Chore-Time Equipment (“Chore-Time”) warrants each new Chore-Time product manufactured by it to be free
from defects in material or workmanship for one year from and after the date of initial installation by or for the
original purchaser. If such a defect is found by the Manufacturer to exist within the one-year period, the
Manufacturer will, at its option, (a) repair or replace such product free of charge, F.O.B. the factory of
manufacture, or (b) refund to the original purchaser the original purchase price, in lieu of such repair or
replacement. Labor costs associated with the replacement or repair of the product are not covered by the
Manufacturer.
Conditions and Limitations
1. The product must be installed by and operated in accordance with the instructions published by the
Manufac
turer or Warranty will be void.
2. W arranty is void if all components of the system are
3. This product must be purchased from and installed by a
not original equipment supplied by the Manufacturer.
n authorized distributor or certified representative
thereof or the Warranty will be void.
4. Malfunctions or failure resulting from misuse, abuse,
negligence, alteration, accident, or lack of proper
maintenance, or from lightning strikes, electrical power surges or interruption of electricity, shall not be
considered defects under the Warranty.
5. This Warranty applies only to systems fo
r the care of poultry and livestock. Other applications in industry
or commerce are not covered by this Warranty.
The M
anufacturer shall not be liable for any Consequential or Special Damage which any purchaser may suffer
or claim to suffer as a result of any defect in the product. “Consequential” or “Special Damages”as used herein
include, but are not limited to, lost or damaged products or goods, costs of transportation, lost sales, lost orders,
lost income, increased overhead, labor and incidental costs and operational inefficiencies.
THIS WARRANTY CONSTITUTES THE MANUFACTURER’S ENTIRE AND SOLE WARRANTY AND
MANUFACTURER EXPRESSLY DISCLAIMS ANY AND ALL OTHER WARRANTIES,
THIS
INCLUDING, BUT NOT LIMITED TO, EXPRESS AND IMPLIED WARRANTIES AS TO
MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSES SOLD AND DESCRIPTION OR
QUALITY OF THE PRODUCT FURNISHED HEREUNDER.
Chore-Time Distributors are not authorized t
o modify or extend the terms and conditions of this Warranty in any
manner or to offer or grant any other warranties for Chore-Time products in addition to those terms expressly
stated above. An officer of CTB, Inc. must authorize any exceptions to this Warranty in writing. The Manufacturer
reserves the right to change models and specifications at any time without notice or obligation to improve previous
models.
The Chore-Tronics® 3 Controls are used to control the Climate in a structure to insure efficient growth of
Livestock. Using this equipment for any other purpose or in a way not within the operating recommendations
specified in this manual will void the warranty and may cause personal injury.
This manual is designed to provide comprehensive planning, inst
information. The Table of Contents provides a convenient overview of the information in this manual. The Table
of Contents also specifies which pages contain information for the sales personnel, installer, and consumer (end
user).
allation, safety, operation, and parts listing
Safety Information
Caution, Warning and Danger Decals have been placed on the equipment to warn
of potentially dangerous situations. Care should be taken to keep this information
intact and easy to read at all times. Replace missing or damaged safety decals
immediately.
Using the equipment for purposes other than specified in this manual ma
personal injury and/or damage to the equipment.
Follow Safety Instructions
Carefully read all safety messages in this manual and on your equipment safety signs.
Follow recommended precautions and safe operating practices.
Keep safety signs in good condition. Replace missing
Decal Descriptions
or damaged safety signs.
y cause
DANGER : Electrical Hazard
Disconnect electrical power before inspecting or servicing equipment unless
maintenance instructions specifically state otherwise.
Ground all electrical equipment for safety.
All electrical wiring must be done by a qualified el
and national electric codes.
Ground all non-current carrying metal parts to guard a
With the exception of motor overload protection, electrical disconnects and over
current protection are not supplied with the equipment.
5
ectrician in accordance with local
gainst electrical shock.
MT2398C
Introduction to the ControlChore-Tronics® 3 Control
Introduction to the Control
Display Screen
The display screen is a 10.1 in. Full Color Touch screen. This screen will display the requested
information when an Icon on the Touch Screen is pressed. The Display Screen always remains lit. When
the Control is left dormant, the Current Conditions Screen will be visible.
Display Screen
Figure 1. Display Screen
Navigation
Navigating the Control can be done in one of two ways.
Navigating option 1.(Touch)- Touch the Icon or simulated button displayed on the screen with your
finger or stylus.
Figure 2. Navigation-Touch
6
MT2398C
Introduction to the ControlChore-Tronics® 3 Control
Navigating option 2.(Mouse)- A USB mouse can be used by plugging it into the USB port located on
the left side of the main Control Box.
To navigate using a mouse, position the cursor on the Icon or
and press the left mouse button to select.
USB Port
USB Mouse
the simulated button displayed on the screen,
Figure 3. Navigation-Mouse
7
MT2398C
Introduction to the ControlChore-Tronics® 3 Control
1. Displays the Path and the house name or number.
2. (T ask Bar) Navigation buttons from left to right are; Back button, Main menu, Forward button, Current
Condition, Alarm, Password and the Help.
3. All menus, viewable data and editable fields.
4. Time, Date and Age.
2
4
3
Figure 4. Screen Layout
Screen Layout
In the top left corner of every screen the path and the screen name is displayed to the screen you are
viewing. In this example the Current Conditions screen is displayed.
1
Navigating the Control’s Screens
In the Current Conditions screen you can view current data and some settings. Each button has an Icon
that represents the data to be displayed.
Selecting the button with the water droplet
Figure 5. Screen Navigation
8
will display the current water usages from 12:00 am.
MT2398C
Introduction to the ControlChore-Tronics® 3 Control
Notice the path displayed (Current Condition/Today's Water)
Current Path
Figure 6. Current Path
To return to the Current Conditions screen, select the back
or select the CC
return you back to the Current Conditions
button. Note: Regardless of the screen you are in selecting the CC button will
screen.
OR
button at the top left corner of the screen,
Figure 7. Returning to Current Conditions Screen
9
MT2398C
Introduction to the ControlChore-Tronics® 3 Control
2
1
3
4
5
1. Scrolls the value up or down.
2. Removes the last number on the right.
3. Changes the entre from a positive to a negative number.
4. Removes the pop up with no changes to the value.
5. After you have made changes select "OK" to confirm the change. The pop up will disappear and the
change will be displayed in the field.
Figure 8. Numeric Keypad
Numeric Keypad
In a screen that has editable fields, select the value you want to edit (In this example: Set Temperature).
A Numeric Key Pad will be displayed. The name of the field will be displayed at the top of the Key pad.
Name of Field being edited.
Editable field
In some editable fields you can enter text, if these fields are selected a Key Board will be displayed. If a
number is needed with the text, select the button labeled 123 on the Key Board and a Numeric Key Pad
will be displayed. To go back to the Key Board select the AZ button on the Numeric Key Pad. The OK
button will save your entry.
Press "OK" to save entry
Toggle back and forth from Keyboard to Number Pad
using the
and the button.
10
Figure 9. Toggling between Keyboard or Numeric Key Pad
MT2398C
Introduction to the ControlChore-Tronics® 3 Control
1. A Graph icon will be displayed in the upper right
of a screen if there is a graphical representation.
1
Graphs
Relay Box Indication Lights and Auto/Manual Switches
Each Relay Output has its own three position switch that allows the user to select manual, off or automatic
control of each Relay. The Relays and their corresponding Switches are located in a separate box. Decals
are supplied to label each Switch for the Output function that is assigned to that Switch. The Switches can
be placed in three positions - "on", "off", or "auto". The "auto" position is for normal automatic operation.
Changing a Switch to "on" or "off" overrides "auto" operations. When a switch that is assigned is placed
in a position other than "auto", a message will appear in the Current Conditions screen advising you to
"Check Switches". The light above each Switch indicates that the Switch's Relay is activated.
1
2
3
ItemDescription
1Indication Light
2Switch
3Decal
Figure 10. Indication Lights and Switches
11
MT2398C
Glossary of TermsChore-Tronics® 3 Control
Glossary of Terms
Analog Input
Analog Inputs can consist of the following:
Temperature sensors
Static Pressure sensor (4-20 mA)
Relative Humidity Sensor (0-10 volts)
Potentiometer (Natural Ventilation)
Anticipation
When the control is turning on the fans assigned to the Minimum Ventilation Timer, the control will open
the inlets to the correct position for static pressure control before the fans are turned on. If calculated
anticipation is used (default), the control teaches itself how much adjustment was required during the
previous on-off cycle, and uses that amount of "anticipation" for the next cycle. If the optional fixed
anticipation is used, the control will NOT teach itself what the correct anticipation should be. It uses the
amount of "anticipation" that is entered in the Static Pressure screen (Screen 11). Anticipation will occur
when the fans assigned to the Minimum Ventilation Timer turn on due to the timer reaches an ON cycle
or the sensor(s) assigned to the fans reach the fans' ON temperature.
Back Up Relay Output
The backup up relay output is a relay that will be energized as soon as the backup output is assigned to a
relay. This relay will stay energized as long as the control is communicating with the manual switch board
where the output is assigned. The 24 Vdc signal that comes from the control to the back up box should be
routed through this relay. If communication is lost between the main box and the manual switch board,
the relay will drop out allowing the first fan stage in the back up box to turn on. See the Wiring Diagrams
section of this manual for more wiring information.
Bend Point (BP)
The Bend Points (BPs) are simply the points on the curve that define the curve. For the Set Temperature
and Minimum Ventilation Timer curves, the curve values are gradually changed between bend points. The
bend point values are the exact values at midnight beginning the day # of each bend point. The curve takes
over when you turn the curve "on" and the day number is equal to or greater than the day number assigned
to BP #1.
Cool Pad Output
The COOL PAD Output is a special function for controlling evaporative cooling that allows you to
modulate the addition of water to the cooling pad in such a way that the usual large temperature swings
associated with a cooling pad are avoided.
Curve
A "curve" is a listing of up to 10 points in time (bend points) that defines how you
want a parameter to automatically vary as the animals age.
Curve Value
The Control will list what the current value(s) the curve would be, if the current day
number is greater than the day # of bend point #1, and the curve is "on", and there is
no "offset" to the curve.
Day Number
The intention is that the day # is the age of the animals whose environment is being
controlled. Day # 0 does not exist. Negative days (down to - 7) are allowed.
Changing the day # in any screen that sho
in all the other screens that show the day #.
12
ws the day number, will change the day #
MT2398C
Glossary of TermsChore-Tronics® 3 Control
Mt1701-Naturalmode 11/01
Digital Input
Digital Inputs can consist of the following:
Water meter
Feed scale
Air speed sensor
Low water pressure switch
Max feed run time Input
PDS flush feed back
Event
This term applies to the time clock Outputs. An "event" is an "on at" time combined
with an "off at" time.
Mode Sensor(s)
The concept of Mode Sensor(s) is essential to the understanding what makes the
Control change from one mode to another. The Mode Sensor(s), of a currently
operating mode, determines when the Control will leave that mode. As an example,
while in the Power Mode, the Power Mode Sensor(s) determines when it's too
stay in the Power Mode (i.e. above the tunnel "on" temperature)
converts to the Tunnel Mode (assuming there
temperature. It comes back to the Power Mode from the
Tunnel Mode Sensor(s) say it's
too cold to stay in the Tunnel Mode (i.e. below the
is no Natural Mode) at the tunnel "on"
Tunnel Mode, when the
. Because of this, it
tunnel "off" temperature).
hot to
Natural Mode
Natural Mode requires the house to be equipped with Curtains in the side walls that
are powered by Drive Units (Curtain Machines). The Control converts to this mode
of operation when the temperature(s) inside the house raise to a level that the Fans of
the Power Mode can't keep the temperature(s) under control. While in the Natural
Mode of operation, the Curtains are opened or closed, as required, to control the
temperature(s). This mode of operation generally happens during moderate weather.
Noticing an Alarm
"Noticing" an alarm is a very important part of using the alarm system. See how to Notice an Alarm
(Active or Recovered) in the "Alarm" section of this manual.
13
MT2398C
Glossary of TermsChore-Tronics® 3 Control
Mt1701-Powermode 11/01
Offset
The term "offset" applies to the Set Temperature and Minimum Ventilation Timer
curves only. If you manually adjust either the Set Temperature or the Minimum
Ventilation Timer settings, while the curve is on, you create an "offset" to that curve
relative to it's "curve value". The "curve value" is not changed. (see the "curve
value" definition above.) The curve value is shown as a convenience so that you
know what you have to change it back to in order to get back on the actual curve's
table listing. While an "offset" is in effect, the parameter of the curve is still modified
versus time. However, the actual parameter value is the "curve value" modified by
the "offset".
