Chloride EDP70, EDP70 Plus User Handbook Manual

PART NUMBER 10H52152PU9C rev.8
EDP70 PLUS
UNINTERRUPTIBLE POWER SYSTEM
24/36/50/80kVA —
3 phase input / 3 phase output
     
1) SAVE THESE INSTRUCTIONS
This manual contains important instructions for the EDP70 PLUS which should be followed during installation and maintenance of the UPS and associated batteries.
2)
The installation must be inspected by trained technicians.
The instructions must be followed.
3)
When external batteries are provided by the Customer and not Chloride, reference must be made to
the installation instructions provided by the battery supplier.

1)
The AC and DC supplies to the EDP70 PLUS UPS and the AC output from the UPS MUST be fed
through suitably rated circuit breakers or fuses and isolating switches suitable for branch circuit operation.
2)
Any external battery cabinet connected to the UPS MUST be provided with an over-current protection
device per UL1778 Par. No. 28.4
3)
To reduce the risk of fire or electric shock, the equipment must be installed indoors, in a humidity
and temperature controlled environment which is free from conductive contaminants.

1)
DO NOT REMOVE COVERS DURING NORMAL OPERATION. The panels will be removed during installation, however this should only be undertaken by qualified technicians. It should be ensured that the UPS is switched off and that all power sources are disconnected (A.C. mains and Battery) before either the rear or side panels are removed.
FOREIGN OBJECTS MUST NOT BE INTRODUCED INTO THE VENTILLATION GRILLES.
2)
HAZARDOUS VOLTAGES are present within the EDP70 PLUS even when it is switched off.
3)
Fuses must ONLY be replaced with the same type and rating.
The EDP70 PLUS contains a battery which can be DANGEROUS if interfered with. Contact the
4)
supplier for replacement.
The UPS and/or its components must be disposed of as notifiable waste in accordance with local
5)
pollution control (special waste) regulations.
page
2 --
MI00/10056 rev. 8 —05/2006
3
WARNING
The UPS contains hazardous voltages, even when all switches are open.
In case of fire in the installation area, do not use water to extinguish fire.
ELECTRICAL PRECAUTIONS:
If the UPS is in By-pass mode and the Output switch is closed, no indications will be displayed;
fans will however function, and hazardous voltages are present downline from the static switches.
EMERGENCY PROCEDURE
In the case of an emergency, the load supply can be interrupted by switching off all the switches fitted in the UPS.
ELECTRIC SHOCK
Switch off power; use dry insulating material for protection when pulling the injured person clear of conductors. NEVER TOUCH THE INJURED PERSON WITH BARE HANDS UNTIL CLEAR OF CONDUCTORS. SEEK QUALIFIED ASSISTANCE IMMEDIATELY.
INJURIES CAUSED BY CONTACT WITH CORROSIVE LIQUIDS
In normal conditions, installed batteries are sealed. A damaged battery container may however leak electrolyte, or cause the latter to come into contact with battery parts. In the event of electrolyte contact with the eyes, rinse eyes thoroughly with a saline solution or fresh water for at least 10 minutes. In the event of electrolyte contact with skin, rinse the affected area with abundant water. Remove contaminated clothing. Cover affected area with dry gauze.
If electrolyte is swallowed, do not induce vomiting. Administer large quantities of milk
or water.
IN ALL CASES, SEEK MEDICAL ATTENTION IMMEDIATELY
MI00/10056 rev. 8 — 05/2006-- page
Contents
1.0 INTRODUCTION ..................................................................................................9
1.1 Summary of the manual...................................................................................................... 9
1.2 Summary of the equipment ................................................................................................ 9
1.3 Block diagram.................................................................................................................... 10
1.4 Functions ........................................................................................................................... 11
1.5 Operational modes............................................................................................................ 12
2.0 SAFETY..............................................................................................................14
2.1 General safety.................................................................................................................... 14
2.2 Symbols ............................................................................................................................. 14
2.3 Electrical precautions ....................................................................................................... 15
2.4 Battery precautions........................................................................................................... 15
2.5 Battery safety equipment.................................................................................................. 15
3.0 STORAGE ..........................................................................................................16
4.0 INSTALLATION .................................................................................................16
4.1 Mechanical characteristics............................................................................................... 16
4.2 Installation ......................................................................................................................... 26
Recommended wire sizes .......................................................................................................... 27
4.4 Ventilation.......................................................................................................................... 29
5.0 CONNECTION....................................................................................................30
5.1 Electrical connections ...................................................................................................... 32
5.2 24 – 12/18/24kVA ............................................................................................................... 33
5.3 36 – 24/30/36kVA ............................................................................................................... 36
5.3 EDP70 PLUS 50/80kVA...................................................................................................... 39
5.4 Signal connections ........................................................................................................... 42
6.0 CONTROLS........................................................................................................43
6.1 User Controls..................................................................................................................... 43
6.2 Control Panel ..................................................................................................................... 44
7.0 START UP..........................................................................................................45
8.0 MAINTENANCE BYPASS .................................................................................45
9.0 SHUT-DOWN .....................................................................................................46
9.1 Installing the EPO.............................................................................................................. 46
10.0 VISUAL AND AUDIBLE ALARMS ....................................................................47
10.1 Silencing Audible Alarm ................................................................................................... 47
page
4 --
MI00/10056 rev. 8 —05/2006
5
10.2 Mimic .................................................................................................................................. 47
10.3 Liquid Crystal Display....................................................................................................... 47
10.4 Display Page Headings ..................................................................................................... 48
10.5 Abnormal operating mode messages.............................................................................. 55
10.6 Power History .................................................................................................................... 60
10.7 Battery Test........................................................................................................................ 61
10.8 Battery Autonomy Test ..................................................................................................... 61
10.9 Resetting data loss manually ........................................................................................... 61
11.0 COMPUTER INTERFACE .................................................................................62
11.1 AS400.............................................................................................................................. 62
