value where retransmit output is at max
476 R/W
level (e.g. 20mA if type is 4-20). Adjustable from -1999 to 9999
46B R/W
0 = Sync with output, 1 = Opposite to output (e.g. ON when output off)
0 = Reset Latch (resets at power on)
46E R/W
1 = Always Latch (latches at power on) 2 = Last Latch (keep last state at power on)
46D R/W 0 = Off, 1 = On (will latch on when active)
46C R/W 0 = Direct, 1 = Reverse (off if alarm active)
461 R/W
0 = Sync with output, 1 = Opposite to output (e.g. ON when output off)
0 = Reset Latch (resets at power on)
464 R/W
1 = Always Latch (latches at power on) 2 = Last Latch (keep last state at power on)
65
Page 72
Parameter Name HMI Mode
Output 2 Alarm Latching
Output 2 Alarm Action
Output 1 Indicator Invert
Limit Output 1 Latching
Outputs
Outputs
Outputs
Outputs
Modbus Address
(Dec)
1123
1122
1101
1103
Modbus Address
(Hex)
463 R/W
462 R/W
44D R/W
44F R/W
Access
R/W Notes
0 = Off, 1 = On (will latch on when ac­tive)
0 = Direct, 1 = Reverse (off if alarm ac­tive)
0 = Sync with output, 1 = Opposite to output (e.g. ON when output off)
0 = Off, 1 = On (will latch on when ac­tive)
Parity Communications
1501
5DD R/W 0 = None, 1 = Even, 2 = Odd
0 = 1200 bps 1 = 2400 bps
Baud Rate Communications
1502
5DE R/W
2 = 4800 bps 3 = 9600 bps 4 = 19200 bps 5 = 38400 bps
Modbus Address Communications
Selected Language
Alterative Language
Display
Display
Screen Timeout Display
Advanced Lock Code
Display
Setup Lock Code Display
1500
1828
1808
1830
1803
1804
5DC R/W
724 R/W
710 RO
726 R/W
70B R/W
70C R/W
DOM Information 505 1F9 RO
Unique instrument network address from 1 to 255
Language selection. 0 = English, 1 = The installed alternative language
The Installed alternative language. 0 = German, 1 = English, 2 = French
0 = 5mins, 1 = 15mins & 2 = 30mins without keypress before timeout
The password to enter the Advanced Menu 0 = Off, or 1 to 9999
The password to enter the Setup Menu 0 = Off, or 1 to 9999
Encoding e.g. 0403 for April 2003 is re­turned as 193 hex.
Serial Number formed of aaaa bbbb cccc (12 BDC digits):
Serial Number High
Information 504 1F8 RO First four digits, aaaa, bits 32-47
Serial Number Mid Information 503 1F7 RO Middle four digits, bbbb, bits 16-31
Serial Number Low
Information 502 1F6 RO Last four digits, cccc, bits 0-15
Formatted as high byte hardware num-
PRL Information 506 1FA RO
ber as integer [0-99], low byte ascii character [A-Z] for software.
Firmware Type Low
Firmware Type High
Firmware Version High
Firmware Version Mid
Information 65451 FFAB RO (e.g. 227E). Returned as ascii
Information 65450 FFAA RO (e.g. 227E). Returned as ascii
Information 65458 FFB2 RO (e.g. 10p12). Returned as ascii
Information 65457 FFB1 RO (e.g. 10p12). Returned as ascii
66
Page 73
Parameter Name HMI Mode
Firmware Version Low Mid
Firmware Version Low
Communications Option (RS485)
Information
Information
Information
Option 3 Information
Option 2 Information
Option 1 Information
Supply Voltage Information
Variant Information
Digital Input Information
Modbus Address
(Dec)
65456
65455
603
602
601
600
511
510
509
Modbus Address
(Hex)
Access
R/W Notes
FFB0 RO (e.g. 10p12). Returned as ascii
FFAF RO (e.g. 10p12). Returned as ascii
25B RO 0= Not Fitted, 1= Fitted.
