Chore-Time Chore-Tronics 3 Control Installation & Operator's Instruction Manual

Chore-T ronics® 3 Control
Installation & Operator’s Instruction Manual
MT2398CNovember 2013
Chore-Time Warranty Chore-Tronics® 3 Control
Chore-Time Warranty
Chore-Time Equipment (“Chore-Time”) warrants each new Chore-Time product manufactured by it to be free from defects in material or workmanship for one year from and after the date of initial installation by or for the original purchaser. If such a defect is found by the Manufacturer to exist within the one-year period, the Manufacturer will, at its option, (a) repair or replace such product free of charge, F.O.B. the factory of manufacture, or (b) refund to the original purchaser the original purchase price, in lieu of such repair or replacement. Labor costs associated with the replacement or repair of the product are not covered by the Manufacturer.
Conditions and Limitations
1. The product must be installed by and operated in accordance with the instructions published by the
Manufac
turer or Warranty will be void.
2. W arranty is void if all components of the system are
3. This product must be purchased from and installed by a
not original equipment supplied by the Manufacturer.
n authorized distributor or certified representative
thereof or the Warranty will be void.
4. Malfunctions or failure resulting from misuse, abuse,
negligence, alteration, accident, or lack of proper maintenance, or from lightning strikes, electrical power surges or interruption of electricity, shall not be considered defects under the Warranty.
5. This Warranty applies only to systems fo
r the care of poultry and livestock. Other applications in industry
or commerce are not covered by this Warranty.
The M
anufacturer shall not be liable for any Consequential or Special Damage which any purchaser may suffer
or claim to suffer as a result of any defect in the product. “Consequential” or “Special Damages” as used herein
include, but are not limited to, lost or damaged products or goods, costs of transportation, lost sales, lost orders, lost income, increased overhead, labor and incidental costs and operational inefficiencies.
THIS WARRANTY CONSTITUTES THE MANUFACTURER’S ENTIRE AND SOLE WARRANTY AND
MANUFACTURER EXPRESSLY DISCLAIMS ANY AND ALL OTHER WARRANTIES,
THIS INCLUDING, BUT NOT LIMITED TO, EXPRESS AND IMPLIED WARRANTIES AS TO MERCHANTABILITY, FITNESS FOR PARTICULAR PURPOSES SOLD AND DESCRIPTION OR QUALITY OF THE PRODUCT FURNISHED HEREUNDER.
Chore-Time Distributors are not authorized t
o modify or extend the terms and conditions of this Warranty in any manner or to offer or grant any other warranties for Chore-Time products in addition to those terms expressly stated above. An officer of CTB, Inc. must authorize any exceptions to this Warranty in writing. The Manufacturer reserves the right to change models and specifications at any time without notice or obligation to improve previous models.
P.O. Box 2000 • Milford, In
Email: ctb@ctbinc.com • Internet: http//www.ctbinc.com
CTB, Inc.
diana 46542-2000 • U.S.A.
Phone (574) 658-4101 • Fax (877) 730-8825
Effective: Nov
ember 2013
MT2398C
Contents
Topic Page
Chore-Time Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Support Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Follow Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Decal Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Introduction to the Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Display Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Relay Box Indication Lights and Auto/Manual Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Glossary of Terms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Anticipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Back Up Relay Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Bend Point (BP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Cool Pad Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Curve Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Day Number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Digital Input. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Event . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Mode Sensor(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Natural Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Offset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Power Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Set Temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Spare Temp Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Tunnel Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Wind Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Overview of Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Alarms (Active or Recovered). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Control Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
General Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Analog Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Analog Input Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Setup House . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Output Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Assignments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Ventilation Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Management Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Programs/Setup Key Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Clocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
MT2398C
* Legend: C = Customer (end user), D = Distributor (sales), I = Installer of equipment
Contents - continued
Topic Page
History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Control Operation Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Standard Mode Functionality. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Control Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
Mounting the Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Wiring the Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Analog Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Remote Light Dimmer Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104
Bird Scale Wiring using the LCC Board (Scales Less than 150’ from Control). . . . . . . . . . . .105
Bird Scale Wiring using the LCC Board (Scales More than 150’ from Control) . . . . . . . . . . .106
Testing the Back Up Box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111
MS Board Dip Switch Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112
PC Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Programming Trouble Shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .114
Programming Troubleshooting Continued..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
Programming Trouble Shooting Continued..... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
Equipment and Potentiometer Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .116
IONet Error Addr:xx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Backup Control Wiring (24Vdc) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
Fan Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Linear Lift Wiring Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
Turbo-Cool™ Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
I/O Board Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
Brooder Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128
Improving Lightning Surge Suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Itemized Parts (Main Box). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Parts Listing (Main Box) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Itemized Parts (Relay Box) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Parts Listing (Relay Box). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Extra Parts and Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Analog Input Add-On Kit (Part No. 49663) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
Digital Input Add-On Kit (Part No. 49665). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
Expansion Board Kit (Part No. 49667) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
IMSCM.8 Red Repair Board (Part No. 49672) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
IMSCM.16 Red Repair Board (Part No. 49673) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .138
Input Wiring Assignment Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
MT2398C
General Chore-Tronics® 3 Control
Technical Specifications140Technical Specifications139
General
Support Information
The Chore-Tronics® 3 Controls are used to control the Climate in a structure to insure efficient growth of Livestock. Using this equipment for any other purpose or in a way not within the operating recommendations specified in this manual will void the warranty and may cause personal injury.
This manual is designed to provide comprehensive planning, inst information. The Table of Contents provides a convenient overview of the information in this manual. The Table of Contents also specifies which pages contain information for the sales personnel, installer, and consumer (end user).
allation, safety, operation, and parts listing
Safety Information
Caution, Warning and Danger Decals have been placed on the equipment to warn of potentially dangerous situations. Care should be taken to keep this information intact and easy to read at all times. Replace missing or damaged safety decals immediately.
Using the equipment for purposes other than specified in this manual ma personal injury and/or damage to the equipment.
Follow Safety Instructions
Carefully read all safety messages in this manual and on your equipment safety signs. Follow recommended precautions and safe operating practices.
Keep safety signs in good condition. Replace missing
Decal Descriptions
or damaged safety signs.
y cause
DANGER : Electrical Hazard
Disconnect electrical power before inspecting or servicing equipment unless maintenance instructions specifically state otherwise.
Ground all electrical equipment for safety. All electrical wiring must be done by a qualified el
and national electric codes. Ground all non-current carrying metal parts to guard a With the exception of motor overload protection, electrical disconnects and over
current protection are not supplied with the equipment.
ectrician in accordance with local
gainst electrical shock.
MT2398C
Introduction to the Control Chore-Tronics® 3 Control
Introduction to the Control
Display Screen
The display screen is a 10.1 in. Full Color Touch screen. This screen will display the requested information when an Icon on the Touch Screen is pressed. The Display Screen always remains lit. When the Control is left dormant, the Current Conditions Screen will be visible.
Display Screen
Figure 1. Display Screen
Navigation
Navigating the Control can be done in one of two ways. Navigating option 1. (Touch)- Touch the Icon or simulated button displayed on the screen with your
finger or stylus.
Figure 2. Navigation-Touch
MT2398C
Introduction to the Control Chore-Tronics® 3 Control
Navigating option 2. (Mouse)- A USB mouse can be used by plugging it into the USB port located on the left side of the main Control Box.
To navigate using a mouse, position the cursor on the Icon or and press the left mouse button to select.
USB Port
USB Mouse
the simulated button displayed on the screen,
Figure 3. Navigation-Mouse
MT2398C
Introduction to the Control Chore-Tronics® 3 Control
1. Displays the Path and the house name or number.
2. (T ask Bar) Navigation buttons from left to right are; Back button, Main menu, Forward button, Current Condition, Alarm, Password and the Help.
3. All menus, viewable data and editable fields.
4. Time, Date and Age.
2
4
3
Figure 4. Screen Layout
Screen Layout
In the top left corner of every screen the path and the screen name is displayed to the screen you are viewing. In this example the Current Conditions screen is displayed.
1
Navigating the Control’s Screens
In the Current Conditions screen you can view current data and some settings. Each button has an Icon that represents the data to be displayed.
Selecting the button with the water droplet
Figure 5. Screen Navigation
will display the current water usages from 12:00 am.
MT2398C
Introduction to the Control Chore-Tronics® 3 Control
Notice the path displayed (Current Condition/Today's Water)
Current Path
Figure 6. Current Path
To return to the Current Conditions screen, select the back
or select the CC return you back to the Current Conditions
button. Note: Regardless of the screen you are in selecting the CC button will
screen.
OR
button at the top left corner of the screen,
Figure 7. Returning to Current Conditions Screen
MT2398C
Introduction to the Control Chore-Tronics® 3 Control
2
1
3
4
5
1. Scrolls the value up or down.
2. Removes the last number on the right.
3. Changes the entre from a positive to a negative number.
4. Removes the pop up with no changes to the value.
5. After you have made changes select "OK" to confirm the change. The pop up will disappear and the change will be displayed in the field.
Figure 8. Numeric Keypad
Numeric Keypad
In a screen that has editable fields, select the value you want to edit (In this example: Set Temperature). A Numeric Key Pad will be displayed. The name of the field will be displayed at the top of the Key pad.
Name of Field being edited.
Editable field
In some editable fields you can enter text, if these fields are selected a Key Board will be displayed. If a number is needed with the text, select the button labeled 123 on the Key Board and a Numeric Key Pad will be displayed. To go back to the Key Board select the AZ button on the Numeric Key Pad. The OK button will save your entry.
Press "OK" to save entry
Toggle back and forth from Keyboard to Number Pad using the
and the button.
10
Figure 9. Toggling between Keyboard or Numeric Key Pad
MT2398C
Introduction to the Control Chore-Tronics® 3 Control
1. A Graph icon will be displayed in the upper right
of a screen if there is a graphical repre­sentation.
1
Graphs
Relay Box Indication Lights and Auto/Manual Switches
Each Relay Output has its own three position switch that allows the user to select manual, off or automatic control of each Relay. The Relays and their corresponding Switches are located in a separate box. Decals are supplied to label each Switch for the Output function that is assigned to that Switch. The Switches can be placed in three positions - "on", "off", or "auto". The "auto" position is for normal automatic operation. Changing a Switch to "on" or "off" overrides "auto" operations. When a switch that is assigned is placed in a position other than "auto", a message will appear in the Current Conditions screen advising you to "Check Switches". The light above each Switch indicates that the Switch's Relay is activated.
1
2
3
Item Description
1 Indication Light 2 Switch 3 Decal
Figure 10. Indication Lights and Switches
11
MT2398C
Glossary of Terms Chore-Tronics® 3 Control
Glossary of Terms
Analog Input
Analog Inputs can consist of the following: Temperature sensors Static Pressure sensor (4-20 mA) Relative Humidity Sensor (0-10 volts) Potentiometer (Natural Ventilation)
Anticipation
When the control is turning on the fans assigned to the Minimum Ventilation Timer, the control will open the inlets to the correct position for static pressure control before the fans are turned on. If calculated anticipation is used (default), the control teaches itself how much adjustment was required during the previous on-off cycle, and uses that amount of "anticipation" for the next cycle. If the optional fixed anticipation is used, the control will NOT teach itself what the correct anticipation should be. It uses the amount of "anticipation" that is entered in the Static Pressure screen (Screen 11). Anticipation will occur when the fans assigned to the Minimum Ventilation Timer turn on due to the timer reaches an ON cycle or the sensor(s) assigned to the fans reach the fans' ON temperature.
Back Up Relay Output
The backup up relay output is a relay that will be energized as soon as the backup output is assigned to a relay. This relay will stay energized as long as the control is communicating with the manual switch board where the output is assigned. The 24 Vdc signal that comes from the control to the back up box should be routed through this relay. If communication is lost between the main box and the manual switch board, the relay will drop out allowing the first fan stage in the back up box to turn on. See the Wiring Diagrams section of this manual for more wiring information.
Bend Point (BP)
The Bend Points (BPs) are simply the points on the curve that define the curve. For the Set Temperature and Minimum Ventilation Timer curves, the curve values are gradually changed between bend points. The bend point values are the exact values at midnight beginning the day # of each bend point. The curve takes over when you turn the curve "on" and the day number is equal to or greater than the day number assigned to BP #1.
Cool Pad Output
The COOL PAD Output is a special function for controlling evaporative cooling that allows you to modulate the addition of water to the cooling pad in such a way that the usual large temperature swings associated with a cooling pad are avoided.
Curve
A "curve" is a listing of up to 10 points in time (bend points) that defines how you want a parameter to automatically vary as the animals age.
Curve Value
The Control will list what the current value(s) the curve would be, if the current day number is greater than the day # of bend point #1, and the curve is "on", and there is no "offset" to the curve.
Day Number
The intention is that the day # is the age of the animals whose environment is being controlled. Day # 0 does not exist. Negative days (down to - 7) are allowed. Changing the day # in any screen that sho in all the other screens that show the day #.
