The information in this document is subject to change without notice.
Chroma ATE INC. makes no warranty of any kind with regard to this manual, including, but
not limited to, the implied warranties of merchantability and fitness for a particular purpose.
Chroma ATE INC. shall not be held liable for errors contained herein or direct, indirect,
special, incidental or consequential damages in connection with the furnishing, performance,
or use of this material.
CHROMA ATE INC.
66 Huaya 1st Road, Guishan, Taoyuan 33383, Taiwan
Copyright Notices. Copyright 2008 Chroma ATE INC., all rights reserved. Reproduction,
adaptation, or translation of this document without prior written permission is prohibited,
except as allowed under the copyright laws.
Page 5
iii
Warranty
All of Chroma’s instruments are warranted against defects in material and workmanship for a
period of one year from date of shipment. Chroma agrees to repair or replace any assembly
or component found to be defective, under normal use during this period. Chroma’s
obligation under this warranty is limited solely to repairing any such instrument, which in
Chroma’s sole opinion proves to be defective within the scope of the warranty when returned
to the factory or to an authorized service center. Purchaser is responsible for the shipping
and cost of the service item to Chroma factory or service center. Shipment should not be
made without prior authorization by Chroma.
This warranty does not apply to any products repaired or altered by persons not authorized
by Chroma, or not in accordance with instructions furnished by Chroma. If the instrument is
defective as a result of misuse, improper repair, or abnormal conditions or operations, repairs
will be billed at cost.
Chroma assumes no responsibility for its product being used in a hazardous or dangerous
manner either alone or in conjunction with other equipment. High voltage used in some
instruments may be dangerous if misused. Special disclaimers apply to these instruments.
Chroma assumes no liability for secondary charges or consequential damages and in any
event, Chroma’s liability for breach of warranty under any contract or otherwise, shall not
exceed the purchase price of the specific instrument shipped and against which a claim is
made.
Any recommendations made by Chroma regarding the use of its products are based upon
tests believed to be reliable; Chroma makes no warranty of the results to be obtained. This
warranty is in lieu of all other warranties, expressed or implied, and no representative or
person is authorized to represent or assume for Chroma any liability in connection with the
sale of our products other than set forth herein.
“O” indicates that the level of the specified chemical substance is less than the threshold
level specified in the standards of SJ/T
“
specified in the standards of SJ/T
Remarks:
Directive 2011/65/EU.
The recycling label shown on the product indicates the Hazardous Substances contained in
the product as the table listed below.
: See <Table 1>.
: See <Table 2>.
<Table 1>
Part Name
PCBA
CHASSIS
ACCESSORY
PACKAGE
Chromium
O O O O O O
O O O O O O
O O O O O O
O O O O O O
Biphenyls/
Group
-11363-2006 and EU Directive 2011/65/EU.
” indicates that the level of the specified chemical substance exceeds the threshold level
-11363-2006 and EU Directive 2011/65/EU.
The CE marking on product is a declaration of product compliance with EU
Disposal
Do not dispose of electrical appliances as unsorted municipal waste, use separate collection
facilities. Contact your local government for information regarding the collection systems
available. If electrical appliances are disposed of in landfills or dumps, hazardous substances
can leak into the groundwater and get into the food chain, damaging your health and wellbeing. When replacing old appliances with new one, the retailer is legally obligated to take
back your old appliances for disposal at least for free of charge.
Page 7
v
<Table 2>
Hazardous Substances
Lead
Mercury
Cadmium
Hexavalent
Polybrominated
Polybromodiphenyl
Ethers
Selected Phthalates
Pb
Hg
Cd
Cr6+
PBB/PBDE
DEHP/BBP/DBP/DIBP
“O” indicates that the level of the specified chemical substance is less than the threshold
level specified in the standards of SJ/T
“
specified in the standards of SJ/T
1.
2.
environment specified in each product’s specification.
Part Name
PCBA
CHASSIS
ACCESSORY
PACKAGE
Chromium
O O O O O
O O O O O
O O O O O
O O O O O O
Biphenyls/
Group
-11363-2006 and EU Directive 2011/65/EU..
” indicates that the level of the specified chemical substance exceeds the threshold level
-11363-2006 and EU Directive 2011/65/EU..
Chroma is not fully transitioned to lead-free solder assembly at this moment; however,
most of the components used are RoHS compliant.
The environment-friendly usage period of the product is assumed under the operating
Disposal
Do not dispose of electrical appliances as unsorted municipal waste, use separate collection
facilities. Contact your local government for information regarding the collection systems
available. If electrical appliances are disposed of in landfills or dumps, hazardous substances
can leak into the groundwater and get into the food chain, damaging your health and wellbeing. When replacing old appliances with new one, the retailer is legally obligated to take
back your old appliances for disposal at least for free of charge.
Page 8
vi
Page 9
vii
Page 10
viii
Page 11
ix
Warning:
This is a class A product. In a domestic environment this product may cause radio
interference in which case the user may be required to take adequate measures.
Page 12
x
Safety Summary
BEFORE APPLYING POWER
PROTECTIVE GROUNDING
NECESSITY OF PROTECTIVE GROUNDING
FUSES
DO NOT OPERATE IN AN EXPLOSIVE ATMOSPHERE
DO NOT REMOVE THE COVER OF THE INSTRUMENT
The following general safety precautions must be observed during all phases of operation,
service, and repair of this instrument. Failure to comply with these precautions or specific
WARNINGS given elsewhere in this manual will violate safety standards of design,
manufacture, and intended use of the instrument. Chroma assumes no liability for the
customer’s failure to comply with these requirements.
Verify that the power is set to match the rated input of this power
supply.
Make sure to connect the protective grounding to prevent an electric
shock before turning on the power.
Never cut off the internal or external protective grounding wire, or
disconnect the wiring of protective grounding terminal. Doing so will
cause a potential shock hazard that may bring injury to a person.
Only fuses with the required rated current, voltage, and specified type
(normal blow, time delay, etc.) should be used. Do not use repaired
fuses or short-circuited fuse holders. To do so could cause a shock or
fire hazard.
Do not operate the instrument in the presence of flammable gases or
fumes. The instrument should be used in an environment of good
ventilation.
Operating personnel must not remove the cover of the instrument.
Component replacement and internal adjustment can be done only by
qualified service personnel.
Page 13
xi
Safety Symbols
The Notice sign highlights an essential operating or maintenance
procedure, condition, or statement.
WARNING
CAUTION
DANGER – High voltage.
Explanation: To avoid injury, death of personnel, or damage to the
instrument, the operator must refer to the explanation in the
instruction manual.
High temperature: This symbol indicates the temperature is
hazardous to human beings. Do not touch it to avoid any personal
injury.
Protective grounding terminal: This symbol indicates that the
terminal must be connected to ground before operation of the
equipment to protect against electrical shock in case of a fault.
Functional grounding: To identify an earth (ground) terminal in
cases where the protective ground is not explicitly stated. This symbol
indicates the power connector does not provide grounding.
Frame or chassis: To identify a frame or chassis terminal.
Alternating Current (AC)
Direct Current (DC) / Alternating Current (AC)
Direct Current (DC)
Push-on/Push-off power switch
The WARNING sign highlights an essential operating or maintenance
procedure, practice, condition, statement, etc., which if not strictly
observed, could result in injury to, or death of, personnel or long term
health hazards.
The CAUTION sign highlights an essential operating or maintenance
procedure, practice, condition, statement, etc., which if not strictly
observed, could result in damage to, or destruction of, equipment.
Page 14
xii
Revision History
Date
Version
Revised Sections
Feb. 2008
1.0
Complete this manual.
Sep. 2008
1.1
Modify the description of section “Protection Features” in the chapter
” for setting slew
– “Status Reporting”
Mar. 2009
1.2
Correct the errors in the manual.
Instruments” in the chapter of “Remote Operation.”
Apr. 2010
1.3
Add the followings:
−System Bus Port: 8-pin connector to 10-pin connector.
May 2012
1.4
Add the following:
Specification of new model 63630-600-15.
The following lists the additions, deletions and modifications in this manual at each revision.
of “Operation Overview.”
Modify the following sections in the chapter of “Local Operation”:
– “Setting Dynamic Load Frequency Sweep Value
rate.
– “Setup of Current Interrupt Function” for set ting Load On Time.
– “Setup of Program Sequences Function” for selecting range.
Add the following chapters:
– “Remote Operation”
Add the following sections:
− “Load ALL RUN” and “Si ne Wave Dynamic” in the chapter of
“Operation Overview.”
− “Sine Wave Dynamic” in the chapter of “Local Operation.”
− “Selecting the LAN Type to be Connected”, “Setting Network
Parameter (IP, Subnet Mask, Gateway)”, “Confirming Network
Connection is Successful” and “Communicating with
− Digitizing function.
− 63600-2 Pin Assignments of the System I/O Port Connector.
− 63600-1 Pin Assignments of the System I/O Port Connector.
CR Mode range, Voltage read back accuracy, Others & Note
3.)
Correct the following errors:
− CONFigure:ALLRun
− DIGitizing:WAVeform:DATA?
− FETCh:AH?
− FETCh:WH?
− CE Declaration for model 63600-1, 63600-2 & 63630-600-15.
− Diagram for standard package and accessories list.
−
Page 15
xiii
− Caution for securing binding post.
− Caution for Timing Measurement Function.
Program sequence flow chart.
Dec. 2012
1.5
Add “MPP Tracker” section in the chapter of “Local Operation.”
and 63600-5.
Mar. 2013
1.6
Add the following:
−“SYSTEM Subs ys tem”
Aug. 2013
1.7
Update the CE Declaration.
Feb. 2014
1.8
Update the CE Declaration.
Subsystem.
Jul. 2014
1.9
Add specifications and the related information of Model 63601-5 in
the manual.
Feb. 2015
2.0
Add the following:
−Operating conditions in CR mode.
Oct. 2016
2.1
Update CE “Declaration of Conformity”.
−“Checking Low Voltage Range”.
Jul. 2017
2.2
Update “Material Contents Declaration” and CE “Declaration of
section.
− Definition of minimum drive current for Ext. Wave.
− Configuration list on the panel for factory default.
− “Verification” and “Appendix A” new chapters.
Modify the following:
−
Modify the Input Rating specification for model 63600-1, 63600-2
−“User Defined Waveform” section in the chapter of “Local
Operation.”
−Appendix “How to Use 63600 UDW to Download Softpanel.”
Modify the following in the chapter of “Remote Operation”:
− “ADVANCE Subsy s tem”
− “CO NF IGURE Subsystem”
− “FETCH Subsystem”
− “MODE Su bs y stem”
Modify “Digitizing Function” section in the chapter of “Operation
Overview.”
Add a Notice in the section of “Remote Sensing Connections.”
Add the contents of “Select the current range” in the section of
“Setting CR Values.”
Modify the syntax description in the sections of “CONFIGURE Subsystem”, “DIGITIZING Subsystem” and “RESISTANCE
−Specifications and related information of Model 63640-150-60
in the manual.
−“LVP” relat ed information in the section of “Protection
Features.”
Update the specification tables in the following sections for “CV
Mode Verification” under the chapter of “Verification”:
− “Checking High Voltage Range”.
− “Checking Medium Voltage Range”.
Conformity”.
Update the accessory list and icon in “Inspection” section.
Add example to “CP Mode Verification” in the chapter of
“Verification”.
Add Ext Wave_Bandwidth to Dynamic CC Mode in “Specifications”
Page 16
Page 17
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
xv
Table of Contents
1. General Information .................................................................................................. 1-1
Appendix B How to Use 63600 UDW to Download Soft Panel ................................ B-1
Page 21
General Information
1-1
1. General Information
1.1 Introduction
This manual contains specifications, installation, operation and programming of 63600
Programmable DC Electronic Load.
The Chroma 63600 Programmable DC Electronic Load System consists of model 63600-1,
63600-2, 63600-5, 63601-5 mainframes, and 63630-80-60, 63610-80-20, 63640-80-80,
63630-600-15 and 63640-150-60 Electronic Load modules.
1.2 Description
The 63600-5, 63601-5 Electronic Load mainframes contain slot for 5 load modules. The
mainframe 63600-5 contains a processor, two System Bus ports, a USB port, a GPIB card
(optional), an Ethernet card (optional), front-panel keypad, a memory channel indicator, and
other circuits common to all the load modules.
The Electronic Load, composed of any of a mainframe plugged-in with at least any of a
module, offers stand-alone operation mode. In addition, the mainframe 63600-5, 63601-5
can be controlled via A636000 GPIB or A636001 Ethernet or USB bus by a remote computer
(see Chapter 5 Remote Operation), or via System Bu s by the remote controller.
The functions of 63610-80-20, 63630-80-60, 63630-600-15, 63640-80-80, 63640-15060…etc. are all the same except the variations on input voltage, load current, and power
ratings. An individual module may have one or two channels. Each channel has its own
channel number, load & measurement connectors, and operates independently in constant
current (CC) mode, constant resistance (CR) mode, constant voltage (CV) mode, constant
power (CP) mode, or Constant Impedance (CZ) mode.…etc.