Power Mode
The building is closed up except for Inlets (usually Baffle Doors) which are powered
open and close in order to control the static pressure level. In some cases Gravity
Inlets are used where the static pressure is not controlled directly. The only
ventilation provided is due to Fans mounted in the end
operation generally happens when the outside temperatures are somewhat lower than
the set temperature.
or side walls. This mode of
14
Program
A "program" is a complete set up of all the screens of a Control. In the main menu Program Tab, six
different "programs" can be saved and later activated. This can be very convenient when it is desired to
change the set up at different points during the grow out, barn cycle, or times of the year.
Set Temperature
The set temperature is another very important, basic, concept. All temperatures are referenced to the set
temperature. When the set temperature is adjusted either manually, or because the set temperature curve
is on, all other temperature settings move up or down by the same amount. For instance, even though you
program an actual temperature for each Fan to come on and off, when you change the set temperature,
those Fan's on and off temperatures are adjusted by the same amount
you changed the set temperature.
Spare Temp Sensor
The spare temperature sensor is a temperature sensor that is separate from one of the 12 controlling
sensors. This sensor can be used to control the temperature in a separate area of the house. The sensor has
its own maximum and minimum alarm parameters that can be set up in the Alarms screen. The sensor can
also turn on and off the Spare Temperature Sensor Output. This output functions like a fan output. The
output has lower Off temperature than its On temperature. The On and Off temperatures for the Spare
Temperature Sensor output are defined in the Outputs and Temperatures screen. The spare temperature
sensor can not be used to control any other output.
MT2398C
Glossary of TermsChore-Tronics® 3 Control
Static Pressure
Static pressure refers to the pressure difference that exists between the inside of the house and the outside
of the house. This pressure difference is the result of Fans in the walls running. The air that they exhaust
enters the house through various types of air inlet openings. In the Power Mode the typical powered baffle
inlets is where the vast majority of the air enters. In the Tunnel Mode, the tunnel inlet at the end of the
house is where the air enters. The pressure drop, due to the resistance to the air flowing through the inlets,
is the reason a static pressure difference exists. If the inlets are all the same size, the same amount of air
will enter through each inlet. In the Natural Mode of operation, the outside wind is the source of the air,
with no exhaust fans running. In general there is little or no static pressure during the Natural Mode due
to the huge area of the open side wall curtains. When the incoming air is cooler than the inside air, it will
tend to drop down onto the birds before it is warmed up. Adequate static pressure brings the air into the
house high and fast so that it heats up before it can fall.
Tunnel Mode
This mode of operation requires a group of large fans at one end of the house with a large air Inlet area at
the opposite end of the house. The control converts to this mode of operation from the Power or Natural
Mode (if used), when the temperature(s) while in those modes get too high. The typical 5 or 6 mph. breeze,
which can be created by the Tunnel Fans running, produces a wind chill effect that is significant. This
mode of operation happens during warm to hot weather.
Mt1701-Tunnelmode 11/01
Wind Delay
The static pressure has to be out of the control limits continuously for the "wind
delay" amount of time before the inlets are adjusted. If a fan or fans has turned
on or off within the last 10 seconds, the wind delay does not happen and the inlets
respond as soon as the static pressure leaves the control limits.
15
MT2398C
Overview of ScreensChore-Tronics® 3 Control
Alarms Button
Message
Alarm Status
Notice Button
From any screen you can select the Alarm button. This will take you to the Alarm Overview
screen.
Alarm Overview Screen- In the Alarm Overview screen an Alarm is listed in three columns.
Message (Type of alarm), Status (Alarm, Recovered and Off For) and a Notice button.
History
Tab
Active Alarm- Select the Notice Button to notice
the Alarm
If the alarm condition is still active, Off For x:xx
will be displayed in the Status column. The specific
alarm will be inactive until it has recovered to within its normal range, at that point the alarm will be
sent to the Alarm History (See below left).
Overview of Screens
Alarms (Active or Recovered)
Active Alarms
To see any current "Active" alarms press the Alarms Button. If there are any Active alarms they will be
listed here (See Figure below).
Alarm Time
Recovered
Noticed
Message
16
Alarm Date
MT2398C
Overview of ScreensChore-Tronics® 3 Control
Alarms Button
Notice Button- Select the Notice button to notice the
alarm, the alarm will be sent to the Alarm History screen.
From any screen you can select the Alarm button. This will take you to the Alarm Overview
screen.
Alarm Overview Screen- If there is a Recovered alarm it will be listed here (See above).
Alarm History- To view the alarm history, select
the History tab at the bottom of the Alarm screen.
The alarm date, time, message, noticed and recovered is displayed for each alarm listed (See below).
Recovered Alarms
To see "Recovered" alarms press the Alarms Button. If there are any Recovered alarms they will be listed
here (See Figure below)
Recovered
Alarm Date
Alarm Time
Recovered
Noticed
Message
17
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Setup button.
3. From the Setup/General screen select
Settings .Setup/General/Settings screen.
2. Select the General button to access the
Setup/General screen.
4. Enter the Computer Number. This will be your house number.
5. Enter the House Name. The house name can be whatever you want, it will be displayed at the
top right of ever screen. A maximum of 14 digits.
6. Choose the Language by pressing the dropdown and select English or Spanish.
7. Choose the Clock Type by pressing on the dropdown and select 12 hour or 24 hour clock.
8. Set the Time of Day by pressing on the time box, a numeric keypad will open allowing you to
set the time of day. (See following page).
9. Set the Date by pressing the date box, a numeric keypad will open allowing you to set the date.
Follow the same procedure used to set the Time (See Following Page).
10. The IP, IP mask and Gateway are used only if C-Central, WebLink and or C-Collect are in use.
These settings are determined by the local network settings.
Note: Path to the Screen being viewed
4
5
6
7
8
9
10
Control Setup
General Setup
From any screen select the Main Menubutton at the top left of the screen.
18
MT2398C
Time of Day
1. Highlight the hours by selecting the hours.
Change the hours by using the up/down arrows or the keypad.
2. Highlight the minutes by selecting the minutes. Change the minutes by using the up/
down arrows or the keypad.
3. Highlight the am/pm by selecting the am/
pm. Use the up/down arrows to toggle.
4. Select OK to save.
Date
The date must be enter in a specific format (
Day.Month.Year )
The example shows, 05.10.2010 for 5 October
2010
Control SetupChore-Tronics® 3 Control
19
MT2398C
Units
In this screen you will choose the unit
of measurement you want to display.
2. Select the Units button
1. Select the General Button in the Setup
Screen.
3. Choose the unit of measurement you
want to display.
Control SetupChore-Tronics® 3 Control
20
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Setup button.2. Select the Analog inputs
1. Select the Sensor Type button
In this screen you choose what type of Analog
Inputs (temperature sensors, relative humidity
sensor, and potentiometers) are connected to
the Control. The Static Pressure Sensor and
House Temperature Sensors 1-3 come from
the factory pre-assigned.
2.
Enter Sensor Types installed
Select the box to the left of the sensor types installed. When a Sensor type is grayed out, that
specific item cannot be selected.
The number of specific sensors (Nbr Sensors)
will be added as you continue with setup.
Grayed out (Cannot select)
Sensor Types
Installed
Number of Sensors
Analog Inputs
To access the Analog Inputs Setup screen start by accessing the Main Menuscreen.
Analog Inputs-Sensor Type
21
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the House Temp. Sensor button
From the Setup/Analog Inputs screen select
House Temp. Sensors button. The Setup/Analog Input/House Temperature screen should be
displayed at this time
2. Factory assigned
Sensor numbers
Temperature sensors 1-3 come from the factory pre-assigned. To assign the next sensor select the Add button and the next sensor will
appear (See below right).
3.
Adding Sensor assignments
Fill in the Board, Input, and backup by selecting from the dropdowns. Continue until all the
temperature sensors have been assigned. If it is
desired to skip a sensor and move to the next
sensor in the list, select the - (not assigned) on
the sensor that needs to be skipped and select
the ADD button, next sensor will appear in the
list.
4
4. Board
The number of the Board the Sensor is connected. Board number 0 is the IOM16 Board.
If the sensor is connected to an additional analog input board, then the Board number
matches the address of the add on Board (see
the installation section of this manual).
5.
Input
This is the input number that the Sensor is
connected to on the Board. On the IO Board
the input number will be 1 thru 16. If the Sensor is connected to an additional Analog Input
Board then the Input number will be 1-4.
5
6
6. Value
This is the current temperature reading.
7. Corr.
This is the amount of correction made when the sensor was calibrated. Calibration will be gone over
later in the manual.
8. Backup
This is the sensor you want to be the backup if the sensor fails.
2
45
78
Analog Inputs-House Temperature Sensors.
Select the Back button after all the House temperatures have been assigned.
22
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Outside Temp. Sensor button
In this screen the Outside sensor is assigned.
Calibration is also done from this screen. Skip
this Screen if no outside sensors are installed.
2. Adding Sensor Assignments
Fill in the Board and Input by selecting from
the dropdowns.
Analog Inputs-Outside Temperature Sensor
Select the Back button after the Outside temperature sensor has been assigned.
23
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Static Pressure Sensor button
2. Assign Static Pressure input as you did for the House Temperature
Sensors. Calibration is also done from this screen.
3. Select the Control Tab button
In this screen you set up the specifications for the Static Pressure Sensors
4. Current Safety Limit
Static Pressure Safety limit- Example: When the
static pressure stays above 0.20 for a continuous
minute, the Tunnel Curtain (if in Power Mode)
and the Inlets (if in Tunnel Mode) will open until
the static pressure reduces below 0.20. Once the
problem is fixed and the static pressure reduces
below 0.18, the Control returns to normal operation. The safety limit can be set from .18 to .27.
This situation will always result in a High Pressure Alarm.
4
Analog Inputs-Static Pressure Sensors
24
MT2398C
5. Second Static Pressure
Selecting this feature a second level of Power
Mode static pressure can be chosen. The Temperature Sensor(s), (Inside Only), that measure
that temperature is defined in this screen. Select the sensor edit field and a sensor assignment window will be displayed.
6. Select/Deselect sensor check box
Select or deselect the sensor check box to
choose the sensor or sensors you want to use.
Select OK to save. The temperature at which
the second static pressure takes over is entered
in Output and Temperature screen.
Control SetupChore-Tronics® 3 Control
25
MT2398C
8. Tunnel Inlet Static Pressure assist in Power
If in the Power Mode, there is inadequate inlet area
to keep the static pressure within the high control
limits, the Tunnel Curtain will open to give additional air inlet area. The Inlets are given continuous open
signals as the Tunnel Curtain takes over the responsibility of controlling the static pressure. The static
pressure has to be above the high Static Pressure
Control limit continuously for one minute with 3 or
more Fans running for this to happen. Responsibility
for Static Pressure Control is passed back to the Inlets as soon as there are fewer than 3 Fans running or
the Tunnel Curtain cannot bring the static pressure
back into the control range (while closing) from the
low side. The static pressure has to be below the low Static Pressure Control limit continuously for
one minute for this to happen.
Select the Back button twice after the Static pressure has been assigned and Control screen is completed
Control SetupChore-Tronics® 3 Control
1. House Relative humidity Sensor
From the Setup/Analog Input screen select House
RH sensor Button.
2. Assign the House RH sensor input as you did
the House Sensors. Calibration is also done from
this screen. See next manual section "Calibrating
Analog Inputs".
Analog Inputs-Relative Humidity Sensor
26
MT2398C
3. Select the Control tab.
4. Select the RH Influence On Minimum Ventilation
box if you want the min/vent timer to be influenced
by the RH.
5. The Minimum Ventilation timer will be adjusted
based on house RH when the temperature is between
set temperature and the Min-Vent fan's ON temperature. The Control will adjust the amount of ON time
between the Min Ventilation value and the Max value. The OFF time will be adjusted by the same
amount of time that the ON is adjusted, thus keeping
the total cycle time constant. The temperature is
checked 30 seconds before the beginning of the ON time cycle of the Minimum Ventilation Timer. This is in addition to any time added by Ventilation
Timer Ramping.
6. Amount Of Influence (sec)- is the amount of decrease or increase time pre movement.
7. Maximum Influence(sec)- is the maximum amount of RH timer influence you need.
Once the fans' temperature sensor(s) reach the fans' ON temperature, the
fan will turn on and run continuously until the fans' OFF temperature is
reached.