11.2 RS232 ................................................................................................................................. 63
12.0 REMOTE ALARMS............................................................................................63
13.0 BATTERIES .......................................................................................................64
13.1 EDP70 PLUS/24/18/12 : Battery Installation/Start-up...................................................... 64
13.2 EDP70 PLUS/24/18/12 : Optional Battery Cubicle ........................................................... 65
13.3 EDP70 PLUS above 24KVA: Battery Installation/Start-up .............................................. 66
13.4 EDP70 PLUS above 24KVA: Battery Cubicle .................................................................. 66
14.0 MAINTENANCE AND SPARE PARTS .............................................................66
MI00/10056 rev. 8 — 05/2006-- page
Figures
Figure 1 – Block diagrams – 24/36kVA Figure 2 – Block diagram – 50/80kVA Figure 3 – Normal operation Figure 4 – Utility Supply failure Figure 5 – Re-establishing the Utility Supply Figure 6 – Transferring the Load onto the Reserve Supply Figure 7 – 24 Footprint and cabinet dimensions Figure 8 – 36 Footprint and cabinet dimensions Figure 9 – 50/80 Footprint and cabinet dimensions
Figure 10 – “A” Battery Cabinet Drawing for 24/36kVA Ratings
Figure 11 – “B” Battery Cabinet Drawing for 24/36kVA Ratings
Figure 12 – “E” Battery Cabinet Drawing for 50/80kVA Ratings
Figure 13 – “F” Battery Cabinet Drawing for 50/80kVA Ratings
Figure 14 – “C” Battery Cabinet Drawing for 36/50/80kVA Ratings
Figure 15 – “D” Battery Cabinet Drawing for 50/80kVA Ratings
Figure 16 – UPS Ratings Figure 17 – Connection diagrams Figure 18 - 24 – 12/18/24kVA: Switches and Breakers Figure 19 - 24 – 12/18/24kVA: Switches Figure 20 - 24 – 12/18/24kVA: Cable Connections Figure 21 - 36 – 24/30/36kVA: Switches and Breakers Figure 22 - 36 – 24/30/36kVA: Connections Figure 23 - 36 – 24/30/36kVA: Cable Connections Figure 24 – 50/80kVA: Switches and Breakers Figure 25 – 50/80kVA: Connections Figure 26 – 50/80kVA: Cable Connections Figure 27 – Control panel
Figure 28: Power History Structure
Figure 29 EDP 70 Plus Computer Interface Pin Layout
Figure 30 EDP70 PLUS Remote Alarms Pin Layout
Figure 31- EDP70 PLUS/24/18/12: Internal Battery Shelves
12
12
26
43
10
11
13
13 17 18
19
20 21 22
23
25
30
33
34
35
36
37
38
39
40
41
60
62
63
65
24
page
6 --
MI00/10056 rev. 8 —05/2006
7
EQUIPMENT DELIVERY AND STORAGE
Delivery
The equipment and battery are delivered separately. On receipt, the packaging must be checked for any signs of damage. Any damage or missing parts should be reported to the carrier within 24 hours of delivery.
Unpacking
Care should be taken when unpacking to avoid damaging the equipment or battery; in particular, avoid short circuiting battery terminals. All packing materials should be checked before disposal to ensure that no items are discarded. The equipment panel rating plate should be checked to ensure that supply voltage and output rating correspond to the equipment and load and that the mode of operation is correct.
Handling
Keep equipment and battery upright at all times, and handle with care. Either may be damaged if dropped or subject to severe impact. Particular care should be taken to protect the controls and instruments. a) Leave the equipment in its packaging and transport it with a fork lift.
b) Cut the tapes and remove the packing case by lifting it upwards. c) Unscrew the screws fastening the pallet to the cubicle feet.
d) Lift the cubicle and remove the pallet.
Storage
Store the equipment and battery in a clean, dry place, free from water, condensation, dirt and extremes of temperature. Sealed lead acid battery cells which are supplied filled and charged must be given a boost charge at least every 3
months. Sealed Nickel-Cadmium battery cells which are supplied filled and discharged must be charged and discharged before
storage.
Sealed Nickel-Cadmium battery cells which are supplied dry must be filled, charged and discharged before storage.
Sealed spare battery cells must be charged at least every 3 months.
Failure to comply with the Manufacturer’s instructions may result in the battery not reaching its rated performance and having a shortened life.
MI00/10056 rev. 8 — 05/2006-- page
?
page
8 --
MI00/10056 rev. 8 —05/2006
9
1.0 INTRODUCTION
1.1 Summary of the manual
This handbook provides for the safe installation, startup and use of the EDP70 PLUS Uninterruptible Power System (UPS). The Company recommends that the equipment be installed and regularly maintained by a Chloride Authorized personnel.
DO: - read the User Handbook before operating the EDP70 PLUS UPS.
- keep a log of all incidents.
- protect the batteries from damage. Batteries leak acid; avoid contact with skin, clothes or eyes.
DO NOT: - operate the control switches.
- operate the EDP70 PLUS UPS with any covers removed.
- obstruct the ventilation grilles.
1.2 Summary of the equipment
The EDP70 PLUS Uninterruptible Power System (UPS) totally isolates the load from voltage drops, spikes, transients frequency variations in the utility supply.
In the event of failure or brownout of the AC utility supply, an internal audible alarm sounds and an LED on the control panel illuminates, the EDP70 PLUS UPS will continue to provide safe, clean continuous power, without interruption, from the battery, for a duration dependent on battery capacity and output load.
The audible alarm alerts the user to start a safe orderly shutdown of the load. When the AC utility supply returns to normal, the EDP70 PLUS UPS automatically recharges the battery ready for any future power failure.
The microprocessor display panel provides access to very detailed information regarding the status of the supplies and EDP70 PLUS UPS. Refer to current publication for detailed specification.
The block diagram, shows the main functional sub-assemblies of the EDP70 PLUS UPS. The AC three phase utility supply is rectified to provide direct current, which maintains the battery in a fully charged state and also supplies the inverter, which provides the three phase output via an electronic static switch.
Normally the supply of the reserve line is taken from the AC utility input, but special units, with a separate reserve input supply, are available. This allows the inputs to be supplied from independent three phase sources.
Provided the reserve supply is within limits, the inverter will match the output frequency with the reserve supply frequency. The inverter has its own internal crystal control to stabilize the output frequency if the reserve supply frequency is out of limits. The electronic static switch switches the output from the inverter to the reserve supply, without interruption, to meet any load current surges, or to supply the load if the battery is discharged during an AC utility supply failure.
Maintenance and testing can be carried out on the EDP70 PLUS UPS without interrupting the output, by switching the load from the reserve supply to the maintenance bypass circuit. This work should only be carried out by Chloride-trained personnel.
MI00/10056 rev. 8 — 05/2006-- page
1.3 Block diagram
24kVA - STANDARD CONFIGURATION
S3
Reserve Supply
208Y/120V
S2
S1
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE
SUPPLY THE RESRVE IS DERIVED FROM THE
AC UTILITY INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Reserve Supply
208Y
S1
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE
SUPPLY THE RESRVE IS DERIVED FROM THE
AC UTILITY INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Maintenance By-pass
290
3
Battery Contactor
208150
1
5
4
144 Cells (Internal)
2
36kVA - STANDARD CONFIGURATION
480
208Y
S2
S3
Battery Contactor
3
250
1
Maintenance By-pass
5
208Y
4
240 Cells (External)
2
S4
S4
page
Reserve Supply
480V
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE SUPPLY THE RESRVE IS DERIVED FROM THE AC UTILITY INPUT WITH THE JUMPER CONNECTED AS INDICATED
10 --
MI00/10056 rev. 8 —05/2006
36kVA - 480V/208V CONFIGURATION
S1
S3
S2
208Y
250
480
Maintenance By-pass
3
208Y
1
Battery Contactor
240 Cells (External)
2
Figure 1 – Block diagrams – 24/36kVA
5
S4
4
11
S3
Maintenance Bypass
Reserve Supply
480V
AC Supply
S2
S1
IN THE ABSENCE OF A SEPARATE
RESERVE SUPPLY THE RESERVE IS
DERIVED FROM THE AC UTILITY
INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Battery Contactor
240 Cells (External)
3
1
2
S5
5
S4
4
480Y/277V
208Y/120V
Figure 2 – Block diagram – 50/80kVA
The uninterruptible power system consists of the following:
1 - RECTIFIER/INVERTER S1 = Equipment ON/OFF switch 2 - BATTERY S2 = Equipment Reserve switch 3 - BACKFEED PROTECTION S3 = Equipment By-pass switch 4 - INVERTER STATIC SWITCH S4 = Equipment OUTPUT switch 5 - RESERVE STATIC SWITCH (INVERTER OUTPUT switch for 50/80kVA only)
S5 = RESERVE OUTPUT switch for 50/80kVA only
1.4 Functions
   