The 63600 Programmable DC Electronic Load System is used for design, manufacturing,
and evaluation of DC power supplies, batteries, and power components. This chapter
contains specifications of Electronic Load modules that apply to the Chroma 63600-5, 636015 Electronic Load mainframes, as well as key features concerning application. The remaining
chapters in this manual contain instructions for installing, operating, and programming the
Electronic Load. The Chroma 63600-5 Mainframe with 5 Load Modules is shown in Figure
1-1 and the Chroma 63601-5 Mainframe with 5 Load Modules is shown in Figure 1-3. The
Chroma 63600-2 Mainframe with 2 Load Modules is shown in Figure 1-3 while the Chroma
63600-1 Mainframe with single Load Module is shown in Figure 1-4. The Chroma 63610-8020, 63630-80-60, 63640-80-80, 63640-150-60 and 63630-600-15 Load Modules are shown
in Figure 1-5~Figure 1-9.
Page 22
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
1-2
Figure 1-1 63600-5 Mainframe (Mounted with 5 Load Modules)
Page 23
General Information
1-3
Figure 1-2 63601-5 Mainframe (Mounted with 5 Load Modules)
Figure 1-3 63600-2 Mainframe (Mounted with 2 Load Modules)
Figure 1-4 63600-1 Mainframe (Mounted with 1 Load Module)
Page 24
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
External Trig. for Digitizing(TTL Compatible, Rising edge)
No. of bits
1 bit per mainframe
1 bit per mainframe
External Trig. for Auto Sequences(TTL Compatible, Rising edge)
No. of bits
1 bit per mainframe
1 bit per mainframe
Load ON - O/P
Level
TTL Compatible, Level, Active High
TTL Compatible, Level, Active High
Short ON - O/P
2 channels per 63600-1 mainframe
10 channels per 63600-5 mainframe
2 channels per 63600-1 mainframe
10 channels per 63600-5 mainframe
Level
TTL Compatible, Level, Active High
TTL Compatible, Level, Active High
General
Short circuit
Current *6
Set to 100% of rated current
Set to 100% of rated current
Input
Typical *12
Dimensions
(HxWxD)
Weight
5kg / 11 lbs
4.5kg / 9.9 lbs
Operating
Temperature
Storage
Temperature
Power
Supply from mainframe
Supply from mainframe
EMC & Safety
CE
CE
Yes Yes
Yes Yes
Optional Optional
No. of channels
Resistance
(Load Off),
4 channels per 63600-2 mainframe
142x86x514mm / 5.6x3.4x20.2 inch 142x86x514mm / 5.6x3.4x20.2 inch
4 channels per 63600-2 mainframe
366kΩ (80V)
600kΩ (150V)
2MΩ (600V)
0~40°C 0~40°C
-20~80°C -20~80°C
60kΩ (6V)
150kΩ (16V)
700kΩ (80V)
Page 32
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
1-12
Model
63640-150-60
Configuration
400Wx1
Voltage *1*8
0~150V
Current
0~1A
0~6A
0~60A
Power
90W
400W
400W
Static Mode
Typical min. operating voltage (DC)
0.3V@1A
0.3V@6A
1.8V@60A*15
Constant Current Mode
Range
0~1A
0~6A
0~60A
Resolution
0.02mA
0.1mA
1mA
Accuracy
0.04%+0.04%F.S.*17
Constant Resistance Mode
Range
CRL : 0.03~60Ω (400W/16V)
CRM: 0.64~800Ω (400W/80V)
CRH: 6.25~1.5kΩ (400W/150V)
Resolution *9
1mS
Accuracy *3
0.1%+0.067S (16V)
0.1%+0.00625S (80V)
0.1%+0.002S (150V)
Constant Voltage Mode
Range
16V
80V
150V
Resolution
1mV
1mV
10mV
Accuracy
0.025%+0.025%F.S.
Constant Power Mode
Range
0~8W
0~40W
0~400W
Resolution *9
4mW
40mW
400mW
Accuracy *4
0.3%+0.3%F.S.
Von/Voff Control*13
Von&Voff Mode
CC / CR / CP
Accuracy
0.2%FS
Dynamic Mode - CC
Min. Operating Voltage *11*16
1.8V
Frequency
100Hz~50kHz/0.01Hz~1kHz
Duty
1~99% (Min. Rise Time Dominated)
Accuracy
1µs/1ms+100ppm
Slew rate
0.2A/ms~
1.2A/ms~
12A/ms~
0.1A/µs
0.6A/µs
6A/µs
Resolution
0.02mA/µs
0.1mA/µs
1mA/µs
Accuracy
10% ±20µs
Min. Rise Time
10µs
Current
Range
0~1A
0~6A
0~60A
Resolution
0.02mA
0.1mA
1mA
Ext Wave
Mode
CC
Bandwidth
20kHz
Range
0~1A
0~6A
0~60A
Level
0~10V
Accuracy
0.5%F.S.
Program mode
Sequence No.
100/Program
Dwell / SEQ
0.1ms ~ 30s (Resolution : 0.1ms)
Load Setting
Refer to Static mode specifications
Spec Check
Voltage/Current/Power
Measurement
Voltage Read Back
Range
0~16V
0~80V
0~150V
Resolution
0.27mV
1.3mV
2.5mV
Accuracy *5
0.025%+0.01%F.S.
Current read back
Range
0~1A
0~6A
0~60A
Resolution
0.02mA
0.1mA
1mA
Accuracy *5
0.04%+0.04%F.S.
Power read back
Range
0~90W
0~400W
0~400W
Accuracy *4 *5
0.1%+0.1%F.S.
Voltage Monitor
Bandwidth
20 kHz
Page 33
General Information
1-13
Range
0~16V
0~80V
0~150V
Output
0~10V
Accuracy
0.5%F.S.
Current Monitor
Bandwidth
20 kHz
Range
0~1A
0~6A
0~60A
Output
0~10V
Accuracy
0.5%F.S.
Protection
Over Power
Yes
Over Current
Yes
Over Voltage Alarm *8
Yes
Over Temperature
Yes
Reverse
Yes
Interface
USB
Standard
Remote controller
Optional
Ethernet
Optional
GPIB
Optional
System Bus
Master/Slave & Remote Controller
Others
Dout
No. of bits
2 bits per mainframe
Level - H
1.8V/3.3V/5V switchable
Level - L
<0.6V@Isink=10mA
Drive
Pull_up resistor = 4.7kΩ
Din (TTL Compatible)
No. of bits
2 bits per mainframe
External Trig. for Digitizing(TTL Compatible, Rising edge)
No. of bits
1 bit per mainframe
External Trig. for Auto Sequences(TTL Compatible, Rising edge)
No. of bits
1 bit per mainframe
Load ON - O/P
Level
TTL Compatible, Level, Active High
Short ON - O/P
No. of channels
2 channels per 63600-1 mainframe
4 channels per 63600-2 mainframe
10 channels per 63600-5 mainframe
6 channels per 63601-5 mainframe
Level
TTL Compatible, Level, Active High
General
Short circuit
Current *6
Set to 100% of rated current
Input Resistance(Load Off), Typical *12
700kΩ
Dimensions (HxWxD)
142x86x514mm / 5.6x3.4x20.2 inch
Weight
4.5kg / 8.8 lbs
Operating Temperature
0~40°C
Storage Temperature
-20~80°C
Power
Supply from mainframe
EMC & Safety
CE
Model
63600-1
63600-2
Number of slots
1 slot
2 slot s
Operating
temperature
φ 100~115VAC ±10%VLN
Switchable / 47~63Hz
φ 100~115VAC ±10%VLN
Switchable / 47~63Hz
Mainframe
(HxWxD)
Weight
7.5kg / 16.53lbs
11.5kg / 25.35lbs
Model*
14
63600-5
63601-5
Number of slots
5 slot s
5 slot s
Operating
temperature
Input Rating
dimension
1
1φ 200~230VAC ±10%V
177x90x554mm /
7.0x3.5x21.8 inch
0~40°C0~40°C
1
LN
0~40°C0~40°C
1φ 200~230VAC ±10%V
177x210x554mm /
7.0x8.27x21.8 inch
LN
Page 34
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
1-14
φ 100~115VAC ±10%VLN
Auto Range / 47~63Hz
φ 100~240VAC ±10%VLN
Auto Range / 47~63Hz
Mainframe
(HxWxD)
Weight
15.6kg / 34.39lbs
13.6kg / 29.98lbs
63610-80-20
63630-80-60
63640-80-80
63630-600-15
63640-150-60
CRH
(unit: S)
1m/V
CRM
(unit: S)
CRL
(unit: S)
63610-80-20
63630-80-60
63640-80-80
63630-600-15
63640-150-60
CPH
(unit: W)
1m x V
CPM
(unit: W)
0.1m x V
CPL
(unit: W)
0.02m x V
Input Rating
dimension
1
1φ 200~230VAC ±10%V
LN
177x447x554mm /
7.0x17.6x21.8 inch (Full Rack)
1
177x447x554mm /
7.0x17.6x21.8 inch (Full Rack)
NOTE*1: The maximum current loading below the mi nimum operating voltage (0. 5V) will fol l ow a derating curve.
NOTE*2: The 400W power rating of the 63640-80-80 specified at an ambient
temperature of 35℃, please refer to the power rating curve on the right.
NOTE*3: Does not apply to setting current < 0.25% full scale current in high range.
Does not apply to setting current < 0.05% full scale current in low and middle range.
NOTE*4: Power F.S.=Vrange F.S. x Irange F.S.
NOTE*5: The DC level measurements are made over a period of 20ms, and does not
measure any transient signals in the DC measurements.
NOTE*6: Its limits are the maximum power and maximum current of the c urrent range.
NOTE*7: The 63600 is guaranteed to meet specified performance at temperature range
of 25±5℃. NOTE*8: If the operati ng voltage exceeds the rated voltage f or 1.1 tim es, it would cause
permanent damage to the device.
NOTE*9: Please refer to user's manual for detail spec ifications, and S (siemens) is the SI unit of conductance, equal to one
reciprocal ohm.
NOTE*10: E xt. Wave Mode: CC minimum driving current is 0.2mA.
NOTE*11: It is the minimum voltage of load measured by Oscilloscope.
NOTE*12: It is the current setti ng and measurement spec. of each mode not including the leakage current caused by Input
Resistance. If leakage current exceeds 0.05%FS, the influence of Input Resistance needs to be taken into consideration.
NOTE*13: Besides the accuracy 0.2%F.S for voltage measurement, 300µs delay time needs to be added.
NOTE*14: The63601-5 only supports 6 Channels (CH1, CH3, CH5, CH7, CH9 and CH10.)
NOTE*15: When loading 60A continuously within 1 minute, the minimum working voltage can drop to 1.6V.
NOTE*16: The test conditions are 0.5µH under for line sense, CCDH loading 0~60A, SR: 0.4A/μs and Overshoot <5%. If the SR
is 6A/µs, the Overshoot should be smal l er than 5% and the minimum working voltage must be above 2.5V.
NOTE*17: CCM: When the loading current is <10mA: 0.04%+0.12% F.S
Table 1
Table 2
0.32879m / V
0.32879m x V
0.03285m x V
0.00326m x V
0.98638m / V
sense
0.98638m x V
sense
0.09861m x V
sense
0.00984m x V
sense
1.32206m / V
sense
1.32206m x V
sense
0.131517m x V
sense
0.01310m x V
sense
sense
sense
sense
sense
0.2661m / V
0.2661m x V
0.026m x V
0.00277m x V
sense
sense
sense
sense
sense
sense
sense
sense
Page 35
1-15
1.5 Dimension Outline of 63600 Series
● 63600-5 Mainframe outline with 5 Load Modules (Unit: mm)
General Information
Page 36
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
1-16
●63601-5 Mainframe outline with 5 Load Modules (Unit: mm)
Page 37
1-17
●63600-2 Mainframe outline with 2 Load Modules (Unit: mm)
16.10
553.85
210.00
16.10
177.00
177.00
35.38
10.05
UNIT : mm
63600-2
General Information
Page 38
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
1-18
●63600-1 Mainframe outline with single Load Module (Unit: mm )
Page 39
1-19
●Module outline (Un it: mm)
142
85.62
510
36
6.32
UNIT : mm
63610-80-60
63610-80-80
General Information
Page 40
Page 41
Installation
2-1
W51 200270
10.8mm
User’s Manual CD
Quick Start Guide
W38 000023
Red & Black
G32 341000
Fixer
W33 000033
W33 000035
Fuse
Fuse
W51 000028
Terminal 13.8mm
Y-type Bare Terminal
14mm
2. Installation
2.1 Introduction
This chapter discusses how to install the 63600. It also discusses turn-on check procedure
and application considerations as well.
2.2 Inspection
Diagram of 63600 Series Standard Package:
Y-type Bare Terminal
White Load Wire
White Load Wire
(English)
2A/250V
Test Wire
5A/250V
Binding Post
Y-type Bare
As soon as the instrument is unpacked, inspect any damage that might have occurred in
shipping. Keep all packing materials in case that the instrument has to be returned. If any
damage is found, please file a claim to the carrier immediately. Do not return the instrument
to Chroma without prior approval.