12
ws the day number, will change the day #
MT2398C
Glossary of Terms Chore-Tronics® 3 Control
Mt1701-Naturalmode 11/01
Digital Input
Digital Inputs can consist of the following: Water meter Feed scale Air speed sensor Low water pressure switch Max feed run time Input PDS flush feed back
Event
This term applies to the time clock Outputs. An "event" is an "on at" time combined with an "off at" time.
Mode Sensor(s)
The concept of Mode Sensor(s) is essential to the understanding what makes the Control change from one mode to another. The Mode Sensor(s), of a currently operating mode, determines when the Control will leave that mode. As an example, while in the Power Mode, the Power Mode Sensor(s) determines when it's too stay in the Power Mode (i.e. above the tunnel "on" temperature) converts to the Tunnel Mode (assuming there temperature. It comes back to the Power Mode from the Tunnel Mode Sensor(s) say it's
too cold to stay in the Tunnel Mode (i.e. below the
is no Natural Mode) at the tunnel "on"
Tunnel Mode, when the
. Because of this, it
tunnel "off" temperature).
hot to
Natural Mode
Natural Mode requires the house to be equipped with Curtains in the side walls that are powered by Drive Units (Curtain Machines). The Control converts to this mode of operation when the temperature(s) inside the house raise to a level that the Fans of the Power Mode can't keep the temperature(s) under control. While in the Natural Mode of operation, the Curtains are opened or closed, as required, to control the temperature(s). This mode of operation generally happens during moderate weather.
Noticing an Alarm
"Noticing" an alarm is a very important part of using the alarm system. See how to Notice an Alarm (Active or Recovered) in the "Alarm" section of this manual.
13
MT2398C
Glossary of Terms Chore-Tronics® 3 Control
Mt1701-Powermode 11/01
Offset
The term "offset" applies to the Set Temperature and Minimum Ventilation Timer curves only. If you manually adjust either the Set Temperature or the Minimum Ventilation Timer settings, while the curve is on, you create an "offset" to that curve relative to it's "curve value". The "curve value" is not changed. (see the "curve value" definition above.) The curve value is shown as a convenience so that you know what you have to change it back to in order to get back on the actual curve's table listing. While an "offset" is in effect, the parameter of the curve is still modified versus time. However, the actual parameter value is the "curve value" modified by the "offset".
Power Mode
The building is closed up except for Inlets (usually Baffle Doors) which are powered open and close in order to control the static pressure level. In some cases Gravity Inlets are used where the static pressure is not controlled directly. The only ventilation provided is due to Fans mounted in the end operation generally happens when the outside temperatures are somewhat lower than the set temperature.
or side walls. This mode of
14
Program
A "program" is a complete set up of all the screens of a Control. In the main menu Program Tab, six different "programs" can be saved and later activated. This can be very convenient when it is desired to change the set up at different points during the grow out, barn cycle, or times of the year.
Set Temperature
The set temperature is another very important, basic, concept. All temperatures are referenced to the set temperature. When the set temperature is adjusted either manually, or because the set temperature curve is on, all other temperature settings move up or down by the same amount. For instance, even though you program an actual temperature for each Fan to come on and off, when you change the set temperature, those Fan's on and off temperatures are adjusted by the same amount you changed the set temperature.
Spare Temp Sensor
The spare temperature sensor is a temperature sensor that is separate from one of the 12 controlling sensors. This sensor can be used to control the temperature in a separate area of the house. The sensor has its own maximum and minimum alarm parameters that can be set up in the Alarms screen. The sensor can also turn on and off the Spare Temperature Sensor Output. This output functions like a fan output. The output has lower Off temperature than its On temperature. The On and Off temperatures for the Spare Temperature Sensor output are defined in the Outputs and Temperatures screen. The spare temperature sensor can not be used to control any other output.
MT2398C
Glossary of Terms Chore-Tronics® 3 Control
Static Pressure
Static pressure refers to the pressure difference that exists between the inside of the house and the outside of the house. This pressure difference is the result of Fans in the walls running. The air that they exhaust enters the house through various types of air inlet openings. In the Power Mode the typical powered baffle inlets is where the vast majority of the air enters. In the Tunnel Mode, the tunnel inlet at the end of the house is where the air enters. The pressure drop, due to the resistance to the air flowing through the inlets, is the reason a static pressure difference exists. If the inlets are all the same size, the same amount of air will enter through each inlet. In the Natural Mode of operation, the outside wind is the source of the air, with no exhaust fans running. In general there is little or no static pressure during the Natural Mode due to the huge area of the open side wall curtains. When the incoming air is cooler than the inside air, it will tend to drop down onto the birds before it is warmed up. Adequate static pressure brings the air into the house high and fast so that it heats up before it can fall.
Tunnel Mode
This mode of operation requires a group of large fans at one end of the house with a large air Inlet area at the opposite end of the house. The control converts to this mode of operation from the Power or Natural Mode (if used), when the temperature(s) while in those modes get too high. The typical 5 or 6 mph. breeze, which can be created by the Tunnel Fans running, produces a wind chill effect that is significant. This mode of operation happens during warm to hot weather.
Mt1701-Tunnelmode 11/01
Wind Delay
The static pressure has to be out of the control limits continuously for the "wind delay" amount of time before the inlets are adjusted. If a fan or fans has turned on or off within the last 10 seconds, the wind delay does not happen and the inlets respond as soon as the static pressure leaves the control limits.
15
MT2398C
Overview of Screens Chore-Tronics® 3 Control
Alarms Button
Message
Alarm Status
Notice Button
From any screen you can select the Alarm but­ton. This will take you to the Alarm Overview screen.
Alarm Overview Screen- In the Alarm Over­view screen an Alarm is listed in three columns. Message (Type of alarm), Status (Alarm, Recov­ered and Off For) and a Notice button.
History Tab
Active Alarm- Select the Notice Button to notice the Alarm
If the alarm condition is still active, Off For x:xx will be displayed in the Status column. The specific alarm will be inactive until it has recovered to with­in its normal range, at that point the alarm will be sent to the Alarm History (See below left).
Overview of Screens
Alarms (Active or Recovered)
Active Alarms
To see any current "Active" alarms press the Alarms Button. If there are any Active alarms they will be listed here (See Figure below).
Alarm Time
Recovered
Noticed
Message
16
Alarm Date
MT2398C
Overview of Screens Chore-Tronics® 3 Control
Alarms Button
Notice Button- Select the Notice button to notice the alarm, the alarm will be sent to the Alarm History screen.
From any screen you can select the Alarm but­ton. This will take you to the Alarm Overview screen.
Alarm Overview Screen- If there is a Recov­ered alarm it will be listed here (See above).
Alarm History- To view the alarm history, select the History tab at the bottom of the Alarm screen. The alarm date, time, message, noticed and recov­ered is displayed for each alarm listed (See below).
Recovered Alarms
To see "Recovered" alarms press the Alarms Button. If there are any Recovered alarms they will be listed here (See Figure below)
Recovered
Alarm Date
Alarm Time
Recovered
Noticed
Message
17
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Setup button.
3. From the Setup/General screen select Settings .Setup/General/Settings screen.
2. Select the General button to access the Setup/General screen.
4. Enter the Computer Number. This will be your house number.
5. Enter the House Name. The house name can be whatever you want, it will be displayed at the top right of ever screen. A maximum of 14 digits.
6. Choose the Language by pressing the dropdown and select English or Spanish.
7. Choose the Clock Type by pressing on the dropdown and select 12 hour or 24 hour clock.
8. Set the Time of Day by pressing on the time box, a numeric keypad will open allowing you to set the time of day. (See following page).
9. Set the Date by pressing the date box, a numeric keypad will open allowing you to set the date. Follow the same procedure used to set the Time (See Following Page).
10. The IP, IP mask and Gateway are used only if C-Central, WebLink and or C-Collect are in use. These settings are determined by the local network settings.
Note: Path to the Screen being viewed
4
5
6
7
8
9
10
Control Setup
General Setup
From any screen select the Main Menu button at the top left of the screen.
18
MT2398C
Time of Day
1. Highlight the hours by selecting the hours. Change the hours by using the up/down ar­rows or the keypad.
2. Highlight the minutes by selecting the min­utes. Change the minutes by using the up/ down arrows or the keypad.
3. Highlight the am/pm by selecting the am/ pm. Use the up/down arrows to toggle.
4. Select OK to save.
Date
The date must be enter in a specific format ( Day.Month.Year ) The example shows, 05.10.2010 for 5 October 2010
Control Setup Chore-Tronics® 3 Control
19
MT2398C
Units
In this screen you will choose the unit of measurement you want to display.
2. Select the Units button
1. Select the General Button in the Setup Screen.
3. Choose the unit of measurement you want to display.
Control Setup Chore-Tronics® 3 Control
20
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Setup button. 2. Select the Analog inputs
1. Select the Sensor Type button
In this screen you choose what type of Analog Inputs (temperature sensors, relative humidity sensor, and potentiometers) are connected to the Control. The Static Pressure Sensor and House Temperature Sensors 1-3 come from the factory pre-assigned.
2.
Enter Sensor Types installed
Select the box to the left of the sensor types in­stalled. When a Sensor type is grayed out, that specific item cannot be selected. The number of specific sensors (Nbr Sensors) will be added as you continue with setup.
Grayed out (Cannot select)
Sensor Types
Installed
Number of Sensors
Analog Inputs
To access the Analog Inputs Setup screen start by accessing the Main Menu screen.
Analog Inputs-Sensor Type
21
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the House Temp. Sensor button
From the Setup/Analog Inputs screen select House Temp. Sensors button. The Setup/Ana­log Input/House Temperature screen should be displayed at this time
2. Factory assigned
Sensor numbers
Temperature sensors 1-3 come from the facto­ry pre-assigned. To assign the next sensor se­lect the Add button and the next sensor will appear (See below right).
3.
Adding Sensor assignments
Fill in the Board, Input, and backup by select­ing from the dropdowns. Continue until all the temperature sensors have been assigned. If it is desired to skip a sensor and move to the next sensor in the list, select the - (not assigned) on the sensor that needs to be skipped and select the ADD button, next sensor will appear in the list.
4
4. Board
The number of the Board the Sensor is con­nected. Board number 0 is the IOM16 Board. If the sensor is connected to an additional an­alog input board, then the Board number matches the address of the add on Board (see the installation section of this manual).
5.
Input
This is the input number that the Sensor is connected to on the Board. On the IO Board the input number will be 1 thru 16. If the Sen­sor is connected to an additional Analog Input Board then the Input number will be 1-4.
5
6
6. Value
This is the current temperature reading.
7. Corr.
This is the amount of correction made when the sensor was calibrated. Calibration will be gone over later in the manual.
8. Backup
This is the sensor you want to be the backup if the sensor fails.
2
45
7 8
Analog Inputs-House Temperature Sensors.
Select the Back button after all the House temperatures have been assigned.
22
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Outside Temp. Sensor button
In this screen the Outside sensor is assigned. Calibration is also done from this screen. Skip this Screen if no outside sensors are installed.
2. Adding Sensor Assignments
Fill in the Board and Input by selecting from the dropdowns.
Analog Inputs-Outside Temperature Sensor
Select the Back button after the Outside temperature sensor has been assigned.
23
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Static Pressure Sensor button
2. Assign Static Pressure input as you did for the House Temperature
Sensors. Calibration is also done from this screen.
3. Select the Control Tab button
In this screen you set up the specifications for the Stat­ic Pressure Sensors
4. Current Safety Limit
Static Pressure Safety limit- Example: When the static pressure stays above 0.20 for a continuous minute, the Tunnel Curtain (if in Power Mode) and the Inlets (if in Tunnel Mode) will open until the static pressure reduces below 0.20. Once the problem is fixed and the static pressure reduces below 0.18, the Control returns to normal opera­tion. The safety limit can be set from .18 to .27. This situation will always result in a High Pres­sure Alarm.
4
Analog Inputs-Static Pressure Sensors
24
MT2398C
5. Second Static Pressure
Selecting this feature a second level of Power Mode static pressure can be chosen. The Tem­perature Sensor(s), (Inside Only), that measure that temperature is defined in this screen. Se­lect the sensor edit field and a sensor assign­ment window will be displayed.
6. Select/Deselect sensor check box
Select or deselect the sensor check box to choose the sensor or sensors you want to use. Select OK to save. The temperature at which the second static pressure takes over is entered in Output and Temperature screen.
Control Setup Chore-Tronics® 3 Control
25
MT2398C
8. Tunnel Inlet Static Pressure assist in Power
If in the Power Mode, there is inadequate inlet area to keep the static pressure within the high control limits, the Tunnel Curtain will open to give addition­al air inlet area. The Inlets are given continuous open signals as the Tunnel Curtain takes over the respon­sibility of controlling the static pressure. The static pressure has to be above the high Static Pressure Control limit continuously for one minute with 3 or more Fans running for this to happen. Responsibility for Static Pressure Control is passed back to the In­lets as soon as there are fewer than 3 Fans running or the Tunnel Curtain cannot bring the static pressure back into the control range (while closing) from the low side. The static pressure has to be below the low Static Pressure Control limit continuously for one minute for this to happen.