The rectifier/battery charger transforms the alternating current of the mains supply to direct voltage to maintain the battery in a fully charged state and also supply the inverter.

The battery is an energy reserve that is used by the inverter and the load whenever the mains supply fails.

The inverter changes the direct voltage from the rectifier or from the battery into a three phase sinusoidal alternating voltage for the external supply.
  
The function of the electronic static switch is to select one of the two sources of alternating voltage and to supply it to the external load. The two sources of voltage supplied to the static switch are the output of the inverter and the reserve supply. In normal working conditions, the static switch supplies the load from the inverter.

The switches permits maintenance and repair of the UPS, without interrupting the supply to the load.
MI00/10056 rev. 8 — 05/2006-- page
1.5 Operational modes
S3
S2
Maintenance By-pass
AC Supply
AC Supply
S1
Battery Contactor
S3
S2
S1
Battery Contactor
24/36kVA Ratings
Maintenance By-pass
50/80kVA Ratings
LOAD
S4
S5
S4
480Y/277V
LOAD
208Y/120V
Figure 3 – Normal operation
During normal operation the load is supplied by the mains through the rectifier and inverter. The rectifier also supplies the current for recharging and maintaining the battery in a fully charged state.
Reserve Supply
AC Supply
S3
S2
S1
Maintenance By-pass
S4
LOAD
Battery
Reserve Supply
Contactor
S3
S2
S1
24/36kVA Ratings
Maintenance By-pass
S5
S4
480Y/277V
LOAD
208Y/120V
AC Supply
Battery Contactor
50/80kVA Ratings
Figure 4 – Utility Supply failure
When the utility supply voltage is absent or outside the allowed tolerances, the battery supplies the inverter. This will be indicated on the UPS front panel display and the Remote Alarm Unit (if fitted). The standby time available depends both on the capacity of the battery and on the size of load. It is possible to extend autonomy by reducing the output power by disconnecting non-important loads. In all cases, the alphanumerical display shows the residual autonomy.
page
12 --
MI00/10056 rev. 8 —05/2006
13
Reserve Supply
S3
S2
Maintenance By-pass
S4
S5
S4
480Y/277V
208Y/120V
AC Supply
Reserve Supply
AC Supply
S1
Battery Contactor
S3
S2
S1
Battery Contactor
24/36kVA Ratings
Maintenance By-pass
50/80kVA Ratings
Figure 5 – Re-establishing the Utility Supply
When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will result in reduced standby times.
Reserve Supply
AC Supply
S3
S2
S1
Battery Contactor
Maintenance By-pass
S4
24/36kVA Ratings
Reserve Supply
AC Supply
S3
S2
S1
Battery Contactor
Maintenance By-pass
50/80kVA Ratings
S5
S4
480Y/277V
208Y/120V
Figure 6 – Transferring the Load onto the Reserve Supply
Transfer onto the reserve line is caused by two conditions: a) inverter stop b) overload In both instances the load is transferred onto the reserve without interruption. If the overload is temporary, the system will re-transfer from reserve to inverter as soon as the it ceases. This allows for the initial start-up of loads with high or excessive switch-on currents.
MI00/10056 rev. 8 — 05/2006-- page
2.0 SAFETY
Read all instructions carefully before installing or operating the equipment.
2.1 General safety
The procedure described in these instructions is intended for use by persons experienced in the operation of Uninterruptible Power Systems and ancillary equipment. Persons unfamiliar with this type of equipment should seek guidance from experienced personnel. The EDP70 PLUS UPS is designed to be operated in accordance with existing safe operating procedures. These instructions are not intended to replace existing safety practices. If there are any questions regarding the safe operation of the system, contact a Chloride service representative.
This equipment is designed and built for safe operation when used to supply its rated load, providing it is installed as specified by qualified, licensed and competent electricians. Electrical energy can be supplied by the equipment and the battery.
2.2 Symbols
The following symbols appear in this book and in the unit:
Warning -
electrical shock and danger to personal safety.
DIRECT CURRENT SUPPLY
Hazardous voltages are present. If the instructions are not heeded, there is a risk of
ALTERNATING CURRENT SUPPLY
ON position of the switches
OFF position of the switches
Inverter Start Up
Inverter Shutdown
Audible Alarm Cancel Switch
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
page
14 --
MI00/10056 rev. 8 —05/2006
15
Page Right Control
Record Up
Record Down
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
2.3 Electrical precautions
Never handle a component or assembly without first confirming that no voltage is applied or present. Remove only those protective covers that are essential to perform the repairs or adjustment currently required, and replace them as soon as possible.
. Use only insulated tools. . Place a rubber insulating mat in front of all equipment doors. . Keep all door closed and locked at all times during normal operation.
2.4 Battery precautions
Always isolate the load before connecting or disconnecting the batteries or battery cells. Ensure that batteries are fully isolated by disconnecting the battery connectors, opening circuit breakers, or both. Remove all jewellery from hands, wrists and neck before working on batteries or battery cells. Before leaning over batteries, remove any metal object that could fall out of pockets. Do not place tools or other conductive objects on the batteries.
2.5 Battery safety equipment
When working on or handling batteries, ensure that the following items are worn:
. Eye goggles . Rubber gloves . Rubber apron . Rubber boots
When batteries are being moved or worked on, ensure the following items are available in the immediate vicinity:
. An eye bath, eyewash station or equivalent . A clean water source to wash spilled acids . Absorbent materials to soak up spilled acids . Disposal for contaminated materials.
MI00/10056 rev. 8 — 05/2006-- page
3.0 STORAGE
If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life. The date the battery was last recharged and the date the battery is due for its next recharge are both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge date. When the EDP70 PLUS is due to be recharged, refer to the Installation instructions and connect the EDP70 PLUS UPS to a temporary AC supply. The battery MUST be recharged for at least 24 hours every 3 months.
4.0 INSTALLATION
4.1 Mechanical characteristics
- Ambient temperature 18°F[-10°C] to 104°F [+40°C ]
- Relative Humidity (w/out condensing @ 68°F[20°C]) < 90%
- Max altitude (w/out derating) 3300 feet [1000 m] above sea-level
- Protection degree (panel fitted)
- Input cables bottom
- Air inlet bottom
- Air outlet rear
UPS model
Description
Size width
Total Weight (UPS +
Battery)
Floor Area
Floor
Loading
(UPS +
Battery)
Air-Flow
Acoustic Noise
100% Linear Load
depth
height
w/out cells 25 Ah cells 30 Ah cells 35 Ah cells
w/out cells 25 Ah cells 30 Ah cells 35 Ah cells
u.m. 24 36 50 80
In
[mm]
Lbs [kg]
2[m2
In
Lbs/in
[kg/m2]
cfm
[mc/h]
dBA 52 55 55 62
28-.5 [700]
28.7 [730] 56 [1420]
880 [400]
1342 [610] 1456 [662] 1526 [694]
] 789 [0.511] 789 [0.511] 1019 [0.657] 1019 [0.657]
2
1.12 [782]
1.70 [1194]
1.85 [1296]
1.93 [1358]
235
[400]
27.5 [700]
28.7 [730] 56 [1420]
1300 [590]
n.a. n.a. n.a.
1.65 [1155] n.a. n.a. n.a.
647
[1100]
35.4 [900]
28.7 [730] 63 [1600]
1342 [610]
n.a. n.a. n.a.
1.32 [930]
n.a. n.a. n.a.
1165
[1980]
35.4 [900]
28.7 [730] 63 [1600]
1800 [818]
n.a. n.a. n.a.
1.77 [1245]
n.a. n.a. n.a.
1553
[2640]
Notes: 1) n.a. = not applicable
2) Longer autonomies, and battery for EDP above 20 kVA are available with external
battery cubicles.
page
16 --
MI00/10056 rev. 8 —05/2006
17
ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES)
6 8 0 ,
700,0 (27.56)
1 4 2 2 ,
0 (
5 6 )
0
(
2 6 .
7 7 )
(28.5)725,0
58,0 (2.28)
N R
4 X
600,0
ø 8
(
ø 0 ,
3 1 )
(23.62)
6 4 5 ,
0
3
(
2
0
5
,
0
.
3
(
1
9
.
)
1 8 )
C
2 6
A
0
B
(
L
1
E
0 .
E
2
N
4 )
T
X
R Y
6 6
(
2 .
6 )
150
(5.9)
(
2 .
6 4 )
(
7 .
8 7 )
SPACE REQUIRED BY THE WHEEL WHEN ROTATING
63,0 (2.48)
Figure 7 – 24 Footprint and cabinet dimensions
730,0 (28.7)
6 7 ,
0
2 0 0
MI00/10056 rev. 8 — 05/2006-- page
N R
4 X
(
ø
0
,
3
1
)
ø
8
ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES)
700,0 (27.56)
1 4 2 2 ,
0 (