25A RO 0= None, 1= Relay, 5=Linear
259 RO 0= None, 1=Relay, 3=SSR
258 RO 1= Relay as fixed output for Option 1.
1FF RO 0= 240V, 1= Low Voltage
1FE RO 1= Standard, 0= Extrusion, 2= Limit
1FD RO 0= Non-isolated, 1= Isolated.
67
Page 74
17 Specifications
Universal Input
Thermocouple calibration:
PT100 calibration:
DC Calibration ±0.25% of full range, ±1LSD.
Sampling Rate: 4 per second.
Impedance: >1MΩ resistive, except dc mA (5Ω) and V (47kΩ)
Sensor Break Detection:
Digital Input (Isolation & Non-isolated version)
Functions:
Signal:
Outputs (Isolation & Non-isolated version)
±0.25% of full range, ±1LSD & ±1°C for Thermocouple CJC.
BS4937, NBS125 & IEC584.
±0.25% of full range, ±1LSD.
BS1904 & DIN43760 (0.00385Ω/Ω/°C).
Thermocouple, RTD, 4 to 20mA, 10 to 50mV, 2 to 10V and 1 to 5V ranges only. Control outputs turn off when a sensor break is detected. Limiter versions go to Exceed condition.
Reset Alarm, Control Enable/Disable, Auto/Manual, Pre-Tune Start/ Stop or Tune at SP Start/Stop.
Fixed function Reset Limit/Alarms only on limiter versions.
Non-isolated - Open or Closed contacts only. Isolated - Open (2 to 24Vdc) or Closed (< 0.8Vdc). Closed to Open transition = Reset, Enabled, Auto or Start.
In addition, on Limiter model – Open on power up gives a Reset signal.
Relays
Output 1 (Limit on Limiter) – Form C SPDT, 2A @250vac, resistive.
Contact Type:
Lifetime: >150,000 operations at rated voltage/current, resistive load.
SSR Driver
Capacity: SSR drive voltage >10Vdc at 20mA
Linear Output
Linear Types: 0 to 20mA, 4 to 20mA, 0 to 5V, 0 to 10V or 2 to 10V
Load Resistance: Current Output 500Ω max, Voltage Output 500Ω min.
Resolution:
Output 2 (Alarm 1 on Limiter) & Output 3 (Alarm 2 on Limiter) – Form A SPST relay, 2A @ 250Vac, resistive.
8 bits in 250ms (10 bits in 1s typical, >10 bits in >1s typical).
68
Page 75
Serial Communications (RS485 – Modbus RTU)
The rear bus connection and top RS485 connection are not intended for use at the same time.
Data Rate: 1200, 2400, 4800, 9600, 19200 or 38400 bps.
Parameter Defaults: Address:1 Baud Rate: 9600 Parity: None.
Please refer to Modbus Addresses section for more information.
Operating Conditions
Usage: For indoor use only. Din-Rail mounted in a suitable enclosure.
Relative Humidity: 20% to 95% non-condensing.
Operating Temperature: <95% humidity 0°C to 55°C
Storage Temperature: <95% humidity –10°C to 80°C
Altitude: < 2000m
Mains power version - 100 to 240Vac ±10%, 50/60Hz, 9VA
Power Supply:
Low voltage version - 24Vac +10/-15% 50/60Hz 9VA or 24Vdc +10/-15% 5W.
Environmental
Standards: CE, UL & cUL. FM 3545 applies to the Limiter model only.
EMI: EN61326-1:2013, Table 2 & Class A.
WARNING: This is a Class A product. In a domestic environment, this product may cause radio interference in which case the user may be required to take adequate measures.
Safety:
UL61010-1 Edition 3 & EN61010 Version 2010, Pollution Degree 2 & Installation Class 2.
Protection Rating: IP20
Physical
Unit Size: Height: 99mm; Width: 22.5mm; Depth: 121mm.
Ventilation: 80mm free space required above and below each unit.
Weight: 0.20kg maximum.
