

2
Congratulations on your purchase of a Chesney’s stove.
Please note that it is a legal requirement under England and Wales
Building Regulations that the installation of the stove is either carried out
under Local Authority Building Control approval or is installed by a
Competent Person registered with a Government Approved Competent
Persons Scheme. HETAS Ltd operate such a scheme. Further information
can be found at
www.hetas.co.uk
This appliance will become hot whilst in operation. It is recommended that
a suitable guard be used for the protection of young children, the elderly or
infirm.
The Chesney’s range of stoves are all CE approved.
This stove must not be adapted or modified in any way.
All Chesney’s stoves have been approved by HETAS as intermittent
operating appliances
Chesney’s stoves are now all DEFRA exempt appliances that can be used
in Smoke Control Zones only when the Smoke Tab is removed and
installed in accordance with the current Building Regulations. The complete
list is available at www.hetas.co.uk/manufacturer/defra-exemption
Activation of the warranty is completed by returning the
warranty form to Chesney’s or filling out the online
registration at
www.chesneys.co.uk/warranty/registration.asp

3
Contents
Section Page
1 Technical Specifications and Dimensions 4
2 Distance to Combustibles 10
3 Pre Installation 11
4 Installation 13
5 Converting Top to Rear Exit 14
6 Smoke Control 15
7 Apollo 4 & 8 Installation 17
8 Door Seal Replacement & Door Handles 19
9 Commissioning 20
10 The Curing Process 23
11 Stove Paint Application Instructions 24
12 First Lighting & Operation 25
13 Maintenance 31
Appendix
Dealer & Installer Details 33
Annual Service Record 34
Warranty Registration 35

4
1. Technical Specifications and Dimensions
Wood Burning 4 Series
Belgravia
Shoreditch
Salisbury
Nominal heat output kW
4.6 4.5 4.6 4.6
Mean CO emission (at 13 % 02)
0.76 0.68 0.76 0.37
Mean flue Gas temperature oC
167 200 262 262
Flue gas mass flow g/s
3.2 3.5 3.6 3.6
Total efficiency %
84.0 82 80 80
Refuelling mins
45 60 45 60
Test fuel wood kg
1 1 1 1.38
Fuel size: 2 x logs mm
at 13-14 % moisture
300 x
130 dia
300 x
130 dia
300 x
130 dia
300 x
130 dia
Maximum hearth temp oC
38.1 N/A 33 55
Dimensions / Weight
Refer to Figure one on page 8
kg
Beaumont 552 456 108 408 305 73
Belgravia 552 456 108 408 305 73
Shoreditch 543 398 108 408 294 78
Shoreditch LS 687 398 108 552 294 88
Shoreditch XLS 787 398 108 652 294 104
Salisbury 534 402 108 408 335 72
Alpine 586 410 110 442 308 74
Milan 750 448 155 580 340 78
Apollo Fire Cube size 409 w x 550 h x 320 d 69
Note: Flue diameter 130mm
Flue Draught at nominal output is 12 Pascal (closed door)

Nominal heat output kW
4.9 4.9 4.9
Mean CO emission (at 13 % 02)
0.23 0.23 0.23
Mean flue Gas temperature oC
211 211 211
Flue gas mass flow g/s
3.6 3.6 3.6
Total efficiency %
84.5 84.5 84.5
Refuelling mins
50 50 50
Test fuel wood kg
1 1 1
Fuel size: 2 x logs mm
at 13-14 % moisture
300 x
150 dia
300 x
150 dia
300 x
150 dia
Maximum hearth temp oC
50 50 50
Dimensions / Weight
Refer to Figure one on Page 8
kg
Salisbury 534 482 108 408
335 79
Shoreditch 543 478 108 408
294 84
Note: Flue diameter 130mm
Flue Draught at nominal output 12 Pascal (closed door)