Once the fans' temperature sensor(s) reach the fans' ON temperature, the fan will turn on and run continuously until the fans' OFF temperature is reached.
6
7
Control SetupChore-Tronics® 3 Control
27
MT2398C
Control SetupChore-Tronics® 3 Control
1. From the Setup/Analog Input screen select
Type & Number.
2. Put a Check in the Bird Scale Box.
3. Select the Back Button and then select
the Bird Scale Button.
4. Select the Board number from the drop down.
5. Select the Input from the drop down. Select 1.
Analog Inputs-Bird Scale
28
MT2398C
Control SetupChore-Tronics® 3 Control
1. To re-calibrate the Temperature Sensors, first obtain a digital thermometer that has a readout of at
least + - 1°. Do not use a temperature gun. A temperature gun measures an object’s temperature, not
air temperatures.
2. Place the digital thermometer next to
the Temperature Sensor that is being
re-calibrated. Take the reading from
the digital thermometer and enter that
number under the Value column of the
Sensor being calibrated.
3. The Correction column is used only
for service information and to return
the Control to the factory settings. The
settings should be reset to factory
whenever a re-calibrated Temperature
Sensor is replaced. To return to factory
settings change the number under the correction column by one digit. This will cause the correction to
automatically zero out and return to factory setting.
All Temperature Sensors are calibrated the same way. (Outside, Spare and Aux temperature sensors)
1. To re calibrate the Relative Humidity Sensor first obtain a sling psychrometer or another humidity
measuring device.
2. Operate the psychrometer in the
same area that the Relative Humidity
Sensor is installed. Take the reading
on the psychrometer and compare it to
the reading on the Setup/Analog Inputs/ House RH Screen. If the readings do not match, then change the
reading under the Value column to
match the reading of the psychrometer.
3. The correction column is to be used for service information and for returning to factory settings
only.
2
3
Analog Input Calibration
The re-calibration section of this screen should not need to be used at initial installation and start-up of
the Control unless natural ventilation is used. If natural ventilation is being used, then the Potentiometers
will need to be calibrated at this time. If it is felt that one of the Inputs needs to be re-calibrated perform
the following steps…
Temperature Sensor Calibration
Relative Humidity Sensor Calibration
2
3
29
MT2398C
Control SetupChore-Tronics® 3 Control
1. To re-calibrate the Static Pressure Sensor first obtain a manometer or other static pressure measuring
device. Then disconnect both hoses
from the Static Pressure Sensor.
2. Go to Setup/Analog Inputs/Static
Pressure screen and look at the Pressure reading in the Zero Level value
box. If the reading is not zero then
change the zero level value pressure to
read zero. The zero level has now been
calibrated.
3. To calibrate the high level, first
make sure that the Manometer has
been installed in the house and reconnect the hoses to the Static Pressure
Sensor. Open the Inlets slightly and turn on enough Fans to create a static pressure of at least 0.15 inches of w.c. at the Manometer. Compare the Manometer reading to the reading on the High Level line on
the Control. If the readings do not match, edit the pressure reading on the High Level value box to
match the reading of the Manometer. As with the Temperature Sensors, the Correction column of the
static pressure calibration is used for service, and to return the Control to factory settings only. This
completes the re-calibration of the static pressure Sensor.
2
3
1. Go to the Setup/Analog Inputs/Bird Scale
Screen and Select Calibrate. (Platform
should be hanging from the Load Cell)
2. With no weight on the Platform select the OK
Button. If there is no error then continue.
3. Place a 5.00 lb. weight on the Platform. In the
"Calibration Weight Box" enter 5.00. Click the
Ok Button. If no error then the calibration is
done.
Static Pressure Sensor Calibration
Bird Scale Calibration
30
MT2398C
Control SetupChore-Tronics® 3 Control
2. Select the Type & Number button.
3. Select the Digital inputs you have connected to the Chore-Tronic's 3.
Digital Inputs
1. Select the Main menu button.Select the Setup buttonfrom the Main Menu screen. Finally, select the Digital inputs Button.
Digital Inputs
The Digital Input Screens are very similar to the Analog Input screens and setup the same way. In these
screens the Control is told what digital inputs (Water Meters, Feed Scales, Airspeed Sensor, Low Water
Pressure Switch, Flush Feed Back, Auger Run Time Alarm, etc.) are connected to the Control and where.
All digital or pulsed inputs that are connected to the Control must be assigned a board number and an
Input number. It is highly recommended that the Input Decal located inside the main box of the Control
be completed before entering information in this screen.
Board- This is the number of the board where the water meter or other digital input device is connected.
Board number 0 is the I/O Board. If the sensor is connected to an additional digital input board, then the
board number matches the address of the add on board (see the installation section of this manual).
Input- This is Input number that the water meter or other digital input device is connected to on the board.
For the I/O Board the input number will be 1 thru 8. If the sensor is connected to an additional
analog input board then the input number will be 1-4.
Name- A name can be entered for the Water meter, feed scale, and auxiliary digital inputs using the al-
phanumeric keypad. The name entered here will appear in the Auxiliary Data and History screens.
Select Add and the next Sensor will appear in the list.
Select Remove and the last Sensor in the list will be deleted.
Type and Number
31
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the Setup but-
tonfrom the Main Menu screen. Finally, select the Digital inputs Button.
2. Select the Water Meters button.
3. Enter all Drinker/Water Meters that are connect-
ed to the CT3 here. A Drinker Water Meter is a Water Meter that is monitoring the water being used by
drinker water lines or the entire house (1 meter for
both drinker lines and Cool Pads). If a Water Meter
is assigned an input here, its daily usage will be added to the total amount of consumed water in the
management screen. When a Water Meter or other
digital input is assigned to a board and an input on
that board, to add the next Water Meter or digital input select the ADD button and Meter #2 will appear.
If it is desired to skip a Meter or other digital input
and move to the next digital input in the list, enter
(not assigned) for the input that needs to be skipped.
it is desired to skip a Meter or other digital input and
move to the next digital input in the list, enter (not
assigned) for the input that needs to be skipped.
4. Select the Control tab
Water Flow Rate Alarm- Put a check in the box if
you want an alarm when flow rate is too high. The parameters are setup in the Alarm screen under the Production tab.
Water Meter
32
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Dump Scale Button.
All feed scales that are connected to the Control
needs the input it is connected to assigned here.
All feed scales that are assigned inputs here will
have their daily usage added to the total amount
of feed consumed in the management screen.
2. Assign an input to each of the feed scales connected to the Control here. Each Input assigned
here will have its daily usage added to the total
amount of feed consumed in the management
screen.
1. Press Auxiliary Input button
Many different types of auxiliary digital Inputs
can be used with the Ct3.
2. Types of auxiliary Inputs include non-drinker
water meters (water meters attached to evaporative cool pads, etc.), pulsed output electric meters, pulsed output gas meters, etc. Each inputs
usage will be monitored separately and will not
be added to any total usage.
1. Press the Air Speed button.2. Enter the board and input numbers for the Air
speed meter. The parameters are setup in the
Alarm screen under the Environment tab.
Dump Scale
Auxiliary Inputs
Airspeed Sensor
33
MT2398C
Control SetupChore-Tronics® 3 Control
1. Press the Feed Lines button.2. Enter the board and input of each Feed Line
connected to the Control. Feed Line run times
will be generated from these inputs.
1. Press the Water Pressure button.2. Enter the board and input for the Water pressure switch. Switch must open with low pressure.
The parameters are setup in the Alarm screen under the Production tab.
1. Press the Auger Run Time button.
2. Enter the board and input of the Auger run time
relay. The parameters are setup in the Alarm
screen under the Production tab.
Feed Lines
Water Pressure
Auger Run Time
34
MT2398C
Control SetupChore-Tronics® 3 Control
1. Press the Flush Feedback button.2. Enter the board and input of the PDS flush feed-
back. The parameters are setup in the Alarm screen
under the Production tab.
Flush Feedback
35
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the
Setup buttonfrom the Main
Menu screen. Finally, select the House Button.
2. In this Screen you set what type of ventilation
is being used in the House.
3. Temp. Influence on Minimum Ventilation.
Select this box if you want the Min. Vent Timer
to ramp up & down based on temperature. See
explanation and example below.
Ventilation timer ramping- If the sensor(s) that are assigned to the Minimum Ventilation fan(s) tem-
perature is at or below set temperature then the fans will use the ON and OFF times that are listed for
the Minimum Ventilation Timer. If the sensor (s) assigned to the Ventilation Time Ramping temperature is between set temperature and the fans' ON temperature the control will adjust the amount of ON
time between the Min Ventilation value and the Max value. The OFF time will be adjusted by the same
amount of time that the ON is adjusted, thus keeping the total cycle time constant. The temperature is
checked 30 seconds before the beginning of the ON time cycle of the Minimum Ventilation Timer.
Once the fans' temperature sensor(s) reach the fans' ON temperature, the fan will turn on and run continuously until the fans' OFF temperature is reached.
Example:
The set temperature is 70.0°F and the fans assigned to the Min Vent timer ON temperature is 72.0°F.
The Minimum Ventilation Timer values are 30 seconds ON time and 270 seconds OFF time. The maximum ON time is 210 seconds. If the sensor(s) assigned to the Ventilation Time Ramping temperature
is 71.0°F at the beginning of the anticipation cycle, then the fans will have an ON time of 125 seconds
and an OFF time of 175 seconds.
4. Mortality
Select this box if you want to keep track of the
Mortality. To separate male and female select
Separate Male Female.
Setup House
36
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the Setup but-
tonfrom the Main Menu screen.
2. Press the Outputs button
Some of the buttons on this screen may be
grayed out at this point of the setup.
1. Press the Outputs button
Some of the buttons on this screen may be
grayed out at this point of the setup.
2. Press the Equipped/Numbers button
Some of the buttons on this screen may be
grayed out at this point of the setup.
3. In this screen the Control is told what equipment it is connected to: Fans, Curtains, Inlets,
clock type and backup relays. The Nbr. Of Outputs column is read only and will be filled in as
Setup continues.
4. Select the Back button to return to the
Setup/Output screen.
Continued to next page.....
Output Assignments
Outputs-Equipped/Numbers
37
MT2398C
Control SetupChore-Tronics® 3 Control
Notice that all the buttons are now active.
1. Select the Ventilation button.
2. Every Output needs to have a relay, mode of operation (Power, Natural, Tunnel, or combinations of the
three), and temperature sensor(s) assigned to it. Initially when pressing the Cool, Exhaust Fan, Stir Fan, Tunnel Fan and Heat Zone buttons only one output will
appear.
3. Select the Tunnel Fans button.
Continue to next page.....
Outputs-Ventilation
Ventilation-Tunnel Fans
38
MT2398C
Refer to the Relay Assignment Decal (Inside the
Relay Box) to assign relays to each of the fans.
2. Select the Relay dropdown
to assign the proper Relay to each Tunnel Fan.
3. Select the Mode dropdown
A list of available Modes will appear. Select the
mode (modes) that the Fan needs to operate in.
Relay assignment Decal
(inside Relay Box)
4. In the Sensors column select the senor/sensors
to be assigned to the Fan. Touch the sensor window and a select sensor box will appear with the available sensors. Select or deselect the sensors to come up
with the sensor or sensors to control the Fan. Select OK
to save.
This completes Tunnel Fan 1.
5. To assign additional Tunnel Fans, select the
Add button. The next fan will appear. Follow the same
steps as used for Tunnel Fan 1 to assign the relay, mode,
and sensor assignments.
Using the same steps continue to add Tunnel fans until
finished.
Control SetupChore-Tronics® 3 Control
39
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Ventilation button.
2. Select the Stir Fans button.
3. Assign Relays, Sensors and Mode values to the
Stir Fans just as you did for Tunnel Fans. (See
previous page)
2. Select the Exhaust Fans button.
3. Assign Relays, Sensors and Mode values to the
Exhaust Fans just as you did for Tunnel Fans.
(See Tunnel Fans previous)
1. Select the Ventilation button.
Ventilation-Stir Fans
Ventilation-Exhaust Fans
40
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Ventilation button.
2. Select the Variable Fans button.
3. Assign Sensors and Mode values
to the Variable Speed Fans.
4. Assign the analog output from the
dropdown.
5. Assign the Output Form- You will
need to know the input range of the
Frequency drive before choosing 0-10
or 10-0 vdc from the dropdown.