Page 42
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
2-2
Model No.
Item Name
Quantity
Quick Start Guide - English
1 piece
User’s Manual CD
1 piece
Binding post fixer
1 piece
Quick Start Guide - English
1 piece
Fuse 2A/250V, 5*20mm
1 piece
User’s Manual CD
1 piece
Binding post fixer
1 piece
Quick Start Guide - English
1 piece
Fuse 5A/250V, 5*20mm
1 piece
User’s Manual CD
1 piece
Binding post fixer
1 piece
Quick Start Guide - English
1 piece
User’s Manual CD
1 piece
Binding post fixer
1 piece
White load wire (W33 00035), 75cm
2 pieces
Test wire red & black
2 pieces each
Y-type bare terminal, exradius ψ10.8mm
4 pieces
White load wire (W33 00033), 75cm
1 piece
Test wire red & black
1 piece each
Y-type bare terminal, exradius ψ13.8mm
2 pieces
White load wire (W33 00033), 75cm
1 piece
Test wire red & black
1 piece
Y-type bare terminal, exradius ψ14mm
2 pieces
White load wire (W33 00033), 75cm
1 piece
Test wire red & black
1 piece each
Y-type bare terminal, exradius ψ13.8mm
2 pieces
Be sure that the following items listed by respective model are received completely.
63600-1
63600-2
63600-5
63601-5
63610-80-20
63630-80-60
63640-80-80
63630-600-15
63640-150-60
2.3 Explanation of Taking Apart
Please refer to Figure 2-1 when taking the instrument apart. Before using, please remove the
protective plate, and then plug the power cord so as to avoid short circuit. The sequences of
taking apart are as follows:
1. Three Screws on the bottom.
2. Four Screws on the two sides.
3. Protective plate
Page 43
Installation
2-3
Load module can be damaged by electronic discharge (static electricity).
modules. Avoid touching the connector and the circuit board.
CAUTION
Figure 2-1
2.4 Installing the Modules
Use standard anti-static work practices when you handle and install
Chroma 63600-5, 63601-5 Mainframe has room for five single-width Loads (63610-80-20,
63630-80-60, 63630-600-15, 63640-80-80, 63640-150-60); Loads can be combined in the
Mainframe in any order. The module installation procedures for all Mainframes are the same.
No special tools are required to install Load Module to Mainframe.
Procedures
1. Power off the Mainframe and disconnect the power cord.
2. Remove any packing materials on the Mainframe.
3. Start to install the modules in the slot (see Figure 2-2).
4. Plugging and sliding the load module into the Mainframe slot along the rail until it locked
and fastened.
5. Install each additional module in the next slot likewise.
Page 44
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
2-4
covered with the panel cover for safety and airflow.
WARNING
Figure 2-2 Installing Modules in the Electronic Load
If the Mainframe is not installed with all modules, the empty slot must be
To unplug it, lift up the switch between the load connectors, using load connectors to help
you draw the module out of the mainframe.
Page 45
Installation
2-5
2.4.1 Channel Number
The channel number of the Load is determined by the module location in the Mainframe
starting from the farthest left slot. As some Load (63610-80-20) has two channels in one
module, channel 1 and 2 are always on the farthest left slot of the Mainframe, and channel 9
and 10 on the farthest right. The channel number is fixed for Mainframe even the Load
module is empty. Figure 2-3 shows the channel assignments for a Chroma 63600-5
Mainframe containing two Loads of 63630-80-60 single channel module, and two Loads of
63610-80-20 dual channel module. Channel number is automatically assigned to 1, 3, 5, 6, 7,
and 8. Channel 2 and 4 are skipped as single module is applied.
Figure 2-3 Example of Channel Number
2.5 Installing the Mainframe
The Electronic Load can operate well within temperature range from 0 to 40 degree C.
However, you must install the Electronic Load in an area that has enough space around for
adequate air flowing through and escaping from the back. You must leave at least 10 cm (4
inch) space above the unit for air circulation. Note that the unit foot stock has enough vertical
space for air circulation when it is stacked. The Mainframe foot stock can be removed for
rack mount.
If you install the equipment on top of your Electronic Load in a cabinet, you must use a filter
panel above the unit to ensure adequate air circulation. A 1U (EIA standard) panel is
sufficient.
2.5.1 Line Voltage
The Electronic Load can operate with a 115/230 Vac input as indicated on the rear LINE
label. The detailed line voltage input range is shown in section 1.4 Specifications. The
Electronic Load can automatically switch correct line voltage range t o corr espond to your
nominal line voltage, when you connect the power cord to correct line voltage and turn on the
Electronic Load.
Page 46
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
2-6
Line fuses do not need to be changed when the line voltage is changed.
setting.
connected to ground.
WARNING
The line fuses will protect the Electronic Load from incorrect voltage
2.5.2 Turn-On Self-Test
Check the following before turning on the Load.
1. The nominal line voltage of the AC input socket is in the range of 100-120/200-240 Vac.
2. The power cord is connected to the AC input socket.
The power cord supplies a chassis ground through a third connector. Be
sure that your outlet is of three-conductor type with the correct pin
Power on the Load by the front panel switch on Mainframe and observe the display.
Immediately after turning on, the Electronic Load executes a self-test that checks firmware
and communication. The Load Module displays,
and then displays the model number as well as firmware version,
63630-80-6 0 < --- Model Number
[636308000066] < --- Serial Number G_FW : 1.00
C1_FW: 1.00
If any error is found during self-test, the display will stop here. Check the Load and
Mainframe connection when an error occurs. When the self-test completes, the VFD will
display measurement V & I. The dual channel module goes to L channel.
In case of failure, return the Mainframe or Load module to Chroma sales or service office for
repair.
< --- F/W version < --- F/W version
Page 47
Installation
2-7
connected to the Electronic Load.
To satisfy our higher slew rate load spec requirement and performance,
between UUT and the load.
the banana plugging connection can’t be used.
When using Y-type (U-type) terminal to connect the load terminal, do not
exceed 30kgf-cm when securing it using Chroma terminal fixture.
WARNING
WARNING
WARNING
2.6 Application Connection
2.6.1 Load Connections
To satisfy safety requirements, load wires must be heavy enough not to
overheat while carrying the short-circuit output current of the device
load wires which have over 2.0μH inductance must be avoided from the
UUT to our load. We have made the adaptable Load Cables along with
the Load. They are better for application connection being the interface
Input connections are made to the + and − terminal connectors on the front of each Load
module. The major considerations for input connections are the wire size, length and polarity.
The minimum wire size required to avoid overheating may not be enough to maintain good
regulation. The wires should be large enough to limit the voltage drop to less than 0.5V per
lead. The wires should be as short as possible, and bundled or tied together to minimize
inductance and noise. Connect the wire from the PLUS (+) terminal on the module to the
HIGH potential output terminal of the power supply (UUT). Connect the wire from the MINUS
(−) terminal on the module to the LOW potential output terminal of the power supply (UUT).
Figure 2-4 illustrates the typical setup of the Load module to the UUT. T he connecting way is:
First Put the Y-type terminal wire into Load terminal from the bottom of the load terminal, and
let Y-type terminal touch the metal post of the load terminal tightly. Then, turn the banana
binding socket of the Load terminal for connection by your hands, and finally use a tailormade spanner to make the connection tightly. Figure 2-5 shows the Load connection with the
tailor-made spanner.
Each terminal with banana binding socket can easily use the banana
plug to make load connection. It is the other way for load connection. But
normally the banana plug can carry only 20 or 10 Amps at most. Before
you use the banana plugs for connections, you must check the
maximum current rating of the banana plugs and the wire. The
connection with the banana plug isn’t fixed in the banana binding socket
tightly. So, when the output voltage of the power supply (UUT) is equal
to or over 70VDC, to prevent accidental contact with hazardous voltage,
overlap 2 (or more) terminals at the same time and the torque cannot
Page 48
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
2-8
Figure 2-4 Load & Remote Sensing Connection
Page 49
Installation
2-9
The potential of Vsense red connector must be higher than that of
Vsense black connector.
Due the nature of load, the associate internal designs are shared for
the UUT voltage measurement function as a power meter.
A. Single Channel Module B. Dual Channel Module
Figure 2-5 Load Connection with the Tailor-made Spanner
2.6.2 Remote Sensing Connections
There are two sensing points in the Electronic Load module. One is measurement at Load
terminal, and another is at Vsense. The Load module will automatically switch to Vsense
when Vsense terminals are connected to UUT, otherwise it will measure at Load terminals.
Remote sensing compensates for voltage drop in applications that require long lead lengths.
It is useful when a module is operating in CV or CR mode, or when it needs precise
measurement. Figure 2-4 also illustrates a typical setup for remote sensing operation.
use. Follow the precautions listed below for operation.
1. The internal resistance of each Electronic Load is different and
varied when connecting to a UUT. Use a professional digital power
meter if more accurate voltage measurement is required.
2. Use t he load UUT Vsense or Local terminal to do voltage
measurement. Connect the negative ends is suggested to avoid any
possible loop current that may affect the measurement result.
3. Cont act Chroma technical service center if there is a need to use
Page 50
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
2-10
2.6.3 Parallel Connections
Figure 2-6 illustrates how modules can be paralleled to increase power dissipation. Modules
can be directly paralleled in CC, CR or CP mode. Modules cannot be paralleled in CV mode.
Each module will dissipate the power it has been programmed. For example, if two modules
are connected in parallel, one is programmed 10A, and another is 15A, the total current
drawn from the source is 25A. Restriction on number of parallel modules depends only on
total modules available in the multi-mainframe environment described in the next section.
Figure 2-6 Parallel Connection
2.6.4 Multi-Mainframe Connections
The Electronic Load system offers multi-mainframe synchronized connectivity for up to 4
mainframes. The user is allowed to connect either System Bus1 or System Bus2 port on rear
panel of a mainframe as input from previous mainframe, and use the remainder as output to
the next mainframe. For a systematic configuration, it is strongly recommended to connect 2
mainframes in the way as from System Bus1 on a mainframe to System Bus2 on the other
mainframe. Figure 2-7 indicates how to connect mainframe1 and mainframe2 along with
extend to mainframe3.
Page 51
Installation
2-11
Figure 2-7 Multi-Mainframe Connections Modes
2.7 Remote Control Connection
The remote operation of Load can be done through GPIB, Ethernet, or USB interface. These
connectors on the rear panel connect the Load to the controller or computer. The GPIB and
Ethernet interface of the electronic load is optional. Connect the Remote Controller to the
Electronic Load before powering it on. If you have not done this, Load will shut down, or the
fuse for remote controller in Mainframe will be broken.
2.8 GPIB Card Setup
The ma i nframe 63600-5, 63601-5 facilitates remote operation via GPIB bus as an option.
Setting up GPIB card, changing GPIB address and its operation are described in Chapter 5.
Page 52
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
2-12
2.9 Ethernet Card Setup
The ma i nframe 63600-2, 63600-5 and 63601-5 facilitate remote operation via Ethernet bus
as an option. Setting up Ethernet card, and its operation are described in Chapter 5.
Page 53
Operation Overview
3-1
The Model 63601-5 only provides commands for save and recall
functions with no support of manual operation.
3. Operation Overview
3.1 Introduction
Chroma 63600-5, 63601-5 multiple electronic load mainframes are suitable for design,
manufacturing, testing and quality assurance for electronic products. The Mainframe
contains five slots of load modules. Each Load module occupies one slot depending on the
power rating of the module.
The Mainframe 63600-5, 63601-5 can dissipate up to 2,000 watts when it is full loaded. It
contains a processor, two System Bus ports, a USB port, a GPIB card (optional), an Ethernet
card (optional), front panel keypad and display, and PASS/FAIL signals. The built-in remote
control function enables you to control and read back the current, voltage and status. The
SYNC function on the Mainframe synchronizes each module when the module current/
voltage level changes. The Save/Recall feature allows you to save up to 100 files, 10
programs, and one default setting. All of them can be saved in module EEPROM for future
use.
The Load Module has one cooling fan. The fan speed automatically increases or decreases
when the module power rises or falls. This feature reduces overall noise level as the fans do
not always run at maximum speed.
Each module can operate independently in constant current (CC), constant resistance (CR),
constant voltage (CV), constant power (CP), and constant impedance (CZ)…etc. An
individual module may have one or two channels. Each of them has its own channel number
with its own input connectors, and can be turned on/off or short-circuited independently. If
your application requires a greater power or current capacity than one module can provide,
you have to connect load modules in parallel in CC, CR, or CP mode.
Each load module can be controlled any remotely via GPIB / Ethernet / USB / System Bus
interface. Once a channel is selected or addressed, all subsequent commands go to that
channel till another channel is selected or addressed. The operation of all modules in the
Mainframe is similar in spite of power ratings; meanwhile each module has a keypad to
control itself.