Select the Back button twice after the Static pressure has been assigned and Control screen is com­pleted
Control Setup Chore-Tronics® 3 Control
1. House Relative humidity Sensor
From the Setup/Analog Input screen select House RH sensor Button.
2. Assign the House RH sensor input as you did the House Sensors. Calibration is also done from this screen. See next manual section "Calibrating Analog Inputs".
Analog Inputs-Relative Humidity Sensor
26
MT2398C
3. Select the Control tab.
4. Select the RH Influence On Minimum Ventilation
box if you want the min/vent timer to be influenced by the RH.
5. The Minimum Ventilation timer will be adjusted based on house RH when the temperature is between set temperature and the Min-Vent fan's ON tempera­ture. The Control will adjust the amount of ON time between the Min Ventilation value and the Max val­ue. The OFF time will be adjusted by the same amount of time that the ON is adjusted, thus keeping the total cycle time constant. The temperature is checked 30 seconds before the beginning of the ON time cycle of the Mini­mum Ventilation Timer. This is in addition to any time added by Ventilation Timer Ramping.
6. Amount Of Influence (sec)- is the amount of decrease or increase time pre movement.
7. Maximum Influence(sec)- is the maximum amount of RH timer influence you need.
Once the fans' temperature sensor(s) reach the fans' ON temperature, the fan will turn on and run continuously until the fans' OFF temperature is reached.
Once the fans' temperature sensor(s) reach the fans' ON temperature, the fan will turn on and run con­tinuously until the fans' OFF temperature is reached.
6
7
Control Setup Chore-Tronics® 3 Control
27
MT2398C
Control Setup Chore-Tronics® 3 Control
1. From the Setup/Analog Input screen select Type & Number.
2. Put a Check in the Bird Scale Box.
3. Select the Back Button and then select
the Bird Scale Button.
4. Select the Board number from the drop down.
5. Select the Input from the drop down. Select 1.
Analog Inputs-Bird Scale
28
MT2398C
Control Setup Chore-Tronics® 3 Control
1. To re-calibrate the Temperature Sensors, first obtain a digital thermometer that has a readout of at least + - 1°. Do not use a temperature gun. A temperature gun measures an object’s temperature, not air temperatures.
2. Place the digital thermometer next to the Temperature Sensor that is being re-calibrated. Take the reading from the digital thermometer and enter that number under the Value column of the Sensor being calibrated.
3. The Correction column is used only for service information and to return the Control to the factory settings. The settings should be reset to factory whenever a re-calibrated Temperature Sensor is replaced. To return to factory settings change the number under the correction column by one digit. This will cause the correction to automatically zero out and return to factory setting.
All Temperature Sensors are calibrated the same way. (Outside, Spare and Aux temperature sensors)
1. To re calibrate the Relative Humid­ity Sensor first obtain a sling psy­chrometer or another humidity measuring device.
2. Operate the psychrometer in the same area that the Relative Humidity Sensor is installed. Take the reading on the psychrometer and compare it to the reading on the Setup/Analog In­puts/ House RH Screen. If the read­ings do not match, then change the reading under the Value column to match the reading of the psychrome­ter.
3. The correction column is to be used for service information and for returning to factory settings only.
2
3
Analog Input Calibration
The re-calibration section of this screen should not need to be used at initial installation and start-up of the Control unless natural ventilation is used. If natural ventilation is being used, then the Potentiometers will need to be calibrated at this time. If it is felt that one of the Inputs needs to be re-calibrated perform the following steps…
Temperature Sensor Calibration
Relative Humidity Sensor Calibration
2
3
29
MT2398C
Control Setup Chore-Tronics® 3 Control
1. To re-calibrate the Static Pressure Sensor first obtain a manometer or other static pressure measuring device. Then disconnect both hoses from the Static Pressure Sensor.
2. Go to Setup/Analog Inputs/Static Pressure screen and look at the Pres­sure reading in the Zero Level value box. If the reading is not zero then change the zero level value pressure to read zero. The zero level has now been calibrated.
3. To calibrate the high level, first make sure that the Manometer has been installed in the house and recon­nect the hoses to the Static Pressure Sensor. Open the Inlets slightly and turn on enough Fans to create a static pressure of at least 0.15 inch­es of w.c. at the Manometer. Compare the Manometer reading to the reading on the High Level line on the Control. If the readings do not match, edit the pressure reading on the High Level value box to match the reading of the Manometer. As with the Temperature Sensors, the Correction column of the static pressure calibration is used for service, and to return the Control to factory settings only. This completes the re-calibration of the static pressure Sensor.
2
3
1. Go to the Setup/Analog Inputs/Bird Scale Screen and Select Calibrate. (Platform should be hanging from the Load Cell)
2. With no weight on the Platform select the OK
Button. If there is no error then continue.
3. Place a 5.00 lb. weight on the Platform. In the
"Calibration Weight Box" enter 5.00. Click the Ok Button. If no error then the calibration is done.
Static Pressure Sensor Calibration
Bird Scale Calibration
30
MT2398C
Control Setup Chore-Tronics® 3 Control
2. Select the Type & Number button.
3. Select the Digital inputs you have connect­ed to the Chore-Tronic's 3.
Digital Inputs
1. Select the Main menu button. Select the Setup but­ton from the Main Menu screen. Finally, se­lect the Digital inputs Button.
Digital Inputs
The Digital Input Screens are very similar to the Analog Input screens and setup the same way. In these screens the Control is told what digital inputs (Water Meters, Feed Scales, Airspeed Sensor, Low Water Pressure Switch, Flush Feed Back, Auger Run Time Alarm, etc.) are connected to the Control and where. All digital or pulsed inputs that are connected to the Control must be assigned a board number and an Input number. It is highly recommended that the Input Decal located inside the main box of the Control be completed before entering information in this screen.
Board- This is the number of the board where the water meter or other digital input device is connected. Board number 0 is the I/O Board. If the sensor is connected to an additional digital input board, then the board number matches the address of the add on board (see the installation section of this manual).
Input- This is Input number that the water meter or other digital input device is connected to on the board.
For the I/O Board the input number will be 1 thru 8. If the sensor is connected to an additional analog input board then the input number will be 1-4.
Name- A name can be entered for the Water meter, feed scale, and auxiliary digital inputs using the al-
phanumeric keypad. The name entered here will appear in the Auxiliary Data and History screens.
Select Add and the next Sensor will appear in the list. Select Remove and the last Sensor in the list will be deleted.
Type and Number
31
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Setup but- ton from the Main Menu screen. Finally, se­lect the Digital inputs Button.
2. Select the Water Meters button.
3. Enter all Drinker/Water Meters that are connect-
ed to the CT3 here. A Drinker Water Meter is a Wa­ter Meter that is monitoring the water being used by drinker water lines or the entire house (1 meter for both drinker lines and Cool Pads). If a Water Meter is assigned an input here, its daily usage will be add­ed to the total amount of consumed water in the management screen. When a Water Meter or other digital input is assigned to a board and an input on that board, to add the next Water Meter or digital in­put select the ADD button and Meter #2 will appear. If it is desired to skip a Meter or other digital input and move to the next digital input in the list, enter (not assigned) for the input that needs to be skipped. it is desired to skip a Meter or other digital input and move to the next digital input in the list, enter (not assigned) for the input that needs to be skipped.
4. Select the Control tab Water Flow Rate Alarm- Put a check in the box if
you want an alarm when flow rate is too high. The pa­rameters are setup in the Alarm screen under the Pro­duction tab.
Water Meter
32
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Dump Scale Button. All feed scales that are connected to the Control needs the input it is connected to assigned here. All feed scales that are assigned inputs here will have their daily usage added to the total amount of feed consumed in the management screen.
2. Assign an input to each of the feed scales con­nected to the Control here. Each Input assigned here will have its daily usage added to the total amount of feed consumed in the management screen.
1. Press Auxiliary Input button Many different types of auxiliary digital Inputs can be used with the Ct3.
2. Types of auxiliary Inputs include non-drinker water meters (water meters attached to evapora­tive cool pads, etc.), pulsed output electric me­ters, pulsed output gas meters, etc. Each inputs usage will be monitored separately and will not be added to any total usage.
1. Press the Air Speed button. 2. Enter the board and input numbers for the Air speed meter. The parameters are setup in the Alarm screen under the Environment tab.
Dump Scale
Auxiliary Inputs
Airspeed Sensor
33
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Press the Feed Lines button. 2. Enter the board and input of each Feed Line
connected to the Control. Feed Line run times will be generated from these inputs.
1. Press the Water Pressure button. 2. Enter the board and input for the Water pres­sure switch. Switch must open with low pressure. The parameters are setup in the Alarm screen un­der the Production tab.
1. Press the Auger Run Time button.
2. Enter the board and input of the Auger run time relay. The parameters are setup in the Alarm screen under the Production tab.
Feed Lines
Water Pressure
Auger Run Time
34
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Press the Flush Feedback button. 2. Enter the board and input of the PDS flush feed-
back. The parameters are setup in the Alarm screen under the Production tab.
Flush Feedback
35
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Setup button from the Main Menu screen. Finally, select the House Button.
2. In this Screen you set what type of ventilation is being used in the House.
3. Temp. Influence on Minimum Ventilation. Select this box if you want the Min. Vent Timer to ramp up & down based on temperature. See
explanation and example below.
Ventilation timer ramping- If the sensor(s) that are assigned to the Minimum Ventilation fan(s) tem-
perature is at or below set temperature then the fans will use the ON and OFF times that are listed for the Minimum Ventilation Timer. If the sensor (s) assigned to the Ventilation Time Ramping tempera­ture is between set temperature and the fans' ON temperature the control will adjust the amount of ON time between the Min Ventilation value and the Max value. The OFF time will be adjusted by the same amount of time that the ON is adjusted, thus keeping the total cycle time constant. The temperature is checked 30 seconds before the beginning of the ON time cycle of the Minimum Ventilation Timer. Once the fans' temperature sensor(s) reach the fans' ON temperature, the fan will turn on and run con­tinuously until the fans' OFF temperature is reached.
Example:
The set temperature is 70.0°F and the fans assigned to the Min Vent timer ON temperature is 72.0°F. The Minimum Ventilation Timer values are 30 seconds ON time and 270 seconds OFF time. The max­imum ON time is 210 seconds. If the sensor(s) assigned to the Ventilation Time Ramping temperature is 71.0°F at the beginning of the anticipation cycle, then the fans will have an ON time of 125 seconds and an OFF time of 175 seconds.
4. Mortality Select this box if you want to keep track of the Mortality. To separate male and female select Separate Male Female.
Setup House
36
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Setup but-
ton from the Main Menu screen.
2. Press the Outputs button Some of the buttons on this screen may be grayed out at this point of the setup.
1. Press the Outputs button Some of the buttons on this screen may be grayed out at this point of the setup.
2. Press the Equipped/Numbers button Some of the buttons on this screen may be grayed out at this point of the setup.
3. In this screen the Control is told what equip­ment it is connected to: Fans, Curtains, Inlets, clock type and backup relays. The Nbr. Of Out­puts column is read only and will be filled in as Setup continues.
4. Select the Back button to return to the Setup/Output screen.
Continued to next page.....
Output Assignments
Outputs-Equipped/Numbers
37
MT2398C
Control Setup Chore-Tronics® 3 Control
Notice that all the buttons are now active.
1. Select the Ventilation button.
2. Every Output needs to have a relay, mode of opera­tion (Power, Natural, Tunnel, or combinations of the three), and temperature sensor(s) assigned to it. Initial­ly when pressing the Cool, Exhaust Fan, Stir Fan, Tun­nel Fan and Heat Zone buttons only one output will appear.
3. Select the Tunnel Fans button.
Continue to next page.....
Outputs-Ventilation
Ventilation-Tunnel Fans
38
MT2398C
Refer to the Relay Assignment Decal (Inside the Relay Box) to assign relays to each of the fans.
2. Select the Relay dropdown to assign the proper Relay to each Tunnel Fan.
3. Select the Mode dropdown A list of available Modes will appear. Select the mode (modes) that the Fan needs to operate in.
Relay assignment Decal (inside Relay Box)
4. In the Sensors column select the senor/sensors to be assigned to the Fan. Touch the sensor win­dow and a select sensor box will appear with the avail­able sensors. Select or deselect the sensors to come up with the sensor or sensors to control the Fan. Select OK to save.
This completes Tunnel Fan 1.
5. To assign additional Tunnel Fans, select the Add button. The next fan will appear. Follow the same steps as used for Tunnel Fan 1 to assign the relay, mode, and sensor assignments.
Using the same steps continue to add Tunnel fans until finished.