5. Assign the Output Form- You will
need to know the input range of the
Frequency drive before choosing 0-10
or 10-0 vdc from the dropdown.
5. Press the Control Tab
6. Enter the amount of startup time needed
to open the fan shutters.
Example: If 5 is entered, the Variable
speed fan will run at full speed for 5 sec. at
startup, then return to the current speed.
Ventilation-Variable Fans
Note: The Var. Speed output is a 0-10 or 10-0 vdc output on the IO board not the Relay box.
41
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Ventilation button.
2. Select the Cool button to assign the Cool outputs..
3. Assign Relays, Sensors and Mode
values to each Cool item.
Relays
Mode
Sensors
Ventilation-Cool
The Cool outputs can be used for cool pads, fogger pads and or inside foggers. The Cool output can be
setup to be on/off based the temperature setting in the Output & Temperature. A t
imer can be assigned to
the Cool output. If a timer is assigned, at the on temperature the output will start timing on/off based on
the timer setting and will not run constant.
Sixteen Cool outputs can be assigned up to four relays per Cool output.
42
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Ventilation button.
2. Select the Cool Pad button to assign the Cool Pad outputs.
3. Assign a Relay, Sensors and a
Mode value to the Cool Pads.
Ventilation-Cool Pad
The COOL PAD output is very different from a COOL output.
It is not intended that the COOL PAD
output and the COOL output would be used together, but it is possible. Both outputs are there to give the
user the choice on which type of output to use. The COOL PAD's relay operation is designed to begin the
cooling caused by the cooling pad by first adding 5 seconds of water to the pad every 5 minutes. If the
temperature is still with the "Cool Pad Range" after 4 doses of 5 seconds of water, the amount of water
added to the pad every 5 minutes remains the same. If the temperature is above or below the temperature
limits of the "Cool Pad Range", the amount of water "on" time each 5 minutes is increased or decreased
5 seconds. With the default settings the temperature is only checked every 20 minutes. If it is desired for
the temperature to be checked more often if a sudden large temperature change occurs, then values should
be entered in the "Extra aggressive if" lines (Items and , Figure ). For example, The Control is set to be
extra aggressive if 3.0 degrees above the upper limit of the COOL PAD range. Whenever the temperature
is more than 3.0 degrees above the upper limit of the COOL PAD range the Control will begin checking
the temperature every 5 minutes (every repetition rate) instead of every 20 minutes (every 4 repetition
rates) until the temperature returns to less than 3.0 degrees above the COOL PAD range. The default extra
aggressive settings are 3 degree.
43
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Control Tab.
2. Measure the number of seconds it takes for water to start
coming out of the holes in the pad system's top distribution
pipe after turning on the COOL PAD manual toggle switch.
This should be entered as the "Water pre-fill time" (Item 2, right) and is likely to be different for the different system
manufacturers. This amount of time is added to the water
run time each repetition because the top distribution pipe
drains out during the off time of the on-off cycle.
Important!! The parameters that determine exactly how the
COOL PAD function reacts are programmed in two separate
screens, (Setup/Outdputs/Ventilation/Coolpad and Ventilation Setting/CoolPad). Chore-Time strongly recommends that the factory default settings be used, unless poor control of temperature during pad operation is noticed. Chore-Time also recommends
that CTB service personnel is contacted before changing the settings.
2
3. Measure the number of seconds it takes for water to start
dripping out the bottom of a dry pad after the COOL PAD
manual toggle switch is turned to the on position. This amount of time should be entered as the "Time
to wet dry pad" (Item 3, above). This will be less than the time to make the pad completely soaked.
When the actual water on time reaches this "Time to wet dry pad" value, the next step is to run the
water continuously, assuming that the temperature is above the Cool Pad Range at the next temperature
3
4
4. If water running on the pad continuously is not
desired, then the "Max water allowed" value
(Item 4, right) should be changed so that it is less
than the repetition rate time. Once the temperature
decreases back below the Cool Pad Range, the actual water on time will return to the "Time to wet
dry pad" value again. From there the water on time
changes in the normal way, with 5 second changes
every 20 minutes, depending on the temperature
check points.
5
5. The "Actual water on time" is for information
only. Showing the value makes it possible to create a graph of it's variations if you have the PC
connection (C-Central). The "Flush cool pad", (Item 5, previous page) is a feature that allows you
to run the water continuously at a time of day each day for the duration you specify. This will guarantee that at least once a day the pad will be flushed to keep it as clean as possible and help lengthen
the pad life. Leaving dashes for the settings disables this feature. Flushing the pad in the night will
have the advantage of causing very little unwanted temperature drop.
On a very hot day it would be possible for the water to be running continuously and the temperature to be
in the "Cool Pad Range". A more moderate day might result in the water running a very small amount of
time in order to keep the temperature within the "Cool Pad Range". Similarly, on a low humidity day the
amount of water required to keep the temperature within the "Cool Pad Range" would be less than for a
high humidity day. The Control will adjust the water as required to keep the temperature in the "Cool Pad
Range". If it is desired to not allow the water to run continuously, then the Max water allowed (Item 4,
Below) value should be changed so that it is less than the repetition rate value.
44
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Heat Zones button.
3. Assign Relays, Sensors, Mode values and
Names just as you did for Tunnel Fans. (See pre-
vious)
3. Select the Control Tab.
4. Select the box if you do not want the Heat
Zones to run in Tunnel assist.
1. Select the Ventilation button.
1. Use the Back button to get to the Setup/Outputs screen and push the Curtain Button.
Ventilation-Heat Zones
Curtain
45
MT2398C
Control SetupChore-Tronics® 3 Control
2. In this screen you will assign Relays to any
and all of the air inlets connected to the Control.
3. Select Sidewall Inlet
Once you enter in the Open relay number the Control
will automatically enter the Close relay.
Two inlet machines can be assigned to the Sidewall
inlet output. Both machines will be given an open or
close signal at the same time.
Note. The Open and Close outputs must always be side by side on the same relay row.
4. Select the Control tab and choose Calculated or Fixed
Anticipation.
Calculated Inlet Anticipation– The Control determines
the amount of time the Inlets will open prior to the Fans
assigned to the Minimum Ventilation timer turn on at a
given static pressure control limits. (Screen not shown)
Fixed Inlet Anticipation- The amount of time the Inlets
will open prior to the Fans assigned to the Minimum Ventilation timer turn on.
Open Relay Number
Close
Relay Number
Sidewall Inlet
46
MT2398C
Control SetupChore-Tronics® 3 Control
1. Use the Back button to get to the Setup/Outputs screen and push the Tunnel Inlet Button.
2. When you enter in the Open relay number
the Control will automatically enter the Close
relay.
Up to four machines can be assigned to the
Tunnel inlet output. All machines will be given an open or close signal at the same time.
Note. The Open and Close outputs must always be side by side on the same relay row.
Open Relay Number
3. Press the Control Tab
4. These numbers are needed for proper
Mode transitions. (Power to Tunnel and
Tunnel to Power).
Full Movement
Measure the full movement of the Curtain or
Tunnel door and enter that number in the FULL
Movement edit box.
Tunnel Speed
With a closed inlet measure 18 inches of the tunnel curtain or door movement. Toggle the open
relay switch to the Manual position.
Time how long it takes to move the the Inlet 18
inches. Enter that number in to the Tunnel
Speed edit box.
Tunnel Inlet
47
MT2398C
Control SetupChore-Tronics® 3 Control
2. Press the Clock button.
All of the Clock output Relays are assigned
here.
1. Select the Main menu button.Select the
Setup buttonfrom the Main
Menu screen. Finally, select the Outputs
button.
1. Press the Light button.
2. Up to four Light clocks can be assigned
with four relays for each Light clock. Use the
Add button to add additional clocks.
External Light Dimmer Control
3. In the "An Out" column, select from the drop-
down the Analog out (on the IO board) used to
control the Dimmer.
4. In the Output from column select ether 0-10
vdc or 10 to 0 vdc.
( 0 vdc = no light or 10 vdc = no light)
2
3
4
Clock Assignments
Light Clock
48
MT2398C
Control SetupChore-Tronics® 3 Control
1. Press the Feed button.
2. Enter the Relay or Relays that the feeders
have been wired to. Only one Feed clock can
be assigned with up to four relays. All four relays will be activated at the same time.
3. Select the Control Tab.
4. If the you wish to turn the Fill System OFF,
check the box.
If a Dry Contact Relay whose coil is energized
when the fill system's Hopper Level Switch
calls for the fill system to run is connected to
a digital input of the Control Then the Control
can be set to detect excessive fill system run
time and activate the Alarm Relay.
Feed Clock
49
MT2398C
Control SetupChore-Tronics® 3 Control
2. The Spare Clocks have 8 on and
off events and cannot be curved. A
maximum of 8 Spare Clocks can be
used, with up to four Relays per
Clock. To add additional Spare
Clocks to the list, select the Add
button. Each Spare Clock can be
given a specific name to identify the
Clock with a particular use.
Enter the Relay number (s) For each
Clock in the list and change the
name if needed.
1. Press the Spare button.
Four Relays per Clock
Clock Name
(editable)
Select "Add" to add Clocks
Spare Clock
50
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the
Setup buttonfrom the Main
Menu screen.
2. Press the Outputs button.
3. Press the Miscellaneous button.
4. select the Backupbutton.
5. Assign a Backup relay from the dropdown list of avalible Relays.
Backup Relays are needed when the
Chore-Tronic's Standard or Expanded
backup is installed for backing up the
Control. If the the brain of the Control
goes down for any reason, the Backup Relay will open, and the first stage of backup
will be activated. See backup wiring di-agram in the Backup installation manuals. Part # MT1805A of MT1561b
Miscellaneous Outputs
Backup Relay
51
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the Setup buttonfrom the Main Menu screen.
2. Select the Sensor button.
Verify Relay Assignments
After assigning all the outputs, verify the Relay assignments with the Output Stickers on the
Manual Toggle Switches.
Manual Toggle Switches
Feed Clock 1
Feed Clock 2
Feed Clock 3
Relay Assignments
(Inside Cover of Relay Box)
Assignments
Sensors
52
MT2398C
3. Power Mode- The temperature sensor (s) assigned here will determine what the control will use to
transition from Power to Tunnel mode.
4. Temp. Influence On Minimum Ventilation
The temperature sensor (s) assigned here will determine the amount of time added or subtracted
away from the Minimum Ventilation timer in Power mode.
For this feature you must first check the box in the (Setup/house screen) for Temp. Influence On
Minimum Ventilation.
Ventilation timer rampingIf the sensor(s) that are assigned to the Minimum Ventilation fan(s) temperature is at or below set temperature then the fans will use the ON and OFF times that are listed for the Minimum Ventilation Timer. If the sensor (s) assigned to the Ventilation Time Ramping temperature is between set temperature
and the fans' ON temperature the control will adjust the amount of ON time between the Min Ventilation value and the Max value. The OFF time will be adjusted by the same amount of time that the
ON is adjusted, thus keeping the total cycle time constant. The temperature is checked 30 seconds before the beginning of the ON time cycle of the Minimum Ventilation Timer. Once the fans' temperature sensor(s) reach the fans' ON temperature, the fan will turn on and run continuously until the fans'
OFF temperature is reached.
Example: The set temperature is 70.0°F and the fans assigned to the Min Vent timer ON temperature
is 72.0°F. The Minimum Ventilation Timer values are 30 seconds ON time and 270 seconds OFF
time. The maximum ON time is 210 seconds. If the sensor(s) assigned to the Ventilation Time Ramping temperature is 71.0°F at the beginning of the anticipation cycle, then the fans will have an ON
time of 125 seconds and an OFF time of 175 seconds
34
Control SetupChore-Tronics® 3 Control
53
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the Setup
buttonfrom the Main Menu screen.
2. Select the Function button.
4. Stir Timer Delay time (sec)
Enter the amount of time you want the Stir fans to delay after the Min.Vent.
fans have turned off.
In screen Setup/Output/Equipped, Stir fans must be checked, and at least one
Relay assigned in the Setup/Outputs/Ventilation/Stir Fans screen to use this
feature.
3. Alternate Min Vent Fans
(Select if you want feature)
The Min Cycle (Alternate Minimum Ventilation
fans) allows the fan(s) assigned to the Min Vent
Timer to alternate with the fans assigned to the
Min Cycle. In the above
example, Exhaust Fans 1 and 2 will run on the
Min Vent timer first. At the next ON time
of the Min Vent Timer the fans assigned Exhaust
Fans 3 and 4 (the fans assigned to the Min Cycle)
will run. The feature will stop when the fans assigned to the Min Vent Timer turn on due to temperature.