Each module operates independently in CC, CR, CV, CP, or CZ mode as a load and
simultaneously measures current, voltage, or power level. The user is allowed to off-line edit
above mentioned parameters. Beside, in any of the operation modes, when active, the online change of parameters changes the Electronic Loading accordingly, thus making it easy
to achieve an optimized test condition and then saved for later use.
The module allows the user to enter specification of a UUT including V and I for later GO/NG
check. In addition, the real time measurement bar on the VFD display indicates the degree of
deviation from specification and guides the users in adjusting to fulfill spec.
This chapter covers the interpretation of the front and rear panel description, the initial setup,
and the operation of static load under different operating modes including CC, CR, CV, CP
and CZ, and CC dynamic load.
Page 54
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-2
Power key
LED Display
Keypads
Power Key
3.2 Front Panel Description
The Mainframe front panel includes a 2 characters 7-segment LED display, and keypads.
The front panels of Mainframe 63600-5, 63601-5, 63600-2, 63600-1 are shown in Figure 3-1,
Figure 3-2, Figure 3-3 and Figure 3-4.
Figure 3-1 Front Panel of 63600-5
Figure 3-2 Front Panel of 63601-5
Page 55
Operation Overview
3-3
Power key
Power key
LED
Keypads
Display
Figure 3-3 Front Panel of 63600-2
Figure 3-4 Front Panel of 63600-1
3.3 Rear Panel Descripti on
The Mainframe rear panel includes two System Bus ports, a USB port, an optional GPIB
connector, an optional Ethernet connector, a System I/O port, an AC LINE socket, a fuse
holder, and five air holes of the fan cooling.
The rear panels of Mainframe 63600-5, 63601-5, 63600-2, 63600-1are shown in Figure 3-5,
Figure 3-6, Figure 3-7 and Figure 3-8.
Page 56
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-4
GPIB
USB
SYSTEM
BUS
ETHERNET
SYSTEM
I/O
FUSE
AC
Socket
FAN
AIR HOLE
FAN
AIR HOLE
SYSTEM
I/O
SYSTEM
USB
GPIB/
AC Socket
COOLING
Figure 3-5 Rear Panel of 63600-5
COOLING
ETHERNET
Figure 3-6 Rear Panel of 63601-5
& FUSE
Page 57
3-5
Item
Description
1
GPIB Interfa c e : A GPIB interface for connecting remote controller using a computer.
2
Ethernet Interface: An Ethernet interface for connecting remote controller using a
computer.
3
USB Interface: An USB interface for connecting remote controller using a computer.
4
SystemBus Interface: Connectors to enable multi-mainframe synchronous operation,
remote controller.
5
System I/O: Connector with which includes Analog signals: voltage and current
with isolation.
6
Fuse: Safe guard against over loading.
7
AC Line: AC power connector that supplies power to all modules in the mainframe.
8
Fan Cooling Air Holes: Air holes with metal fan guard on the rear of the mainframe for
decreases as load power rises or falls in each individual load module.
GPIB
USB
SYSTEM
BUS
ETHERNET
SYSTEM
I/O
FUSE
AC
Socket
SWITCH
SYSTEM
I/O
FUSE
FAN
AIR HOLE
Operation Overview
COOLING
Figure 3-7 Rear Panel of 63600-2 Figure 3-8 Rear Panel of 63600-1
Table 3-1 Definition for Rear Panel Connectors on the Mainframe
with USB/Ethernet/GPIB/MANUAL control. A System Bus port also for connecting
monitor and external wave input, and Digital System Input/Output signals. The Digital
System Input/Output signals are TTL Compatible. The signal is connected to module
air flow. Fan is on the module and the cooling fan speed automatically increases or
3.4 Local/Remote Control
Local (front panel) control is in effect immediately after the power is applied. The front panel
keypad and display allow manual control of individual module when Load is used in bench
test applications. Remote control goes into effect as soon as the Mainframe receives a
command via GPIB / Ethernet / USB / System Bus interface. When the remote control is in
effect, only the computer/remote controller can control the Load. The front panel keypad has
no effect except the LOCAL key. You can return to local control by pressing LOCAL key.
Page 58
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-6
MODE
Most of the functions that perform remotely can be done locally too at the Load Module front
panel. The keypads on the Mainframe can perform simple functions like specific setting, data
lock operation, save/recall setting.
Details of local operation are given in Chapter4Local Operation. Fundamentals of remote
programming are described in Chapter5Remote Operation.
3.5 Modes of Operation
There are five modes of operation: Constant Current (CC), Constant Resistance (CR),
Constant Voltage (CV), Constant Power (CP), and Constant Impedance (CZ).
When you press key to program a mode, the module will change to a new mode. In
change of modes the module’s input is momentarily disabled before a new mode is enabled.
This ensures the minimum overshoots during mode change. The parameters in current,
resistance or voltage mode can be programmed easily when the mode is selected.
All data set in CC/CR/CV/CP/CZ mode will be rescaled to fit the resolution of current/voltage
levels or slew rate. In local mode any value can be set from the keypad. But, if ther e is no
upper and lower limit that would cause an error. The Load automatically selects data, which
is rescaled from the programmed value, truncates and checks high, low boundary before
fitting it into the memory. When the programmed data is over the boundary, the Load will set
the maximum or minimum level. In remote mode the programmed value cannot be over
boundary. An error will occur when the data is over the maximum or minimum value.
3.5.1 Constant Current Mode
Figure 3-9 Constant Current Mode
Page 59
Operation Overview
3-7
MODE
RAN GE
A/B
A/B
Time
Current
rise slew rate
fall slew rate
State A
State B
4A
2A
10uS
25uS
press key "A/B"
A/B
In CC mode, the Load will sink a current in accordance with the programmed value
regardless of the input voltage. To enter into the CC mode, press the key a few times
until the VFD displays CC mode.
Current Ranges (Low, Middle, High)
Current can be programmed in any of the three ranges, low range, middle range and high
range. The low range provides better resolution at low current setting. If any value is over the
maximum of low range, you must select the middle range. When any value is over the
maximum of middle range, you must select the high rang e. To change the ra nge, press the
key few times until the LED range indicator is active at you want to select.
The mode change will affect the module, so will the change of range. Both of them will cause
the input to go through an off state. If the CC mode of Load module is active, the new setting
will change the input immediately at a rate determined by the slew rate setting.
Static Load Mode
In CC mode two operation modes Static load and Dynamic load are available for selection.
Static function checks the stability of output voltage from a power supply. In some modules
(single channel module) there are two current levels (A or B) for static function. Both A and B
states use the same range. You can program the current loading to two different levels, A
and B, and then switches manually between two programmed states A and B using the
key on the module’s keypad. Slew rate determines the rate at which Load level
changes from one load level state to another. Figure 3-10 shows the current level of load
module after pressing key.
State A=4A, State B=2A, Rise =0.2A/μs, Fall =0.08A/μs
Figure 3-10 Load Level after Pressing Key
Page 60
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-8
DYNA
Time
Current
Load1
load2
10mS
10mS
10mS
10mS
4A
2A
T1
T2
T1
T2
DYNA
Dynamic Load Mode
There are two Operation Modes for dynamic load: Dynamic load mode and Dynamic load
frequency sweep mode. Press to select Dynamic load or Dynamic load frequency
sweep mode.
Dynamic load operation offers the user to program 2 load levels (Load1 and Load2), load
durations (T1 and T2), slew rates (Rise and Fall), and Repeat times (RT). During operation,
the loading value is switched between those two load levels according to your specific setting
parameters. The Dynamic Load is commonly used for testing the UUT’s performance under
high speed, transient loading condition.
Load1=4A, Load2=2A, Rise =0.2A/μs, Fall =0.2A/μs, T1=10ms, T2=10ms, RT=0
Figure 3-11 Dynamic Current Waveform
The STATic/DYNAmic functions can also be selected through key on the Load
module.
Slew Rate (Rise, Fall A/μs or mA/μs)
Slew rate determines the rate at which the current input of a module change to a newly
programmed value. There are two slew rate values, which are rise rate and fall rate.
Voltage Ranges (Low, Middle, High)
There are three voltage ranges for voltage measurement and Von voltage setting. The low
range provides better resolution at low voltage measurements. If the value is over the
maximum of low range, you must select the middle range. When the value is over the
maximum of middle range, you must select the high range. The CC mode voltage range
selection is in configuration setting.
Repeat time s ( ti mes)
The Load provides a unique simulation capability, which allows users to set the number of
the period times. When the tim es is set a limited period times, the load is automatically off till
the period time is over. If you want to continue the load with unlimited times, just to set the
value to be zero.
Page 61
Operation Overview
3-9
Dynamic Load Frequency Sweep Mode
Figure 3-12 CC dynamic Frequency Sweep Current Waveform
The Load offers a unique CC dynamic frequency sweep with variable frequency to find the
worst case UUT voltage.
Frequency Sweep Function operation enables you to program two load levels (Load1 and
Load2), Start frequency, End frequency, Step frequency, Dwell time, duty, slew rate (Rise
and Fall). During operation, the loading value is switched between those two load levels
according to such user specified parameters.
Frequencies (Start frequency, End frequency, Step frequency Hz)
The setting range of the Frequencies is from 0.01Hz to 50kHz.
Dwell time (s)
Dwell time is the elapse time of each setting step frequencies from start frequency to End
frequency. T he setting range of the Dwell time is from 1ms to 100s.
Duty (%)
The duty in percentage of Load1 is in one dynamic loading cycle, and it is expressed by %.
The duty can be set from 1%-99%. The Duty setting will be limited within the transition time
of the two load levels.
Page 62
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-10
The standard option refrigerant line or the cable with line sense lower
during loading needs to be larger than 1.8V to avoid loading error.
RAN GE
A/B
3.5.2 Constant Resistance Mode
Figure 3-13 Constant Resistance Mode
In CR mode, the Load will sink a current linearly proportional to the input voltage in
accordance with the programmed resistance. This mode is operated under the F/W
calculation. That is, take the measured V data, divide the resistance setting and get the I
setting value. There is a moving average calculation process for the measuring data. High
frequency parts will be removed, and the minimum transient time of the loading current in this
mode is 400us. To avoid the load current change caused by the input voltage variation, the
power source impedance should be as low as possible, and remote sensing cable must be
used to sense load input voltage when high sink current (low setting resistance) is
programmed.
Voltage Ranges (Low, Middle, High)
Resistance can be programmed in any of low, middle, or high range. The low range is used
for input voltage in low voltage range. The middle range is used for input voltage in middle
voltage range while the high range is for input voltage over middle voltage range. The current
range in CR mode is high range.
If input voltage is over the maximum of low range, you must select the middle range. When
input voltage is over the maximum of middle range, you must select the high range. To
change the range, press the key few times until the LED range indicator is active at
you want to select. In some modules (single channel module) there are two resistance levels
(A or B) for CR function. Both A and B states use the same range. You can select state A or
state B through the key on the module’s keypad. Slew rate determines the rate at
which load level changes from one load level state to another.
than 0.5µH should be used between the UUT and Electronic Load.
When doing low voltage and large current testing, the load voltage
Page 63
3-11
3.5.3 Constant Voltage Mode
RAN GE
A/B
Operation Overview
Figure 3-14 Constant Voltage Mode
In CV mode the Load will sink current to control the voltage source in programmed value.
This mode is operated under the F/W calculation. That is, take the voltage setting, divide the
measured output current of UUT’s CC mode and get the suitable resistance as the
equivalent resistance of the Cells. Then, take the voltage setting, divide the suitable
resistance and get the I setting value. There is a moving average calculation process for the
measuring data. High frequency parts will be removed, and the minimum transient time of the
loading current in this mode is 400μs.
Voltage can be programmed in any of low range, middle, or high range by the key.
The low range is used for input voltage in low voltage range. The middle range is used for
input voltage in middle voltage range while the high range is for the input voltage over middle
voltage range.
In some modules (single channel module), there are two voltage levels (A or B) for CV
function. You can select state A or state B using key. Both A and B states use the
same range.
Current Range (High)
The current range in CV mode is high range.
Page 64
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-12
RAN GE
A/B
3.5.4 Constant Power Mode
Figure 3-15 Constant Power Mode
In CP mode, the Load will sink a current according to the programmed power. This mode is
operated under the F/W calculation. That is to divide the power setting by the measured V
data and get the I setting value. There is a moving average calculation process for the
measuring data. High frequency parts will be removed, and the minimum transient time of the
loading current in this mode is 400μs.
Power can be programmed in any of low range, middle, or high range by the key.
The low power range is operated under low current range mode. The middle power range is
operated under middle current range mode while the high power range is under high current
range mode.
In some modules (single channel module), there are two power levels (A or B) for CP
function as other modes. Both A and B states use the same range. You can select CPLA or
CPLB using key. Slew rate determines the rate that the load level changes from one
state to another.
Page 65
Operation Overview
3-13
3.5.5 Constant Impedance Mode
Figure 3-16 Constant Impedance Mode
In CZ mode, the Load will sink a current according to the programmed impedance. This
mode is operated under the F/W calculation. That is, take the measured V data, divide the
Impedance setting and get I setting value.
