Chloride CMFIC Series, ZMFIC Series, TMFIC Series Installation And Operating Instructions Manual

WARNING – Shut off AC power to branch
CMFIC/TMFIC/ZMFIC Series
75W-150W Emergency
Luminaire
INSTALLATION AND
OPERATING
INSTRUCTIONS
IMPORTANT
SAFEGUARDS
When using electrical equipment, basic safety precautions should always be followed, including the following:
READ AND FOLLOW ALL
SAFETY INSTRUCTIONS
All servicing should be performed by qualified personnel only.
Equipment should be mounted in locati ons a nd a t he ight s where it will not be readily subjected to tampering by unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Do not use this equipment for other than intended use.
Do not use outdoors.
Do not let supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
CAUTION: Halogen cycle lamp(s) are used in this equipment. To avoid shattering: Do not operate lamp in excess of rated voltage, protect lamp against abrasion and scratches and against liquids when lamp is operating, dispose of lamp with care.
Halogen cycle lamps operate at high temperatures. Do not store or place flammable m aterials near lamp.
CAUTION: “To avoid electrical overload, total connected lamp load (factory and field installed) should not exceed output rating”.
SAVE THESE
INSTRUCTIONS
circuits to which units will be connected. All wiring should be per N.E.C. Articles 501-4(b) and local codes.
To maintain warranty, equipment with batteries must be installed or placed on charge within prescribed period after shipment.
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.chloride-lighting.com
Signify Canada Ltd./Signify Canad a Ltée. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
July 2018
12NC: 443580503951
GENERAL INSTRUCTIONS
1) Begin the installation process by securing the unit
less battery to the mounting surface. Three slotted vertical keyway knockouts in the housing are to be used to attach the housing to independent anchor supports. Use three ¼” toggle bolts (supplied by others) minimum to secure the unit to drywall. If mounting t o holl ow concrete masonry, a minimum of two ¼” toggle bolts must be used. When using wall recessed wiring, the slotted, circular keyway s can be used to secure the housing to a standard junction box for wiring purposes only. Run the wires through center hole of housing in preparation for unit wiring. For surface conduit wiring , there are a total of six knockouts which can be used for service entrance and exit.
2) If desired, wall mounting can also be
accomplished with use of the optional mounting shelf (See Optional Mounting Shelf and Figure
2).
1. Connect remote lamps, if applicable, to orange
and yellow flying leads conn ected to
RL+ and
RL- respectively. Ensure total unit load (including internal lamps) does not exceed unit rating.
2. Adjust head(s) to illuminate desired area(s) .
3. Close cover and screw shut. Ensure electrical
wires and membrane switch cable remain insid e unit and that the cover d oes not pi nch wir es whe n closed. Hand tighten two thumb nuts to finalize cover closure.
INSTALLING BATTERIES
1. Units ship without batteries installed. For lead
units, battery wiring harnesses are already connected to PCB assembly and co nnection to the batteries is required. In the case of Nic ad units, connection of battery harness to the PCB is required.
2. Install and wire batteries as appropriate. (See
Page 5-8 for battery configurations)
3. Tighten straps to secure batteries inside unit.
OPTIONAL MOUNTING SHELF
1. If the unit is to be mounted to poles, columns or
I-Beams, use the optional mounting shelf kit and strapping kit (ordered separately).
2. Use four ¼” toggle bolts (supplied by others)
minimum to secure the unit to drywall and hol low concrete masonry.
HOOKUP INSTRUCTIONS
Standard Units:
Connect A.C. service to unit charger leads: Blue = 277 VAC Black = 120 VAC White = Common Green = Ground
Figure 1
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.chloride-lighting.com
Figure 2
3. Once the mounting shelf is installed, the unit is
ready for installation.
4. Place unit on shelf less batteries and secu re with
three (3) securing screws (supplied with mounting shelf) to shelf threaded inserts.