3
4
Function
54
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the Ventilation Settings button.
2. Select the Set Temp Timer button.
Note: Only the values with a white background
are editable. All other boxes are information only.
3. Set temperature
Set Temperature is a very important parameter. All other temperatures are dependant on the set temperature. When the
set temperature is changed, all other temperature settings are also changed by the
same amount to maintain the same temperature differences relative to the set
temperature.
4. Day
Day is the age of the animals or birds.
Changing the age with Set temp and or
Min Vent curve on will change their values to the current curve values.
3
4
5. Current Min.Vent. ON Time
Current Min. Vent. ON Time is the current amount of ON time the fans assigned to the Minimum
Ventilation Timer will run while cycling on the timer. This amount of time compines both Temperature and if being used RH influence. If (TMP) is displayed the Min. Vent. Fan (s) are on by
temperature.
6. The status of the Set Temperature and Min Vent curve and curve values are displayed at the
bottom of this screen.
The Temp Curve and Min Vent Curve "on" indications are not editable. They only indicate that
the curve(s) are "on" and the curve's value. If a curve is not "on", there is no indication in this area.
The values shown at the bottom of the screen are the current curve's values. If the actual values
are different, the difference represents the "offset". Editing the actual values to be the same as the
values displayed at the bottom of the screen will erase the offset(s). An "offset" is caused if you
change a value when its curve is on.
5
6
Ventilation Settings
Set Temp Timer
55
MT2398C
7. Current Stir ON Time
Current Stir ON Time is the current amount of Stir On Time. If (TMP) is displayed the Stir Fan
(s) are on by temperature.
The "stir on" Timer is different than
the other Timers. It can only be attached to Stir Fan Outputs in the "Outputs" screen. The "stir on" time value
is set in this screen. The purpose of
this feature is to allow you to cause a
Stir Fan Output to run for the "stir on"
amount of time immediately following
the end of the Minimum Ventilation
Timer's "on" time. Because of this, the
Stir Fan is synchronized with the minimum ventilation Timer. The "stir on"
setting can be any value up to the "off"
time of the minimum ventilation Timer. The Stir Fan Outputs will come on full when the temperature rises to the "on" temperature value set in the "Outputs and Temperature" screen.
8. Temp. Influence
is the amount of time added by Ventilation timer ramping- If the sensor(s) that are assigned to the
Minimum Ventilation fan(s) temperature is at or below set temperature then the fans will use the
ON and OFF times that are listed for the Minimum Ventilation Timer. If the sensor (s) assigned
to the Ventilation Time Ramping temperature is between set temperature and the fans' ON temperature the Control will adjust the amount of ON time between the Min Ventilation value and the
Max value. The OFF time will be adjusted by the same amount of time that the ON is adjusted,
thus keeping the total cycle time constant. The temperature is checked 30 seconds before the beginning of the ON time cycle of the Minimum Ventilation Timer. Once the fans' temperature sensor(s) reach the fans' ON temperature, the fan will turn on and run continuously until the fans' OFF
temperature is reached.
78
Example:
The set temperature is 70.0°F and the fans assigned to the Min Vent timer ON temperature is
72.0°F. The Minimum Ventilation Timer values are 30 seconds ON time and 270 seconds OFF
time. The maximum ON time is 210 seconds. If the sensor(s) assigned to the Ventilation Time
Ramping temperature is 71.0°F at the beginning of the anticipation cycle, then the fans will have
an ON time of 125 seconds and an OFF time of 175 seconds.
9. RH Influence
The actual amount of influence time the RH function is adding to the minimum ventilation timer.
The Control may not always add the full amount of time if the amount of influence would add up
to be more than the maximum allowed.
9
Control SetupChore-Tronics® 3 Control
56
MT2398C
Control SetupChore-Tronics® 3 Control
1. Min Ventilation Timer
Min Ventilation Timer can be attached to Exh Fan, Tun Fan, and Stir Fan Outputs in the "Outputs"
screen. The "on" and "off" times for this Timer are set up here in there. The Timer turns the Fan
on or off when the temperature is below the Fan's "on" temperature. A Timer can only be attached
to a Tun Fan Output if the "on" temperature setting of the Tunnel Fan is
set lower than the "on" temperature of
the Tunnel Mode. Allowable "on"
times for this Timer are 0 or greater
than 30 seconds (5 through 29 seconds is only allowed if fixed Anticipation is used). Allowable "off" times
for this Timer are 0 or greater than 60
seconds (1 through 59 seconds is not
allowed). The "on" and "off" times
cannot both be set at 0.
2. Max Ventilation On Time
Max Ventilation On Time-The maximum amount of ON time the fans assigned to the Minimum Ventilation timer can run before reaching the fans' ON temperature. The
maximum allowed value for the Max Ventilation On Time is the amount of ON time (seconds) + the
amount of OFF time(seconds) of the Min Vent timer - 60 (seconds).
3. Timers 1 and 2
Timers 1 and 2 can be attached to Cool, Tun Fan, Exh Fan, and Stir Fan Outputs in the "Outputs/
Temperature" screen. The "on" and "off" times for these Timers are set in this screen. These Timers
behave like the minimum ventilation Timer except when they are attached to a Cool Output. When
attached to a Cool Output, the timer has no effect until the Cool Output is "on" due to it's temperature
settings. At that point the Cool Output goes on and off with the Timer. The Cool Output never comes
on continuously when Timer 1 or Timer 2 is attached to it. There are no limitations to the "on" and
"off" settings for Timer 1 and Timer 2 except that the "on" time and "off" time cannot both be set at 0.
4. Stir Timer
is different than the other Timers. It can only be attached to Stir Fan Outputs in the "Outputs" screen.
The "stir on" time value is set in this screen. The purpose of this feature is to allow you to cause a
Stir Fan Output to run for the "stir on" amount of time immediately following the end of the Minimum Ventilation Timer's "on" time. Because of this, the Stir Fan is synchronized with the minimum
ventilation Timer. The "stir on" setting can be any value up to the "off" time of the minimum ventilation Timer. The Stir Fan Outputs will come on full when the temperature rises to the "on" temperature value set in the "Outputs" screen
5. Status
Status-The status column shows the current status of each of the timer. If the Status is ON then the
timer is active and the Output(s) currently assigned to that timer should be running. If the Status is
OFF, then the timer is active, but the Output(s) assigned to that timer should NOT be running. If the
Status is "-" or "tmp", then the timer is not currently active and the Output(s) assigned to that timer
may or may not be running (depends on the type of Output due to temperature). If there is a NA (not
active) in the Status column then the timer is not assigned to any Outputs and will not be active.
Timer Settings
5
2
1
3
4
57
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the Ventilation Settings button.
2. Select the Static Pressure button.
3. Current Static Pressure- The amount of static pressure currently measured by the Control.
4. Current Static Pressure Limits- The Current SP Lim-
its are the current high and low limit settings the Control
is using to control the inlets or tunnel curtain.
5. Static Pressure Control Limits- The Static Pressure Control limits are the values of static pressure
the Control attempts to maintain by using the powered Inlets, the Tunnel Curtain, or both. A second
level of Power Mode static pressure can be chosen in the (Setup/Analog Inputs/Static Pressure) screen
in the Control tab. The temperature at which
the second static pressure takes over is entered
in the (Output/Temperature) screen. The Temperature Sensor(s), (Inside Only), that measure
that temperature is defined in the (Setup/Analog Inputs/Static Pressure) screen.
6. Fixed Inlet An ticipation- Fixed Inlet Antic-
ipation is the amount of time the inlets will
open prior to the fans assigned to the Minimum
Ventilation timer turn on. Fixed inlet anticipation must be selected from the (Setup/Analog
Inputs/Static Pressure) screen in the Control
tab.
7. Wind Delay- The wind delay is the amount of time the static pressure has to be continuously outside of the
Control limits before the appropriate open or close Relay will be energized to bring the static pressure back
within the control limits. The wind delay is bypassed if a Fan or Fans turning on or off is what causes the static
pressure to move outside the Static Pressure Control limits
5
3
4
6
7
Static Pressure
The Static Pressure screen indicates the current static pressure plus provides the fields that can be edited
to set the Static Pressure Control limits and the wind delay. The open and close Inlet Relays respond as
required to keep the static pressure within the Control limits while in the Power Mode and the open and
close Tunnel Curtain Relays do the same to control the static pressure during the Tunnel Mode. If it is not
desired to control the static pressure during the Tunnel Mode, the high control limit in the Tunnel Mode
must be edited to be .00. Static Pressure Control w/ Tunnel Curtain during Power Mode-If in the Power
Mode, there is inadequate inlet area to keep the static pressure within the high control limits, the Tunnel
Curtain will open to give additional air inlet area. The Inlets are given continuous open signals as the
Tunnel Curtain takes over the responsibility of controlling the static pressure. The static pressure has to
be above the high Static Pressure Control limit continuously for one minute with 3 or more Fans running
for this to happen. Responsibility for Static Pressure Control is passed back to the Inlets as soon as there
are fewer than 3 Fans running or the Tunnel Curtain cannot bring the static pressure back into the control
range (while closing) from the low side. The static pressure has to be below the low Static Pressure
Control limit continuously for one minute for this to happen.
58
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the Venti-
lation Settings button.
2. Select the Cool Pad button.
3. Measure the number of seconds it takes for water to
start coming out of the holes in the pad system's top distribution pipe after turning on the COOL PAD manual
toggle switch. This should be entered as the "Water pre-fill time" (Item 3) and is likely to be different
for the different system manufacturers. This amount of time is added to the water run time each repetition because the top distribution pipe drains out during the off time of the on-off cycle.
4. Measure the number of seconds it takes for water to start dripping out the bottom of a dry pad after
the COOL PAD manual toggle switch is turned to the on position. This amount of time should be entered as the "Time to wet dry pad" (Item 4), This will be less than the time to make the pad completely
soaked. When the actual water on time reaches this "Time to wet dry pad" value, the next step is to run
the water continuously, assuming that the temperature is above the Cool Pad Range at the next temperature check point.
5. If water running on the pad continuously is not desired, then the "Max water allowed" value
(Item 5), should be changed so that it is less than the repetition rate time. Once the temperature decreases back below the Cool Pad Range, the actual water on time will return to the "Time to wet dry
pad" value again. From there the water on time changes in the normal way, with 5 second changes every 20 minutes, depending on the temperature check points.
6. Actual water on time- For information only. Showing the value makes it possible to create a graph
of it's variations if you have the PC connection (C-Central).
Setup/Outputs/Ventilation/Coolpad Screen...
3
45
6
Cool Pad
The parameters that determine exactly how the COOL PAD function reacts are programmed in two
separate screens, (Setup/Outdputs/Ventilation/Coolpad and Ventilation Setting/CoolPad). Chore-Time
strongly recommends that the factory default settings be used, unless poor control of temperature during
pad operation is noticed. Chore-Time also recommends that CTB service personnel is contacted before
changing the settings.
59
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the Ventilation Settings button.
2. Select the Cool button.
3. Cool OutputsDisabled Above RH- If there are
relays assigned to cool output(s), and a relative humidity sensor is connected to the Control, the Control can block the cool output from turning on if the
relative humidity sensor reading is higher than entered value.
4. Allow Cool From- User can also specify a specific time of day in which the cool outputs
are allowed to operate. A setting of 12:00a to 12:00a means that the cool outputs are allowed
to operated 24 hours per day.
5. Do Not Allow Cool To Go Below- Outputs
can have a minimum temperature setting. If the
cool or Cool Pad outputs reach this minimum
temperature due to the set temperature changing
the outputs will not go below this minimum temperature even though the set temperature may
continue to lower due to the set temperature
curve.
34
5
Cool Setting
60
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the
Ventilation Settings button.
2. Select the Air Speed Tunnel button.
3. Selecting Airspeed Control in TunnelTo activate put a Check Mark in the Box as
shown. This function is used to maintain a
minimum airspeed while in Tunnel mode.
After making the transition from Power to
Tunnel mode, the Control will turn on
enough Fans until the airspeed reaches the
speed entered in the Start turning on Fans Below line above. When coming out of full tunnel, the Control will continue to allow fans to
turn off according to temperature until the
airspeed reaches the number entered in the
Start turning Fans off line (Item 1, Right).
Example: Using the settings above, when the Control completes the transition to Tunnel Mode, the
Control will check to the airspeed to make sure it at or above the Start turning on Fans Below setting.