5 6 )
6 8 0 ,
0 (
2 6 .
7 7 )
page
6 4 5
3
,
0
0
,
0
(
2
(
1
5
.
.
1
3
8
9
)
)
600,0
18 --
MI00/10056 rev. 8 —05/2006
8 8 ,
0
(
700,0
(27.5)
125,0 (4.92)
530 (20.9)
500 (19.7)
CABLE ENTRY 500 (19.68) X 110 (4.33)
(23.62)
150 (5.9)
3 .
4 6 )
200 (7.87)
SPACE REQUIRED BY THE WHEEL WHEN ROTATING
50,0
(1.97)
730,0 (28.7)
Figure 8 – 36 Footprint and cabinet dimensions
19
N R
4 X
ø
8
(
ø
0
,
3
1
)
ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES)
900,0 (35.4)
1 6 0 0
(
6 3 .
0 )
6 8 ,
0 (
2 .
6 8
100,0
(3.94)
200
6 4 5
3
,
0
0
,
0
(
2
(
1
5
.
.
1
3
8
9
)
)
CABLE ENTRY
700 (27.56) X 110 (4.33)
800,0
(31.5)
Figure 9 –
(7.87)
150
(5.9)
50/80 Footprint and cabinet dimensions
)
SPACE REQUIRED BY THE WHEEL WHEN ROTATING
50,0
(1.97)
730,0 (28.7)
MI00/10056 rev. 8 — 05/2006-- page
Figure 10 — “A” Battery Cabinet Drawing for 24/36kVA Ratings
page
20 --
MI00/10056 rev. 8 —05/2006
21
Figure 11 — “B” Battery Cabinet Drawing for 24/36kVA Ratings
MI00/10056 rev. 8 — 05/2006-- page
Figure 12 — “E” Battery Cabinet Drawing for 50/80kVA Ratings
page
22 --
MI00/10056 rev. 8 —05/2006
23
Figure 13 — “F” Battery Cabinet Drawing for 50/80kVA Ratings
MI00/10056 rev. 8 — 05/2006-- page
70
-
Connection Points
(Terminal Blocks)
ACCESS
PLATE
+
FUSE
32.13
32.88
22.70
2.75
CABLE
ENTRY
MOUNTING FEET
ALL MEASUREMENTS ARE IN INCHES
Figure 14 — “C” Battery Cabinet Drawing for 36/50/80kVA Ratings
page
24 --
MI00/10056 rev. 8 —05/2006
25
70
Connection Points
(Terminal Blocks)
ACCESS PLATE
+ -
FUSE
40.16
28.35
5.33
CABLE ENTRY
MOUNTING FEET
ALL MEASUREMENTS ARE IN INCHES
Figure 15 — “D” Battery Cabinet Drawing for 50/80kVA Ratings
32.68
MI00/10056 rev. 8 — 05/2006-- page
4.2 Installation
Check the rating label on the rear of the front panel of the EDP70 PLUS UPS to ensure the input/output voltages, frequency and load are all within the rating of the UPS.
EDP70 PLUS is designed to operate in an office environment with an optimum temperature of 68°F [20 C]. A gap of at least 4 in [ 10cm. ] must be maintained at rear of the UPS to ensure adequate ventilation. Nothing should be placed around the equipment which might restrict the airflow. Ensure the interconnecting cables do not cause a hazard to the user. A gap of at least 32 in [ 812 mm] must be maintained above the UPS to ensure adequate space for maintenance. The appropriate lifting equipment must be used to move the EDP70 PLUS UPS.
Description
Output power
Nominal Load
Maximum input power (with unit @ nominal Load & battery recharge) Maximum dissipation (with inverter @ nominal Load) Number of battery cells
Battery voltage range
Battery end-discharge current
Description
Output power
Nominal Load
Maximum input power (with unit @ nominal Load & battery recharge) Maximum dissipation (with inverter @ nominal Load)
Number of battery cells
Battery voltage range
Battery end-discharge current
Figure 16 – UPS Ratings
UPS ratings
U.M. 24
12kVA
kVA 12 18 24 24 30 36
kW 8 12 16 16 20 24
kVA 15 21 28 28 35 42
BTU/H
n 144 240
V 238-327 396-545
A 37 55 74 53 67 80
U.M. 50
kVA 30 40 50 50 65 80
kW 24 32 40 40 52 64
kVA 43 57 71 71 91 112
BTU/H
n 240
V 396-545
A 67 88 110 105 140 173
3750 5460 6800 7700 9500 11300
UPS ratings
30kVA
9300 11700 14300 14300 18600 22100
24
18kVA
50
40kVA
24
24kVA
50
50kVA
36
24kVA
80
50kVA
36
30kVA
80
65kVA
36
36kVA
80
80kVA
page
26 --
MI00/10056 rev. 8 —05/2006
27
Recommended wire sizes
It is recommended that the external cables and protection be selected for the highest rated
1)
unit of the model in use.
Reserve (or primary) input and output Neutral cable size should be greater than that of the
2)
line cables in order to be able to supply non-linear loads having a Crest Factor of up to 3:1 (i.e. where neutral current = 1.7 x line current). If non-linear loads are not to be supplied from the Installation, the Neutral can be of the same size as the load cable.
Recommended AC input overcurrent protection represents 125% of nominal full load
3)
current (continuous) plus the short duration input current (non-continuous) for battery re­charging per NEC 215.2.
UPS output cables should be run in separate conduits from input cables.
4)
5)
Grounding conductors are sized per NEC 250.122.
6)
Cable sizes are based upon NEC.
Refer to local codes applying to your installation prior to choosing appropriate cable size.
Refer to UPS ampacity table on following page.
MI00/10056 rev. 8 — 05/2006-- page
Vin/V
out
current (A) 24/12kVA 42 60 33 33 50 24/18kVA 60 80 50 50 70
208/120-
208/120
24/24kVA 24/12kVA 19 30 33 14 20 24/18kVA 26 40 50 22 30
480-208/120 24/24kVA 24/12kVA 19 30 14 14 20 24/18kVA 26 40 22 22 30
480-480/277 24/24kVA 36/24kVA 78 125 67 67 90 36/30kVA 97 150 83 83 125
208/120-
208/120
36/36kVA 36/24kVA 34 50 67 29 40 36/30kVA 42 60 83 36 50
480-208/120 36/36kVA 36/24kVA 34 50 29 29 40 36/30kVA 42 60 36 36 50
480/277-
480/277
36/36kVA 50/30kVA 132 175 83 83 125 50/40kVA 152 200 111 111 150
208-208/120 50/50kVA 50/30kVA 57 80 83 36 50 50/40kVA 66 90 111 48 60 50/50kVA 50/30kVA 57 80 36 36 50 50/40kVA 66 90 48 48 60
480-208/120
480-480/277 50/50kVA 80/50kVA 192 250 139 139 175 80/65kVA 254 350 180 180 225
208-208/120 80/80kVA 80/50kVA 83 125 139 60 80 80/65kVA 110 150 180 78 100
480-208/120 80/80kVA 80/50kVA 83 125 60 60 80 80/65kVA 110 150 78 78 100
480-480/277 80/80kVA
A.C. Supply Reserve Supply UPS Type
Rated
Protection device (A)
78 100 67 67 90
34 50 67 29 40
34 50 29 29 40
118 160 100 100 150
51 70 100 43 60
51 70 43 43 60
192 250 138 138 175
83 125 138 60 80
83 125 60 60 80
311 400 222 222 300
135 175 222 96 125
135 175 96 96 125
Output
Nominal
current (A)
Nominal
current (A)
Protection device (A)
page
28 --
MI00/10056 rev. 8 —05/2006
29
4.4 Ventilation
UPS can work in a continuous environment within 18°F[-10°C] to 104°F [+40°C ] temperature range, although, ideally the ambient temperature should be below 78°F [25°C].
The heat, dissipated by the UPS (indicated on figure 7), is extracted by internal fans and then dissipated into the air.
The heat can be removed from the UPS room by a forced cooling ventilation system or, alternatively, an air conditioning system.
The required air changes per hour will depend on the UPS rating and this heat loss and on the cooling air temperature.
To calculate the required air flow for the dissipated power, the altitude and the cooling air temperature, the following equation can be used:
P
V = 2770 - - - - - - e
d
(0.125 h Tk / T0 )
T
- T
r
with: V = air flow [mc/h]
= total dissipated power [kW]
P
d
= max. temperature allowed into the room [104°F = 40°C = 313°K]
T
r
= Temperature of input cooling air
T
k
T
= 273 °K
0
h = altitude above the sea level [km]
k
MI00/10056 rev. 8 — 05/2006-- page
5.0 CONNECTION
Protection devices to be installed by the customer according to the information shown on page 23
UTILITY INPUT
RESERVE
INPUT
UTILITY INPUT
L1 L2 L3 N
Neutral not present on 50 and 80kVA ratings
GROUND
Protection devices to be installed by the customer according to the information shown on page 23
L1 L2 L3 N
L1 L2 L3 W
U V W N
G
U1 V1 W1
Neutral not
N
present on 50 and 80kVA ratings
U V
U2
V2
W2
N
1
Remove link to connect remote E.P.O.
2 3
Battery Charge Inhibit
4 5 6
U2 V2 W2 N
L1 L2
OUTPUT
L3 N
(Neutral separately derived on 50 and 80kVA ratings)
EXTERNAL BATTERIES
L1 L2
OUTPUT
L3 N
(Neutral separately derived on 50 and 80kVA ratings)
EXTERNAL BATTERIES
1
Remove link to connect remote E.P.O.
2 3
Battery Charge Inhibit
4
G
5 6
GROUND
Figure 17 – Connection diagrams
THE AC AND DC SUPPLIES TO THE EDP70 PLUS UPS, AND THE AC OUTPUT FROM THE UPS, SHOULD BE FED THROUGH SUITABLY RATED CIRCUIT BREAKER OR FUSE(S) AND ISOLATING SWITCH SUITABLE FOR BRANCH CIRCUIT PROTECTION. NOTE: INTERRUPTING THE NEUTRAL FEED MAY CAUSE THE CHANGE IN GROUND-NEUTRAL VOLTAGE TO AFFECT
THE LOAD.
NOTE: ALL CIRCUIT BREAKERS OR FUSES AND ISOLATING SWITCHES SHOULD BE FITTED AS CLOSE TO THE EDP70
PLUS UPS AS POSSIBLE AND MARKED WITH THE LABELS PROVIDED WITH THE UNIT. IT IS ALSO RECOMMENDED A LABEL AS FOLLOWS
UNINTERRUPTIBLE POWER SYSTEM
NO UNAUTHORIZED OPERATION
page
30 --
MI00/10056 rev. 8 —05/2006
31
CAUTION!
All power connection must carried out by qualified
licensed personnel experienced
in wiring this type of equipment
The safety ground wire must
be connected before the power input cables
The correct phase rotation
(phase A leads B leads C)
must be observed on the UPS terminals.
WARNING!
   