69
Page 76
18 Glossary
PV HIGH
ALARM
PV LOW
ALARM
BAND ALARM
DEVIATION
HIGH ALARM
Inactive
Inactive
Inactive
Alarm Inactive Alarm Inactive
Alarm Active
Active
Inactive
Active
Active
Alarm Value
Alarm Value
Alarm Value
Setpoint
Process Variable
Process Variable
Process Variable
Process Variable
Process Variable
Alarm Hysteresis Value
Setpoint
Setpoint
Alarm Value
Alarm Value
Alarm Value
DEVIATION
LOW ALARM
Alarm Hysteresis Value
Alarm Hysteresis Value
Alarm Hysteresis Value
Alarm Hysteresis Value
Alarm Hysteresis Value
Inactive
Inactive
Inactive
Inactive
Inactive
This Glossary explains the technical terms and parameters used in this manual. The entry type is also shown:
Actual Setpoint
Actual Setpoint is the current effective value of the Setpoint. This will be different to the target value of the setpoint if it is currently ramping. The actual setpoint s rises or falls at the ramp-rate set, until it reaches the target Setpoint value.
Also refer to Active Setpoint, Setpoint, Setpoint Ramp Enable and Setpoint Select
Alarm Hysteresis
An adjustable band on the “safe” side of an alarm point, through which the process variable must pass before the alarm will change state, as shown in the dia­gram below.
Also refer to Alarm Operation
Alarm Operation
The different alarm types are shown below, together with the action of any outputs.
Also refer to Alarm Hysteresis, Alarm Inhibit, Band Alarm, Deviation Alarm, Latching Relay, Logical Alarm Combinations, Loop Alarm, Process High Alarm and Process Low Alarm
70
Page 77
Alarm Inhibit
Inhibits an alarm at power-up or when the controller setpoint is changed, until that alarm would become inactive. The alarm operates normally from that point onwards.
Note that on the Limiter there is a similar function called Start Up Inhibit which is applicable only at power up, not when the limit setpoint is changed.
Also refer to Alarm Operation.
Automatic Reset (Integral time)
Used to automatically bias proportional control output(s) to compensate for process load variations. It is adjustable in the range 1 seconds to 99 minutes 59 seconds per repeat and OFF Decreasing the time in­creases Integral action. This parameter is not available if the primary output is set to On-Off.
Also refer to Heat Proportional Band, Cool Proportional Band, Rate, and Tuning.
Auto-Tune
Refer to Pre-Tune and Tune at Setpoint.
Band Alarm Value
Refer to Alarm Operation.
Bumpless Transfer
A method used to prevent sudden changes to the out­put power level when switching between automatic and manual control modes. During a transition from automatic to manual, the initial Manual Power value is set equal to the previous automatic mode value. The user then adjusts as required.
During a transition from Manual to Automatic, the ini­tial Automatic Power value is set to equal the previous manual value. The correct power level is gradually ap­plied by the control algorithm at a rate dependant on the integral action (see Automatic Reset). Since integral action is essential to Bumpless Transfer, this feature is not available if Automatic Reset is turned off.
Also refer to Automatic Reset (Integral time) and Man­ual Mode.
Calibration - 2 Point (High/Low PV Offset)
Two-point calibration uses two separate points of ref­erence, usually at the process high and low operating limits, to determine the required offsets. These offsets are used to rescale all readings over the full range of the controller minimizing inaccuracies in the input reading. See the User Calibration section.
Also refer to Calibration - Single Point (PV Offset) , In­put Span & Span and Process Variable.
Basic Setpoint Control
When Basic Setpoint Control is enabled the user can only change the set point or the Auto/Man power from the User mode screen. To change other settings the user must enter the Advanced Configuration Mode. The parameter to enable/disable Basic Setpoint Con­trol is in the Display menu.
Bias (Manual Reset)
Used to manually bias the proportional output(s) to compensate for process load variations. Bias is ex­pressed as a percentage of output power, and is ad­justable in the range 0% to 100% (for Heat or Cool outputs alone) or -100% to +100% (for both Heat and Cool Outputs). This parameter is not applicable if the primary output is set to ON-OFF control mode. If the process settles below setpoint use a higher Bias val­ue to remove the error, if the process variable settles above the setpoint use a lower value. Lower Bias val­ues also help to reduce overshoot at process start up.
Also refer to ON/OFF Control.