Control Setup Chore-Tronics® 3 Control
39
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Ventilation button.
2. Select the Stir Fans button.
3. Assign Relays, Sensors and Mode values to the Stir Fans just as you did for Tunnel Fans. (See
previous page)
2. Select the Exhaust Fans button.
3. Assign Relays, Sensors and Mode values to the Exhaust Fans just as you did for Tunnel Fans.
(See Tunnel Fans previous)
1. Select the Ventilation button.
Ventilation-Stir Fans
Ventilation-Exhaust Fans
40
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Ventilation button.
2. Select the Variable Fans button.
3. Assign Sensors and Mode values to the Variable Speed Fans.
4. Assign the analog output from the dropdown.
5. Assign the Output Form- You will need to know the input range of the Frequency drive before choosing 0-10 or 10-0 vdc from the dropdown.
5. Assign the Output Form- You will need to know the input range of the Frequency drive before choosing 0-10 or 10-0 vdc from the dropdown.
5. Press the Control Tab
6. Enter the amount of startup time needed to open the fan shutters.
Example: If 5 is entered, the Variable speed fan will run at full speed for 5 sec. at startup, then return to the current speed.
Ventilation-Variable Fans
Note: The Var. Speed output is a 0-10 or 10-0 vdc output on the IO board not the Relay box.
41
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Ventilation button.
2. Select the Cool button to assign the Cool outputs..
3. Assign Relays, Sensors and Mode values to each Cool item.
Relays
Mode
Sensors
Ventilation-Cool
The Cool outputs can be used for cool pads, fogger pads and or inside foggers. The Cool output can be setup to be on/off based the temperature setting in the Output & Temperature. A t
imer can be assigned to the Cool output. If a timer is assigned, at the on temperature the output will start timing on/off based on the timer setting and will not run constant.
Sixteen Cool outputs can be assigned up to four relays per Cool output.
42
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Ventilation button.
2. Select the Cool Pad button to assign the Cool Pad outputs.
3. Assign a Relay, Sensors and a Mode value to the Cool Pads.
Ventilation-Cool Pad
The COOL PAD output is very different from a COOL output.
It is not intended that the COOL PAD output and the COOL output would be used together, but it is possible. Both outputs are there to give the user the choice on which type of output to use. The COOL PAD's relay operation is designed to begin the cooling caused by the cooling pad by first adding 5 seconds of water to the pad every 5 minutes. If the temperature is still with the "Cool Pad Range" after 4 doses of 5 seconds of water, the amount of water added to the pad every 5 minutes remains the same. If the temperature is above or below the temperature limits of the "Cool Pad Range", the amount of water "on" time each 5 minutes is increased or decreased 5 seconds. With the default settings the temperature is only checked every 20 minutes. If it is desired for the temperature to be checked more often if a sudden large temperature change occurs, then values should be entered in the "Extra aggressive if" lines (Items and , Figure ). For example, The Control is set to be extra aggressive if 3.0 degrees above the upper limit of the COOL PAD range. Whenever the temperature is more than 3.0 degrees above the upper limit of the COOL PAD range the Control will begin checking the temperature every 5 minutes (every repetition rate) instead of every 20 minutes (every 4 repetition rates) until the temperature returns to less than 3.0 degrees above the COOL PAD range. The default extra aggressive settings are 3 degree.
43
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Control Tab.
2. Measure the number of seconds it takes for water to start
coming out of the holes in the pad system's top distribution pipe after turning on the COOL PAD manual toggle switch. This should be entered as the "Water pre-fill time" (Item 2, right) and is likely to be different for the different system manufacturers. This amount of time is added to the water run time each repetition because the top distribution pipe drains out during the off time of the on-off cycle.
Important!! The parameters that determine exactly how the COOL PAD function reacts are programmed in two separate screens, (Setup/Outdputs/Ventilation/Coolpad and Ventilation Set­ting/CoolPad). Chore-Time strongly recommends that the factory default settings be used, un­less poor control of temperature during pad operation is noticed. Chore-Time also recommends that CTB service personnel is contacted before changing the settings.
2
3. Measure the number of seconds it takes for water to start dripping out the bottom of a dry pad after the COOL PAD manual toggle switch is turned to the on position. This amount of time should be entered as the "Time to wet dry pad" (Item 3, above). This will be less than the time to make the pad completely soaked. When the actual water on time reaches this "Time to wet dry pad" value, the next step is to run the water continuously, assuming that the temperature is above the Cool Pad Range at the next temperature
3
4
4. If water running on the pad continuously is not desired, then the "Max water allowed" value (Item 4, right) should be changed so that it is less than the repetition rate time. Once the temperature decreases back below the Cool Pad Range, the ac­tual water on time will return to the "Time to wet dry pad" value again. From there the water on time changes in the normal way, with 5 second changes every 20 minutes, depending on the temperature check points.
5
5. The "Actual water on time" is for information only. Showing the value makes it possible to cre­ate a graph of it's variations if you have the PC connection (C-Central). The "Flush cool pad", (Item 5, previous page) is a feature that allows you to run the water continuously at a time of day each day for the duration you specify. This will guar­antee that at least once a day the pad will be flushed to keep it as clean as possible and help lengthen the pad life. Leaving dashes for the settings disables this feature. Flushing the pad in the night will have the advantage of causing very little unwanted temperature drop.
On a very hot day it would be possible for the water to be running continuously and the temperature to be in the "Cool Pad Range". A more moderate day might result in the water running a very small amount of time in order to keep the temperature within the "Cool Pad Range". Similarly, on a low humidity day the amount of water required to keep the temperature within the "Cool Pad Range" would be less than for a high humidity day. The Control will adjust the water as required to keep the temperature in the "Cool Pad Range". If it is desired to not allow the water to run continuously, then the Max water allowed (Item 4, Below) value should be changed so that it is less than the repetition rate value.
44
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Heat Zones button.
3. Assign Relays, Sensors, Mode values and Names just as you did for Tunnel Fans. (See pre-
vious)
3. Select the Control Tab.
4. Select the box if you do not want the Heat Zones to run in Tunnel assist.
1. Select the Ventilation button.
1. Use the Back button to get to the Setup/Out­puts screen and push the Curtain Button.
Ventilation-Heat Zones
Curtain
45
MT2398C
Control Setup Chore-Tronics® 3 Control
2. In this screen you will assign Relays to any and all of the air inlets connected to the Control.
3. Select Sidewall Inlet
Once you enter in the Open relay number the Control will automatically enter the Close relay. Two inlet machines can be assigned to the Sidewall inlet output. Both machines will be given an open or close signal at the same time.
Note. The Open and Close outputs must always be side by side on the same relay row.
4. Select the Control tab and choose Calculated or Fixed Anticipation.
Calculated Inlet Anticipation– The Control determines the amount of time the Inlets will open prior to the Fans assigned to the Minimum Ventilation timer turn on at a given static pressure control limits. (Screen not shown)
Fixed Inlet Anticipation- The amount of time the Inlets will open prior to the Fans assigned to the Minimum Ven­tilation timer turn on.
Open Relay Number
Close
Relay Number
Sidewall Inlet
46
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Use the Back button to get to the Setup/Out­puts screen and push the Tunnel Inlet Button.
2. When you enter in the Open relay number the Control will automatically enter the Close relay.
Up to four machines can be assigned to the Tunnel inlet output. All machines will be giv­en an open or close signal at the same time. Note. The Open and Close outputs must al­ways be side by side on the same relay row.
Open Relay Number
3. Press the Control Tab
4. These numbers are needed for proper Mode transitions. (Power to Tunnel and Tunnel to Power).
Full Movement
Measure the full movement of the Curtain or Tunnel door and enter that number in the FULL Movement edit box.
Tunnel Speed
With a closed inlet measure 18 inches of the tun­nel curtain or door movement. Toggle the open relay switch to the Manual position. Time how long it takes to move the the Inlet 18 inches. Enter that number in to the Tunnel Speed edit box.
Tunnel Inlet
47
MT2398C
Control Setup Chore-Tronics® 3 Control
2. Press the Clock button. All of the Clock output Relays are assigned here.
1. Select the Main menu button. Select the Setup button from the Main Menu screen. Finally, select the Outputs button.
1. Press the Light button.
2. Up to four Light clocks can be assigned
with four relays for each Light clock. Use the Add button to add additional clocks.
External Light Dimmer Control
3. In the "An Out" column, select from the drop-
down the Analog out (on the IO board) used to control the Dimmer.
4. In the Output from column select ether 0-10 vdc or 10 to 0 vdc. ( 0 vdc = no light or 10 vdc = no light)
2
3
4
Clock Assignments
Light Clock
48
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Press the Feed button.
2. Enter the Relay or Relays that the feeders
have been wired to. Only one Feed clock can be assigned with up to four relays. All four re­lays will be activated at the same time.
3. Select the Control Tab.
4. If the you wish to turn the Fill System OFF, check the box.
If a Dry Contact Relay whose coil is energized when the fill system's Hopper Level Switch calls for the fill system to run is connected to a digital input of the Control Then the Control can be set to detect excessive fill system run time and activate the Alarm Relay.
Feed Clock
49
MT2398C
Control Setup Chore-Tronics® 3 Control
2. The Spare Clocks have 8 on and off events and cannot be curved. A maximum of 8 Spare Clocks can be used, with up to four Relays per Clock. To add additional Spare Clocks to the list, select the Add button. Each Spare Clock can be given a specific name to identify the Clock with a particular use. Enter the Relay number (s) For each Clock in the list and change the name if needed.
1. Press the Spare button.
Four Relays per Clock
Clock Name (editable)
Select "Add" to add Clocks
Spare Clock
50
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Setup button from the Main Menu screen.
2. Press the Outputs button.
3. Press the Miscellaneous button.
4. select the Backup button.
5. Assign a Backup relay from the drop­down list of avalible Relays.
Backup Relays are needed when the Chore-Tronic's Standard or Expanded backup is installed for backing up the Control. If the the brain of the Control goes down for any reason, the Backup Re­lay will open, and the first stage of backup will be activated. See backup wiring di- agram in the Backup installation manu­als. Part # MT1805A of MT1561b
Miscellaneous Outputs
Backup Relay
51
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Setup but­ton from the Main Menu screen.
2. Select the Sensor button.
Verify Relay Assignments
After assigning all the outputs, verify the Relay assignments with the Output Stickers on the Manual Toggle Switches.
Manual Toggle Switches
Feed Clock 1 Feed Clock 2 Feed Clock 3
Relay Assignments (Inside Cover of Relay Box)
Assignments
Sensors
52
MT2398C
3. Power Mode- The temperature sensor (s) assigned here will determine what the control will use to transition from Power to Tunnel mode.
4. Temp. Influence On Minimum Ventilation The temperature sensor (s) assigned here will determine the amount of time added or subtracted away from the Minimum Ventilation timer in Power mode. For this feature you must first check the box in the (Setup/house screen) for Temp. Influence On Minimum Ventilation.
Ventilation timer ramping­If the sensor(s) that are assigned to the Minimum Ventilation fan(s) temperature is at or below set tem­perature then the fans will use the ON and OFF times that are listed for the Minimum Ventilation Tim­er. If the sensor (s) assigned to the Ventilation Time Ramping temperature is between set temperature and the fans' ON temperature the control will adjust the amount of ON time between the Min Venti­lation value and the Max value. The OFF time will be adjusted by the same amount of time that the ON is adjusted, thus keeping the total cycle time constant. The temperature is checked 30 seconds be­fore the beginning of the ON time cycle of the Minimum Ventilation Timer. Once the fans' tempera­ture sensor(s) reach the fans' ON temperature, the fan will turn on and run continuously until the fans' OFF temperature is reached.
Example: The set temperature is 70.0°F and the fans assigned to the Min Vent timer ON temperature is 72.0°F. The Minimum Ventilation Timer values are 30 seconds ON time and 270 seconds OFF time. The maximum ON time is 210 seconds. If the sensor(s) assigned to the Ventilation Time Ramp­ing temperature is 71.0°F at the beginning of the anticipation cycle, then the fans will have an ON time of 125 seconds and an OFF time of 175 seconds
34
Control Setup Chore-Tronics® 3 Control
53
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Setup button from the Main Menu screen.
2. Select the Function button.
4. Stir Timer Delay time (sec) Enter the amount of time you want the Stir fans to delay after the Min.Vent. fans have turned off.
In screen Setup/Output/Equipped, Stir fans must be checked, and at least one Relay assigned in the Setup/Outputs/Ventilation/Stir Fans screen to use this feature.
3. Alternate Min Vent Fans
(Select if you want feature)
The Min Cycle (Alternate Minimum Ventilation fans) allows the fan(s) assigned to the Min Vent Timer to alternate with the fans assigned to the Min Cycle. In the above example, Exhaust Fans 1 and 2 will run on the Min Vent timer first. At the next ON time of the Min Vent Timer the fans assigned Exhaust Fans 3 and 4 (the fans assigned to the Min Cycle) will run. The feature will stop when the fans as­signed to the Min Vent Timer turn on due to tem­perature.