    
     
    
     
    
          
 
MI00/10056 rev. 8 — 05/2006-- page
5.1 Electrical connections
WARNING!
All electrical connections must
be made by a qualified electrician
and meet local electrical code standards
Before attempting to connect the mains supply, the reserve/bypass supply or the load, ensure that all supplies, including the battery, are isolated and that all the equipment switches are in their »OFF» position. Open UPS front access panel and remove internal panel over main switches and terminal blocks.
NOTES:
1) Installation must be performed by a qualified electrician. The terminals require the use of
the proper crimp tools and terminals in order to perform an installation in accordance with the National Electrical Code (NEC). The recommended crimp tools, terminals and torque are shown in the following tables:
2) Use Copper Conductors Only
Table 1 – T&B’s Cat. N°s. for terminals and crimp tools
Indentor
(Moveable)
Used ON
EDP70Plus
up to 24kVA
EDP70Plus
above 24kVA
Wire Size
(AWG)
8 D10711 D975 11803 6 E10711 E975 11803 4 F10711 F975 11805 3 F10711 F975 11805 2 G971 G974 WT117 11806 11802
1 G671 G974 11806 1/0 H971 H974 11807 2/0 J971 J974 11808 3/0 K971 K974 11809 4/0 L971 L974 11810
Terminals
Hole for screw
M6 M10
Toggle
hand
Nest
(stationary)
tool
Table 2 – Recommended torque
Torque Type Screw Wrench
Entrelec
M 35/26.FF
-------
(mm)
M6
M10 17
10
(Nm) (lb.in)
4.5
39 340
39
page
32 --
MI00/10056 rev. 8 —05/2006
33
5.2 24 – 12/18/24kVA
Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see
The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the EDP70 PLUS UPS terminals is within +/- 10% of nominal.
The EDP70 PLUS UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box.
Installation and connection should only be carried out by qualified electrical personnel.
Figure 18
.
S2 = Equipment Reserve Switch
S1 = Equipment ON/OFF Breaker
S3 = Equipment By-pass Switch
S4 = Equipment OUTPUT Breaker
Battery Compartment
Figure 18 - 24 – 12/18/24kVA: Switches and Breakers
MI00/10056 rev. 8 — 05/2006-- page
Output, Reserve, Input and External Battery Terminals
Hinged panel security screws
Cable support
Cable channel
Figure 19 - 24 – 12/18/24kVA: Switches
Access to the terminals for electrical connections is as follows:
a) Remove front panel see
b) Remove the two securing screws for the hinged front panel.
c) This exposes the electrical terminal rail, see
d) Remove the screws securing the access plate.
e) Push the interconnection cables up through the cable channel and the access plate.
f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be
terminated with the correct size lugs and connected on the bottom side terminals as marked.
g) Install or start-up batteries see section 13.1
h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate.
i) Replace the terminal board compartment panel and the front cover.
OBSERVE POLARITIES AND ORIENTATIONS.
See Remote Alarms and Computer Interface for connections to these facilities. For optional battery cubicles, refer to section 13.2.
page
34 --
MI00/10056 rev. 8 —05/2006
Figure 18.
Figure 20
35
Computer relay interface - FEMALE
RAU - FEMALE
RS232 - MALE
M6
FRONT
W1V1U1 N PE U V W N
E V R E S E R
T U P N
I
D N U O R G
Modem and Multicom power supplies
sec. max 14 AWG
U2
Y R A
T
M
U
I
P
R
N
P
I
V2 NW2
T U P
T U O
L A N R E T X E
S E
I R E
T T A B
. O
. P
. E
r e g
r a h
C y
r e
t
t a
B
REAR
Label
d e
t
i b
i h n
I
Figure 20 - 24 – 12/18/24kVA: Cable Connections
MI00/10056 rev. 8 — 05/2006-- page
5.3 36 – 24/30/36kVA
Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see figure 13.
The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the EDP70 PLUS UPS terminals is within +/- 10% of nominal.
The EDP70 PLUS UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box.
Installation and connection should only be carried out by qualified electrical personnel.
S3 = Equipment By-pass switch
S4 = Equipment OUTPUT Breaker
S1 = Equipment ON/OFF Breaker
S2 = Equipment Reserve switch
Terminal board compartment
Figure 21 - 36 – 24/30/36kVA: Switches and Breakers
page
36 --
MI00/10056 rev. 8 —05/2006
37
S3 = Equipment By-pass switch
S4 = Equipment OUTPUT Breaker
S1 = Equipment ON/OFF Breaker
S2 = Equipment Reserve switch
Output, Input, Reserve and External Battery Terminals
Access plate
Figure 22 - 36 – 24/30/36kVA: Connections
Access to the terminals for electrical connections is as follows: a) Remove front panel see
Figure 22.
b) Remove the terminal board compartment panel by unscrewing the fixing screws at the front.
c) This exposes the electrical terminal rail, see
d) Remove the screws securing the access plate.
e) Push the interconnection cables up through the access plate.
f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be
terminated with the correct size lugs and connected on the bottom side terminals as marked.
g) Install or start-up batteries see section 13.3 and 13.4.
h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate.
i) Replace the terminal board compartment panel and the front cover.
OBSERVE POLARITIES AND ORIENTATIONS.
See Remote Alarms and Computer Interface for connections to these facilities.
Figure 23
MI00/10056 rev. 8 — 05/2006-- page
Computer relay interface - FEMALE
RAU - FEMALE
FRONT
QS1
Modem and Multicom power supplies
QS4
RS232 - MALE
REAR
QS3
UPE
W2U1V W N U2 V2V1 W1
QS2
E.P.O.
Battery charge
inhibited
PRIMARY
INPUT
GROUND
RESERVE
INPUT
OUTPUT
EXTERNAL
BATTERIES
NEUTRAL (RES/OUT)
Figure 23 - 36 – 24/30/36kVA: Cable Connections
page
38 --
MI00/10056 rev. 8 —05/2006
4/2005
39
5.3 EDP70 PLUS 50/80kVA
Ensure the AC supplies and load are switched OFF. Check that all the EDP70 PLUS UPS Switches (behind the front panel) are switched OFF, see figure 16.
The AC supply cables must be suitable for carrying the maximum supply demand. The voltage drop in the cable should be minimized to ensure the AC supply voltage at the EDP70 PLUS UPS terminals is within +/- 10% of nominal.
The EDP70 PLUS UPS should be connected to the main/reserve supplies and output load via a wall mounted junction box.
Installation and connection should only be carried out by qualified electrical personnel.
S5 = RESERVE OUTPUT switch
S4 = INVERTER OUTPUT Breaker
S3 = BY-PASS switch
S2 = Equipment RESERVE switch
S1 = Equipment ON/OFF Breaker
Terminal board compartment
Figure 24 – 50/80kVA: Switches and Breakers
MI00/10056 rev. 8 — 05/2006-- page
S5 = RESERVE OUTPUT switch
S4 = INVERTER OUTPUT Breaker
S3 = BY PASS switch
S2 = Equipment RESERVE switch
S1 = Equipment ON/OFF Breaker
Output, Input, Reserve and External Battery Terminals
Access plate
Figure 25 – 50/80kVA: Connections
Access to the terminals for electrical connections is as follows:
a) Remove front panel see b) Remove the terminal board compartment panel by unscrewing the fixing screws at the front. e) This exposes the electrical terminal rail, see f) Remove the screws securing the access plate. e) Push the interconnection cables up through the access plate. f) Release the terminal securing nuts by unscrewing fully anti-clockwise. All cables must be terminated with
the correct size lugs and connected on the bottom side terminals as marked.
g) Install or start-up batteries see section 13.3 and 13.4. h) Replace and tighten the terminal securing screws fully clockwise and refit the access plate. i) Replace the terminal board compartment panel and the front cover.
OBSERVE POLARITIES AND ORIENTATIONS.
See Remote Alarms and Computer Interface for connections to these facilities.
Figure 22
.
Figure 23
page
40 --
MI00/10056 rev. 8 —05/2006
41
Computer relay interface - FEMALE
RAU - FEMALE
FRONT
QS1
QS2
RS232 - MALE
Modem and Multicom power supplies
QS3
QS4
REAR
QS5
U U1 V1 W1V W
Y R A M
I R P
W2 N NU2 V2 PE
E
S
L
V
E
A
I
R
T
T
N
E
U P N
I
R
U
R
S
E
P
T
E
E
N
T
T
I
R
A
X
B
E
1 2 3 4 5 6
.
s
d
t
e
O
c
t
.
i
a t
P
b
.
i
n
h
E
o
n
c
i
k
e
c
i
g
t
r
s
a
o
h c
m r
y r
e
e
h t t
T a B
T U P T U O
Figure 26 – 50/80kVA: Cable Connections
MI00/10056 rev. 8 — 05/2006-- page
5.4 Signal connections
a) Emergency Power Off
When the connection between terminals 1 and 2 is opened, the UPS will stop, and it will automatically
restart when the switch is closed. This allows a remote E.P.O. to be installed, in series with the standard one installed inside the UPS. (See Para. 9.1)
Warning: To avoid unauthorized stopping, it is strongly recommended that some form of security switch be used..
b) Battery charge inhibited
By removing the link between terminals 3 and 4, the battery charge will be inhibited, and a warning
message will be displayed.
Possible uses of this could be one, or more, of the following:
connect the above terminals to a contact which will be opened if there is Hydrogen within the battery compartment(s).
In this way the cause of hydrogen generation will be stopped, and a warning about the operating
status of the system will be displayed.
connect the above terminals to a contact which will be opened when the UPS is supplied by a Generator (it should be an auxiliary contact of the Line <-> Generator changeover).
In this way it will be possible to limit the power supplied by the Generator to the only value required to
supply the critical loads, and not to charge the battery until the mains supply returns.
In this way it is possible to use a Generator having a power rating less than the maximum input power
of the UPS.
Also in this case a warning about the operating status of the system will be displayed.
c) Thermostick connector (50/80kVA only)
This connection provides the customer with remote control over the output transformer Overtemperature
Alarm (T
NOTE: If more than one of the above applications (or similar) are installed, the contacts MUST be connected in
= 180°C).
CORE
series.
page
42 --
MI00/10056 rev. 8 —05/2006
43
6.0 CONTROLS
6.1 User Controls
The user controls are situated on the front panel, see Figure 27.
Access to the Equipment Power Switches can be obtained by removing the front cover.
Figure 27 – Control panel
1 2 3 4 5
Illuminated Liquid
Crystal Display
~
R
B
User
Switches Audible Alarm
Cancel Switch
6
Inverter
Start
I
S
~
Inverter
Stop
~
~
~
Display indicators
1) Utility Supply Indicator (Green)
2) Battery Indicator (Green)
3) Inverter Indicator (Green)
4) Static Switch indicator (Green)
5) Reserve Supply Indicator (Green)
6) Warning Indicator (Red)
MI00/10056 rev. 8 — 05/2006-- page
6.2 Control Panel
This allows the user to turn on and reset the inverter. This is normally only used when starting the UPS.
Inverter Shutdown
The switch incorporates a safety feature to prevent inadvertent operation yet still allow rapid shutdown in the event of an emergency. This is achieved by the requirement that the switch be depressed for 2 seconds before the inverter stops during which time the audible alarm will be heard.
Audible Alarm Cancel Switch
This switch cancels the audible alarm. When pressed the red warning light goes from continuous illumination to flashing on and off.
Page Right Control
This switch changes the page headings displayed on the LCD. It also allows the alarm and measurement statuses to be stepped through when examining the power history (refer to section 10.6)
Inverter Start Up
Record Up
This switch changes the record displayed on the LCD to the previous message displayed. When the top of the page has been reached the display will no longer scroll.
Record Down
This switch changes the record displayed on the LCD to the next record on the page. When the bottom of the page has been reached the display will no longer scroll.
page
44 --
MI00/10056 rev. 8 —05/2006
45
7.0 START UP
1. Switch on the AC reserve and the main AC Utility supply to the UPS.
2. Turn on the Utility supply Input, Reserve Input (if fitted) and UPS Output switches located behind the front
panel, see figure 18 for 24kVA, figure 21 for 36kVA or figure 24 for 50/80kVA.