Calibration - Single Point (PV Offset)
Single point calibration uses one point of reference, usually set at a critical process operating value, for the required calibration offset. This offset is applied to all measurements across the input span. See the User Calibration section.
This can be used to compensate for errors in the dis­played process variable. Positive values are added to the process variable reading, negative values are sub­tracted, so MUST be used with care. Incorrect use could cause the displayed value not to show the actual process value.
Also refer to Calibration - 2 Point (High/Low PV Offset), Input Span & Span and Process Variable.
Control Type
In the Out 1, Out 2 and Out 3 parameters to set the direction of output increase/decrease vs the movement of the process. Heat is reverse acting, Cool is direct acting (e.g. cooling output in-creases when the tem­perature rises).
Refer to Heat Proportional Band, and Cool Proportional Band.
71
Page 78
Controller
An instrument that can control a process, using either PID or On-Off control methods. Alarm outputs are also available, as are other options and Serial Communica­tions.
Refer to Alarm Operation, Limit Controller, On-Off Con­trol, and Serial Communications.
Cool Proportional Band
The Cool Proportional Band is only applicable when a Cool Output is used. It is the portion of the input span over which the Cool Output power level is proportional to the process variable value. Adjustable in input units’ equivalent to 0.5% to 999.9% of span (zero = On-Off control). The Control action for the Cool outputs is di­rect acting.
Refer to Control Type, On-Off Control, Heat Propor­tional Band and Tuning.
Heat Proportional Band
The Heat Proportional Band is only applicable when a Heat output is used. It is the portion of the input span over which the Heat Output power level is proportional to the process variable value. Adjustable in input units’ equivalent to 0.5% to 999.9% of span (zero = On-Off control). The Control action for the Heat outputs is re­verse acting.
Also refer to Control Type, On-Off Control, Cool Pro­portional Band, and Tuning.
Input Filter Time
Used to filter out extraneous impulses (“noise”) on the process input. The filtered PV is used for all PV-depen­dent functions (display, control, alarm etc). The time constant is adjustable from 0.0 seconds (off) to 100.0 seconds in 0.5 second increments.
Also refer to Process Variable.
Cycle Time
For time-proportioning outputs, cycle time is used to define the time over which the average ON vs. OFF time is equal to the required PID output level. The range of values is 0.1 to 512 seconds in 0.1s steps. Shorter cycle times will give better control, but at the expense of reduce life when used with an electromechanical control device (e.g. relays or solenoid valves).
Also refer to Time Proportioning.
Deadband
Refer to Overlap/Deadband.
Derivative
Refer to Rate.
Deviation Alarm
Refer to Alarm Operation.
Input Range and Input Span
The Input Range is the overall non-restricted range as determined by the Type parameter in the input menu.
The Input Span (or Scaled Range) is the limited work­ing range set by the upper and lower limits in the input menu. The input span is used as the basis for calcu­lations that relate to the span of the instrument (e.g. controller proportional bands).
Also refer to Scale Range Lower and Scale Range Up­per.
Limit Controller
A protective device that can shut down a process at a pre-set Exceed Condition, to prevent possible dam­age to equipment or products. They are recommended for any process where product or equipment damage might occur, or if it could become hazardous under fault conditions.
Heat or Cool Output Power Limits
Used to limit the power level for heating or cooling to protect the process or heaters. Adjustable from 0% to 100%. This parameter is not applicable if the primary output is set for On-Off control.
Also refer to On-Off Control.
72
Page 79
Loop Alarm
This is a special alarm, to detect problems with the control feedback loop. It continuously monitors the process response to the control output.
If control is at the maximum or minimum limit (0% or 100% for single Heat or Cool output and -100% & +100% for dual Heat and Cool outputs), an internal timer starts. If the process variable is not moved in the expected direction by a predetermined amount ‘V’ after time ‘T’ has elapsed, the loop alarm becomes active.
Only when the process has moved by “V”, or when the output is no longer at the limit, does the loop alarm deactivate.
*If the heat or cool power limits are less than 100% the limited value is used as the maximum. E.g. if the limit is 70%, the timer begins at 70%.