There is a moving average calculation process for the measuring data. High frequency parts
will be removed, and the minimum transient time of the loading current in this mode is 400us.
Impedance can be programmed by set the equivalent series resistance Rs, equivalent series
inductance Ls, equivalent parallel load capacitance C
and Ip (max)
needs to be set before loading and the parameter range for setting is listed in the
specifications.
To avoid the load current change caused by the input voltage variation, the power source
impedance should be as low as possible, and remote sensing cable must be used to sense
load input voltage when high sink current (low setting resistance) is programmed.
parameters for loading when operating in this mode. The UUT Ip (max) value
, equivalent parallel load resistance RL
L
3.6 Load ALL RUN
Chroma 63600-5 multiple electronic load mainframes can have at most up to ten channels.
The method each channel loads On/Off can be controlled by the ALL RUN setting. The
loading of channels with the ALL RUN function turned on, can be controlled via other
channels with ALL RUN settings turned on. Channels with ALL RUN turned off will load
On/Off individually.
3.7 Measurements
Each module measures current and voltage of a UUT. The sampling rate is about 2μs.
Voltage and current measurements are performed with a 16-bit resolution of full scale ratings.
Page 66
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-14
In order to prevent the voltage transient of UUT from damaging the
and Middle current range.
3.8 Slew Rate & Minimum Transient Time
Slew rate is defined by the change in current over time. A programma ble slew rate allows a
controlled transition from one load setting to another to minimize the induced voltage drops
on inductive power wiring, or control the induced transients on a test device. If the transient
from one setting to another is large, the actual transient time can be calculated by dividing
the current transition by the slew rate. The actual transition time is defined as the time
required for the change of input from 10% to 90% or from 90% to 10% of the programmed
excursion. If the transition from one setting to another is small, the small signal bandwidth of
Load will limit the minimum transition time for all programmable slew rates. Because of the
limit, the actual transition time is longer than the expected time based on the slew rate.
Therefore, both minimum transition time and slew rate must be considered when determining
the actual transition time. The minimum transition time is from 10μs in the CC mode and CC
dynamic mode slew rate setting.
Load, the electronic short function is not available in each mode for Low
3.9 Start/Stop Sink Current
To simulate the transient characteristics of load to UUT, the critical problems are when and
how the Load starts sinking current from UUT. You may set the conducting voltage Von to
solve the problems. The Load will start or stop sinking current when the UUT output voltage
reaches the Von voltage. You can start sinking current when the load is ON and the input
voltage of the module is over Von voltage, but stop sinking when load is OFF or the input
voltage is below Von voltage. See Figure 3-17 and Figure 3-18 for start/stop sinking current.
There are two operation modes for Von control, latch and non-latch. Latch means that when
voltage is over Von voltage, Load will start sinking current continuously in spite of input
voltage drop is below Von voltage. Non-latch means that when input voltage is below Von
voltage, Load will stop sinking current. The Von voltage and its operation mode are set in
configuration.
Page 67
Operation Overview
3-15
Figure 3-17 Start Sinking Current (Von Non-Latch)
Figure 3-18 Stop Sinking Current (Von Non-Latch)
In the battery discharge timing measuring mode, you may set the conducting voltage Voff to
avoid repeatedly start sinking and stop sinking current when the UUT output voltage is
repeatedly up and down near the Von voltage.
When you set the conducting voltage Voff, the Load will start sinking current when the load is
ON and the UUT output voltage reaches the Von voltage, and stop sinking current when the
UUT output voltage is below the Voff voltage. Then, the load is OFF. I t will not sink current
when the UUT output voltage reaches the Von voltage again, until you turn it on.
The conducting voltage Voff is only available in Timing mode, and to avoid the logic error, the
Voff should be less than or equal to Von.
Page 68
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-16
The delay time spec for Von is 300µs.
In order to simulate a real short circuit, the electronic short function is
Low and Middle current range.
SHORT
SHORT
SHORT
SHORT
ENTER
3.10 Short On/Off
Load module can simulate a short circuit at input by setting the load on with full-scale current.
The short circuit can be on/off from the front panel or via remote control. There are two
operations for key on the front panel. One is toggled on/off, and the other is
controlled by key. They are selected in configuration. The key will be enabled only
when Load is ON.
Toggled on/off means pressing once to enable short circuit, and again to disable.
Controlled by key means pressing and holding it to enable short circuit, and
releasing it to return to normal operation.
The actual value of electronic short depends on the limit is the maximum current range and
the maximum power range the Load can supply. Turning on the short circuit does not affect
the programmed setting, and Load input will return to the previous programmed values when
the short circuit is turned off.
only available in each mode for High current range, but not available in
3.11 Digitizing Fun ction
To record the transient voltage and current waveforms, the 63600 series offer a digitizing
function for recording the transient waveforms. It is very convenient to record the information
via this function.
In the page of system configuration, turn the Rotary knob to change the display value to 9,
then press key into Digitizing Function edit page of system configuration.
Set the Sampling Time. Set the interval of sampling time. The range is from 2μs to 40ms,
and the resolution is 2μs. If Set the Sampling Point is 4097 to 15,000 dots, the setting
range is 100μs - 40ms
SAMPLING_TIME
: 40.000ms
Set the Sampling Point. Set the total sampling points. The range is from 1 to 15,000 points.
The default of Sampling Point is 4,096 points.
SAMPLING_POINT
: 4096
and the resolution is 100μs. The default of Sampling Time is 40mS.
Page 69
Operation Overview
3-17
ENTER
ENTER
ADVA
ADVA
ADVA
Set the Trigger Source. Set the Trigger Source of Digitizing Function. Load ON, Load OFF,
TTL (External trigger, TRIG_DIGI signal), BUS tr igger, and Manual trigger could be chosen
to be the Trigger Source. The default setting of Trigger Source is Load ON.
TRIG_SOURCE
: LOAD ON
Set the Trigger point. Set the Trigger point of Digitizing Function. The range is f rom 1 to
4,096 points. The default of Sampling Point is 2,000 points.
TRIG_ POINT
: 2000
Then the display will go to the first editing page again.
To leave out of the Digitizing Function edit page of system configuration, you need to press
and simultaneously to go back to the page of system configuration
When Setting the Configuration is over, to leave out of the page of system configuration, you
need to press and simultaneously to quit the Setting page of system
configuration.
3.12 Timing MeasurementFunction
The Load includes unique timing function allowing precise time measurements in the range
of 0s to 100,000s. This feature allows users to set the final voltage & timeout value for
battery discharge testing and other similar applications.
.
Figure 3-19 Timing Measurement Function
Press key to select the timing measurement operation. In timing measurement
function, the Load will measure the duration from the load on to the UUT output voltage
equal to the setting trigger voltage.
The Load allow user to specify measuring trigger levels of the UUT output voltage and the
operation mode. Figure 3-19 shows the Timing measurement function. In this mode, the
Page 70
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-18
For battery discharge test, to protect the Electronic Load from damage,
please refer to Appendix A Precautions for Loading Battery.
LOAD
CAUTION
Ch1
Ch2
Load will automatically stop sink current and finish the operation after the timing
measurement is taken without pressing the key.
3.13 Sine Wave Dynami c
If the load has a unique sine wave loading current that allows the user to set the loading
current bias (I_DC), the loading sine wave (I_AC) and sine wave frequency (Frequency). The
lowest point of sine wave cannot be smaller than 0 ampere. As Figure 3-20 shows Ch1 is the
actual loading current waveform and Ch2 is the voltage waveform of the UUT (AC
component.)
Figure 3-20
The dynamic current loading bandwidth varies with the load designed on the market and the
response speed of loading slow rate is different by the bandwidth. For instance, using two
loads of different brands to set the dynamic current conditions as I
max
= 6A, I
= 1A, T1=
min
0.1ms, T2= 0.9ms, Slew Up= 0.23A/μs and Slew Down = 0.23A/μs to test the voltage
transient response character of the same power supply. The result shows in Figure 3-21
Load of A Brand and Figure 3-22 Load of B Brand are set in the same current slew rate but
with different voltage waveform. Therefore, using sine wave loading to test the dynamic load
modulation rate will not cause any measurement error due to different load design and
different bandwidth. It wil l make t he test more perfect.
Page 71
Operation Overview
3-19
LOAD
Figure 3-21 Load of A Brand
Figure 3-22 Load of B Brand
3.14 OCP Test Function
The Load provides ramped up current for the load to test the UUT voltage whether has
reaches trigger voltage level to judge the OCP protection movement normally or not. This
test checks the response of one UUT output under overloaded condition.
3.15 Program Sequences Function
The Program Sequences Function feature is very powerful. The electronic load has 10
programs that can set up 100 sequences maximum. For instance, when program 1 is set up
with 5 sequences and program 2 is set up with 8 sequences, the rest programs from 3 to 10
can set up the remaining 87 sequences. Please see section 4.6.5 for setting and running the
Program Sequences Function.
3.16 Load On/Off
A module’s input can be toggled on/off through the key on module, or the remote
control. The on/off change for input is done according to the slew rate.
Turning off the load does not affect the programmed setting. The load will return to the
previous programmed values when the Load is turned on again.
3.17 Protection Features
Each load module has the following features: Over Current Protection, Over Power
Protection, Over Temperature Protection and Over Voltage, Reverse Voltage Warnings.
Page 72
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-20
To protect the Electronic Load from possible damage, the input voltage
potential.
ENTER
CAUTION
The appropriate bits in the Mainframe’s status registers are set when any of the protection
features listed above is active. The Load’s buzzer will beep to inform you till the protection
status is reset. When any of the protections occurs, the Load input will turn off.
●Over Voltage Warning
The over voltage protection circuit is set at a level slightly above the voltage range
specified in the Load specification. The over voltage (OV) and voltage fault (VF) status
register bits are set when the OV condition occurs and will remain set till they are reset.
The Load module will appear OVP when over voltage protection occurs.
●Over Current Protection
When the Load is operating in CR or CV mode, it is possible for a module to attempt to
sink current more than it is rated for. The limit level of current is set at a level slightly
above the current of the Load. The over current (OC) and current error (CE) status
register bits are set when the OC condition occurs, and will remain set till they are reset.
The Load module will appear OCP when over current protection occurs.
●Over Power Protection
The overpower protection circuit is set at a level slightly above the power range
specified in the Load specifications. The over power (OP) and power error (PE) status
register bits are set when the OP condition occurs, and will remain set till they are reset.
The Load module will appear OPP when overpower protection occurs.
●Over Temperature Protection
Each Load has an over temperature protection circuit, which will turn off the load if
internal temperature exceeds the safety limit. The over temperature (OT) and
temperature error (TE) status register bits are set when the OT condition occurs, and
will remain set till they are reset. The Load module will appear OTP when over
temperature protection occurs.
●Reverse Voltage Warning
The Load conducts a reverse current when the UUT polarity connection is not correct.
The maximum safe reverse current is same as the Load rated current. If the UUT
reverse current is over the rated current of Load, the Load may be damaged. If a
reverse voltage condition is detected, you must turn off the power to UUT immediately,
and correct the connection. The reverse voltage (RV) and voltage fault (VF) status
register bits are set when the RV condition occurs, and will remain set till they are reset.
The Load module will appear REV when reverse voltage protection occurs.
●Max sine wave current
When the LOAD is operating under SINE WAVE DYNA function, the panel will show
“MAX LIM” once the loading current caused the voltage to change exceedingly beyond
the condition allowed.
All of the above protection features will latch when they are tripped. When any of the
protections occurs the module will turn off the load input, and beep till you remove the
condition and reset the protection by pressing key on the module.
must not exceed the maximum input voltage rating specification. In
addition, the Load + terminal potential must be higher than the − terminal
Page 73
Operation Overview
3-21
When high voltage models are in used, the “CC,CP V RANGE SELECT”
default protection voltage range is about 0.02V~1.2V.
CAUTION
V
SW
●LVP
The desi gn of LVP is mainly to prevent the UUT from sudden voltage drop to 0V and rise
again when the Von point is set to 0V or in current loading state at “LOAD ON” as it could
cause the voltage or current to overshoot. Also it could damage the UUT or Electronic Load
if the UUT is connected.
The LVP is a default protection voltage set internally. When t he Electronic Load is under this
voltage and in loading mode, it does not perform current loading until the external voltage is
larger than the LVP set protection voltage. Therefore, there will be no overshoot even though
the Von point is set to 0V or the voltage is suddenly dropped to 0V and raised again. This
way is to prevent the overshoot to damage the UUT and Electronic Load.
is set to “HIGH” and “LVP” is set to protection, it may not able to operate
the maximum current under minimum working voltage as the LVP
For example,
UUT
Electronic
Load
Figure 3-23 Power, UUT & Electronic Load Connecting Diagram
(1) When the Von Point is set to 0V and the LVP sets no protection during “LOAD ON”,
current overshoot will occur on the Electronic Load when the Switch (SW) is off. It may
damage the UUT and Electronic Load under this circumstance as shown in Figure 3-24.