3. Replace the front panel.
4. Press the CANCEL AUDIBLE ALARM switch (see section 6.2)
5. Initially, all the green indicators will flash on the display mimic. After about 30 seconds the supply and
battery indicators should stop flashing.
6. Press the Inverter On push button (I).
7. The inverter should now start and after a delay of approximately 30 seconds the message ‘SYSTEM
NORMAL’, in English, will appear on the liquid crystal display.
8. Select the required language by pressing page right control
message appears on the liquid crystal display. Press the page down control
language is selected. Press the page right control
once more confirm the language selection.
until the ‘SELECT LANGUAGE’
until the required
Thereafter, all messages will appear in the selected language.
8.0 MAINTENANCE BYPASS
The EDP70 PLUS UPS is equipped with Manual Maintenance Bypass systems. If a unit requires servicing, the Manual Maintenance Bypass allows the load to be connected directly to the AC supply so that the unit may be serviced in safety. The following instructions must be followed:
1. Ensure that ‘SYSTEM NORMAL’ is displayed on the LCD. (Note: If ‘SYSTEM NORMAL’ is not displayed check that the inverter is not ‘OUT OF SYNC’, see section 10.7. Turning the inverter off under this fault condition will interrupt the load supply.)
2. Turn off the inverter by pressing the inverter shutdown button for more than 2 seconds
3. Turn the Maintenance Bypass Switch (located behind front panel, see figure 18, 21 or 24) to ON.
4. Turn off the Primary Input, Reserve Input and UPS Output Switches, see figure 18, 21 or 24.
THE LOAD IS NOW SUPPLIED DIRECTLY FROM THE AC UTILITY SUPPLY AND IS NO LONGER PROTECTED BY THE UPS
CAUTION: Some components in the UPS will retain a static voltage even after the switches have been
opened. Also, on the 50/80kVA ratings, the isolating transformer and the relative cooling fans are still supplied from the Bypass.
To return to the normal operating mode, follow the above procedure in reverse.
Note: The EDP70 PLUS UPS must not be left operating with the Maintenance Bypass Switch in the ON
position.
MI00/10056 rev. 8 — 05/2006-- page
9.0 SHUT-DOWN
1. Close down the load in an orderly manner.
2. Push the
(inverter shutdown) button for more than 2 seconds.
3. Turn the main switch to OFF.
Note: If the electricity supply to the site is switched off outside normal working hours, the EDP70 PLUS should be shut
down each evening, by either using the shutdown procedure or wiring in the Emergency Power Off (EPO) function, see figures 20, 23 or 26 (depending on the UPS size).
This will prevent the battery from discharging.
If, on the other hand, the supply to the site is continuous, the EDP70 PLUS should be operated 24 hours a day.
9.1 Installing the EPO
To wire the EPO, open the link between terminal boards 1 and 2 and connect a signal switch, having the characteristics of an emergency button, closed under normal operating conditons and held open mechanically when operated: when the switch is enabled, the inverter and rectifier will stop, the battery relay will be opened and the load will be de-energized
To ensure that the EPO functions correctly, the signal should remain active for a period > 400 msec.
page
46 --
MI00/10056 rev. 8 —05/2006
47
10.0 VISUAL AND AUDIBLE ALARMS
The EDP70 PLUS UPS is equipped with visual and audible alarms which indicate the status of the UPS to the operator. The visual alarms are displayed on the LCD and the mimic panel.
10.1 Silencing Audible Alarm
The audible alarm sounds when the UPS is in an alarm condition. The sound is silenced by pressing the button marked
.
When pressed, the red warning light which is illuminated continuously starts to flash, providing an even clearer indication of the alarm condition, even though the audible alarm has been silenced.
10.2 Mimic
The display mimic consists of a pictorial representation of the functional blocks in the EDP70 PLUS UPS. When the system is in NORMAL OPERATING CONDITION the green indicators are illuminated continuously.
In the event of an ALARM condition the indicators start to flash identifying the part (or parts) of the system in alarm (see figure 19).
Further information on the alarms can be obtained from the LCD by scrolling through the page headings using the button (page right control) until the message on the display describes the functional block in the UPS identified by the flashing LED(s).
The alarms can then be accessed using the procedure is described in detail in section 10.4.
(scrolling up) and (scrolling down) record buttons. This
10.3 Liquid Crystal Display
The display is a 40-character (2 line x 20 character) module which is back lit.
The messages describing the functioning of the system are accessed via the user switches (see figure 18).
MI00/10056 rev. 8 — 05/2006-- page
10.4 Display Page Headings
After initial power up, under normal operating conditions, the main page heading will be displayed:
UPS xx KVA
SYSTEM NORMAL
The first line displays the power rating of the EDP70 PLUS UPS, the second line is the system status.
During normal operating conditions, the display reading always returns to this page heading whenever the user switches are not operated for at least 5 minutes.
By pressing the button marked
once, the battery rectifier heading is displayed:
RECT/BATT ALARMS
NO ALARMS ACTIVE
The second line of the display confirms that the rectifier and battery are functioning correctly.
By pressing the button marked
again, the inverter heading is shown on the display:
INVERTER ALARMS
NO ALARMS ACTIVE
The second line of the display confirms that the inverter is functioning correctly.
By pressing the button marked
again, the load output and reserve supply heading is displayed:
LOAD/RES ALARMS
NO ALARMS ACTIVE
The second line of the display indicates that the UPS load output and reserve supply input are correct.
page
48 --
MI00/10056 rev. 8 —05/2006
49
By pressing the button marked
again, the selected battery test period appears on the display:
BATTERY TEST
WEEKLY
The button marked is pressed to scroll through the 4 battery test period available (WEEKLY, FORTNIGHTLY, MONTHLY and NONE).
The button marked
When the required battery test period appears, press the button marked selected language heading appears on the display.
is pressed to scroll through the list in reverse order.
to select the battery test period and the
SELECTED LANGUAGE
ENGLISH
The button marked is pressed to scroll through the languages available (English, French, German, Italian and Spanish).
The button marked
When the required language appears, press the button marked the main UPS status message.
is pressed to scroll through the list in reverse order.
to select the language and to return the display to
MI00/10056 rev. 8 — 05/2006-- page
If at any time the inverter is blocked then the power history heading appears:
POWER HISTORY
DOWN TO ACCESS
The power history page is described in detail in section 10.6.
The machine measurement signals are accessed from the main page heading as follows:
UPS xx kVA
SYSTEM NORMAL
press once
RECTIFIER
Vdc xxx V Idc xxx A
press once
BATTERY
Vb xxx V Ib xxx A
press once
INVERTER F xx.x Hz
A xxx V B xxx V C xxx V
press once
INVERTER F xx.x Hz
AB xxx V BC xxx V CA xxx V
Displays the output voltage and current supplied by the rectifier.
Displays the battery voltage and the charge or discharge current of the battery (ve = charge, - ve = discharge)
Displays the frequency and phase-neutral voltage at which the inverter is running.
Displays the frequency and phase-phase voltage at which the inverter is running.
press once
RESERVE F xx.x Hz
A xxx V B xxx V C xxx V
press once
RESERVE F xx.x Hz
AB xxx V BC xxx V CA xxx V
page
50 --
MI00/10056 rev. 8 —05/2006
Displays the frequency and the phase-neutral voltage of the reserve supply.
Displays the frequency and the phase-phase voltage of the reserve supply.
51
press once
LOAD F xx.x Hz
A xxx V B xxx V C xxxV
press once
LOAD F xx.x Hz
AB xxx V BC xxx V CA xxxV
press once
LOAD
A xxx A B xxx A C xxx A
press once
Displays the frequency and phase-neutral voltage supplied to the load.
Displays the frequency and phase-phase voltage supplied to the load.
Displays the current supplied to the load.
press once
press once
press once
LOAD
A x% B x% C x%
LOAD P.F. 0.99
P = 80kW s = 80kVA
TIME ON INVERTER xxg: xxh: xxm: xxs
TIME ON RESERVE
xxg: xxh: xxm: xxs
Displays the load capacity percentage of the UPS rated value.
Displays the Peak Factor of the load current.
Displays the total time the load has been supplied by the inverter since the machine was last switched off.
Displays the total time the load has been supplied by the reserve since the machine was last switched off.
MI00/10056 rev. 8 — 05/2006-- page
press once
LAST MAINS FAILURE
xxd: xxh: xxm: xxs
press once
MAINS FAILURE yy
xxgg: xxh: xxm: xxs
press once
TOTAL MAINS FAILURE yy
xxg: xxh: xxm: xxs
press once
REV A. XX xx-xx-xx
10h00yyy
Displays the duration time of the most recent Mains Failure
Displays the number of mains failures and the total duration of these failures since the machine was last switched off.
Displays the total number of mains failures and their total duration since the machine was installed.
Displays the code for the version of software resident (and relevant data) within the EDP70 PLUS UPS system
page
52 --
MI00/10056 rev. 8 —05/2006
53
The measurement signals are accessed from the battery rectifier page as follows:
Normal operating mode
RECT/BATT ALARMS
NO ALARMS ACTIVE
press once
RECTIFIER
Vdc xxx V Idc xxx A
press once
BATTERY
Vdc xxx V Ib xxxx A
Displays the output voltage and current supplied by the rectifier.
Displays the battery voltage and the charge or discharge current of the battery (ve = charge, - ve = discharge)
The measurement signals are accessed from the inverter page as follows:
Normal operating mode
INVERTER ALARMS
NO ALARMS ACTIVE
press once
INVERTER F xx.x Hz
A xxx V B xxx V C xxx V
press once
INVERTER F xx.x Hz
AB xxx V BC xxx V CA xxx V
press once
INVERTER
A xxx A B xxx A C xxx A
Displays the frequency and phase-neutral voltage at which the inverter is running.
Displays the frequency and phase-phase voltage at which the inverter is running.
Displays the current at which the inverter is running.
MI00/10056 rev. 8 — 05/2006-- page
The measurement signals are accessed from the load output - reserve supply page as follows:
Normal operating mode
LOAD/RES ALARMS
NO ALARMS ACTIVE
press once
LOAD f xx.x Hz
A xxx V B xxx V C xxx V
press once
LOAD f xx.x Hz
AB xxx V BC xxx V CA xxx V
press once
LOAD
Displays the frequency and phase-neutral voltage supplied to the load.
Displays the frequency and phase-phase voltage supplied to the load.
Displays the current supplied to the load.
A xxx A B xxx A C xxx A
press once
Displays the load capacity percentage of the UPS rated
LOAD
A x% B x% C x%
value.
press once
LOAD P.F. 0.99
P = 80kW s = 80kVA
press once
RESERVE F xx.xHz
A xxx V B xxx V Cxxx V
press once
RESERVE F xx.xHz
AB xxx V BC xxx V CA xxx V
page
54 --
MI00/10056 rev. 8 —05/2006
Displays the Peak Factor of the load current.
Displays the frequency and phase-neutral voltage supplied to the reserve line.
Displays the frequency and phase-phase voltage supplied to the reserve line.
55
10.5 Abnormal operating mode messages
Under abnormal operating conditions, the normal functioning heading on the main page
UPS xx KVA
SYSTEM NORMAL
is replaced with the alarm page:
UPS xx KVA
SYSTEM ALARM
If at least 1 alarm is activated for each block; the »NO ALARMS ACTIVE» message in the second line on the display is replaced with the first active alarm. Whenever there is more than one active alarm, they can be scrolled through using the
and keys.
Each message is associated with one of the following conditions:

Conditions which do not adversely affect the normal functioning of the machine are identified under this heading.
No action is required on the part of the operator.

Transitory conditions which can either return to normal condition or result in a permanent fault are identified under this heading. No action is required on the part of the operator.

Faults are identified under this heading. The intervention of a qualified technician is required.
Alarms which do not come under any of these headings do not require any action if arising separately.
MAIN PAGE HEADING ALARMS
MESSAGE CONDITION
TESTING BATTERY
EPO ACTIVE
NOT CALIBRATED
TESTING AUTONOMY
SYSTEM TEST MODE
NORMAL
WARNING
FAULT
WARNING
FAULT
MI00/10056 rev. 8 — 05/2006-- page
When the battery is discharging, the machine displays the residual autonomy and the discharging time

information.
1. If no information on autonomy is available, then the following message is displayed:
BATTERY DISCHARGING
AUT calc DIS xx min
where xx represents the discharging time
2. Where AUTONOMY information is available, the following message will appear:
BATTERY DISCHARGING
AUT yy min DIS xx min
where yy represents the residual autonomy of the batteries.

In overload condition, the machine calculates the time remaining before the inverter is switched off.
Under this condition, the following message is displayed:
OVERLOAD
INV STOP xx min: yy:s
If the inverter is inhibited due to overloading, the time at which the inverter will be reactivated is displayed, with the following message:
STOP DUE TO OVERLOAD
RESTART IN xx min: yy: s
page
56 --
MI00/10056 rev. 8 —05/2006
57
RECTIFIER/BATTERY ALARMS
MESSAGE CONDITION
NOT CALIBRATED
DC FEEDBACK FAULT
VERIFY DC FEEDBACK
PRIMARY SUPPLY FAULT
PHASE SEQUENCE ERROR
BATTERY FAULT
PCB SUPPLY FAULT
BATT CONTACTOR OPEN
BATTERY DISCHARGING
SHUTDOWN IMMINENT
DC VOLTAGE HIGH
DC VOLTAGE LOW
INPUT SWITCH OPEN
HARMONIC FILTER OPEN
RECTIFIER ALARM
RECTIFIER INHIBITED
RECTIFIER BLOCKED
BATT. CHARGE INHIBIT
FAULT
FAULT
NORMAL
WARNING
FAULT
FAULT
FAULT
-
WARNING
WARNING
FAULT
WARNING
FAULT
FAULT
FAULT
WARNING
FAULT
WARNING
MI00/10056 rev. 8 — 05/2006-- page
INVERTER ALARMS
MESSAGE CONDITION
NOT CALIBRATED PCB SUPPLY FAULT OUT OF SYNC
DESATURATION
OVER TEMPERATURE
BYPASS SWITCH CLOSED SHUTDOWN IMMINENT
DC VOLTAGE HIGH DC VOLTAGE LOW INVERTER NOT RUNNING
INVERTER INHIBITED INVERTER BLOCKED
INVERTER VOLTS HIGH INVERTER VOLTS LOW OVERLOAD
STOP DUE TO OVERLOAD
CURRENT LIMIT
INV.ST. SWITCH FAULT INV.FREQ.OUT RANG. 8%
INV. FEEDBACK FAULT VERIFYING INV. FREQ.
VERIFYING BATT. CONT.
INV.FREQ.OUT 1%
FAULT
FAULT
WARNING
FAULT
FAULT
FAULT
WARNING
FAULT
WARNING
FAULT
FAULT
FAULT
FAULT
FAULT
WARNING
FAULT
WARNING
FAULT
FAULT
FAULT
-
-
FAULT
page
58 --
MI00/10056 rev. 8 —05/2006
59
LOAD/RESERVE ALARMS
MESSAGE CONDITION
NOT CALIBRATED LOAD ON RESERVE
LOAD NOT SUPPLIED BYPASS SWITCH CLOSED
RESERVE SUPPLY FAULT RESERVE FREQ FAULT
RESERVE VOLTS HIGH RESERVE VOLTS LOW
ST. SW. BLOCKED ON INV
ST. SW. BLOCKED ON RES INV.ST. SWITCH FAULT
OVERLOAD OUTPUT SWITCH OPEN
RESERVE SWITCH OPEN
PHASE SEQUENCE ERROR RESERVE INHIBITED
BACKFEED PROT ACTIVE
FAULT
WARNING
FAULT
FAULT
WARNING
WARNING
WARNING
WARNING
FAULT
FAULT
FAULT
WARNING
FAULT
FAULT
FAULT
WARNING
FAULT
MI00/10056 rev. 8 — 05/2006-- page
10.6 Power History
The power history is only available when the inverter is blocked; it provides a visual display of the status of the alarms and measurements over a period of 10 seconds before and 1 second after the inverter stops in steps of 0.1 s. The power history is lost when the inverter is restarted.
Figure 28 provides a graphic representation of how to access the Power History.
Figure 28: Power History Structure
LOAD
ALARMS
Time
(seconds)
-10
Inverter
Shutdown
+1
AlarmsMeasurements
Initial
BATTERY TEST
SELECT
POWER HISTORY
UP TO EXIT
POWER HISTORY
DOWN TO ACCESS
POWER HISTORY MATRIX
position
0
Measurement
RECTIFIER +0.3 SEC
VDC = 327V IB = 5A
page
60 --
MI00/10056 rev. 8 —05/2006
Typical Power History Display
Alarm
-5.3 SEC ON
OVER TEMPERATURE
61
10.7 Battery Test
The EDP70 PLUS has an automatic battery control function which checks the condition of the battery periodically without affecting the output in any way. While this test is being carried out, the message »TESTING BATTERY» will appear. This test can also be activated manually. Return to the main title page so that ‘SYSTEM NORMAL’ is displayed.
system normal message
UPS xx KVA
SYSTEM NORMAL
PRESS SIMULTANEOUSLY
UPS xx KVA
TESTING BATTERY
(The test is disabled if the BATTERY TEST selected is NONE)
The battery test is underway and takes approx. 1 minute. If the test is completed without giving off any alarm, then the system returns to normal operating mode; otherwise, the alarm message »BATTERY FAULT» is displayed.
10.8 Battery Autonomy Test
The EDP70 PLUS has a battery autonomy test which disables the rectifier manually. To carry out this test, return to the main title page so that ‘SYSTEM NORMAL’ is displayed.
system normal message
UPS xx KVA
SYSTEM NORMAL
PRESS SIMULTANEOUSLY and keep pressed for 2 seconds
UPS xx KVA
TESTING AUTONOMY
(The test is diabled if the BATTERY TEST selected is NONE)
The battery starts to discharge completely thereby allowing the autonomy to be checked. Once the battery has been discharged, the test comes to an end automatically and the rectifier restarts.
To interrupt BATTERY autonomy Test, at any time: PRESS SIMULTANEOUSLY and keep pressed for 2 seconds
10.9 Resetting data loss manually
If the message »NOT CALIBRATED» appears on the main title page, this means that data (language and total number of mains failures) which do not directly affect the functioning of the machine have been lost. Despite this, data has still been lost and the intervention of a qualified technician is required.It is, nevertheless, possible to reset the normal operating mode by selecting the language desired as described under sect. 7.0.
MI00/10056 rev. 8 — 05/2006-- page
11.0 COMPUTER INTERFACE
11.1 AS400
The EDP70 PLUS UPS is fitted with a 9 pin female ‘D’ type socket for direct connection to a IBM AS/400 computer or equivalent, see Figure 29. This facility can also be used with operating system software of other manufacturers. The function of the pins on the socket are shown below:
Pin
Number
8 EDP70 PLUS UPS ON The UPS is supplying the load.
6 RESERVE TO LOAD The reserve AC supply is supplying the load.
9 UTILITY SUPPLY FAIL The AC utility supply to the UPS has failed.
7 BATTERY LOW The battery capacity is at a minimum and the inverter
5 COMMON All the above are connected to common when the
DESCRIPTION FUNCTION NUMBER
will shortly shut down and the load will be automatically transferred to the reserve AC supply.
function is true.
Figure 29 EDP 70 Plus Computer Interface Pin Layout
page
62 --
MI00/10056 rev. 8 —05/2006
63
11.2 RS232
The EDP70 PLUS UPS is fitted with a 9 pin male ‘D’ type plug which enables a communication link to be established between a computer and the microprocessor controller in the EDP70 PLUS UPS. The link allows the Chloride ‘EASY PLUS’ and ‘LIFE 2000’ software to be run on an IBM compatible PC. The link also allows the communications with a Master JBUS and Multicom/LIFE 2000 adapter. The function of the pins on the socket are shown below:
The function of each pin is the following :
Pin 1 DCD (Data Carrier Detect) Pin 2 RXD (Received data) Pin 3 TXD (Transmitted data) Pin 4 DTR (Data terminal ready) Pin 5 GND (Ground) Pin 6 DSR (Data Set Ready) Pin 7 RTS (Request To Send) Pin 8 CTS (Clear To Send)