It will turn on Fans until the minimum airspeed is reached. The Control will stop allowing Fans to turn
off once the airspeed drops below the number entered in the "Start turning off Fans" box (Item 2,
above). It will maintain that airspeed until the control reaches the Tunnel Off temperature.
Deselecting Airspeed Control in Tunnel-
Enter the minimum number of Tunnel Fans needed
in Tunnel. The number of Fans entered will stay on
until the control transition back to Power, overriding
the fans off temperature setup in the (Outputs/Temperature) screen.
The tunnel fans picked will be the first Tunnel fans
in the(Outputs/Temperature) setup.
2
1
Airspeed Tunnel Settings
61
MT2398C
Control SetupChore-Tronics® 3 Control
3. Current Speed- is the current speed in percent and can
hot be edited.
4. Variable Speed Maximum- Enter the maximum speed in percent that you want to operate
the Var. Speed fan.
5. Variable Speed Minimum- Enter the
minimum speed that you want the operate
the Var. Speed fan.
1. Select the Main menu button.Select the
Ventilation Settings button.
2. Select the Variable Speed button.
3
4
5
Variable Speed Settings
62
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.Select the
Ventilation Settings button.
2. Select the RH Influence button.
3. Actual Influence- The actual amount of
influence time the RH function is adding to
the minimum ventilation timer. The control may not always add the full amount of
time if the amount of influence would add
up to be more than the maximum allowed
setup in the (Ventilation Settings/Set
Temp) screen.
5. Low Control Limit- If the RH in the house is below this setting than the control will
subtract an increment of on time to the minimum ventilation timer down to the minimum
setting is (Ventilation Settings/Set Temp) screen.
Note: If the RH is between the High and Low Control limit, then the control will neither
add or subtract on time to the minimum ventilation timer. The RH is check 30 seconds
prior to an ON time cycle of the minimum ventilation timer.
4. High Control Limit- If the RH in the
house is above this setting than the control will add
an increment of on time to the minimum ventilation timer up to the maximum amount of
influence allowed or the maximum possible amount of ventilation on time that is set in the (Ventilation
Settings/Set Temp) screen.
3
4
5
RH (Relative Humidity) Settings
63
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Curves Button.
3. Select the Set Temp button.
There are several terms that need to be defined in order to understand the Set Temperature Curve
Screen.....
4. A "curve" is a listing of up to 10 points
in time (bend points) that defines how
you want a parameter to automatically
vary as the animals grow. Turn curves
on here.
5. Curve Value- This indicates the current
value(s) of the specified curve.
6. The Bend Points (BPs)- are points on
the curve that define the curve. The
curve values are adjusted between the
Bend Points. The bend point values are
the exact values at midnight of the day # of each Bend Point. The curve takes over when you turn
the curve "on" and the day number is equal to or greater than the day number assigned to BP #1.
7. Day- The intention is that the day # is age of the animals. Negative days (down to - 7) are allowed
if it is desired to preheat the house, for example, prior to the arrival of the animals. The day # of a
BP can also be negative, if desired. Changing the day # in any screen that shows the day number,
will change the day # in all the other screens that show the day #.
8. Temperature- is the temperature you want the Set temp.to be at 12:00am on a specific day. Based
on the bend points setting the temperature increase or decrease between bend points.
9. The graphs on the right side of Set temperature screen shows the progress of the curve. The dashed
line indicated the current day number of the curve.
45
6
78
9
Curves
Curves/Set Temp
64
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Curves Button.
3. Select the Min Vent button.
There are several terms that need to be defined in order to understand the Minimum Ventilation Curve
Screen.
4. A "curve" is a listing of up to
10 points in time (bend points)
that defines how you want a
parameter to automatically
vary as the animals grow. By
turning the curve "on" the
Control will follow the curve
settings .
5. Curve Value- This indicates
the current value(s) of the
specified curve.
6. The Bend Points (BPs)- are
points on the curve that define
the curve. The curve values are
adjusted between the Bend
Points. The bend point values are the exact values at midnight of the day # of each Bend Point. The
curve takes over when you turn the curve "on" and the day number is equal to or greater than the
day number assigned to BP #1.
7. Day- The intention is that the day # is age of the animals. Negative days (down to - 7) are allowed
if it is desired to preheat the house, for example, prior to the arrival of the animals. The day # of a
BP can also be negative, if desired. Changing the day # in any screen that shows the day number,
will change the day # in all the other screens that show the day #.
8. On and Off columns- are the Min. Vent. time for a specific bend point
9. The graphs on the right side of the Minimum Ventilation Curve screen shows the progress of the
curve. The dashed line indicated the current day number of the curve.
Minimum Vent Curve Settings
7
8
45
6
9
65
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Curves Button.
3. Select the Light Clock button.
4. Curves- Four different curves can be setup and assigned to four different Light clocks. For light
level spiking and for the use of independent clocks to control different light types (incandescent
and fluorescent for example) within the house. Select the curve you want to setup from the drop
down.
5. Bend Point- This is the current dis-
played bend point of the Light Clock
Curve. Only one bend point can be
shown at a time. Up to ten bend points
can be used on each Curve. Select the
Bend point you want to setup from the
drop down.
6. Active From Day- This is the day that
current bend point will become the active light clock settings.
7. Events- The Control allows a maxi-
mum of 24 events. Each event the user chooses whether the Relay (if used) assigned to the clock
turns on or off, what the dimmer (if used) level setting should be at the time of the event and how
long it should take to get to that dimmer setting (sunrise/sunset time).
4
5
6
7
8. Time- Enter the time of day.
9. Relay- Turns the relay assigned to the
Light clock that the curve has been assigned to on or off.
10. Enter the amount of time you want to
ramp up or down the output to the Dimmer. If OFF is selected in the relay column
the lights will be turned off with no ramping.
11. Dim perc- Enter the percentage of light level wanted.
See Next Page for Example.....
89
1011
Light Clock Curve Settings
66
MT2398C
Example: In the example (right), the lights
will turn on at 5:00a and will take 15 minutes
to go from 0 percent light to 70 percent light.
At 9:00a the lights will take 5 minutes to
"spike" up to 100 percent. At 10:00a the light
spike is removed immediately (no sunset
time) and the lights return to 70 percent. At
10:00p the lights are immediately turned off.
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Curves Button.
3. Select the RunFor Clock button.
4. Curves- Four different curves can be setup. Select the curve you want to setup from the drop
down. The curves are assigned to the
Feed clock in the (Clocks/Feed/Feed
Clocks) screen.
5. Bend Point- This is the current displayed bend point of the Light Clock
Curve. Only one bend point can be
shown at a time. Up to ten bend points
can be used on each Curve. Select the
Bend point you want to setup from the
drop down.
6. Active From Day- This is the day
that the current bend point will become
the active light clock settings.
7. Events- A maximum of 24.
8. On-at- Enter the start time of the feeding in
this column.
9. Off-at- Enter the off time of the feeding.
This column allows the user to enter a time
down to the second for operating feeders that
only need to run for (mins. /sec or stimulations).
10. Run-for- Shows the amount of feeding time per Event.
4
5
67
RunFor Clock Settings
67
8910
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Management Button.
3. Select the Mortality button.
4. Picked Up- The number of dead and culled animals collected is entered on the Picked Up line. Select the Agreed button
and the number(s) entered in the picked up line will be added
to the Today and the Accum lines. The %Mort and the Curr
(Current) Housed will be recalculated. The total daily mortality will also appear in the Daily HistoryProduction screen.
5. Agreed- When the Agreed button is
selected, the number(s) entered in the
picked up line will be added to the Today
and the Accum lines, the % Mort and the
Curr (Current) Housed will be recalculated, and the total daily mortality will
also appear in the Daily History-Production screen.
6. Partial Taken Out- This is used if
live birds/animals are removed for any
reason other than dead or culled.
7. Initial Housed number- must be entered first.
4
5
6
7
Management Screens
Mortality Screen
68
MT2398C
7. If Males and Females are being entered separately, use the tab buttons toggle between the
Male, Female and Total Screens. When Male
and Female Mortality is entered separately,
the Total Mortality Screen is a summary of
the Male and Female screens and is non-editable. See the Setup/House screen from the
Main menu to tell the Control to keep track of
Male and Female Mortality separately.
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Management Button.
3. Select the Water button.
4. Water Consumed Previous- This num-
ber can be 1 to 60 minutes.
5. Water Cumulative Per- Select from drop
down 1, 100 or 1000 birds.
6. Water Today Per- Select from drop
down 1, 100 or 1000 birds.
4
56
Water Screen
This screen will be available if a drinker line Water Meter is connected to the Control. This screen
indicates the total water consumed in the house and how much water has been consumed in a
certain period of time (for example, how much water was consumed in the house in the previous
5 minutes). If house mortality is being entered into the Control, then the total amount of water
per 1000 birds (or per animal) will also be displayed.
69
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
3. Select the Flock button.
5. Growth Curve- Enter the Growth curve
for the type of bird you have. This can be
entered by Day # or by Week # by selecting from the drop down in the "Use" box.
4. Select the Standard button.
8. Enter the Setup Day number. This example
shows Day 2.
7. Select the Setup button.
5
6. Click on the Back Button and select
"Info".
9. Enter the Flock number.
10. Enter Initial Weight.
11. Setup Date- Enter the current weight of
the birds.
12. Click on Agreed when you are done.
910
11
2. Select the Management Button.
8
Flock Setup
70
MT2398C
Control SetupChore-Tronics® 3 Control
13. Select the Deliver Button.
14. Delivery Day (Optional)
15. Delivery weight- The measured live weight
in the slaughterhouse can differ from the
wight readout on the CT3 Control. This
difference in live weight can be caused by
transport, animals having empty/full stomachs, differences in the house, etc. Using
this option can correct the difference and
take this correction into account during the
next flock.
1415
1. Select the Main menu button.
2. Select the Management Button.
3. Select the Flock button.
4. Select the Zero Calibration button.
4. Calibrate- Ensure that the weighing scale is
empty and select the Calibrate Button.
Flock Setup/Delivery
Flock Setup/Zero Calibration
71
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Management Button.
3. Select the Reset button.
3. Select the "OK" button.
All History will be lost!!
Management Reset Button
Selecting the Reset button from the Management screen will erase all management data.
Warning!! Once the Reset Button has been pressed it can not be reversed.
72
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Programs Button.
3. Select the Programs button.
Programs already programmed into the Control.
You then can choose an action for each program
as follows: Activate Program Settings, Delete
Program Settings, Save Program Settings, Yesterday's Settings. This is a very powerful screen
that allows the user to store up to 6 complete
setups of the Control that can be re-activated at
any time.
4
5. Select the Activate button from the Programs / Setup Key screen.
The Programs / Activate screen will open.
6. Select the desired saved program from the
drop down.
7. Select the OK button.
8. A window will open to ask you if you are sure
you want to continue and that all control settings will be overwritten. Select OK to continue with the activation or Cancel to cancel the
activation of the program.
9. If OK is selected the control will restart with
all the selected program settings.
Programs/Setup Key Screens
Programs Screen/ Activate
5
6
73
7
8
9
MT2398C
Control SetupChore-Tronics® 3 Control
1. Press the Programs Screen/ Programs Button
2. Programs Available- Choose from available Pro-
grams already programmed into the Control.
3. Choose Delete from action choices.
4. Select the OK button.
5. A window will open to ask you if you are sure
you want to delete the selected program.
3
4
6. A window will open to ask you if you are sure you want to delete
the selected program. Select OK to delete the program or Cancel
to stop the operation.
This Does Not delete the current setting in the Control, just the saved program.
In the Program / Available screen Program 1 ( Brood ) has been removed from the list.
2
Programs Screen / Delete
6
74
MT2398C
Control SetupChore-Tronics® 3 Control
2. Programs Available- Choose from available Pro-
grams already programmed into the Control.
3. Choose Save from action choices.
4. Select the Program Number from the drop
down. 1 - 6
5. Enter the Program Name. Ten characters or
less.
6. SelectOK to Save the program or Cancel to
stop the operation.
7. A confirmation window will open letting you know that all the present
settings will be stored in the selected program. Select OK to Confirm or
Cancel to stop the operation.
1. Press the Programs Screen/ Programs Button
Program Screen / Save
2
3
4
5
6
7
75
MT2398C
Control SetupChore-Tronics® 3 Control
2. Programs Available- Choose from available Programs
already programmed into the Control.