For PID control, the loop alarm time ‘T’ is always twice the Automatic Reset (Integral) parameter value. For On-Off control, a user defined value for the Loop Alarm Time parameter is used.
The value of ‘V’ is dependent upon input type. For tem­perature inputs, V = 2°C or 3°F. For linear inputs, V = 10 least significant display units.
Correct operation of the loop alarm depends upon reasonably accurate PID tuning. The loop alarm is au­tomatically disabled during manual control mode and during automatic tuning.
Also refer to Manual Mode, On-Off Control, and Pro­cess Variable.
Manual Mode
If manual mode is selected from operator mode (if en­abled), via the digital input or serial comms, the PID algorithm is suspended. It must therefore be used with care, because the controller is no longer in control of the process. The operator must maintain the process at the required value, by adjusting the % power output value.
In Manual mode, the display shows the current pro­cess value as normal, but the setpoint is replaced with the % output power. This value may be adjusted us­ing keypad, between 0% to 100% for controllers using Heat control only, and -100% to +100% for controllers using dual Heat and Cool control.
Switching between automatic and manual modes is achieved using bumpless transfer.
Note: Manual power is not limited by the power output limits.
Also refer to Bumpless Transfer, and Heat/Cool Output Power Limit.
Master & Slave
The terms master & slave are used to describe the con­trollers in applications where one instrument controls the setpoint of another. The master controller (e.g. a profile controller) transmits a setpoint to 1020 using RS485 serial communications (analog signals cannot be used because 1020/1030 does not have a remote setpoint input option). 1020/1030 cannot act as a Mas­ter.
Also refer to Serial Communications and Setpoint
On-Off Control
On-Off control mode, the output(s) turn on or off as the process variable crosses the setpoint just like a home heating thermostat. Some oscillation of the process variable is inevitable with On-Off control.
On-Off control is enabled by setting the corresponding proportional band(s) to Off (zero). It can be assigned to the Heat output alone (Cool output not present), Heat and Cool outputs or Cool output only (with the Heat Output set for time proportional).
Also refer to Heat Proportional Band, Cool Proportional Band, On-Off Differential, Setpoint and Time Propor­tioning Control.
On-Off Differential (Hysteresis)
A switching differential, centred about the Setpoint, when one or both control outputs have been set to On­Off. It is adjustable from 0.1% to 10.0% of input span, entered in display units.
Relay chatter can be eliminated by proper adjustment of this parameter, but larger values do increase ampli­tude of process oscillations.
Also refer to Input Range and Input Span and On-Off Control.
Overlap/Deadband
Defines the portion of the Heat and Cool proportional bands over which both outputs are active (Overlap), or neither is active (Deadband). It is set in display units, within a range of -20% to +20% of the sum of the two proportional bands (e.g. If Heat PB is 3 and Cool PB is 2, their sum is 5, and ±20% is -1 to +1). Positive + val­ues = Overlap, Negative - values = Deadband.
If the Cool Output is set for On-Off, this parameter moves the Differential band of the Cool Output to cre­ate the overlap or deadband. When Overlap/Deadband = 0, the “OFF” edge of the Cool Output Differential band coincides with the point at which the Heat Output = 0%. ).
Also refer to Differential, On-Off Control, Heat Propor­tional Band and Cool Proportional Band.
73
Page 80
PID Control
Proportional Integral and Derivative control maintains accurate and stable levels in a process (e.g. tempera­ture control). It avoids the oscillation characteristic of On-Off control by continuously adjusting the output to keep the process variable stable at the desired Set­point.
Also refer to Automatic Reset, Controller, Manual Mode, On-Off Control, PI Control, Heat Proportional Band, Process Variable, Rate, Cool Proportional Band, Setpoint and Tuning
Pre-Tune
Starting with the load cool*, Pre-Tune disturbs the pro­cess start-up pattern, so that the PID values are calcu­lated before the setpoint is reached.
During Pre-Tune, the controller outputs full Heat Power until the process value has moved approximately half­way to the Setpoint. At that point, power is removed (or full Cool Power with dual control), thereby introduc­ing a process oscillation. Once the oscillation peak has passed, the instrument calculates the PID tuning terms: proportional band(s), automatic reset and rate. Normal PID control operation begins using these calculated values, and Pre-Tune automatically disengages.