Page 74
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-22
Load Sink
Current
UUT
Output
I
V
t
t
Settin
Load Sink
Current
UUT
Output
I
V
t t
Settin
Von
Figure 3-24 When Von Point sets to 0V without Protection
(2) When the Von Point is set to 0V and protection is selected for LVP during “LOAD ON”,
the Electronic Load starts current loading when the SW is off and the external voltage is
over the protection voltage. Current overshoot will not occur under this circumstance as
shown in Figure 3-25 .
Figure 3-25 When Von Point sets to 0V with Protection
(3) When the Von Point is not set to 0V and protection is selected for LVP during “LOAD
ON”, turn off the SW after it is turned off a period of time and then turn the SW off again.
It will not perform current loading if the power is lower than the default protection voltage
as shown in Figure 3-26. The loading state restores when the SW is off and the power
is larger than the default voltage.
Page 75
Operation Overview
3-23
V
UUT
Output
Current
Load Sink
Von
Setting
t t I
UUT
Output
Current
Load Sink
Von
Setting
LVP
t
t
V
I
Figure 3-26 When Von Point is not set to 0V with Protection
(4) When the Von Point is not set to 0V and the LVP sets no protection during “LOAD ON”,
turn off the SW after it is turned off a period of time and then turn the SW off again.
Current loading continues when there is no power as shown in Figure 3-27. Current
overshoot may occur when the SW is off with power input. It could damage the UUT and
Electronic Load under this circumstance.
3.18 Save/Recall Setting
The Electronic Load setting for all channels can be saved and recalled for various test setup
use. In the Save file 00~99, each file has the settings of Configure, CC, CR, CV, CP, CZ,
CCD, CCFS, TIMING, S INE WAVE DYNAMIC and OCP TEST without AUTO SEQUENCE.
Moreover, there is an addition file for power on setting file which the contents are the same
as File 0 ~ 99. Once there is a Load on or it is exited from Configure screen during normal
operation, the present settings will be saved in this file. When the SAVE key is pressed, it will
not only save the settings to the file user specified but also save them to the Power On file.
To recall the saved settings (file 00~99), press ▲or ▼ key to adjust the file number (file
Figure 3-27 When Von Point is not set to 0V without Protection
Page 76
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
3-24
00~99) set by the 7-segament digit display on the Mainframe panel and then press RECALL
to recall the saved settings.
3.19 External Waveform Control
The external dynamic test, operated in the CC mode, is similar to that under the Dynamic
test, but the load level switching is controlled by the duty cycle of an External signal. It wo r ks
the same way as the dynamic test except that the Period control signals are not generated
internally, but are inputted from V EXT. Connectors are on the rear panel. A 0-to-10V
external signal corresponds to the 0-to-full scale input range, so that users should apply DC
offset for the external signal in the range from 0 to 10V. For the configuration of external
waveform control usage, refer to section 4.7.1 for details.
3.20 Voltage & Current Monitor
Each channel of the Load has two isolated connectors to monitor load voltage and current,
the output signal to I MON and V MON. Connectors are on the rear panel. A 0-to-10V output
signal corresponds to the 0-to-full scale load V&I range.
Page 77
Local Operation
4-1
When you edit the setting, the display will blink to let you know which
setting is to be edited or has been selected.
When setting the load module level, the resolution of current, voltage,
setting will be degraded when higher values are entered.
4. Local Operation
4.1 Introduction
This chapter describes how to operate the electronic load from the local panel in details. The
descriptions include: Mainframe panel control, Module panel control and indicators.
In order to use the front panel keys to control the electronic load, local operation must be in
effect. Immediately after the power is applied, local operation will be in effect. When local
operation is in effect, you can operate each module independently, and use the display with
keypad on the Load front panel to control the Load. The input voltage/current is displayed on
the module’s display.
Each module operates independently in CC, CR, CV, CP or CZ mode as a load and
simultaneously measures current, voltage, and power level. Each module also operates
independently in the dynamic load or dynamic load frequency sweep, or the Advance
functions including Timing Measurement, SINE WAVE DYNA, OCP Test, and Program
Sequences. The user is allowed to off-line edit above mentioned parameters. Beside, in any
of the operation modes, when active, the on-line change of parameters changes the
Electronic Loading accordingly, thus making it easy to achieve an optimized test condition
and then saved for later use.
The module allows the user to enter specification of a UUT including V, I, Watt for later
GO/NG check. In addition, the real time measurement bar on the VFD display indicates the
degree of deviation from spec. and guides the users in adjusting to fulfill spec.
This chapter covers the interpretation of the front and rear panel description, the initial setup,
the operation of the different load modes including CC, CR, CV, CP and CZ, the operation of
the two dynamic load modes including dynamic load and dynamic load frequency sweep,
and the operation of the Advance functions including Timing Measurement, SINE WAVE
DYNA, OCP Test, and Program Sequences.
In remote state, the keys on the front panel have no effect. Only remote controller can
program the Load. The display of module will show the present input voltage and current
readings or the last display while local state is in effect. The display of the Module will show
REMOTE message.
resistance and slew rate will be different from the entered values. The
displayed or stored value for setting is the actual value of D/A
programmed in the load module. The current, voltage and slew rate
setting will be degraded when low values are entered. The resistance
Page 78
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-2
Item
Name
Description
1
Spec key
SPEC key enables the SPEC function for all channel’s GO/NG
CC/CR/CV/CP.
2
Lock key
This system provides data lock feature in order that the stored
enabled, any data enter is prohibited and this LED indicator lights
To change lock or unlock state, the user must press and hold this
key for at least 2 seconds.
3
Save key
To save the entire present mode settings of all channels in the
ac power is cycled. The memory channel indicated on the LED.
4
Recall key
To recall the saved settings from EEPROM, and all channel’s
The memory channel indicated on the LED
5
Local key
Local key can recover local control of each module when the
Load module is running under remote control mode.
4.2 Front Panel Keys & Indicators
4.2.1 Front Panel Keys & Indicators of the Mainframe
Figure 4-1 Front Panel of the 63600-5 Mainframe
Figure 4-2 Front Panel Keys and Indicators of the 63600-5 Mainframe
Front Panel Keys and Indicators (mainframe)
Table 4-1 Description of Front Panel for the Mainframe
inspection.
PS: The electronic load allows the user to program specification
at configuration for Voltage in CC/CR/CP/CZ/DYNA/SW P mode,
and Current in CC/CR/CV/CP mode, and Power in
data will only be erasable by authorized user. When data lock is
up when any data key is pressed.
specified files (00 to 99). Saving DEFAULT is to save the status
of all channels for the next time the electronic load is turned on.
All saved settings are stored in EEPROM, and will not lose when
settings from specified files (00 to 99).
Page 79
Local Operation
4-3
6
Memory channel
A total of 100 sets of memory are built in the Load module for
loading setup.
7
Up and Down
keys
Up and Down keys enables the user change memory channel
number for save and recall.
8
A/B/C/D/E
These 5 mnemonic keys allow users to define and save 5 sets of
automatically.)
9
Power Switch
Main power switch.
indicator
Mnemonic keys
storage of programmed setup. The user can save into (or recall
from) any memory channel from 00 to 99, a pre-programmed
loading profile for all channels so that users can switch the load.
(Press and hold the key for 3 seconds can save the profile
4.2.2 Front Panel Keys and Indicators of the Load Module
There are two types of panels in Load module, single channel module panel and dual
channel module panel. They are almost the same, but only different from one key and the
amount of the connectors.
The single c hannel module means there is one channel in one module. The dual channel
module means there are two channels in one module. Each channel is isolated from the
other. The module display/keypad can control both channels. The left channel is called
channel L while the right one is channel R.
A. Single Channel Module B. Dual Channel Module
Figure 4-3 Front Panel of the Module
Page 80
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-4
Zone
Symbol
Description
1
Indicates acting mode is at one of the followings: constant
(CV), or constant power (CP).
2
Indicates acting mode of impedance load simulation.
3
Indicates the Electronic Load is in Frequency sweep in
operation.
4
Indicates the Electronic Load is in Dynamic load operation.
5
Indicates the Electronic Load is in short circuit simulation for
UUT to test short protection.
6
This indicates the SPEC inspection for GO (PASS).
7
This indicates the SPEC inspection for NG (FAIL).
8
Indicates the load module is in load ON status.
9
Indicates the remote operation via USB/Ethernet/System or
GPIB bus is enabled.
10
Indicates the load module is in parallel control mode of
MASTER unit or in Sync Dynamic mode of MASTER unit.
11
Indicates the load module is in parallel control mode of
SLAVE unit or in Sync Dynamic mode of SLAVE unit. (Slave
display.)
VFD Display Symbols
Figure 4-4 VFD Display
Figure 4-5 Symbols of VFD Display
Table 4-2 Definition for VFD Display Symbols on the Module
current (CC), constant resistance (CR), constant voltage
module in parallel control mode will show “SLAVE” on the
Page 81
Local Operation
4-5
Keys
Description
The system provides CC, CR, CV, CP and CZ modes for loading
accordingly for users to edit and test.)
The system provides programmable dynamic loading for power
channel module
The system of the single channel module provides two load
A/B
MODE
DYNA
A/B
L/R
Front Panel Keys (Load module)
There are twelve keys for each of the module panel. Only one key is different from the
keypads, which is key in the single channel module panel and key in the
dual channel module panel. Figure 4-6 shows the front panel Keys of th e Module.
A. Single Channel Module
exists in single
B. Dual Channel Module
Figure 4-6 Front Panel Keys of the Module
Table 4-3 Definition for Front Panel Keys on the Module
simulation. This key is used to change the operation mode for
power supply testing. (Press MODE r epeat edly will switch the
mode in the sequence of CC CR CV CP CZ
supply test simulation. This key enables the system to enter into
dynamic test. This dynamic mode provides two setting method
of DYNAMIC + COUNT and FREQUENCY SW EEP. ( Press
DYNA repeatedly will switch the function in the sequence of
Dynamic F_SweepStatic accordingly for users to edit and
test.) The LED lit when users enable this function.
only
settings of A and B for STATIC test. This key enables user to
select static A or B directly.
Page 82
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-6
channel module
This key is used to select the left channel or right channel
This key is used to select the system operation mode for EDIT
or changed the next parameter when press EDIT key again.
This system provides HIGH, MIDDLE or LOW loading range for
alternately changed.
The system provides other functions of TIMING, SINE WAVE
Default of any mode.
This key is used to trigger the short circuit function. (Active at
load ON status)
This key is used to start or stop sinking current from the power
supply.
This key is used for confirming data entry.
To select the other measurement and editing parameters.
+
To enter into the setup of system configuration.
These 2 keys are used to change the cursor position of data
when operating using rotary knob. Or, under configuration setup,
use them to select the desired parameter.
Rotary Knob
Under configuration setup, this knob is used for changing
cursor position which is moved by the above 2 arrows.
EDIT
RAN GE
SHORT
LOAD
ENTER
DATA
ENTER
L/R
ADVA
AVDA
only
exists in dual
directly for the dual channel module.
data input. The low range offers a better accuracy than that of
high range. Whenever this key is pressed, the range will be
DYNA, OCP TEST, AUTO_SEQUENCES for battery discharg e,
fuel cell and power supply testing. (Press ADVA repeatedly will
switch the function in the sequence of TIMING SINE WAVE
DYNA OCP TEST AUTO SEQUENCES accordingly for
users to edit and test. This key can define the default mode for
power on. Press and hold this key for 3 seconds to save is the
or
options of a parameter. On data entry, it changes values of the
Front Panel Connectors
There are two Vsense connectors and two Load connectors in the single channel
module panel, but there are four Vsense connectors and four Load connectors in the
dual channel module panel. Figure 4-7 shows the front panel Connectors of the Module.
A. Single Channel Module
Page 83
Local Operation
4-7
Connector
Description
V Sense TERMINAL
A connector for remote sensing directly at the UUT
connecting cable. If it is not connected, the sensing
connectors.
LOAD TERMINAL
Input connectors of the Electronic Load for
(+) and the black one is for the negative (-) pole.
A/B
A/B
L/R
L/R
L/R
L/R
L/R
B. Dual Channel Module
Figure 4-7 Front Panel Connectors of the Module
Table 4-4 Definition for Front Panel Connectors on the Module
terminal eliminates any voltage drop on the
terminal switches automatically to the LOAD
connecting to the UUT. The red one is for positive
4.3 Selecting the Channel f or a Dual Channel
Module
The key is used to select one of the channels for a dual channel module, like the
model Chroma 63610-80-20. To edit the channel settings, you must select a channel first.
Press the key to select left channel or right channel for the dual channel module,
then the LED “L” or LED “R” above the key lights up. If the load model is a single
channel module, the key does not exist, it is instead of key. The model
Chroma 63630-80-60 is a single channel module, so it has the key, without
key.
4.4 Setting Operation Mode of Static Load
There are five operation modes for static load: constant current (CC), constant resistance
(CR), constant voltage (CV), constant power (CP), and constant impedance (CZ).