The signals applied on each pin follows the standard EIA RS232.
12.0 REMOTE ALARMS
Remote indication of the state of the EDP70 PLUS UPS is provided by a 15 pin female ‘D’ type socket and is designed to be used in conjunction with the Chloride EDP Remote Alarm Unit. The function of the pins on the socket are shown below:
Figure 30 EDP70 PLUS Remote Alarms Pin Layout
Pin 1 System normal signal Pin 2 System normal and system summary alarm ground Pin 3 Inverter fail signal Pin 4 Inverter fail ground Pin 5 Reserve to load signal Pin 6 Reserve to load ground Pin 7 Primary supply failure signal Pin 8 Primary supply failure ground Pin 9 Shutdown imminent signal Pin 10 Shutdown imminent ground
Pin11, 12 supply: 18V/200mA nominal AC output
Pin 15 Summary alarm signal
Pins 1,2 and15 are available for use as a remote summary alarm indicator in alternative to the Chloride Remote Alarm Unit. All pins are volt free contacts which are capable of carrying a current of 0.5 A and switching 30 V.
MI00/10056 rev. 8 — 05/2006-- page
13.0 BATTERIES
13.1 EDP70 PLUS/24/18/12 : Battery Installation/Start-up
SAFETY
- Ensure all the Switches are turned to OFF before starting to install the batteries. If any Switches are not turned to OFF the equipment and battery may be damaged. It is also essential for safety reasons that the battery connectors be disconnected before removing the fuse F2 (located behind the hinged panel, see Figure 31) to interrupt the battery circuit.
- Stand on a rubber mat and use insulated tools.
- Remove all personal effects, rings, watches, pens, which might cause a short circuit when working on the battery. Batteries are live at all times and short circuits can melt metals and cause injury, damage or fire.
- DO NOT smoke or use naked flames, and avoid creating arcs or sparks when working on the equipment; do not wear clothes which may generate static electricity.
- The sealed lead-acid batteries contain sulphuric acid. If a battery container is broken any acid leaking will cause burns on contact with skin and attack metal, paint and fabrics. Any area contaminated with acid should be thoroughly washed with large volumes of clean water. Rubber gloves should be worn when handling damaged batteries.
i) Remove front panel see figure 10
ii) Remove the battery compartment panel by unscrewing the fixing screws at the front.
DO NOT remove the safety ground connection. Battery connections are provided with the UPS. Each battery is provided with fastenings.
Internal batteries are housed on three shelves at the bottom of the equipment as shown on Figure 31.
If the batteries are fitted, starting with the lower shelf first, remove the packaging. Connect the batteries to the UPS using the plug/socket connectors provided.
Starting with the lower shelf, fit and connect the batteries. Ensure that the polarities are correct in accordance with the relevant battery layout diagram.
For each shelf make sure that the polarities are correct and the overall battery shelf voltage is at least 108v for the bottom two shelves and 72v for the top shelf.
Replace the fuse F2, then connect the intershelves connectors and all panels in reverse order of removal before operating the equipment.
page
64 --
MI00/10056 rev. 8 —05/2006
65
13.2 EDP70 PLUS/24/18/12 : Optional Battery Cubicle
The battery autonomy can be increased by employing either one or two optional battery cubicles. Both the UPS and battery cubicles are similar in appearance, however, there is no display panel in the battery cubicle.
All cabinets (UPS, BATTERIES, TRANSFORMER, PDU, MAINTENANCE BYPASS PANEL, etc.) must be connected to a grounding system complying with national safety regulations. Cables connecting the cabinets to the grounding system must be sized according to National Electrical Code requirements.
The battery cubicle has independent fuse located internally. To connect the battery cubicle to the EDP70 PLUS UPS follow the following procedure:
1. Shutdown the UPS using the procedure set out in section 9. Access the terminal rail.
2. Disconnect the battery connectors of the internal battery, then remove the fuse F2 located behind the
hinged panel, see Figure 31.
3. Be sure that the battery on the cubicle are disconnected. Remove the fuse of the battery cubicle.
4. Wire the cubicle according to the extension battery cubicle wiring instructions and the relevant battery
layout diagram.
5. Replace the fuses F2 both on the cubicle and the UPS, then connect all the intershelves connectors, and all the panels and restart UPS using the procedure set out in section 7.
Figure 31- EDP70 PLUS/24/18/12: Internal Battery Shelves
FUSE F2
SHELF RETAINING SCREW
SHELF
GUIDE
MI00/10056 rev. 8 — 05/2006-- page
13.3 EDP70 PLUS above 24KVA: Battery Installation/Start-up
SAFETY
- Ensure the Equipment ON/OFF Switch is turned to OFF before starting to install the batteries. If the Equipment ON/OFF Switch is not turned to OFF the equipment and battery may be damaged. It is also essential for safety reasons that the battery connectors are disconnected before to remove the fuse of the battery cubicle.
- Stand on a rubber mat and use insulated tools.
- Remove all personal effects, rings, watches, pens, which might cause a short circuit when working on the battery. Batteries are live at all times and short circuits can melt metals and cause injury, damage or fire.
- DO NOT smoke or use naked flames and avoid creating arcs or sparks when working on the equipment; do not wear clothes which may generate static electricity.
- The sealed lead-acid batteries contain sulphuric acid. If a battery container is broken any acid leaking will cause burns on contact with skin and attack metal, paint and fabrics. Any area contaminated with acid should be thoroughly washed with large volumes of clean water. Rubber gloves should be worn when handling damaged batteries.
13.4 EDP70 PLUS above 24KVA: Battery Cubicle
For these sizes of EDP70 PLUS, the batteries are housed in battery cubicles. Both the UPS and battery cubicles are similar in appearance, however, the battery cubicle does not have a dusplay.
All cabinets (UPS, BATTERIES, TRANSFORMER, PDU, MAINTENANCE BYPASS PANEL, etc.) must be connected to a grounding system complying with national safety regulations. Cables connecting the cabinets to the grounding system must be sized according to National Electrical Code requirements.
The battery cubicle has a separate fuse, located internally. To connect the battery cubicle to the EDP70 PLUS UPS follow the following procedure:
1. Shutdown the UPS using the procedure set out in section 9. Access the terminal rail.
2. Be sure that all the batteries in the cubicle(s) are disconnected. Remove the fuses from the battery
cubicle(s).
4. Wire the cubicle according to the extension battery cubicle wiring instructions and the relevant battery layout diagram.
5. Replace the fuses on all the cubicles then connect all the inter-shelf connectors, and replace all the panels and restart UPS using the procedure described in section 7.
14.0 MAINTENANCE AND SPARE PARTS
The EDP70 PLUS UPS is designed to be virtually user maintenance free, requiring only the occasional wipe with a damp cloth or non-abrasive cleaner.
Spares kits are available for the EDP70 PLUS series, please contact a Chloride UPSystems service center for details.
page
66 --
MI00/10056 rev. 8 —05/2006
67
EDP70 PLUS SYSTEM LOG
It is recommended that any maintenance action or failure of the SYSTEM be recorded in this log.
Date Time Event Action/Result
MI00/10056 rev. 8 — 05/2006-- page
Loading...