3
4
Function
54
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Ventilation Settings button.
2. Select the Set Temp Timer button.
Note: Only the values with a white background are editable. All other boxes are information only.
3. Set temperature Set Temperature is a very important pa­rameter. All other temperatures are de­pendant on the set temperature. When the set temperature is changed, all other tem­perature settings are also changed by the same amount to maintain the same tem­perature differences relative to the set temperature.
4. Day
Day is the age of the animals or birds. Changing the age with Set temp and or Min Vent curve on will change their values to the current curve values.
3
4
5. Current Min.Vent. ON Time
Current Min. Vent. ON Time is the current amount of ON time the fans assigned to the Minimum Ventilation Timer will run while cycling on the timer. This amount of time compines both Tem­perature and if being used RH influence. If (TMP) is displayed the Min. Vent. Fan (s) are on by temperature.
6. The status of the Set Temperature and Min Vent curve and curve values are displayed at the
bottom of this screen.
The Temp Curve and Min Vent Curve "on" indications are not editable. They only indicate that the curve(s) are "on" and the curve's value. If a curve is not "on", there is no indication in this area. The values shown at the bottom of the screen are the current curve's values. If the actual values are different, the difference represents the "offset". Editing the actual values to be the same as the values displayed at the bottom of the screen will erase the offset(s). An "offset" is caused if you change a value when its curve is on.
5
6
Ventilation Settings
Set Temp Timer
55
MT2398C
7. Current Stir ON Time
Current Stir ON Time is the current amount of Stir On Time. If (TMP) is displayed the Stir Fan (s) are on by temperature. The "stir on" Timer is different than the other Timers. It can only be at­tached to Stir Fan Outputs in the "Out­puts" screen. The "stir on" time value is set in this screen. The purpose of this feature is to allow you to cause a Stir Fan Output to run for the "stir on" amount of time immediately following the end of the Minimum Ventilation Timer's "on" time. Because of this, the Stir Fan is synchronized with the min­imum ventilation Timer. The "stir on" setting can be any value up to the "off" time of the minimum ventilation Tim­er. The Stir Fan Outputs will come on full when the temperature rises to the "on" temperature val­ue set in the "Outputs and Temperature" screen.
8. Temp. Influence
is the amount of time added by Ventilation timer ramping- If the sensor(s) that are assigned to the Minimum Ventilation fan(s) temperature is at or below set temperature then the fans will use the ON and OFF times that are listed for the Minimum Ventilation Timer. If the sensor (s) assigned to the Ventilation Time Ramping temperature is between set temperature and the fans' ON tem­perature the Control will adjust the amount of ON time between the Min Ventilation value and the Max value. The OFF time will be adjusted by the same amount of time that the ON is adjusted, thus keeping the total cycle time constant. The temperature is checked 30 seconds before the be­ginning of the ON time cycle of the Minimum Ventilation Timer. Once the fans' temperature sen­sor(s) reach the fans' ON temperature, the fan will turn on and run continuously until the fans' OFF temperature is reached.
78
Example: The set temperature is 70.0°F and the fans assigned to the Min Vent timer ON temperature is
72.0°F. The Minimum Ventilation Timer values are 30 seconds ON time and 270 seconds OFF time. The maximum ON time is 210 seconds. If the sensor(s) assigned to the Ventilation Time Ramping temperature is 71.0°F at the beginning of the anticipation cycle, then the fans will have an ON time of 125 seconds and an OFF time of 175 seconds.
9. RH Influence
The actual amount of influence time the RH function is adding to the minimum ventilation timer. The Control may not always add the full amount of time if the amount of influence would add up to be more than the maximum allowed.
9
Control Setup Chore-Tronics® 3 Control
56
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Min Ventilation Timer
Min Ventilation Timer can be attached to Exh Fan, Tun Fan, and Stir Fan Outputs in the "Outputs" screen. The "on" and "off" times for this Timer are set up here in there. The Timer turns the Fan on or off when the temperature is below the Fan's "on" temperature. A Timer can only be attached to a Tun Fan Output if the "on" tem­perature setting of the Tunnel Fan is set lower than the "on" temperature of the Tunnel Mode. Allowable "on" times for this Timer are 0 or greater than 30 seconds (5 through 29 sec­onds is only allowed if fixed Anticipa­tion is used). Allowable "off" times for this Timer are 0 or greater than 60 seconds (1 through 59 seconds is not allowed). The "on" and "off" times cannot both be set at 0.
2. Max Ventilation On Time
Max Ventilation On Time-The maxi­mum amount of ON time the fans as­signed to the Minimum Ventilation timer can run before reaching the fans' ON temperature. The maximum allowed value for the Max Ventilation On Time is the amount of ON time (seconds) + the amount of OFF time(seconds) of the Min Vent timer - 60 (seconds).
3. Timers 1 and 2 Timers 1 and 2 can be attached to Cool, Tun Fan, Exh Fan, and Stir Fan Outputs in the "Outputs/ Temperature" screen. The "on" and "off" times for these Timers are set in this screen. These Timers behave like the minimum ventilation Timer except when they are attached to a Cool Output. When attached to a Cool Output, the timer has no effect until the Cool Output is "on" due to it's temperature settings. At that point the Cool Output goes on and off with the Timer. The Cool Output never comes on continuously when Timer 1 or Timer 2 is attached to it. There are no limitations to the "on" and "off" settings for Timer 1 and Timer 2 except that the "on" time and "off" time cannot both be set at 0.
4. Stir Timer is different than the other Timers. It can only be attached to Stir Fan Outputs in the "Outputs" screen. The "stir on" time value is set in this screen. The purpose of this feature is to allow you to cause a Stir Fan Output to run for the "stir on" amount of time immediately following the end of the Mini­mum Ventilation Timer's "on" time. Because of this, the Stir Fan is synchronized with the minimum ventilation Timer. The "stir on" setting can be any value up to the "off" time of the minimum venti­lation Timer. The Stir Fan Outputs will come on full when the temperature rises to the "on" temper­ature value set in the "Outputs" screen
5. Status Status-The status column shows the current status of each of the timer. If the Status is ON then the timer is active and the Output(s) currently assigned to that timer should be running. If the Status is OFF, then the timer is active, but the Output(s) assigned to that timer should NOT be running. If the Status is "-" or "tmp", then the timer is not currently active and the Output(s) assigned to that timer may or may not be running (depends on the type of Output due to temperature). If there is a NA (not active) in the Status column then the timer is not assigned to any Outputs and will not be active.
Timer Settings
5
2
1 3 4
57
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Ventila­tion Settings button.
2. Select the Static Pressure button.
3. Current Static Pressure- The amount of static pres­sure currently measured by the Control.
4. Current Static Pressure Limits- The Current SP Lim- its are the current high and low limit settings the Control is using to control the inlets or tunnel curtain.
5. Static Pressure Control Limits- The Static Pressure Control limits are the values of static pressure the Control attempts to maintain by using the powered Inlets, the Tunnel Curtain, or both. A second level of Power Mode static pressure can be chosen in the (Setup/Analog Inputs/Static Pressure) screen in the Control tab. The temperature at which the second static pressure takes over is entered in the (Output/Temperature) screen. The Tem­perature Sensor(s), (Inside Only), that measure that temperature is defined in the (Setup/Ana­log Inputs/Static Pressure) screen.
6. Fixed Inlet An ticipation- Fixed Inlet Antic- ipation is the amount of time the inlets will open prior to the fans assigned to the Minimum Ventilation timer turn on. Fixed inlet anticipa­tion must be selected from the (Setup/Analog Inputs/Static Pressure) screen in the Control tab.
7. Wind Delay- The wind delay is the amount of time the static pressure has to be continuously outside of the Control limits before the appropriate open or close Relay will be energized to bring the static pressure back within the control limits. The wind delay is bypassed if a Fan or Fans turning on or off is what causes the static pressure to move outside the Static Pressure Control limits
5
3
4
6
7
Static Pressure
The Static Pressure screen indicates the current static pressure plus provides the fields that can be edited to set the Static Pressure Control limits and the wind delay. The open and close Inlet Relays respond as required to keep the static pressure within the Control limits while in the Power Mode and the open and close Tunnel Curtain Relays do the same to control the static pressure during the Tunnel Mode. If it is not desired to control the static pressure during the Tunnel Mode, the high control limit in the Tunnel Mode must be edited to be .00. Static Pressure Control w/ Tunnel Curtain during Power Mode-If in the Power Mode, there is inadequate inlet area to keep the static pressure within the high control limits, the Tunnel Curtain will open to give additional air inlet area. The Inlets are given continuous open signals as the Tunnel Curtain takes over the responsibility of controlling the static pressure. The static pressure has to be above the high Static Pressure Control limit continuously for one minute with 3 or more Fans running for this to happen. Responsibility for Static Pressure Control is passed back to the Inlets as soon as there are fewer than 3 Fans running or the Tunnel Curtain cannot bring the static pressure back into the control range (while closing) from the low side. The static pressure has to be below the low Static Pressure Control limit continuously for one minute for this to happen.
58
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Venti-
lation Settings button.
2. Select the Cool Pad button.
3. Measure the number of seconds it takes for water to
start coming out of the holes in the pad system's top dis­tribution pipe after turning on the COOL PAD manual toggle switch. This should be entered as the "Water pre-fill time" (Item 3) and is likely to be different for the different system manufacturers. This amount of time is added to the water run time each repe­tition because the top distribution pipe drains out during the off time of the on-off cycle.
4. Measure the number of seconds it takes for water to start dripping out the bottom of a dry pad after
the COOL PAD manual toggle switch is turned to the on position. This amount of time should be en­tered as the "Time to wet dry pad" (Item 4), This will be less than the time to make the pad completely soaked. When the actual water on time reaches this "Time to wet dry pad" value, the next step is to run the water continuously, assuming that the temperature is above the Cool Pad Range at the next tem­perature check point.
5. If water running on the pad continuously is not desired, then the "Max water allowed" value
(Item 5), should be changed so that it is less than the repetition rate time. Once the temperature de­creases back below the Cool Pad Range, the actual water on time will return to the "Time to wet dry pad" value again. From there the water on time changes in the normal way, with 5 second changes ev­ery 20 minutes, depending on the temperature check points.
6. Actual water on time- For information only. Showing the value makes it possible to create a graph
of it's variations if you have the PC connection (C-Central).
Setup/Outputs/Ventilation/Coolpad Screen...
3
45
6
Cool Pad
The parameters that determine exactly how the COOL PAD function reacts are programmed in two separate screens, (Setup/Outdputs/Ventilation/Coolpad and Ventilation Setting/CoolPad). Chore-Time strongly recommends that the factory default settings be used, unless poor control of temperature during pad operation is noticed. Chore-Time also recommends that CTB service personnel is contacted before changing the settings.
59
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Ventilation Settings button.
2. Select the Cool button.
3. Cool Outputs Disabled Above RH- If there are relays assigned to cool output(s), and a relative hu­midity sensor is connected to the Control, the Con­trol can block the cool output from turning on if the relative humidity sensor reading is higher than en­tered value.
4. Allow Cool From- User can also specify a specific time of day in which the cool outputs are allowed to operate. A setting of 12:00a to 12:00a means that the cool outputs are allowed to operated 24 hours per day.
5. Do Not Allow Cool To Go Below- Outputs can have a minimum temperature setting. If the cool or Cool Pad outputs reach this minimum temperature due to the set temperature changing the outputs will not go below this minimum tem­perature even though the set temperature may continue to lower due to the set temperature curve.
34
5
Cool Setting
60
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Ventilation Settings button.
2. Select the Air Speed Tunnel button.
3. Selecting Airspeed Control in Tunnel­To activate put a Check Mark in the Box as shown. This function is used to maintain a minimum airspeed while in Tunnel mode. After making the transition from Power to Tunnel mode, the Control will turn on enough Fans until the airspeed reaches the speed entered in the Start turning on Fans Be­low line above. When coming out of full tun­nel, the Control will continue to allow fans to turn off according to temperature until the airspeed reaches the number entered in the
Start turning Fans off line (Item 1, Right).
Example: Using the settings above, when the Control completes the transition to Tunnel Mode, the
Control will check to the airspeed to make sure it at or above the Start turning on Fans Below setting. It will turn on Fans until the minimum airspeed is reached. The Control will stop allowing Fans to turn off once the airspeed drops below the number entered in the "Start turning off Fans" box (Item 2,
above). It will maintain that airspeed until the control reaches the Tunnel Off temperature.
Deselecting Airspeed Control in Tunnel-
Enter the minimum number of Tunnel Fans needed in Tunnel. The number of Fans entered will stay on until the control transition back to Power, overriding the fans off temperature setup in the (Outputs/Tem­perature) screen. The tunnel fans picked will be the first Tunnel fans in the(Outputs/Temperature) setup.