*Ideally the Tune program should be used when the load temperature is close to ambient.
Care should be taken to ensure that any overshoot is safe for the process and if necessary tune at a lower setpoint.
Pre-Tune will not engage if either Heat or Cool outputs on a controller are set for On-Off control, the control­ler is set to Manual, during Setpoint ramping, or if the process variable is less than 5% of the input span from the Setpoint. Refer to the Automatic Tuning section for further details.
Also refer to Automatic Reset, On-Off Control, Input Span, PID, Heat Proportional Band, Process Vari­able, Rate, Cool Proportional Band, Setpoint, Setpoint Ramping and Tuning.
PV High Alarm Value
Refer to Alarm Operation.
PV Low Alarm Value
Refer to Alarm Operation.
74
Page 81
Process Variable (PV)
Process Variable is the signal measured by the primary input. The PV can be anything that can be converted into a compatible electronic signal. Common types are Thermocouple or PT100 temperature probes, %RH or pressure etc. from transducers that convert them to linear dc signals (e.g. 4 to 20mA). These signals are scaled into engineering units using the Scale Range Lower Limit and Scale Range Upper Limit parameters.
Also refer to Input Range & Span, Scale Range Lower Limit and Scale Range Upper Limit.
Rate (Derivative)
Rate is adjustable from 0 (OFF) to 99 minutes 59 sec­onds. It defines how the control output responds to the rate of change in the process. Rate is not available in On-Off.
Also refer to On-Off Control, PID, Process Variable and Tuning.
Reset / Integral
Refer to Automatic Reset.
Reverse Acting
Refer to Direct/Reverse Action of Control Output
For thermocouple and RTD inputs, this parameter is used to reduce the effective range of the input. All span related functions, work from the trimmed span. The pa­rameter can be adjusted within the limits of the Input Range selected. It is adjustable to within 100 degrees of the Scale Range Upper Limit.
Also refer to Input Range & Span, Process Variable and Scale Range Upper Limit.
Serial Communications Option
A feature that allows devices such as PC’s, PLC’s or a master controller to read or change an instrument’s pa­rameters via a communications link. 1020 & 1030 Con­trollers optionally support RS485 Modbus RTU com­munications as a factory fitted option, in addition to the front configuration port.
Also refer to Controller, Indicator, Master & Slave and Limit Controller.
Setpoint
The target value at which a controller will attempt to maintain the process by adjusting its power output level. Setpoints can be adjusted between the Setpoint Upper Limit and Setpoint Lower Limits.
Also refer to Limit Setpoint, Process Variable, and Set­point Upper & Lower Limits
Scale Range Maximum
For linear inputs, this parameter is used to scale the process variable into engineering units. It defines the displayed value when the process variable input is at its maximum value. It is adjustable from -1999 to 9999 and can be set to a value less than (but not within 100 units of) the Scale Range Lower Limit, in which case the sense of the input is reversed.
For thermocouple and RTD inputs, this parameter is used to reduce the effective range of the input. All span related functions work from the trimmed input span. The parameter can be adjusted within the limits of the Input Range selected. It is adjustable to within 100 de­grees of the Scale Range Lower Limit.
Also refer to Input Range & Span, Process Variable and Scale Range Lower Limit.
Scale Range Minimum
For linear inputs, this parameter can be used to display the process variable in engineering units. It defines the displayed value when the process variable input is at its minimum value. It is adjustable from -1999 to 9999 and can be set to a value more than (but not within 100 units of) the Scale Range Upper Limit, in which case the sense of the input is reversed.
Setpoint Upper Limit and Setpoint Lower Limit
The maximum and minimum values allowed for set­point adjustments. Set as required to prevent the pro­cess going too high or low. Setting both limits to the same value locks the setpoint at that value.
The adjustment range for Setpoint Upper Limit is be­tween current Setpoint and Scale Range Maximum. The value cannot be moved below the current value of the Setpoint.
The adjustment range is between Scale Range Lower Limit and current Setpoint. The value cannot be moved above the current value of the Setpoint.