Page 84
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-8
MODE
MODE
MODE
A/B
RAN GE
RAN GE
RAN GE
RAN GE
RAN GE
CC
CC
4.4.1 Se ttin g the Ope ra tion Mod e
Press the key until the desired mode is displayed on the VFD. So, when operate in
CC mode, press the key until the VFD displays CC mode.
0 . 0 0 0 0 V
0 . 0 0 0 0 A
0 . 0 0 0 0 mW
The sequence of mode selection after pressing key is as follows:
CC CR CV CP CZ goes back to CC
The load levels and slew rate are common to CC, CR and CP modes. CV mode sets voltage
level and current limit. There are two level settings in CC, CR, CV and CP modes for single
channel module, like the model Chroma 63630-80-60. They can be switched by the
key.
4.4.2 Setting CC Values
When operate in CC mode, the VFD displays CC mode.
0 . 0 0 0 0 V
0 . 0 0 0 0 A
0 . 0 0 0 0 mW
There are three current ranges for CC operation: high current range, middle current range,
and low current range. The current levels are programmed in milliamps at low range and in
Amps at middle range and high range. The slew rate levels are programmed in milliamps/μs
at low range and in Amps/μs at middle range and high range. The timings are programmed in
millisecond. The setting buffers of six CC modes and ranges are independent. Changing the
operation range doesn’t affect the settings of other ranges. The following examples show
how to set the CC values of Load module for model 63630-80-60.
1. Select Range
Select proper range, by pressing key, u ntil t he LED of the desired range above
the key is lig ht s up. High range is used when higher current level is required,
and LOW range is used when better resolution is required.
Select LOW range, by pressing key, until the LED “L” above the key
lights up.
The sequence of range selection after pressing key is as follows:
Page 85
Local Operation
4-9
A/B
A/B
A/B
A/B
EDIT
ENTER
DATA
ENTER
ENTER
A/B
A/B
ENTER
DATA
High range Middle range Low range goes back to High range
2. Select state A/B for single channel module
For single channel module, press the key to select state A or state B, then the
LED “A” or LED “B” above the key lights up. Select state A, by pressing the
key to select state A, then the LED “A” above the key lights up.
3. Set Current Level
There are 15,000 discrete steps from 0 to full scale in each range. Press the
key to enter into the editing mode. Turn the Rotary knob to change the display value to
500mA, then press key to confirm.
500.00 mA
The user may use or key to change the cursor position to different digit of
data, then turn the rotary knob to change the value of that digit.
If the user does not use or key to display the cursor, then resolution of the
value changes according to the rotary knob turning speed.
4. Set Slew Rate
There are 500 discrete steps in each range. Press the key to set slew rate of
rise. Turn the Rotary knob to change the display value to 30mA/μs, and the VFD
displays:
: 30.00 mA/μs
Then press
key to confirm the setting, and the slew rate settings change to fall
at the same time. Turn the Rotary knob to change the display value to 30mA/μs, and the
VFD displays:
: 30.00 mA/μs
Then press
key to confirm t he setting, and the setti ng page change to Cu rrent
Level at the same time.
5. Set the second Current Level for single channel module
Press the key to select State B then the LED “B” above the key lights
up.
Turn the Rotary knob to change the display value to 100.00mA, then press key
to confirm.
100.00 mA
6. Review and update the values of the setting parameters
Review the values of the setting parameters by pressing key. Update them by
Page 86
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-10
ENTER
DATA
EDIT
RAN GE
RAN GE
RAN GE
RAN GE
RAN GE
EDIT
DATA
ENTER
CR
I_RANGE:LOW
CR
set new value in their setting pages.
After completion of the data edit, key must be pressed. Otherwise, pressing the
key, new data will not be written into the internal memory, the previous value for
the parameter is kept.
7. Quit from editing mode
Press to quit from editing mode. Then, the VFD display will go back to the
voltage, current, and watt measurement display mode.
4.4.3 Setting CR Values
When operate in CR mode, the VFD displays CR mode.
0 . 0 0 0 0 V
0 . 0 0 0 0 A
3 0 0 0 . 0
There are three resistance ranges for CR operation: high resistance range, middle resistance
range, and low resistance range. The current setting of all resistance ranges can select high,
middle or low 3 types of ranges. ALL resistance levels are programmed in ohms (Ω). The
following examples show how to set the CR values of Load module for model 63630-80-60.
1. Select the resistance range
Ω
Select proper range, by pressing key, until the LED of the desired range above
the key is lights up. High range is used when higher resistance level is required,
and LOW range is used when better resolution is required.
Select LOW range, by pressing key, until the LED “L” above the key
lights up.
The sequence of range selection after pressing key is as follows:
High range Middle range Low range goes back to High range.
2. Select the current range
Press to enter into the editing mode and press again to set the current
parameter as the figure shown below:
L
I
0.0000mA
12000Ω
Turn the rotary to select the current range and press to confirm the selection;
Page 87
Local Operation
4-11
EDIT
A/B
A/B
A/B
A/B
EDIT
ENTER
A/B
A/B
ENTER
DATA
ENTER
DATA
EDIT
otherwise, the new data won’t be written into the internal memory. At last, press
to exit the editing mode and complete the current range setting.
3. Select state A/B for single channel module
For single channel module, press the key to select state A or state B, then the
LED “A” or LED “B” above the key lights up. Select state A, by pressing the
key to select state A, then the LED “A” above the key lights up.
4. Set Resistance Level
There are 15,000 discrete steps from 0 to full scale in each range. Press the
key to enter into the editing mode. Turn the Rotary knob to change the display value to
2Ω, then press key to confirm.
2.000 Ω
The user may use or key to change the cursor position to different digit of
data, then turn the rotary knob to change the value of that digit.
If the user does not use or key to display the cursor, then resolution of the
value changes according to the rotary knob turning speed
5. Set the second Resistance Level for single channel module
Press the key to select State B then the LED “B” above the key lights
up.
Turn the Rotary knob to change the display value to 1Ω, then press key to
confirm.
1.000 Ω
6. Review and update the values of the setting parameters
Review the values of the setting parameters by pressing key. Update them by
set new value in their setting pages.
After completion of the data edit, key must be pressed. Otherwise, pressing the
key, new data will not be written into the internal memory, the previous value for
the parameter is kept.
7. Quit from editing mode
Press to quit from editing mode. Then, the VFD display will go back to the
voltage, current, and resistance display mode.
Page 88
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-12
RAN GE
RAN GE
RAN GE
RAN GE
RAN GE
A/B
A/B
A/B
A/B
EDIT
ENTER
A/B
CV
4.4.4 Setting CV Values
When operate in CV mode, the VFD displays CV mode.
0 . 0 0 0 0 mV
0 . 0 0 0 0 mA
There are three voltage ranges for CV operation: high voltage range, middle voltage range,
and low voltage range. The current is always in high range. ALL voltage levels are
programmed in V. The following examples show how to set the CV values of Load module
for model 63630-80-60.
1. Select Range
Select proper range, by pressing key, until the LED of the desired range above
the key is lights up. High range is used when higher voltage level is required,
and LOW range is used when better resolution is required.
0 . 0 0 0 0mW
Select LOW range, by pressing key, until the LED “L” above the key
lights up.
The sequence of range selection after pressing key is as follows:
High range Middle range Low range goes back to High range
2. Select state A/B for single channel module
For single channel module, press the key to select state A or state B, then the
LED “A” or LED “B” above the key lights up. Select state A, by pressing the
key to select state A, then the LED “A” above the key lights up.
3. Set Voltage Level
There are 15,000 discrete steps from 0 to full scale in each range. Press the
key to enter into the editing mode. Turn the Rotary knob to change the display value to
5 V, then press key to confirm.
5.0000 V
The user may use or key to change the cursor position to different digit of
data, then turn the rotary knob to change the value of that digit.
If the user does not use or key to display the cursor, then resolution of the
value changes according to the rotary knob turning speed.
4. Set the second Voltage Level for single channel module
Press the key to select State B then the LED “B” above the key lights up.
Page 89
Local Operation
4-13
ENTER
EDIT
ENTER
ENTER
DATA
ENTER
DATA
EDIT
Turn the Rotary knob to change the display value to 6V, then press key to
confirm.
6.0000 V
5. Set Current Limit
This function will limit the current sinking of Load to protect the UUT in CV mode. There
are two CV modes: VOLT_PSU and CURR_PSU. The defa ult sett i ng of curr ent limit is
the maximum Load current.
There are 15,000 discrete steps from 0 to full scale in each range. Press key to
enter into the editing mode. Turn the Rotary knob to change the display value to 60A,
then press key to confirm.
I-LIM : 60.000 A
Users may use or key to change the cursor position to different digit of data,
and then turn the rotary knob to change the value of that digit.
6. Set Response Speed
There are three response speeds for CV mode (CURR_PSU), fast, normal and slow for
different UUTs testing. Their response time is Fast:3ms, Normal:10ms, Slow:50ms.
Turn the Rotary knob to change the speed until the desired response speed is displayed
on the VFD. Then, press key to select mode and confirm the testing.
RESPONSE : FAST
Fast, Normal and Slow settings are invalid in CV mode (VOLT_PSU).
7. Review and update the values of the setting parameters
Review the values of the setting parameters by pressing key. Update them by
set new value in their setting pages.
After completion of the data edit, key must be pressed. Otherwise, pressing the
key, new data will not be written into the internal memory, the previous value for
the parameter is kept.
8. Quit from editing mode
Press to quit from editing mode. Then, the VFD display will go back to the
voltage, current, and watt display mode.
Page 90
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-14
RAN GE
RAN GE
RAN GE
RAN GE
RAN GE
A/B
A/B
A/B
A/B
EDIT
ENTER
CP
4.4.5 Setting CP Values
When operate in CP mode, the VFD displays CP mode.
0 . 0 0 0 0 mV
0 . 0 0 0 0 mA
There are three power ranges for CP operation: high power range, middle power range, and
low power range. ALL power levels are programmed in watts. The slew rate levels are
programmed in mA/μs at low range and in A/μs at middle range and high range.
The following examples show how to set the CP values of Load module for model 63630-80-
60.
1. Select Range
Select proper range, by pressing key, until the LED of the desired range above
0 . 0 0 0 0 mW
the key is lights up. High range is used when higher power level is required, and
LOW range is used when better resolution is required.
Select LOW range, by pressing key, until the LED “L” above the key
lights up.
The sequence of range selection after pressing key is as follows:
High range Middle range Low range goes back to Hig h range
2. Select state A/B for single channel module
For single channel module, press the key to select state A or state B, then the
LED “A” or LED “B” above the key lights up. Select state A, by pressing the
key to select state A, then the LED “A” above the key lights up.
3. Set Power Level
There are 15,000 discrete steps from 0 to full scale in each range. Press the
key to enter into the editing mode. Turn the Rotary knob to change the display value to
2 watts, then press key to confirm.
2.0000 W
The user may use or key to change the cursor position to different digit of
data, then turn the rotary knob to change the value of that digit.
If the user does not use or key to display the cursor, then resolution of the
value changes according to the rotary knob turning speed
Page 91
Local Operation
4-15
DATA
ENTER
ENTER
A/B
A/B
ENTER
DATA
ENTER
DATA
EDIT
4. Set Slew Rate
There are 500 discrete steps in each range. Press the key to set slew rate of
rise. Turn the Rotary knob to change the display value to 0.03A/μs, and the VFD
displays:
: 00.030 A/μs
Then press
key to confirm the setting, and the slew rate settings change to fall
at the same time. Turn the Rotary knob to change the display value to 0.03A/μs, and the
VFD displays:
: 00.030A/μs
Then press
key to confirm t he setting, and t he setting page ch ange to Power
Level at the same time.
5. Set the second Power Level for single channel module
Press the key to select State B then the LED “B” above the key lights
up.
Turn the Rotary knob to change the display value to 6 watts, then press key to
confirm.
6.0000 W
6. Review and update the values of the setting parameters
Review the values of the setting parameters by pressing key. Update them by
set new value in their setting pages.
After completion of the data edit, key must be pressed. Otherwise, pressing the
key, new data will not be written into the internal memory, the previous value for
the parameter is kept.
7. Quit from editing mode
Press to quit from editing mode. Then, the VFD display will go back to the
voltage, current, and watt measurement display mode.
Page 92
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-16
EDIT
ENTER
EDIT
ENTER
EDIT
ENTER
CZ
4.4.6 Setting CZ Values
When operate in CZ mode, the VFD displays CZ mode.
There is only one impedance range for CZ operation. The current is always in high range.
ALL resistance levels are programmed in Ω. The C
following examples show how to set the CZ values of Load module for model 63630-80-60.
1. Set the Level of the equivalent parallel load capacitance C
The setting range is from 30μF to 50,000μF. There are 15,000 discrete steps in the
is in μF, and the Ls is in μH. The
L
L
range. Press the key to enter into the editing mode. Turn the Rotary knob to
change the display value to 2,000μF, then press key to confirm .