Nominal heat output kW
7.0 / 6.0 6.2 / 6.0 6.2 / 6.7
Mean CO emission (at 13 % 02)
0.34 / 0.37 0.34 /
0.37
0.3 / 0.23
Mean flue Gas temperature oC
265 / 199 324 / 294 324 / 294
Flue gas mass flow g/s
3.7 / 4.1 5.4 / 4.1 5.4 / 3.7
Total efficiency %
85.1 / 80.4 85.1 / 80 85.1 / 80.4
Refuelling mins
45 / 150 45 / 150 60 / 60
Test fuel wood / ancit Kg
1.5 / 2.1 1.5 / 2.1 2.09 / 2.1
Fuel 2 x logs mm 13-14 % moisture
Ancit per 2.1kg 2.3 % moisture
300 x 150
dia
300 x 150
dia
300 x 150
dia
Maximum hearth temp oC
56.1 56 55 to log store
Dimensions / Weight
Refer to Figure one on Page 8
kg
Beaumont 704 522 155 541 395 128
Belgravia 704 522 155 541 395 120
Shoreditch 685 448 155 531 393 120
Shoreditch LS 803 448 155 648 393 132
Shoreditch XLS 903 448 155 748 393 139
Salisbury 653 450 155 505 440 123
Shipton 634 488 155 480 395 131
Alpine 686 460 140 523 386 125
Milan 920 525 195 740 472 127
Note:
Milan and Shoreditch LS and XLS can be installed with skirting
boards 50mm from rear of the stove to a maximum height of 200mm
Flue diameter 150mm
Flue Draught at Nominal output 12 Pascal (closed door)

Belgravia
Shipton
Shoreditch
Salisbury
Nominal heat output kW
8.3 / 8.5 10.2 / 8.1
Mean CO emission (at 13 % 02)
0.23 /0.19 0.70 / 0.18
Mean flue Gas temperature oC
360 / 331 328 / 319
Flue gas mass flow g/s
6.0 / 6.0 5.3 / 4.2
Total efficiency %
76.7/75.1 78.7 /79.9
Refuelling mins
60 / 120 45 / 60
Test fuel wood /ancit kg
2.5 / 2.5 2.5 / 2.5
Fuel 3 x logs mm 13-14 % moisture
Ancit per 2.5kg 2.3 % moisture
360 x 150 dia
360 x 150 dia
Maximum hearth temp oC
70.3 n/a
Dimensions / Weight
Refer to Figure one on Page 8
kg
Beaumont 704 642 155 538 395 148
Belgravia 704 626 155 538 389 148
Shipton 634 608 155 480 379 151
Salisbury 653 570 155 505 428 143
Shoreditch 685 568 155 531 378 155
Shoreditch LS 803 568 155 650 378 172
Shoreditch XLS 903 568 155 750 378 180
Apollo Fire cube size 600 w x 616 h x 384 d 124
Note: Flue diameter 150mm
Flue Draught at Nominal output 12 Pascal

2. Distance to Combustibles
4 Series
Belgravia 400 350 300
Shoreditch 400 350 300
Shoreditch LS 400 350 300
Shoreditch XLS 400 350 300
Salisbury 400 350 300
Alpine 150 100 300
Milan 45 125 300
Apollo N/A 100 600
5 Series
Shoreditch 380 320 450
Salisbury 380 320 450
6 Series
Beaumont 500 650 300
Belgravia 500 650 300
Shoreditch 500 650 300
Shoreditch LS 500 650 300
Shoreditch XLS 500 650 300
Salisbury 500 650 300
Shipton 500 650 300
Alpine 450 350 300
Milan 45 200 300
8 Series
Beaumont 650 600 400
Belgravia 650 600 400
Shipton 650 600 400
Salisbury 650 600 400
Shoreditch 650 600 400
Shoreditch LS 650 600 400
Shoreditch XLS 650 600 400
Apollo
Side 100mm up to 100mm from front face
600

3. Pre Installation
This appliance must be fitted in accordance with the current
Building Regulations and by an approved HETAS registered installer.
Note: This appliance is heavy and must be handled with care.
The appliance is supplied fully assembled for a top flue arrangement.
The lid, door and internal parts can all be removed to reduce the stove
weight during installation
The paint is soft and vulnerable to marking; refer to the maintenance
section.
Chesney’s stoves must be connected to a suitable chimney. Chesney’s
strongly recommend using a complete and compliant chimney lining
system.
Inside the stove you will find an Installation and user manual and a pair of
Chesney’s Gauntlets. The multi-fuel stoves also have an ash pan and tool.
Ventilation
Please refer to Document J section 2 (table 1) Outside Air Kits are
available please ask your stockist.
The installation of extract ventilation or other appliance that requires air for
combustion in the same area are not recommended and will effect this
appliance. Refer to page 12 Flue Requirements
Chesney’s recommend an appropriate spillage test be conducted with all
appliances post installation.
Air inlet grilles must be so positioned that they are not liable to blockage.