2
1
Airspeed Tunnel Settings
61
MT2398C
Control Setup Chore-Tronics® 3 Control
3. Current Speed- is the current speed in percent and can
hot be edited.
4. Variable Speed Maximum- Enter the maximum speed in percent that you want to operate
the Var. Speed fan.
5. Variable Speed Minimum- Enter the
minimum speed that you want the operate the Var. Speed fan.
1. Select the Main menu button. Select the Ventilation Settings button.
2. Select the Variable Speed button.
3
4
5
Variable Speed Settings
62
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. Select the Ventilation Settings button.
2. Select the RH Influence button.
3. Actual Influence- The actual amount of influence time the RH function is adding to the minimum ventilation timer. The con­trol may not always add the full amount of time if the amount of influence would add up to be more than the maximum allowed setup in the (Ventilation Settings/Set Temp) screen.
5. Low Control Limit- If the RH in the house is below this setting than the control will subtract an increment of on time to the minimum ventilation timer down to the minimum setting is (Ventilation Settings/Set Temp) screen.
Note: If the RH is between the High and Low Control limit, then the control will neither add or subtract on time to the minimum ventilation timer. The RH is check 30 seconds prior to an ON time cycle of the minimum ventilation timer.
4. High Control Limit- If the RH in the house is above this setting than the control will add an increment of on time to the minimum ventilation timer up to the maximum amount of influence allowed or the maximum possible amount of ventilation on time that is set in the (Ventilation Settings/Set Temp) screen.
3
4
5
RH (Relative Humidity) Settings
63
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Curves Button.
3. Select the Set Temp button.
There are several terms that need to be defined in order to understand the Set Temperature Curve
Screen.....
4. A "curve" is a listing of up to 10 points
in time (bend points) that defines how you want a parameter to automatically vary as the animals grow. Turn curves on here.
5. Curve Value- This indicates the current
value(s) of the specified curve.
6. The Bend Points (BPs)- are points on
the curve that define the curve. The curve values are adjusted between the Bend Points. The bend point values are the exact values at midnight of the day # of each Bend Point. The curve takes over when you turn the curve "on" and the day number is equal to or greater than the day number assigned to BP #1.
7. Day- The intention is that the day # is age of the animals. Negative days (down to - 7) are allowed
if it is desired to preheat the house, for example, prior to the arrival of the animals. The day # of a BP can also be negative, if desired. Changing the day # in any screen that shows the day number, will change the day # in all the other screens that show the day #.
8. Temperature- is the temperature you want the Set temp.to be at 12:00am on a specific day. Based
on the bend points setting the temperature increase or decrease between bend points.
9. The graphs on the right side of Set temperature screen shows the progress of the curve. The dashed
line indicated the current day number of the curve.
4 5
6
7 8
9
Curves
Curves/Set Temp
64
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Curves Button.
3. Select the Min Vent button.
There are several terms that need to be defined in order to understand the Minimum Ventilation Curve
Screen.
4. A "curve" is a listing of up to
10 points in time (bend points) that defines how you want a parameter to automatically vary as the animals grow. By turning the curve "on" the Control will follow the curve settings .
5. Curve Value- This indicates
the current value(s) of the specified curve.
6. The Bend Points (BPs)- are
points on the curve that define the curve. The curve values are adjusted between the Bend Points. The bend point values are the exact values at midnight of the day # of each Bend Point. The curve takes over when you turn the curve "on" and the day number is equal to or greater than the day number assigned to BP #1.
7. Day- The intention is that the day # is age of the animals. Negative days (down to - 7) are allowed
if it is desired to preheat the house, for example, prior to the arrival of the animals. The day # of a BP can also be negative, if desired. Changing the day # in any screen that shows the day number, will change the day # in all the other screens that show the day #.
8. On and Off columns- are the Min. Vent. time for a specific bend point
9. The graphs on the right side of the Minimum Ventilation Curve screen shows the progress of the
curve. The dashed line indicated the current day number of the curve.
Minimum Vent Curve Settings
7
8
4 5
6
9
65
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Curves Button.
3. Select the Light Clock button.
4. Curves- Four different curves can be setup and assigned to four different Light clocks. For light
level spiking and for the use of independent clocks to control different light types (incandescent and fluorescent for example) within the house. Select the curve you want to setup from the drop down.
5. Bend Point- This is the current dis-
played bend point of the Light Clock Curve. Only one bend point can be shown at a time. Up to ten bend points can be used on each Curve. Select the Bend point you want to setup from the drop down.
6. Active From Day- This is the day that
current bend point will become the ac­tive light clock settings.
7. Events- The Control allows a maxi-
mum of 24 events. Each event the user chooses whether the Relay (if used) assigned to the clock turns on or off, what the dimmer (if used) level setting should be at the time of the event and how long it should take to get to that dimmer setting (sunrise/sunset time).
4
5
6
7
8. Time- Enter the time of day.
9. Relay- Turns the relay assigned to the Light clock that the curve has been as­signed to on or off.
10. Enter the amount of time you want to ramp up or down the output to the Dim­mer. If OFF is selected in the relay column the lights will be turned off with no ramp­ing.
11. Dim perc- Enter the percentage of light level wanted.
See Next Page for Example.....
8 9
10 11
Light Clock Curve Settings
66
MT2398C
Example: In the example (right), the lights will turn on at 5:00a and will take 15 minutes to go from 0 percent light to 70 percent light. At 9:00a the lights will take 5 minutes to "spike" up to 100 percent. At 10:00a the light spike is removed immediately (no sunset time) and the lights return to 70 percent. At 10:00p the lights are immediately turned off.
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Curves Button.
3. Select the RunFor Clock button.
4. Curves- Four different curves can be setup. Select the curve you want to setup from the drop
down. The curves are assigned to the Feed clock in the (Clocks/Feed/Feed Clocks) screen.
5. Bend Point- This is the current dis­played bend point of the Light Clock Curve. Only one bend point can be shown at a time. Up to ten bend points can be used on each Curve. Select the Bend point you want to setup from the drop down.
6. Active From Day- This is the day that the current bend point will become the active light clock settings.
7. Events- A maximum of 24.
8. On-at- Enter the start time of the feeding in
this column.
9. Off-at- Enter the off time of the feeding. This column allows the user to enter a time down to the second for operating feeders that only need to run for (mins. /sec or stimula­tions).
10. Run-for- Shows the amount of feeding time per Event.
4
5
6 7
RunFor Clock Settings
67
8 9 10
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Management Button.
3. Select the Mortality button.
4. Picked Up- The number of dead and culled animals collect­ed is entered on the Picked Up line. Select the Agreed button and the number(s) entered in the picked up line will be added to the Today and the Accum lines. The %Mort and the Curr (Current) Housed will be recalculated. The total daily mortality will also appear in the Daily History­Production screen.
5. Agreed- When the Agreed button is selected, the number(s) entered in the picked up line will be added to the Today and the Accum lines, the % Mort and the Curr (Current) Housed will be recalcu­lated, and the total daily mortality will also appear in the Daily History-Produc­tion screen.
6. Partial Taken Out- This is used if live birds/animals are removed for any reason other than dead or culled.
7. Initial Housed number- must be entered first.
4
5
6
7
Management Screens
Mortality Screen
68
MT2398C
7. If Males and Females are being entered sepa­rately, use the tab buttons toggle between the Male, Female and Total Screens. When Male and Female Mortality is entered separately, the Total Mortality Screen is a summary of the Male and Female screens and is non-edit­able. See the Setup/House screen from the Main menu to tell the Control to keep track of Male and Female Mortality separately.
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Management Button.
3. Select the Water button.
4. Water Consumed Previous- This num-
ber can be 1 to 60 minutes.
5. Water Cumulative Per- Select from drop
down 1, 100 or 1000 birds.
6. Water Today Per- Select from drop
down 1, 100 or 1000 birds.
4
5 6
Water Screen
This screen will be available if a drinker line Water Meter is connected to the Control. This screen indicates the total water consumed in the house and how much water has been consumed in a certain period of time (for example, how much water was consumed in the house in the previous 5 minutes). If house mortality is being entered into the Control, then the total amount of water per 1000 birds (or per animal) will also be displayed.
69
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
3. Select the Flock button.
5. Growth Curve- Enter the Growth curve
for the type of bird you have. This can be entered by Day # or by Week # by select­ing from the drop down in the "Use" box.
4. Select the Standard button.
8. Enter the Setup Day number. This example shows Day 2.
7. Select the Setup button.
5
6. Click on the Back Button and select "Info".
9. Enter the Flock number.
10. Enter Initial Weight.
11. Setup Date- Enter the current weight of the birds.
12. Click on Agreed when you are done.
9 10
11
2. Select the Management Button.
8
Flock Setup
70
MT2398C
Control Setup Chore-Tronics® 3 Control
13. Select the Deliver Button.
14. Delivery Day (Optional)
15. Delivery weight- The measured live weight
in the slaughterhouse can differ from the wight readout on the CT3 Control. This difference in live weight can be caused by transport, animals having empty/full stom­achs, differences in the house, etc. Using this option can correct the difference and take this correction into account during the next flock.
1415
1. Select the Main menu button.
2. Select the Management Button.
3. Select the Flock button.
4. Select the Zero Calibration button.
4. Calibrate- Ensure that the weighing scale is
empty and select the Calibrate Button.
Flock Setup/Delivery
Flock Setup/Zero Calibration
71
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Management Button.
3. Select the Reset button.
3. Select the "OK" button.
All History will be lost!!
Management Reset Button
Selecting the Reset button from the Management screen will erase all management data.
Warning!! Once the Reset Button has been pressed it can not be reversed.
72
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Programs Button.
3. Select the Programs button.
Programs already programmed into the Con­trol.
You then can choose an action for each program
as follows: Activate Program Settings, Delete Program Settings, Save Program Settings, Yes­terday's Settings. This is a very powerful screen that allows the user to store up to 6 complete setups of the Control that can be re-activated at any time.
4
5. Select the Activate button from the Programs / Setup Key screen.
The Programs / Activate screen will open.
6. Select the desired saved program from the
drop down.
7. Select the OK button.
8. A window will open to ask you if you are sure you want to continue and that all control set­tings will be overwritten. Select OK to contin­ue with the activation or Cancel to cancel the activation of the program.
9. If OK is selected the control will restart with all the selected program settings.
Programs/Setup Key Screens
Programs Screen/ Activate
5
6
73
7
8
9
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Press the Programs Screen/ Programs Button
2. Programs Available- Choose from available Pro-
grams already programmed into the Control.
3. Choose Delete from action choices.
4. Select the OK button.
5. A window will open to ask you if you are sure you want to delete the selected program.
3
4
6. A window will open to ask you if you are sure you want to delete the selected program. Select OK to delete the program or Cancel to stop the operation.
This Does Not delete the current setting in the Control, just the saved program.
In the Program / Available screen Program 1 ( Brood ) has been removed from the list.
2
Programs Screen / Delete
6
74
MT2398C
Control Setup Chore-Tronics® 3 Control
2. Programs Available- Choose from available Pro- grams already programmed into the Control.
3. Choose Save from action choices.
4. Select the Program Number from the drop down. 1 - 6
5. Enter the Program Name. Ten characters or less.
6. Select OK to Save the program or Cancel to stop the operation.
7. A confirmation window will open letting you know that all the present settings will be stored in the selected program. Select OK to Confirm or Cancel to stop the operation.
1. Press the Programs Screen/ Programs Button
Program Screen / Save
2
3
4
5
6
7
75
MT2398C
Control Setup Chore-Tronics® 3 Control
2. Programs Available- Choose from available Programs
already programmed into the Control.
3. Select Yesterday from action choices.
1. Press the Programs Screen/ Programs Button
Every day at midnight, the settings of the Con­trol is saved which can be activated anytime during the following day. This can be helpful if a mistake in setup is made and it is desired to undo the changes and go back to Yesterdays settings.
4. Select OK from the Program / Yesterday screen.
A window opens letting you know that all the present settings will be overwritten and the Con­trol will restart.
5. Select OK to confirm or cancel to stop the opera-
tion.
4
6. The Alarm will be sent two messages, Power Failure and Program "X" Acti­vated. At this time notice the alarms and they will be sent to the Alarm his­tory. These are not hard alarms.
5
Programs / Yesterday
3
2
6
76
MT2398C
Control Setup Chore-Tronics® 3 Control
Setup Key Screen/ Activate
Insert a USB Flash Drive into the USB adaptor located on the lower left side of the main box. Unscrew the protective cap and plug-in the Flash Drive.
77
MT2398C
1. Select the Programs Button.
2. Select the Setup Key button. This screen is only available if a Setup Key (USB drive ) is inserted in the USB plug located on the lower left side of the Con­trol.
5. Transfer FROM Control TO Setup Key- Select the Transfer button to the left of Transfer FROM Control TO Setup Key to transfer all of the Controls settings to the setup key.