C
: 2000 μF
L
The user may use or key to change the cursor position to different digit of
data, then turn the rotary knob to change the value of that digit.
If the user does not use or key to display the cursor, then resolution of the
value changes according to the rotary knob turning speed
2. Set the Level of the equivalent parallel load resistance R
L
The setting range is the same as the CR mode high range of the Load model. There are
15,000 discrete steps in the range. Press the key to enter into the editing mode.
Turn the Rotary knob to change the display value to 3Ω, then press key to
confirm.
R
: 3.0 Ω
L
3. Set the Level of the equivalent series inductance Ls
The setting range is from 0.1μH to 20μH. There are 15,000 discrete steps in the range.
Press the key to enter into the editing mode. Turn the Rotary knob to change
the display value to 0.1μH, then press key to confirm.
Ls : 0.1 μH
Page 93
Local Operation
4-17
EDIT
ENTER
DATA
ENTER
DATA
EDIT
MODE
MODE
CC
4. Set the Level of the equivalent series resistance Rs
The setting range is from 30mΩ to 20Ω. There are 15,000 discrete steps in the range.
Press the key to enter into the editing mode. Turn the Rotary knob to change
the display value to 0.15Ω, then press key to confirm.
Rs : 00.15 Ω
5. Review and update the values of the setting parameters
Review the values of the setting parameters by pressing key. Update them by
set new value in their setting pages.
After completion of the data edit, key must be pressed. Otherwise, pressing the
key, new data will not be written into the internal memory, the previous value for
the parameter is kept.
6. Quit from editing mode
Press to quit from editing mode. Then, the VFD display will go back to the
voltage, current, and peak plus/minus voltage display mode.
4.5 Setting Operation Mode of Dynamic Load
4.5.1 Se ttin g the Ope ra tion Mod e to C C Mode
Dynamic load is only operation in CC mode. Press the key repeatedly until the VFD
displays CC mode.
0 . 0000 mV
0 . 0000 mA
0 . 0000 mW
The sequence of mode selection after pressing key is as follows:
CC CR CV CP CZ goes back to CC
Page 94
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-18
DYNA
DYNA
DYNA
RAN GE
RAN GE
RAN GE
RAN GE
RAN GE
CC
CC
4.5.2 Select the Operation Mode of Dynamic Load
There are two Operation Modes for dynamic load: Dynamic load mode and Dynamic load
frequency sweep mode. Press to select dynamic load, then the LED above the key
lights up, and the VFD displays:
0 . 0 0 0 0 V+
0 . 0 0 0 0 V 0 . 0 0 0 0 A
The sequence of mode selection after pressing key is as follows:
Dynamic load mode Dynamic load frequency sweep modeStatic load mode goes back to
Dynamic mode.
4.5.3 Setting Dynamic Load Values
When operate in CC Dynamic load mode, the VFD displays CC Dynamic Load mode.
0 . 0 0 0 0 V+
0 . 0 0 0 0 V 0 . 0 0 0 0 A
There are three current ranges for CC Dynamic load operation: high current range, middle
current range, and low current range. The current levels are programmed in milliamps at low
range and in Amps at middle range and high range. The slew rate levels are programmed in
mA/μs at low range and in A/μs at middle range and high range. The timings are
programmed in millisecond. The se tting buffers of six CC Dynamic load modes and ranges
are independent. Changing the operation range doesn’t affect the settings of other ranges.
The following examples show how to set the CC Dynamic load val ues of Load module for
model 63630-80-60.
1. Select Range
Select proper range, by pressing key, until the LED of the desired range above
the key is lights up. High range is used when higher current level is required,
and LOW range is used when better resolution is required.
Select High range, by pressing key, until the LED “H” above the key
lights up.
The sequence of range selection after pressing key is as follows:
High range Middle range Low range goes back to High range
Page 95
Local Operation
4-19
Period
Resolution
Low
0.020ms ~10ms
1μs
High
1ms ~ 100s
1ms
EDIT
ENTER
ENTER
ENTER
ENTER
2. Set Current Level
There are 15000 discrete steps from 0 to full scale in each range. Press the key
to enter into the editing mode, and the VFD displays:
Turn the Rotary knob to change the display value to 30A for Load1, then press
key to confirm. At the same time it changes to load level setting for Load2.
The VFD displays now:
Turn the Rotary knob to change the display value to 10A for Load2, then press
key to confirm. At the same time it changes to setting period T1 for Load1.
The user may use or key to change the cursor position to different digit of
data, then turn the rotary knob to change the value of that digit.
If the user does not use or key to display the cursor, then resolution of the
value changes according to the rotary knob turning speed.
Notations for Load1 and Load2 are and respectively, values for Load1 and for
Load2 have nothing to do with comparison between them as their implied meaning high
and low.
3. Set period T1 & T2
The VFD displays:
Turn the Rotary knob to change the display value to 10.000 ms, then press key
to confirm. At the same time period setting changes to T2.
The VFD displays now:
Turn the Rotary knob to change the display value to 01.000 ms, then press key
to confirm. At the same time it changes to setting slew rate for rise.
If one of the periods T1 and T2 is larger than 50 ms, full scale switches from low to high,
and resolution switches to 1ms automatically. Period range and resolution see following:
Page 96
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-20
RT
ENTER
ENTER
ENTER
DATA
ENTER
DATA
EDIT
CC
SW
4. Set Slew Rate
The VFD displays:
Turn the Rotary knob to change the display value to 1.000A/μs, then press key
to confirm. The slew rate settings change to fall at the same time.
The VFD displays:
Turn the Rotary knob to change the display value to 1.000A/μs, then press key
to confirm. At the same time it changes to setting Repeat times.
Full scale range of slew rate switches automatically among low, middle and high.
5. Set Repeat times
The VFD displays:
Turn the Rotary knob to change the display value to 0 times, then press key to
confirm. Then the display will go to the first editing page again.
6. Review and update the values of the setting parameters
Review the values of the setting parameters by pressing key. Update them by
set new value in their setting pages.
After completion of the data edit, key must be pressed. Otherwise, pressing the
key, new data will not be written into the internal memory, the previous value for
the parameter is kept.
7. Quit from editing mode
Press to quit from editing mode. Then, the VFD display will go back to the
voltage, current, and peak plus/minus voltage measurement display mode.
4.5.4 Setting Dynamic Load Frequency Sweep Values
When operate in CC Dynamic load frequency sweep mode, the VFD displays CC Dynamic
load frequency sweep mode.
0 . 0 0 0 0 mV
0 . 0 0 0 0 mA
0 . 0 0 0 0 mW
Page 97
Local Operation
4-21
DATA
RAN GE
RAN GE
RAN GE
RAN GE
RAN GE
ENTER
ENTER
ENTER
CC
SW
Press key to switch the measurement page as shown below. The F_R means the
executing frequency at present, the Vp+ and Vp- are the voltage positive/negative peaks
measured and the F/P is the frequency under voltage positive/negative peak.
There are three current ranges for CC Dynamic load frequency sweep operation: high
current range, middle current range, and low current range. The current levels are
programmed in milliamps at low range and in Amps at middle range and high range. The
slew rate levels are programmed in mA/μs at low range and in A/μs at middle range and high
range. The frequencies are programmed i n Hz. The Dwell time is in Second. Duty is in %.
The following examples show how to set the CC Dynamic load frequency sweep values of
Load module for model 63630-80-60.
1. Select Range
Select proper range, by pressing key, until the LED of the desired range above
the key is lights up. High range is used when higher current level is required,
and LOW range is used when better resolution is required.
Select Middle range, by pressing key, until the LED “M” above the key
lights up.
The sequence of range selection after pressing key is as follows:
High range Middle range Low range goes back to High range
2. Set Current Level
There are 15,000 discrete steps from 0 to full scale in each range. Turn the Rotary knob
to change the display value to 6A for Load1, then press key to conf irm the
setting. At the same time it changes to load level setting for Load2.
Turn the Rotary knob to change the display value to 1A for Load2.
The VFD displays:
I_MAX : 6.0000 A
I_MIN : 1.0000 A
Then, press key to confirm. At the same time it changes to setting Start
Frequency.
3. Set Frequencies
The setting range of the Frequencies is from 0.01Hz to 50kHz.
Turn the Rotary knob to change the display value to 100Hz for Start frequency, then
press key to confirm the setting. At the same time it changes to setting End
Frequency.
Page 98
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-22
ENTER
ENTER
ENTER
ENTER
ENTER
ENTER
Turn the Rotary knob to change the display value to 1kHz for End Frequency, then
press key t o confirm . At the same time it changes to setting Step Frequency.
Turn the Rotary knob to change the display value to 100Hz for Step frequency.
The VFD displays:
Then press key to confirm the setting. At the same time it changes to setting
Dwell time.
4. Set Dwell tim e
Dwell time is the elapse time of each setting step frequencies from start frequency to
End frequency. The setting range of the Dwell time is from 1ms to 100s. Turn the Rotary
knob to change the display value to 0.1s.
The VFD displays:
DWELL : 0.100 s
Then press key to confirm the setting. At the same time it changes to setting
Duty.
5. Set Duty
The duty can be set from 1%-99%, but the Duty setting will be limited within the
transition time of the two load levels. Dwell time is the elapse time of each setting step
frequencies from start frequency to End frequency. Turn the Rotary knob to change the
display value to 50%.
The VFD displays:
DUTY : 50 %
Then press key to confirm the setting. At the same time it changes to setting
Slew Rate.
6. Set Slew Rate
Turn the Rotary knob to change the display value to 0.600A/μs, then press key
to confirm. The slew rate settings change to fall at the same time.
Turn the Rotary knob to change the display value to 0.600A/μs.
SR/ : 0.600 A / μs
SR\ : 0.600 A / μs
Then press key to confirm. At the same time it changes and goes back to load
level setting for Load1.
Page 99
Local Operation
4-23
DATA
ENTER
DATA
EDIT
ENTER
EDIT
DATA
ENTER
ADVA
Full scale range of slew rate switches automatically among low, middle and high.
7. Review and update the values of the setting parameters
Review the values of the setting parameters by pressing key. Update them by
set new value in their setting pages.
After completion of the data edit, key must be pressed. Otherwise, pressing the
key, new data will not be written into the internal memory, the previous value for
the parameter is kept.
8. Quit from editing mode
Press to quit from editing mode. Then, the VFD display will go back to the
voltage, current, and peak plus/minus voltage measurement display mode.
4.6 Setting the Advance Function
The Electronic Load provides useful advance functions such as Timing Measurement, Sine
Wave Dynamic, etc. To use these powerful functions, you must set relevant parameters in
accordance with application needs. To set the Advance function you need to press to
enter into the page of Advance function, the VFD displays Advance function.
[ A D V A N C E ]
1. TIMING
2. SINE WAVE DYNA
3. OCP TEST
4. AUTO SEQUENCES
4.6.1 Se tup of Timing Measurement Function
In the page of Advance function, turn the Rotary knob to change the display value to 1, then
press key into the page of Timing Measurement Function, the VFD displays Timing
Measurement Function.
[ T I M I N G ]
0 . 0 0 0 0 mV
0 . 0 0 0 0 mA
Press the key to enter into the editing mode. Then, press to select the
setting param eter.
1. Select the operation mode. There are three operation modes for Timing Measurement
Function. They are CC, CR and CP modes. Turn the Rotary knob to change the mode
until the desired mode is displayed on the VFD. Then, press key to select mode
and confirm the setting.
Page 100
Programmable DC Electronic Load 63600 Series Operation & Programming Manual
4-24
ENTER
ENTER
ENTER
ENTER
ENTER
MODE: CC
2. Set Load Level. There are 15,000 discrete steps from 0 to full scale in each range and
each mode. Turn the Rotary knob to change the display value to 10.000A, then press
key to confirm.
I_SET: 10.000 A
3. Set Slew Rate. Setting the rising and falling slew rate. Turn the Rotary knob to change
the display value, then press key to confirm.
: 0.0012A/μs
: 0.0012A/μs
4. Set Trigger Mode. There are three Trigger Modes and they are RISE , FALL and
HOLD_UP. Turn the Rotary knob to change the mode until the desired mode is
displayed on the VFD. Then, press key to select mode and confirm the setting.
TRG_M: FALL
5. Set Trigger Volt age. Trigger Voltage is the conduction voltage level.
TRG_S: It sets the start trigger voltage level for measurement time.
TRG_E: It sets the end trigger voltage level for measurement time.
The Electronic Load will measure the duration from the load on to the UUT output
voltage equal to the setting trigger voltage, and the Load stops sinking current when the
UUT output down to reach the voltage. Turn the Rotary knob to change the display
value, then press key to confirm.
TRG_S :3.000 V
TRG_E :5.000 V
6. Set the period of time out. The Electronic Load will measure the duration from the load
on to the UUT output voltage equal to the setting trigger voltage. When the time is
already over the period of time out, but the UUT output voltage still isn’t achieve to the
trigger voltage, the Load will load off and stop counting the timing. Turn the Rotary knob
to change the display value, then press key to confirm.
T_OUT: 600 s
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.