Chicago Faucet 115.840.21.1 Installation Manual

Exposed Electronic Flushometer Valve – Installation Instructions
Urinal Models Toilet Models
Retrofit Right Rough-In 115.840.21.1 Retrofit Right Rough-In 115.844.21.1 Retrofit Left Rough-In 115.841.21.1 Retrofit Left Rough-In 115.845.21.1 Complete Right Rough-In 115.842.21.1 Complete Right Rough-In 115.846.21.1 Complete Left Rough-In 115.843.21.1 Complete Left Rough-In 115.847.21.1
Box Contents:
Retrofit Models Complete Models Flushometer Body Flushometer Body 4 - “AA” Batteries 4 - “AA” Batteries Battery Holder Battery Holder Allen Wrench Allen Wrench Inlet Filter Inlet Filter
Control Stop Valve Spud Tube with Vacuum Breaker and Nuts Spud Flange
** For Retrofit models, skip to Step 3
Step 1 – Install Control Stop Valve
Thread the 1" or 3⁄
4" Stop Valve to the pipe nipple extending
from the wall.
The water inlet to the flushometer body should be aligned with the spud inlet on top of the fixture (i.e. urinal) but at a minimum of 2–
3
4".
Pipe sealant is acceptable on the connecting thread with the pipe nipple only.
Flush water line to clear debris by opening Stop Valve momentarily
Step 2 – Install Spud Tube with Vacuum Breaker and Flange
Place Spud Flange on top of fixture
Assemble: Spud Coupling, Spud Nut, Slip Ring, and Rubber Washer onto Spud Tube with Vacuum Breaker
Insert Spud Tube with parts into Spud Inlet on top of fixture
Hand Tighten
Settings:
(Adjustments Made with Service Remote Control 115.830.00.1) Flush Volume (Specified when ordering)
Model
Default Adjustment Range Increment Urinal 0.5 or 1.0 or 1.5 (GPF) 0.3 – 1.5 0.1 Toilet 1.6 or 3.5 (GPF)1.0 – 3.5 0.1
Dwell Time (Time a person must be in range)
Model
Default Adjustment Range Increment All 7 (Sec.) 1 – 10 1
Flush Delay (Delay after person leaves range to flush start)
Model Default
Adjustment Range Increment
All 2 (Sec.) 0 – 5 1
Reseal Volume (Optimizes flush performance)
Model Default
Adjustment Range Increment
Toilet 0.3 – 0.5 (GPF) 0.1 – 0.9 0.1
Dynamic Flush (Reduces GPF in very frequent usage periods)
Model Default Adjustment Range Urinal Off On/Off
User Detection Range (Adjusts max. range of sensor)
Model
Default Adjustment Range Incr
ement Urinal 20" 15" – 42" 1 Toilet 30" 15" – 42" 1
* See the Service Remote Control documentation for many other adjustable settings