3
4
The Alarm will be sent two messages, Power Failure and Program "x" Activated. At this time you should notice the alarms and they will be sent to the Alarm history. These are not hard alarms.
3. Info Control- The current software level operat-
ing on the Control.
4. Info Setup Key- The software level of the contents stored on the Setup Key. The software level
stored on the Setup Key must match the current Control software level in order to transfer settings from the Setup Key to the Control.
6. Transfer From Setup Key to Control- Se-
lect the Transfer button to the left of Transfer From Setup Key to Control to transfer the settings currently stored on the Control to the Setup Key.
Control Setup Chore-Tronics® 3 Control
78
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the Clocks Button.
1. Select the Light button.
This screen displays all the Light Clocks assigned to re­lays and/or analog outputs. Each Light Clock button is as­signed to a particular Light Clock.
3. If a Dimmer is used the current light
level percent is displayed.
2. A number or icon is displayed to the left of the
Light clock buttons.
3
4. If no dimmer is used, the icon shows if the lights are On
or Off.
5. To access the settings for each Light Clock press
the desired Light button. Press the Light 1 button.
Clocks
The Clocks screen consists of the Current Light Clock, Current Feed Clock and Spare Clocks. The Lights and Feed Curves are assigned to their specific Clock in theses screens.
Light Clock
79
MT2398C
6. Name Clock- Is the current displayed
clock.
7. Events- The current number of events that
the Clock is using to control the lignts.
8. Use Curve- selecting On or Off from the
dropdown activates or deactivates the curve selected. If the light clock curve is set to ON, then the current light clock set­tings will not be editable. To temporarily change the current light clock settings, first set the curve to OFF, then make the desired changes. To return to the curve set­tings, change the curve back to ON.
678
Light Clock Curve Set "ON"
Light Clock Curve Set "OFF"
9. Time- Enter the time of day.
10. Relay: Turns the relay assigned to the Light clock that the curve has been assigned to on or off. This column will be blank if only an Analog output is assigned.
Control Setup Chore-Tronics® 3 Control
80
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
3. Select the Feed button.
4. This screen displays the Feed Clock settings link for the Feed clock.
5. The icon displayed to the left of the Feed button indicates if the feed output is on or off.
6. Selecting the Feed button will open Feed clock. Only one Feed clock is available.
7. Name Clock- Is the current dis­played clock.
8. Events- Is the current number of event the clock is using to control the Feeder.
9. Use Curve- selecting On or Off from the dropdown activates or deactivates the curve selected. If the Feed clock curve is set to ON, then the current Feed clock set­tings will not be editable. To temporarily change the current light clock settings, first set the curve to OFF, then make the de­sired changes. If the Use Curve is set to OFF, the Feed output will follow the settings displayed ever day until the Use Curve is set to ON then the output will follow whatever curve is selected.
10. On-at:- Enter the start time of the feeding in this column.
11. Off-at:- Enter the off time of the feeding. This column allow the user to enter a time down to the
second for operating feeders that only need to run for (mins. /sec or stimulations).
12. Run-for:- Shows the amount of feeding time per Event.
Feed Clock
2. Select the Clocks Button.
10
11
12
7 8
9
81
5
6
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
3. Select the Feed button.
4. This screen displays the Spare Clock settings links for the Spare clock. Up to eight Spare clocks.
5. Use the slide bar on the right to display the other Spare clocks if more than four Spare clocks are in use.
6. The icon displayed to the left of the Feed button indicates if the Clock Output is on or off.
Spare Clock Setup­Example:
7. Select the Spare Clock you wish to set up. In the example shown we chose Spare Clock 1.
8. Name Clock- Is the current displayed clock.
9. Events- Is the current number of event the clock is using to control the Feeder.
10. On-at: Enter the start time of the feeding in this column.
11. Off-at: 11. Off-at: Enter the off time of the feeding. This column allows the user to enter a time accurate to the number of seconds.
12. Run-for: displays the amount of time per Event.
2. Select the Clocks Button.
Spare Clocks
5
6
10
11
12
9 8
82
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the History button.
1. Select the Environment button.
History Number of days.
Mode Temperature 100 days Sensors (all assigned) 14 days Humidity House 14 days Heat Run Times 14 days
2. Select one of the tab buttons along the bottom to view that Tab’s History.
Note: Tabs that are grayed out have no history because no sensor has been installed.
3. Press the Mode Temperature Tab
4. Use the slide bar on the right to move history up and down.
5. Press the Sensors Tab Some of the history selections have more than one sensor. To select a Sensor, use the drop down as shown to the right.
Environment
Code Number of days. Water 14 days Feed 14 days Mortality 100 days Auxiliary 14 days Feed Lines 14 days
4
5
History
History-Environment
83
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button.
2. Select the History button.
3. Select the Production button.
4. To view production history for; Water, Feed, Mor­tality, Auxiliary, or Feed line, select the Tab at the appropriate Tab at the bottom of the screen. Water History has been selected in the example.
5. Use the Slide Bar at the right of the screen to scroll through the history.
Some of the history selections have more than one sensor. To view select the sensors from the drop drown in the upper left of the screen.
Note: Tabs that are grayed out have no history,
because no sensor has been installed.
1. Select the Main menu button.
2. Select the History button.
3. Select the Reset button.
4. If "OK" is selected, all History will be lost.
History-Production
5
History-Reset
84
MT2398C
Control Setup Chore-Tronics® 3 Control
1. Select the Main menu button. 2. Select the Setup button.
3. Select the Outputs button. 4. Select the Equipped/Numbers button.
5. Select both the Sidewall inlets
and Ceiling inlets check boxes. The number 1 will appear in the box to the right. This shows that at least one pair of relays are to be used. (Open/Close)
6. Select the Back button to
return to the Outputs Screen.
7. Select the Curtain button
8. Select the Sidewall Inlet button.
9. In the Setup/Outputs/Curtain/
Sidewall inlet screen select the re­lays that are to be assigned to the Sidewall inlets. Select the Open re­lay from the drop down and the Close relay will be assigned by the control. Only two sets of (Open/ Close) relays can be assigned. Ex­ternal relays must be used if there are more than two machines. Both sets of relays are operated at the same time.
Setting up Sidewall Inlets
5
9
85
MT2398C
10. Select the Control Tab at the bottom of the screen.
11. Inlet Anticipation- Select from the drop down Calculated or Fixed.
11a. If Fixed anticipation is chosen fill in the amount of time in seconds you want the inlets to anticipate.
11
11a
Control Setup Chore-Tronics® 3 Control
86
MT2398C
Control Setup Chore-Tronics® 3 Control
If continuing to setup Ceiling Inlets from the Sidewall screen above, select the Back button twice to return to the Setup/Outputs/Curtain Screen.
1. Select the Main menu button. 2. Select the Setup button.
3. Select the Outputs button. 4. Select the Ceiling Inlet button.
5. In the Setup/Outputs/Curtain/Ceiling Inlet screen select the relays that are to be assigned to the Ceiling inlets. Select the Open relay from the drop down and the Close relay will be assigned by the control. Only two sets of (Open/Close) relays can be assigned. External relays must be used if more than two ma­chines are installed. Both sets of relays are operated at the same time.
Continue Setup of the Attic Inlet by selecting the Control Tab...
6. Use Attic Air Sensors- Choose the inside sensor (s) you want to use as controlling sensors.
7. Inlet Anticipation- Select from the drop down Calculated or Fixed.
8. Controlled By- Select from the dropdown SP (Controlled by static pressure or Gravity) If Gravity is se­lected the Inlet anticipation Fix or Calculated will have no effect.
9. Allow Attic Air From- Enter the time of day you want to use the attic air to ventilate. In the example to
the right; Attic air can be used from 8:00am until 5:00pm.
Setting up Ceiling Inlets
5
7
6
9
8
87
MT2398C
Control Setup Chore-Tronics® 3 Control
Setting the parameters for the Ceiling Inlet is done in the Outputs and Temperature screen.
1. Select the Main menu button.
2. Select the Outputs and Temperature button.
3. In the output column you will see "Use Attic Air output".
4. To the left are an ON and Off temperature.
Example:
a) On temp of 84.2. All the air will come from the attic if the temperature of the sensor(s) assigned to
the Ceiling inlet is at or below the on temperature.
b) if the temperature of the sensor(s)
assigned to the Ceiling inlet is above the on temperature but at or below the Off temp of 85.2. and the static pressure stays above the high setting for one minute the Side wall inlets will open to main­tain the correct static pressure and allow the mixing of attic and out­side air.
c) If the temperature of the sensor(s)
assigned to the Ceiling inlet is above the Off temperature the Ceiling inlet will close. The Side­wall inlets may open or close to maintain the correct static pressure.
d) If the temperature drops below the ON temp the Sidewall inlets will close and the Ceiling inlets will
open to maintain static pressure. If the static pressure is above the high setting the Sidewall inlets will open to maintain the correct pressure.
Setting up Ceiling Inlet Parameters
a
3
b
88
MT2398C
Control Operation Overview Chore-Tronics® 3 Control
Control Operation Overview
Standard Mode Functionality
Power Mode
All curtain(s) are given a continuous close signal. Inlets are controlled by static pressure (if used). All outputs that are allowed to operate in Power Mode turn on and off per screen 4 trying satisfy their sensors assigned in Screen 13.
Natural Mode
Main Curtain Range- The Main curtain range is defined in the Outputs and Temperature screen (Screen
4) and has a default setting of + or - 1.5 degrees F of the set temperature. Once the Control has made the full transition from Power to Natural mode (or Tunnel to Natural), each main curtain's control sensor will either open or close the main curtain(s) to try to keep the sensor's temperature within the Main curtain range. If the curtain's control sensor temperature goes above the range then the curtain will open. If the curtain's control sensor temperature goes below the range then the curtain will close. The amount the curtain moves is based upon how far the curtain's control sensor(s) is from the AVERAGE of the Main curtain range. If the curtain's control sensor(s) goes more than 8 degrees F ABOVE the AVERAGE of the Main curtain range, the curtains will be given a continuous open signal until the temperature returns to within the Main curtain range. If the curtain's control sensor(s) goes more than 8 degrees F BELOW the AVERAGE of the Main curtain range the curtains will be given a continuous close signal until the temperature returns to within the Main curtain range or until the Control returns to Power Mode. The control returns to power mode when the main curtain(s) reach the first opening position (see Natural to Power Mode transition).
Time Between Curtain Movements
The Time between curtain movements is the amount of time the control will wait after an opening or closing of the main curtain(s) before checking the temperature again and doing another open or close movement. The default time between curtain movements is 2 minutes. The amount time between curtain movements can be set between 1 minute and 5 minutes. The time between curtain movements is set in Screen 14, Curtains tab.
Rate of Curtain Movement
The Rate of Curtain Movement is the amount the control will either open or close the curtain(s) during a curtain movement. The actual amount of curtain movement is calculated by taking the Rate of curtain movement and multiplying by the number of degrees the curtains control sensor is from the AVERAGE of the Main Curtain Range. For example, if the Rate of curtain movement is 1.2 inches per degree F, the AVERAGE of the Main Curtain Range is 74.0 degrees F and the curtains control sensor is reading 76.0 degrees F then the control will open the curtain 2.4 inches (1.2 x [76-74]). The default Rate of Curtain Movement is 1.2 inches per degree F and can be set between 1 in and 4 inches per degree F. The rate of curtain movement is set in Screen 14, curtains tab.
All Outputs that are allowed to operate in Natural Mode turn screen (Screen 4) trying to satisfy their sensors assigned in the Setup-General screen.
on and off per the Outputs and Temperatures
89
MT2398C
Control Installation Chore-Tronics® 3 Control
Note:
21" Min. 22" Min.
43" Min.
21" [53cm] Min.
Control Installation
Mounting the Control
56 Output Control Mounting
A 56 Output Chore-Tronics® 3 Control consists of a Main Box and a Relay Box. The Main Box requires a minimum mounting area of 21 in. [53 cm] x 21 in. [53 cm] (See Figure below).The Relay Box requires 22 in. [56 cm] x 27 in. [69 cm]. This dimension allows extra room for the control doors to open. The boxes should be mounted level and square on a solid backing using the mounting holes provided.
When mounting the Main Box and the Relay Box, make sure the two boxes are as close together as possible to reduce the likely hood of a communication failure. Make sure that the Relay Box is mounted so that the relay indicator lights are visible when standing at the Main Box.
1
Item Description
1 Main Box 2 Relay Box
Figure 11. 56 Output Control Mounting
2
27" Min.
90
MT2398C
Warning!
Control Installation Chore-Tronics® 3 Control
1
3
Item Description
1 Main Box 2 Relay Box 3 Jumper (In On Position) 4 I/O Net and 24Vdc Wire Routing Decal (Communication Wire)
2
Figure 12. I/O Net and 24Vdc Wiring (Communication Wire)
2527-72
COMMUNICATION WIRES
Route Main Box / Relay Box communication wires here.