Also refer to Scale Range Lower Limit, Scale Range Upper Limit and Setpoint
Ramp Rate
The rate at which the actual effective setpoint value moves towards its target value, when the Setpoint is adjusted. With ramping in use, the initial value of the actual Setpoint at power up, enabling control or when switching back to automatic mode from manual con­trol, is equal to the current process variable value. The Actual Setpoint will rise/fall at the ramp rate set, until it reaches the target Setpoint value.
75
Page 82
Setpoint ramping is used to protect the process from sudden changes in the Setpoint, which would result in a rapid rise in the process variable. If the setpoint is changed controller attempts to follow at the predefined ramp rate until the new setpoint is reach.
Also refer to Actual Setpoint, Manual Mode and Set­point.
Solid State Relay (SSR)
An external device manufactured using Silicone Con­trolled Rectifiers, which can be used to replace me­chanical relays in most AC power applications. As a solid-state device, an SSR does not suffer from contact degradation when switching electrical current. Much faster switching cycle times are also possible, leading to superior control. 1020 optional SSR Driver outputs give time-proportioned 10Vdc pulses, which causes conduction of current to the load when the pulse is on.
Also refer to Cycle Time and Time Proportioning Con­trol.
Solenoid Valve
An electro-mechanical device to control gas or liq­uid flow. It has two states, open or closed. Typically, a spring holds the valve closed until current passes through the solenoid coil, forcing it open. Standard Process Controllers with Time Proportioned outputs are used to control solenoid valves.
Solenoid valves are often used with high/low flame gas burners. A bypass supplies some gas at all times, but not enough to heat the process more than a nominal amount (low flame). The controller output opens the valve when the process requires additional heat (high flame).
Time Proportioning Control
This type of control can be used with electrical contac­tors, Solid State Relays or valves whenever Relay or SSR Driver outputs are used for either primary (Heat) or secondary (Cool) control.
Time-proportioning control is accomplished by cycling the output on and off during the prescribed cycle time, whenever the process variable is within the proportion­al band. The control algorithm determines the ratio of time (on vs. off) to achieve the level of output power required to correct any error between the process val­ue and Setpoint. E.g. for a 32 second cycle time, 25% power demand would result in the output turning on for 8s, then off for 24s.
Also refer to Cycle Time, PID, Heat Proportional Band, Process Variable, Cool Proportional Band, Setpoint and SSR.
Tuning PID
PID Controllers must be tuned to the process for them to maintain optimum control. Adjustment is made to the tuning terms either manually, or by using the con­troller’s automatic tuning facilities. Tuning is not re­quired if the controller is configured for On-Off Control.
Also refer to Automatic Reset, Cool Proportional Band, Heat Proportional Band, ON-OFF control, PID, Pre­Tune, Rate and Tune at Setpoint.
Tune at Setpoint
This automatic tuning method can be used if Pre-Tune cannot to run, because the current process tempera­ture is too close to the target setpoint.
Tune at SP is activated via the Setup or Advanced Con­figuration menus. It can also be activated via the Digital Input or a Modbus command. It works by waiting for the process to “line-out” (approximately stable), then adds a pulse to the control output to cause a small process disturbance. This disturbance is analyzed to establish the correct PID tuning terms for the applica­tion – see below.
The message ‘TUNE’ is displayed whilst Tune at SP is running. The ‘TUNE’ notification ends when the tuning is complete.
Tune at Setpoint will not engage, and a Tune Error mes­sage will be displayed if:
1). There is a sensor break
2). A setpoint ramp has been set
3). A Timer is running
4). Control is Disabled
5). The current control mode is On-OFF). The controller is in Manual mode.
If you have defined outputs for heating and cooling, Tune at SP is not offered in the tuning menu. Instead use Pre-Tune.
76
Page 83
Running Tune at Setpoint from Automatic Control
It is important to set Scale Range Maximum and Scale Range Minimum correctly before tuning, Also, because Tune at SP needs a reasonable level of process stabil­ity to run, it is recommended to set the initial PID values in the Control menu back to their default values. See the Automatic Tuning section for further information.