3. Select Yesterday from action choices.
1. Press the Programs Screen/ Programs Button
Every day at midnight, the settings of the Control is saved which can be activated anytime
during the following day. This can be helpful if
a mistake in setup is made and it is desired to
undo the changes and go back to Yesterdays
settings.
4. Select OK from the Program / Yesterday screen.
A window opens letting you know that all the
present settings will be overwritten and the Control will restart.
5. Select OK to confirm or cancel to stop the opera-
tion.
4
6. The Alarm will be sent two messages,
Power Failure and Program "X" Activated. At this time notice the alarms
and they will be sent to the Alarm history. These are not hard alarms.
5
Programs / Yesterday
3
2
6
76
MT2398C
Control SetupChore-Tronics® 3 Control
Setup Key Screen/ Activate
Insert a USB Flash Drive into the USB adaptor located on the lower left side of the main box. Unscrew
the protective cap and plug-in the Flash Drive.
77
MT2398C
1. Select the Programs Button.
2. Select the Setup Key button. This
screen is only available if a Setup Key
(USB drive ) is inserted in the USB plug
located on the lower left side of the Control.
5. Transfer FROM Control TO Setup Key- Select the Transfer button to the left
of Transfer FROM Control TO Setup Key
to transfer all of the Controls settings to
the setup key.
3
4
The Alarm will be sent two messages, Power Failure and Program "x" Activated. At this time you
should notice the alarms and they will be sent to the Alarm history. These are not hard alarms.
3. Info Control- The current software level operat-
ing on the Control.
4. Info Setup Key- The software level of the contents stored on the Setup Key. The software level
stored on the Setup Key must match the current Control software level in order to transfer settings
from the Setup Key to the Control.
6. Transfer From Setup Key to Control- Se-
lect the Transfer button to the left of Transfer
From Setup Key to Control to transfer the
settings currently stored on the Control to the
Setup Key.
Control SetupChore-Tronics® 3 Control
78
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Clocks Button.
1. Select the Light button.
This screen displays all the Light Clocks assigned to relays and/or analog outputs. Each Light Clock button is assigned to a particular Light Clock.
3. If a Dimmer is used the current light
level percent is displayed.
2. A number or icon is displayed to the left of the
Light clock buttons.
3
4. If no dimmer is used, the icon shows if the lights are On
or Off.
5. To access the settings for each Light Clock press
the desired Light button. Press the Light 1 button.
Clocks
The Clocks screen consists of the Current Light Clock, Current Feed Clock and Spare Clocks. The Lights
and Feed Curves are assigned to their specific Clock in theses screens.
Light Clock
79
MT2398C
6. Name Clock- Is the current displayed
clock.
7. Events- The current number of events that
the Clock is using to control the lignts.
8. Use Curve- selecting On or Off from the
dropdown activates or deactivates the
curve selected. If the light clock curve is
set to ON, then the current light clock settings will not be editable. To temporarily
change the current light clock settings,
first set the curve to OFF, then make the
desired changes. To return to the curve settings, change the curve back to ON.
678
Light Clock Curve Set "ON"
Light Clock Curve Set "OFF"
9. Time- Enter the time of day.
10. Relay: Turns the relay assigned to the
Light clock that the curve has been assigned
to on or off. This column will be blank if only
an Analog output is assigned.
Control SetupChore-Tronics® 3 Control
80
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
3. Select the Feed button.
4. This screen displays the Feed
Clock settings link for the Feed clock.
5. The icon displayed to the left of the
Feed button indicates if the feed
output is on or off.
6. Selecting the Feed button will open
Feed clock. Only one Feed clock
is available.
7. Name Clock- Is the current displayed clock.
8. Events- Is the current number of
event the clock is using to control
the Feeder.
9. Use Curve- selecting On or Off
from the dropdown activates or
deactivates the curve selected. If
the Feed clock curve is set to ON,
then the current Feed clock settings will not be editable. To
temporarily change the current
light clock settings, first set the
curve to OFF, then make the desired changes.
If the Use Curve is set to OFF,
the Feed output will follow the
settings displayed ever day until the Use Curve is set to ON then the output will follow whatever
curve is selected.
10. On-at:- Enter the start time of the feeding in this column.
11. Off-at:- Enter the off time of the feeding. This column allow the user to enter a time down to the
second for operating feeders that only need to run for (mins. /sec or stimulations).
12. Run-for:- Shows the amount of feeding time per Event.
Feed Clock
2. Select the Clocks Button.
10
11
12
78
9
81
5
6
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
3. Select the Feed button.
4. This screen displays the Spare
Clock settings links for the
Spare clock. Up to eight Spare
clocks.
5. Use the slide bar on the right to
display the other Spare clocks
if more than four Spare clocks
are in use.
6. The icon displayed to the left
of the Feed button indicates if
the Clock Output is on or off.
Spare Clock SetupExample:
7. Select the Spare Clock you wish to set up. In the example shown we chose Spare Clock 1.
8. Name Clock- Is the current
displayed clock.
9. Events- Is the current number
of event the clock is using to
control the Feeder.
10. On-at: Enter the start time of
the feeding in this column.
11. Off-at: 11. Off-at: Enter the
off time of the feeding. This
column allows the user to enter
a time accurate to the number
of seconds.
12. Run-for: displays the amount
of time per Event.
2. Select the Clocks Button.
Spare Clocks
5
6
10
11
12
98
82
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the History button.
1. Select the Environment button.
History Number of days.
Mode Temperature 100 days
Sensors (all assigned) 14 days
Humidity House 14 days
Heat Run Times 14 days
2. Select one of the tab buttons along the bottom to
view that Tab’s History.
Note: Tabs that are grayed out have no history
because no sensor has been installed.
3. Press the Mode Temperature Tab
4. Use the slide bar on the right to move history up
and down.
5. Press the Sensors Tab
Some of the history selections have more than
one sensor. To select a Sensor, use the drop
down as shown to the right.
Environment
Code Number of days.
Water 14 days
Feed 14 days
Mortality 100 days
Auxiliary 14 days
Feed Lines 14 days
4
5
History
History-Environment
83
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the History button.
3. Select the Production button.
4. To view production history for; Water, Feed, Mortality, Auxiliary, or Feed line, select the Tab at the
appropriate Tab at the bottom of the screen. Water
History has been selected in the example.
5. Use the Slide Bar at the right of the screen to
scroll through the history.
Some of the history selections have more than
one sensor. To view select the sensors from the
drop drown in the upper left of the screen.
Note: Tabs that are grayed out have no history,
because no sensor has been installed.
1. Select the Main menu button.
2. Select the History button.
3. Select the Reset button.
4. If "OK" is selected, all History will be lost.
History-Production
5
History-Reset
84
MT2398C
Control SetupChore-Tronics® 3 Control
1. Select the Main menu button. 2. Select the Setup button.
3. Select the Outputs button. 4. Select the Equipped/Numbers button.
5. Select both the Sidewall inlets
and Ceiling inlets check boxes. The
number 1 will appear in the box to
the right. This shows that at least
one pair of relays are to be used.
(Open/Close)
6. Select the Back button to
return to the Outputs Screen.
7. Select the Curtain button
8. Select the Sidewall Inlet button.
9. In the Setup/Outputs/Curtain/
Sidewall inlet screen select the relays that are to be assigned to the
Sidewall inlets. Select the Open relay from the drop down and the
Close relay will be assigned by the
control. Only two sets of (Open/
Close) relays can be assigned. External relays must be used if there
are more than two machines. Both
sets of relays are operated at the
same time.
Setting up Sidewall Inlets
5
9
85
MT2398C
10. Select the Control Tab at the bottom of the screen.
11. Inlet Anticipation- Select from the drop
down Calculated or Fixed.
11a. If Fixed anticipation is chosen fill in the
amount of time in seconds you want the inlets
to anticipate.
11
11a
Control SetupChore-Tronics® 3 Control
86
MT2398C
Control SetupChore-Tronics® 3 Control
If continuing to setup Ceiling Inlets from the Sidewall screen above, select the Back button
twice to return to the Setup/Outputs/Curtain Screen.
1. Select the Main menu button. 2. Select the Setup button.
3. Select the Outputs button. 4. Select the Ceiling Inlet button.
5. In the Setup/Outputs/Curtain/Ceiling
Inlet screen select the relays that are to
be assigned to the Ceiling inlets. Select
the Open relay from the drop down and
the Close relay will be assigned by the
control. Only two sets of (Open/Close)
relays can be assigned. External relays
must be used if more than two machines are installed. Both sets of relays
are operated at the same time.
Continue Setup of the Attic Inlet by
selecting the Control Tab...
6. Use Attic Air Sensors- Choose the
inside sensor (s) you want to use as
controlling sensors.
7. Inlet Anticipation- Select from the
drop down Calculated or Fixed.
8. Controlled By- Select from the
dropdown SP (Controlled by static
pressure or Gravity) If Gravity is selected the Inlet anticipation Fix or
Calculated will have no effect.
9. Allow Attic Air From- Enter the
time of day you want to use the attic
air to ventilate. In the example to
the right; Attic air can be used from 8:00am until 5:00pm.
Setting up Ceiling Inlets
5
7
6
9
8
87
MT2398C
Control SetupChore-Tronics® 3 Control
Setting the parameters for the Ceiling Inlet is done in the Outputs and Temperature screen.
1. Select the Main menu button.
2. Select the Outputs and Temperature button.
3. In the output column you will see "Use Attic Air output".
4. To the left are an ON and Off temperature.
Example:
a) On temp of 84.2. All the air will come from the attic if the temperature of the sensor(s) assigned to
the Ceiling inlet is at or below the
on temperature.
b) if the temperature of the sensor(s)
assigned to the Ceiling inlet is
above the on temperature but at or
below the Off temp of 85.2. and
the static pressure stays above the
high setting for one minute the
Side wall inlets will open to maintain the correct static pressure and
allow the mixing of attic and outside air.
c) If the temperature of the sensor(s)
assigned to the Ceiling inlet is
above the Off temperature the
Ceiling inlet will close. The Sidewall inlets may open or close to maintain the correct static pressure.
d) If the temperature drops below the ON temp the Sidewall inlets will close and the Ceiling inlets will
open to maintain static pressure. If the static pressure is above the high setting the Sidewall inlets
will open to maintain the correct pressure.
Setting up Ceiling Inlet Parameters
a
3
b
88
MT2398C
Control Operation OverviewChore-Tronics® 3 Control
Control Operation Overview
Standard Mode Functionality
Power Mode
All curtain(s) are given a continuous close signal. Inlets are controlled by static pressure (if used). All
outputs that are allowed to operate in Power Mode turn on and off per screen 4 trying satisfy their sensors
assigned in Screen 13.
Natural Mode
Main Curtain Range- The Main curtain range is defined in the Outputs and Temperature screen (Screen
4) and has a default setting of + or - 1.5 degrees F of the set temperature. Once the Control has made the
full transition from Power to Natural mode (or Tunnel to Natural), each main curtain's control sensor will
either open or close the main curtain(s) to try to keep the sensor's temperature within the Main curtain
range. If the curtain's control sensor temperature goes above the range then the curtain will open. If the
curtain's control sensor temperature goes below the range then the curtain will close. The amount the
curtain moves is based upon how far the curtain's control sensor(s) is from the AVERAGE of the Main
curtain range. If the curtain's control sensor(s) goes more than 8 degrees F ABOVE the AVERAGE of the
Main curtain range, the curtains will be given a continuous open signal until the temperature returns to
within the Main curtain range. If the curtain's control sensor(s) goes more than 8 degrees F BELOW the
AVERAGE of the Main curtain range the curtains will be given a continuous close signal until the
temperature returns to within the Main curtain range or until the Control returns to Power Mode. The
control returns to power mode when the main curtain(s) reach the first opening position (see Natural to
Power Mode transition).
Time Between Curtain Movements
The Time between curtain movements is the amount of time the control will wait after an opening or
closing of the main curtain(s) before checking the temperature again and doing another open or close
movement. The default time between curtain movements is 2 minutes. The amount time between curtain
movements can be set between 1 minute and 5 minutes. The time between curtain movements is set in
Screen 14, Curtains tab.
Rate of Curtain Movement
The Rate of Curtain Movement is the amount the control will either open or close the curtain(s) during a
curtain movement. The actual amount of curtain movement is calculated by taking the Rate of curtain
movement and multiplying by the number of degrees the curtains control sensor is from the AVERAGE
of the Main Curtain Range. For example, if the Rate of curtain movement is 1.2 inches per degree F, the
AVERAGE of the Main Curtain Range is 74.0 degrees F and the curtains control sensor is reading 76.0
degrees F then the control will open the curtain 2.4 inches (1.2 x [76-74]). The default Rate of Curtain
Movement is 1.2 inches per degree F and can be set between 1 in and 4 inches per degree F. The rate of
curtain movement is set in Screen 14, curtains tab.