24 Vdc +
24 Vdc-
IONET +
IONET -
ON OFF
4
Do Not run I/O Net or 24 Vdc Twisted Pair wire close to and/or parallel with line voltage wires. (See Figure 75)
The I/O Net terminals of the Main Box and the Relay box must be connected together using the Non-Shiel
ded
Twisted Pair Wire (Chore Time Part no. 42208) included within the Main Box. There is a Decal (Figure 11, Item
4) on the Main Box as well as the Relay Box showing the location to route the I/O Net wires (Communication Wires). I/O Net is polarity sensitive so be sure that the positive and negative I/O Net terminals of both the Main Box and the Relay Box are connected properly (See Figure 12). Make sure that the Jumper on the I/O Board is i n the ON position (See below). The 24 Vdc must also be connected from the Main Box to the Relay Box using the Twisted Pair wire included within the Main Box. Route the wires along with the I/O Net Wires according to the Communication Wire Decals (Item 4) on the Boxes.
91
MT2398C
Control Installation Chore-Tronics® 3 Control
90°
Line Voltage Wiring
Non Shielded Twisted
Pair Wire
Figure 13. 90° Crossover
Note:
Caution: Do NOT run 24 Vdc and I/O
Net wire close (120 Vac or greater) voltage wires. Doing so can cause operational failure in the Control and will void Warranty. If 24 Vdc or I/O Net wires need to cross line voltage wires make sure the wires cross at a 90 degree angle. Also, no other electrical devices such as transformers, light dimmers, additional relays, etc. should be mounted inside the Main Box or near the 24 Vdc power or I/O Net wires.
56 Output Controls
to and/or parallel with line
A 56 Output Chore-Tronics® 3 Control consists of a Main Box, two Relay Boxes, and an External Power Supply for the Second Relay Box. The Main Box and the Relay Box/s Each require a space of 21 in. [53 cm] x 21 in. [53 cm]. The External Power Supply requires 12" [30cm] x 15" [38cm]. These dimensions allow extra room for the Control doors to open. The boxes should be mounted level and square on a solid backing using the mounting holes provided.
21" [53cm] Min.
21" [53cm] Min.
1 2 3
When mounting the Main Box and the two Relay Boxes, make sure that the boxes are mounted as close together as possible to reduce the likely hood of a communication failure. Make sure that the Relay Boxes are mounted so that the relay indicator lights are visible when standing at the Main Box. (See Figure 14)
75" [190.5cm] Min.
21" [53cm] Min.
21" [53cm] Min. 12" [30cm] Min.
15" [38cm] Min.
4
92
Item Description
1 Main Box 2 Relay Box 3 2nd Relay Box 4 External Power Supply
Figure 14. 56 Output Control Mounting
MT2398C
Chore-Tronics® 3 Control Control Installation
Important!
1
2
3
4
Item Description
1 Main Box
2 Relay Box
3 2nd Relay Box
4 External Power Supply
5 Dip Switch #1 (In Off Position)
Figure 15. 56 Output Control Mounting
5
Caution:
terminals in all boxes are connected properly (Figure 15). Also make sure that DIP switch #1 on the IO board of the Main Box is
in the OFF position. 24 Vdc must be connected from the Main Box to the first Relay Box (relays 1-40) using the Twisted Pair Wire
The I/O Net terminals of the Main box and the two Relay Boxes must be connected using Non-shielded Twisted Pair Wire (Chore-
Time part no. 42208). Using the Twisted Pair Wire provided, hook the I/O Net wires from the first Relay Box to the Main Box,
then from the Main Box to the Second Relay Box. I/O Net is polarity sensitive so be sure that the positive and negative I/O Net
provided. The 24 Vdc for the Second Relay Box (relays 41-56) must be connected to the External Power Supply (See Figure 15).
The supply voltage for the External Power Supply needs to come from the same breaker as the Main Box.
Do NOT run 24 Vdc and I/O Net wire close to and/or parallel with line (120 Vac or greater) wires. Doing so can cause operational
failure in the Control and Void Warranty. If 24 Vdc or I/O Net wires need to cross line voltage wires make sure the wires cross at
a 90 degree angle (See Figure 13). Also, no other electrical devices such as transformers, light dimmers, additional relays, etc.
should be mounted inside the main box or near the 24 Vdc power or I/O Net wires.
ON OFF
MT2398C
93
Control Installation Chore-Tronics® 3 Control
Item Description
1 Main Box 2 Relay Box 3I/O Board 4 Power Supply 5 RM Board (Relay Module) 6 SP (Static Pressure) Sensor 7 Display Board 8 KD Board 9 HI Basic Board 10 IMCM.16 Board 11 IMCM.8 Board
3
1
4
5
6
7
8
10
11
9
2
Figure 16. Wiring/
Wiring the Control
Note As with all electronic controls, we recommend the use of a backup system. This
will provide continuous operation in the unlikely event of Control failure. Use the current Back Up Box Manual for wiring instructions.
The Chore-Tronics Figure 16. The two Boards involved in wiring the Controls are the I/O Board and the Relay Module (RM Board).
®
3 Controls consist of several different types of boards shown in
94
MT2398C
Control Installation Chore-Tronics® 3 Control
Figure 17. Low Voltage Wire Routing
Item Description
1 Temperature Sensor, Potentiometer,
relative humidity wires etc. (Low
Voltage) 2 Line Voltage Wires 3 Input/Output wires (High Voltage)
3
2
1
Figure 18. Ground Wire Routing
Item Description
1 Ground Rails 2 Ground Wires 3 8’-10’[2.438 m-3.048 m] Max.
Earth Ground
3
2
1
When wiring the Control it is recommended that the line voltage wires be brought into the bottom of the Boxes and the low voltage wires (Temperature Sensors, Potentiometers, relative humidity, etc.) be brought in the side of the Control Box (See Figure 17).
When grounding the Control, connect only the Ground Rail of the Main Box to the Earth ground. Connect the Ground Rail from the Main Box to the Ground Rail of the Relay Box. It is recommended that a ground
rod be located no more than 8’[2.438 m] to 10’ [3.048 m] away from the Control. The Chore-Tronics
®
3 Control should be connected to ground using a 12 gauge wire or larger. As always, check the local electric code for additional requirements.
95
MT2398C
Control Installation Chore-Tronics® 3 Control
AI5
24V
A6I
U
R
I
U
R
I
Analog Inputs
Analog Inputs consist of temperature sensors, the static pressure sensor, the relative humidity sensor and potentiometers (natural ventilation only). These inputs can be wired to any of the analog inputs (AI 1 thru AI 12) on the I/O board. The inputs that are pre-assigned are temperature sensors 1, 2 and 3, and the static pressure sensor. Use the diagram located on page 137 to record where each Input is wired to the Control.
Temperature Sensors
The Temperature Sensors require Non-Shielded 20 Gauge Twisted Pair Wire. This wire is available through Chore-Time. When routing this wire in the house be sure to keep it a minimum of 12"(305mm) away from line voltage wiring. If there is a need for the Sensor wire to cross line voltage wires cross them at a 90° angle to each other as shown below.
1
90°
2
Figure 19. 90° Cross-over
Item Description
1 Non-Shielded Twisted Pair Wire 2 Line Voltage Wiring
The Temperature Sensor wires can be connected to any one of the Analog Inputs (AI1 through AI16) of the I/O board. Whatever AI Inputs the Temperature Sensors are connected to, make sure that the blue jumper above each Input is set to "R" as shown in Figure 82 below. There are no polarity restrictions for the Temperature Sensors.
2
1
96
Red
Black
Item Description
1 Analog Input (AI5) 2 blue jumper set to "R"
Figure 20. Temperature Sensor Wiring
MT2398C
Control Installation Chore-Tronics® 3 Control
Mv1701-010 10/01
3
1
Front View (with Lid Off)
2
Figure 21. Drip Loop
Item Description
1 T emperature Sensor (Back Side) 2 Non-Shielded Twisted Pair 3 Drip Loop
AI15
24V
A6I1
AI1
24V
AI2
U
R
I
Figure 23. Static Pressure Sensor
Wired to AI1
Blue Jumper in the "U" position
Blue Jumper in the "U" position
Figure 22. Static Pressure Sensor
Pre-wired to AI15
Black
Red
Red
Black
Temperature Sensors Continued.....
Route the wire through the back of the Temperature Sensor and connect it as shown in Figure below. Pull the wire through the back of the box until a drip loop is formed as shown.
Static Pressure (SP) Wiring
There is a Static Pressure Sensor included with every Chore-Tronics® 3 Control. This sensor is pre-wired from the factory to Analog Input #4 (AI 4) (Figure 22). If it is desired, the Static Pressure Sensor can be wired to any of the Analog Inputs (AI1 through AI16) (See Figure 23 for example wired to AI1). Please note that the Red wire must always be connected to the +24 volt terminal, the Blue wire must be connected to the AI terminal being used and the Black wire must be connected to the ground terminal of the analog Input being use. Make sure that whichever AI Input the SP sensor is connected to, that the blue jumper above the Input is set to "U" position as shown.
97
MT2398C
Control Installation Chore-Tronics® 3 Control
2
1
Item Description
1 Static Pressure Sensor 2 Static Pressure Hose 3 1/2" Water Tight Connector 4 Barb Reducer Plugs
Figure 24. Static Pressure Sensor Hose Routing
Low Pressure Barb
High Pressure Barb
Run into Attic
Run into House
4
3
To route the Static Pressure Hoses into the Chore-Tronics® 3 Main Box, first drill two 5/8" holes in the side of the Box, next to the sensor. Place a ½" water tight connector (Item 3, Figure 24) into each hole and tighten using the hardware provided. Route a 3/16" ID hose (Chore-Time part number 43071) through each of the Water Tight Connectors. Connect one hose to the low pressure barb on the SP module, and run that house into the house. Connect another hose to the high pressure barb on the Sp Module. Run that hose into the attic or to outside air. Make sure the high pressure hose is in still air. Once the hoses have been routed and connected, place the Barb Reducer Plugs into the end of the hose opposite of the SP sensor.
98
MT2398C
Chore-Tronics® 3 Control Control Installation
Note:
AI10
24V
AI11
U
R
I
To Potentiometer
Blue Jumper set to the "R" position
UR I
AI10
24V
AI11
Relative Humidity Sensor(RH) Wiring
The optional Relative Humidity Sensor (Item 1, Figure 25) requires a three-conductor wire to connect
®
the sensor to the Chore-Tronics
3 I/O board. The Sensor is connected to one of the Analog (AI) Inputs
on the IO board.
Terminal #1 on the relative humidity sensor is connected to the +24 v terminal on the IO board (see
diagram). This is the same +24 v terminal used by the Static Pressure Sensor. Terminal #2 on the Relative Humidity Sensor is connected to the Analog Input (AI) terminal of the analog Input being used (See Figure 25). Terminal #3 is connected to the ground terminal of the Analog Input (AI) being used. Make sure that the Blue Jumper above the Analog Input that the RH sensor is connected to is set to "U".
Blue Jumper in the "U" position
2
1
Item Description
1 Relative Humidity Sensor Quick Connect 2 I/O Board Analog Input (AI) Terminal of
your Choice
Figure 25. Relative Humidity Sensor Wiring
Potentiometer Wiring (Natural Ventilation only)
If natural ventilation is being used, the Potentiometer(s) either the main curtain machine(s) (Internal Potentiometer), or the main curtain cables (External Potentiometer)
need to be wired to the Chore-Tronics 3 I/O Board. The Potentiometers need to be connected using the same Twisted Pair Wire that is used for the Temperature Sensors and follows the same wiring rules. Each Potentiometer needs to be wired to one of the Analog Input (AI) Terminals on the IO board. Make sure that whichever AI Input the Potentiometer is connected to that the Blue Jumper above the Input is set to "R" (See Figure 26). To connect the sensor wire to the Potentiometer itself, please see Chore-Time instruction manual MV1251 for internal Potentiometer wiring, or MV1566 for external Potentiometer wiring.
that are attached to
®
Figure 26. Potentiometer Wiring
MT2398C
99
Control Installation Chore-Tronics® 3 Control
DI1
12V
DI5
24V
DI6
Digital Inputs Wiring
Digital inputs consist of Water Meters, Feed Scales, Air Speed Sensor, Low Water Pressure Switch, Max Feed Run Time Alarm Input, and PDS Flush Feedback. These Inputs can be wired to any of the digital inputs (DI 1 thru DI 8) on the IO board (Figure 27 below). Complete the analog input Assignment diagram on page 137 to indicate where each digital input is connected to the IO board and also record it on the Input Assignment Decal (Item 1, Figure 27) that is placed on the Cover Plate inside the Chore-
®
Tronics input.
3 Main Box. Also refer to the following sections for information specific to each type of digital
Item Description
1 Input Assignment Decal
1
To Feed Scale
100
To Water Meter
Figure 27. Digital Input Wiring
MT2398C
Loading...