1. Activate Tune at SP.
2. When Tune at SP begins, the controller carries out a “steady state estimation”. It waits until the process has achieved reasonable stability (±1% of span & max control power variation ±10)% for 5 minutes.
3. After 5 minutes of stability (see T0 below) the Pulse response evaluation is carried out.
A “power pulse” is applied that reduces the current
control power by -20% (except if the current power is already 20% or less, when a positive +20% pow­er pulse is applied instead).
4. The power pulse is maintained until the process re­sponds by 1% of span (see T1 below). E.g. falling by 1% if the power pulse was negative, or rising if the pulse was positive.
5. The 20% pulse is removed, returning the power to the value just before T0.
The process will continue to its maximum deflection,
and returns towards the original value.
6. The controller notes the time taken to recover
0.15% of span, then waits for the recovery to reach
0.3% (see T2 and T3 below) before using the pulse response deflection and the time T3 - T2 to calcu­late new PID terms.
Note: The time tuning takes to complete will vary from process to process.
Also refer to Automatic Reset, Cool Proportional Band, Heat Proportional Band, ON-OFF control, PID, Pre­Tune, Rate and Tuning.
77
Page 84
19 Order Tables
20 Series DIN Rail Over Temperature Controller
1020
DIN Rail Mountable Temperature Controller. Standard Features: Universal Input, PID or On/Off Control with Auto or Manual Tuning, Up to 3 Outputs (SSR Drive, Relay or Analog/DC Linear), Bright LED text/Icon Display, Heat/Cool Operation, Digital Input, Latching/Non-Latching Alarms and Configuration via Front Panel or Software. Options: ModBus RTU/RS485 Digital Communications, Low Voltage Supply. Operating Temperature: 32°-131°F (0°-55°C), IEC IP20 Enclosure Protection. CE, UL, CUL & 2-Year Warranty
Code Output 1
S
SSR Drive (>10VDC @ 20mA)
R
Relay (SPDT, Form C, 2A at 250VAC)
Code Output 2
S
SSR Drive (>10VDC @ 20mA)
R
Relay (SPST, Form A, 2A at 250VAC)
Code Output 3
0
None
R
Relay (SPST, Form A, 2A at 250VAC)
A
Analog (Linear DC: 0/4-20mA, 0-5V, 0/2-10V)
Code Digital Communications
0
None
1
Modbus RTU/RS485 Digital Communications
Code
0 1
1
Power Supply
100 to 240VAC 50/60Hz 24VDC/VAC +10%/-15%, AC 50/60Hz
1020 - S R A 0 0 Typical Model Number
1
Only available when Output 1 is Relay
78
Page 85
30 Series DIN Rail Over Temperature Controller
1030
DIN Rail Mountable Over Temperature Controller. Universal Input, Fixed Relay Output 1 with Up to 2 additional Alarms/Outputs (SSR Drive, Relay or Analog/DC Linear), Bright OLED Display, Digital Input, Latching/Non-Latching Alarms and Configuration via Front Panel or Software. Options: ModBus RTU/RS485 Digital Communications, Low Voltage Supply. Operating Temperature: 32°-131°F (0°-55°C), IEC IP20 Enclosure Protection. CE, UL, CUL & 2-Year Warranty
Code Output 1
1
Relay - SPDT Form C, 2A at 250VA (Resistive)
Code Alarm 1 / Output 2
S
SSR Drive (>10VDC @ 20mA)
R
Relay (SPST, Form A, 2A at 250VAC)
Code Alarm 2 / Output 3
0
None
R
Relay (SPST, Form A, 2A at 250VAC)
A
Analog (Linear DC: 0/4-20mA, 0-5V, 0/2-10V)
Code Digital Communications
0
None
1
Modbus RTU/RS485 Digital Communications
Code
0 1
Power Supply
100 to 240VAC 50/60Hz 24VDC/VAC +10%/-15%, AC 50/60Hz
1030 - 1 R A 0 0 Typical Model Number
79
Page 86
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.
Chromalox, Inc.
1347 Heil Quaker Boulevard
Lavergne, TN 37086
(615) 793-3900
www.chromalox.com
© 2018 Chromalox, Inc.
80
Loading...