Signify Canada Ltd./Signify Canad a Ltée. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
12NC: 443580503951
July 2018
Self Diagnostic System Operation – Emergency Light or EXIT Sign Products
Normal Power Up Sequence
At power up the red and green LED indicators will alternately flash for one to two seconds. Next the product will execute a “Power Up Quick Test” causing the green LED indicator to flash rapidly. If any faults are detected during the “Power Up Quick Test” these will be evident by a flashing red LED indicator. If the audible diagnostic option has been ordered, the flashing red LED will be accompanied by a simultaneous beeping tone. (Note: A continuous rapid alternating Red/Green
flash with rapid beeping tone indicates 277V applied to 120V input lead. TURN OFF POWER IMMEDIATELY!)
Emergency Operation Emergency operation occurs when AC power fails. The product remains in emergency operation until AC power is restored or battery capacity is depleted. During emergency operation both red and green LED indicators are disabled.
User Interface Green LED indicator
Slow Flash/Continuous ON = AC power present; normal operating condition
Rapid Flash = product performing an automatic or manually initiated diagnostic test
Red LED indicator
Single Flash = battery fault
Two Flashes = lamp failure (light bar failure – EXIT signs)
Three Flashes = charger fault
Four Flashes = transfer fault
(If more than one fault condition is present simultaneously, the red LED will flash the indication pattern for each fault independently then repeat the cycle.)
Pushbutton Test Switch
Long Press (longer than 0.5sec) transfers product to emergency operation during time the button is
pressed.
Short Press initiates self diagnostic activities as follows:
One Press cancels diagnostic test presently running.Two Presses starts a one minute diagnostic test.Three Presses starts a 90 minute diagnostic test.Four Presses conducts a lamp load calibration (emergency light products only). Seven Presses initiates a system reset.
(Note: the microprocessor will allow up to seven, one minute diagnostic tests within the first 24 hours of operation. Allow 24 hours of charging before performing any long duration testing.)
Buzzer (optional)– Sounds in unison with the flashing red LED if a fault condition is present. Buzzer may be silenced for up to 196 hours by a short press of either the test switch or the optional IR remote control device “silence” button. Correcting fault condition will cancel fault notification. Lamp failure indication requires a manually activated diagnostic test after lamp replacement to cancel notification.
IR Remote Control (optional)- is a hand held device that allows remote activation of diagnostic testing and silencing of the optional buzzer during fault conditions.
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.chloride-lighting.com
Signify Canada Ltd./Signify Canad a Ltée. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
July 2018
12NC: 443580503951
OPTIONAL REMOTE CONTROL
Front
Press appropriate button to perform the indicated test or silence the audible alarm.
Cancel stops any test currently in process.
Back
Explanation of indicator light flash sequences.
Refer to Table 2 above for further information.
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.chloride-lighting.com
Signify Canada Ltd./Signify Canad a Ltée. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
July 2018
12NC: 443580503951
BATTERY HOOKUP DIAGRAMS
6V 75W LEAD
6V 100W LEAD
6V 75W LEAD
6V 100W LEAD
12V 75W LEAD
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.chloride-lighting.com
Signify Canada Ltd./Signify Canad a Ltée. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
12V 75W LEAD
12NC: 443580503951
July 2018
12V 100W LEAD
12V 100W LEAD
12V 150W LEAD
24V 100W LEAD
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.chloride-lighting.com
12V 150W LEAD
24V 100W LEAD
Signify Canada Ltd./Signify Canad a Ltée. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
12NC: 443580503951
July 2018
NICAD BATTERY HOOKUP DIAGRAMS
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.chloride-lighting.com
Signify Canada Ltd./Signify Canad a Ltée. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
July 2018
12NC: 443580503951
Signify North America Corporation 200 Franklin Square Drive Somerset, NJ 08873, USA Phone: 855-486-2216
www.chloride-lighting.com
Signify Canada Ltd./Signify Canad a Ltée. 281 Hillmount Road, Markham ON, Canada L6C 2S3 Phone: 800-668-9008
July 2018
12NC: 443580503951
Loading...