All Outputs that are allowed to operate in Natural Mode turn
screen (Screen 4) trying to satisfy their sensors assigned in the Setup-General screen.
on and off per the Outputs and Temperatures
89
MT2398C
Control InstallationChore-Tronics® 3 Control
Note:
21" Min.22" Min.
43" Min.
21" [53cm] Min.
Control Installation
Mounting the Control
56 Output Control Mounting
A 56 Output Chore-Tronics® 3 Control consists of a Main Box and a Relay Box. The
Main Box requires a minimum mounting area of 21 in. [53 cm] x 21 in. [53 cm] (See Figure below).The Relay Box requires 22 in. [56 cm] x 27 in. [69 cm]. This
dimension allows extra room for the control doors to open. The boxes should be
mounted level and square on a solid backing using the mounting holes provided.
When mounting the Main Box and the Relay Box, make sure the two boxes are as
close together as possible to reduce the likely hood of a communication failure. Make
sure that the Relay Box is mounted so that the relay indicator lights are visible when
standing at the Main Box.
1
Item Description
1Main Box
2Relay Box
Figure 11. 56 Output Control Mounting
2
27" Min.
90
MT2398C
Warning!
Control InstallationChore-Tronics® 3 Control
1
3
Item Description
1Main Box
2Relay Box
3Jumper (In On Position)
4I/O Net and 24Vdc Wire Routing Decal (Communication Wire)
2
Figure 12. I/O Net and 24Vdc Wiring (Communication Wire)
2527-72
COMMUNICATION WIRES
Route Main Box / Relay Box
communication wires here.
24 Vdc +
24 Vdc-
IONET +
IONET -
ONOFF
4
Do Not run I/O Net or 24 Vdc Twisted Pair wire close to and/or parallel with line
voltage wires. (See Figure 75)
The I/O Net terminals of the Main Box and the Relay box must be connected together using the Non-Shiel
ded
Twisted Pair Wire (Chore Time Part no. 42208) included within the Main Box. There is a Decal (Figure 11, Item
4) on the Main Box as well as the Relay Box showing the location to route the I/O Net wires (Communication
Wires). I/O Net is polarity sensitive so be sure that the positive and negative I/O Net terminals of both the Main
Box and the Relay Box are connected properly (See Figure 12). Make sure that the Jumper on the I/O Board is i n
the ON position (See below). The 24 Vdc must also be connected from the Main Box to the Relay Box using the
Twisted Pair wire included within the Main Box. Route the wires along with the I/O Net Wires according to the
Communication Wire Decals (Item 4) on the Boxes.
91
MT2398C
Control InstallationChore-Tronics® 3 Control
90°
Line Voltage Wiring
Non Shielded Twisted
Pair Wire
Figure 13. 90° Crossover
Note:
Caution: Do NOT run 24 Vdc and I/O
Net wire close
(120 Vac or greater) voltage wires. Doing so
can cause operational failure in the Control
and will void Warranty. If 24 Vdc or I/O Net
wires need to cross line voltage wires make
sure the wires cross at a 90 degree angle.
Also, no other electrical devices such as
transformers, light dimmers, additional
relays, etc. should be mounted inside the
Main Box or near the 24 Vdc power or I/O
Net wires.
56 Output Controls
to and/or parallel with line
A 56 Output Chore-Tronics® 3 Control consists of a Main Box, two Relay Boxes, and
an External Power Supply for the Second Relay Box. The Main Box and the Relay
Box/s Each require a space of 21 in. [53 cm] x 21 in. [53 cm]. The External Power
Supply requires 12" [30cm] x 15" [38cm]. These dimensions allow extra room for the
Control doors to open. The boxes should be mounted level and square on a solid
backing using the mounting holes provided.
21" [53cm] Min.
21" [53cm] Min.
123
When mounting the Main Box and the two Relay Boxes, make sure that the boxes
are mounted as close together as possible to reduce the likely hood of a
communication failure. Make sure that the Relay Boxes are mounted so that the relay
indicator lights are visible when standing at the Main Box. (See Figure 14)
75" [190.5cm] Min.
21" [53cm] Min.
21" [53cm] Min.12" [30cm] Min.
15" [38cm] Min.
4
92
Item Description
1Main Box
2Relay Box
32nd Relay Box
4External Power Supply
Figure 14. 56 Output Control Mounting
MT2398C
Chore-Tronics® 3 ControlControl Installation
Important!
1
2
3
4
Item Description
1Main Box
2Relay Box
32nd Relay Box
4External Power Supply
5Dip Switch #1 (In Off Position)
Figure 15. 56 Output Control Mounting
5
Caution:
terminals in all boxes are connected properly (Figure 15). Also make sure that DIP switch #1 on the IO board of the Main Box is
in the OFF position. 24 Vdc must be connected from the Main Box to the first Relay Box (relays 1-40) using the Twisted Pair Wire
The I/O Net terminals of the Main box and the two Relay Boxes must be connected using Non-shielded Twisted Pair Wire (Chore-
Time part no. 42208). Using the Twisted Pair Wire provided, hook the I/O Net wires from the first Relay Box to the Main Box,
then from the Main Box to the Second Relay Box. I/O Net is polarity sensitive so be sure that the positive and negative I/O Net
provided. The 24 Vdc for the Second Relay Box (relays 41-56) must be connected to the External Power Supply (See Figure 15).
The supply voltage for the External Power Supply needs to come from the same breaker as the Main Box.
Do NOT run 24 Vdc and I/O Net wire close to and/or parallel with line (120 Vac or greater) wires. Doing so can cause operational
failure in the Control and Void Warranty. If 24 Vdc or I/O Net wires need to cross line voltage wires make sure the wires cross at
a 90 degree angle (See Figure 13). Also, no other electrical devices such as transformers, light dimmers, additional relays, etc.
should be mounted inside the main box or near the 24 Vdc power or I/O Net wires.
When wiring the Control it is recommended that the line voltage wires be brought into the bottom of the
Boxes and the low voltage wires (Temperature Sensors, Potentiometers, relative humidity, etc.) be
brought in the side of the Control Box (See Figure 17).
When grounding the Control, connect only the Ground Rail of the Main Box to the Earth ground. Connect
the Ground Rail from the Main Box to the Ground Rail of the Relay Box. It is recommended that a ground
rod be located no more than 8’[2.438 m] to 10’ [3.048 m] away from the Control. The Chore-Tronics
®
3
Control should be connected to ground using a 12 gauge wire or larger. As always, check the local electric
code for additional requirements.
95
MT2398C
Control InstallationChore-Tronics® 3 Control
AI5
24V
A6I
U
R
I
U
R
I
Analog Inputs
Analog Inputs consist of temperature sensors, the static pressure sensor, the relative humidity sensor and
potentiometers (natural ventilation only). These inputs can be wired to any of the analog inputs (AI 1 thru
AI 12) on the I/O board. The inputs that are pre-assigned are temperature sensors 1, 2 and 3, and the static
pressure sensor. Use the diagram located on page 137 to record where each Input is wired to the Control.
Temperature Sensors
The Temperature Sensors require Non-Shielded 20 Gauge Twisted Pair Wire. This wire is available through
Chore-Time. When routing this wire in the house be sure to keep it a minimum of 12"(305mm) away from
line voltage wiring. If there is a need for the Sensor wire to cross line voltage wires cross them at a 90° angle
to each other as shown below.
1
90°
2
Figure 19. 90° Cross-over
Item Description
1Non-Shielded Twisted Pair Wire
2Line Voltage Wiring
The Temperature Sensor wires can be connected to any one of the Analog Inputs (AI1 through AI16) of
the I/O board. Whatever AI Inputs the Temperature Sensors are connected to, make sure that the blue
jumper above each Input is set to "R" as shown in Figure 82 below. There are no polarity restrictions for
the Temperature Sensors.
Route the wire through the back of the Temperature Sensor and connect it as shown in Figure below. Pull the
wire through the back of the box until a drip loop is formed as shown.
Static Pressure (SP) Wiring
There is a Static Pressure Sensor included with every Chore-Tronics® 3 Control. This sensor is pre-wired
from the factory to Analog Input #4 (AI 4) (Figure 22). If it is desired, the Static Pressure Sensor can be
wired to any of the Analog Inputs (AI1 through AI16) (See Figure 23 for example wired to AI1). Please
note that the Red wire must always be connected to the +24 volt terminal, the Blue wire must be connected
to the AI terminal being used and the Black wire must be connected to the ground terminal of the analog
Input being use. Make sure that whichever AI Input the SP sensor is connected to, that the blue jumper
above the Input is set to "U" position as shown.
To route the Static Pressure Hoses into the Chore-Tronics® 3 Main Box, first drill two 5/8" holes in the
side of the Box, next to the sensor. Place a ½" water tight connector (Item 3, Figure 24) into each hole
and tighten using the hardware provided. Route a 3/16" ID hose (Chore-Time part number 43071)
through each of the Water Tight Connectors. Connect one hose to the low pressure barb on the SP module,
and run that house into the house. Connect another hose to the high pressure barb on the Sp Module. Run
that hose into the attic or to outside air. Make sure the high pressure hose is in still air. Once the hoses
have been routed and connected, place the Barb Reducer Plugs into the end of the hose opposite of the SP
sensor.
98
MT2398C
Chore-Tronics® 3 ControlControl Installation
Note:
AI10
24V
AI11
U
R
I
To Potentiometer
Blue Jumper set to
the "R" position
UR I
AI10
24V
AI11
Relative Humidity Sensor(RH) Wiring
The optional Relative Humidity Sensor (Item 1, Figure 25) requires a three-conductor wire to connect
®
the sensor to the Chore-Tronics
3 I/O board. The Sensor is connected to one of the Analog (AI) Inputs
on the IO board.
Terminal #1 on the relative humidity sensor is connected to the +24 v terminal on the IO board (see
diagram). This is the same +24 v terminal used by the Static Pressure Sensor. Terminal #2 on the Relative
Humidity Sensor is connected to the Analog Input (AI) terminal of the analog Input being used (See Figure 25). Terminal #3 is connected to the ground terminal of the Analog Input (AI) being used. Make
sure that the Blue Jumper above the Analog Input that the RH sensor is connected to is set to "U".
Blue Jumper in the "U" position
2
1
Item Description
1Relative Humidity Sensor Quick Connect
2I/O Board Analog Input (AI) Terminal of
your Choice
Figure 25. Relative Humidity Sensor Wiring
Potentiometer Wiring (Natural Ventilation only)
If natural ventilation is being used, the
Potentiometer(s)
either the main curtain machine(s)
(Internal Potentiometer), or the main
curtain cables (External Potentiometer)
need to be wired to the Chore-Tronics
3 I/O Board. The Potentiometers need
to be connected using the same Twisted
Pair Wire that is used for the
Temperature Sensors and follows the
same wiring rules. Each Potentiometer
needs to be wired to one of the Analog
Input (AI) Terminals on the IO board.
Make sure that whichever AI Input the
Potentiometer is connected to that the
Blue Jumper above the Input is set to
"R" (See Figure 26). To connect the
sensor wire to the Potentiometer itself,
please see Chore-Time instruction
manual MV1251 for internal
Potentiometer wiring, or MV1566 for
external Potentiometer wiring.
that are attached to
®
Figure 26. Potentiometer Wiring
MT2398C
99
Control InstallationChore-Tronics® 3 Control
DI1
12V
DI5
24V
DI6
Digital Inputs Wiring
Digital inputs consist of Water Meters, Feed Scales, Air Speed Sensor, Low Water Pressure Switch, Max
Feed Run Time Alarm Input, and PDS Flush Feedback. These Inputs can be wired to any of the digital
inputs (DI 1 thru DI 8) on the IO board (Figure 27 below). Complete the analog input Assignment
diagram on page 137 to indicate where each digital input is connected to the IO board and also record it
on the Input Assignment Decal (Item 1, Figure 27) that is placed on the Cover Plate inside the Chore-
®
Tronics
input.
3 Main Box. Also refer to the following sections for information specific to each type of digital
Item Description
1Input Assignment Decal
1
To Feed Scale
100
To Water Meter
Figure 27. Digital Input Wiring
MT2398C
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.