A11/24/2015Original manual
B02/22/2016Add information on thermocouple to the end of 5500 VHP Operation section
C09/08/2016Add information for 5500 MP model; update Filling Weight Table
The new Perma-Cyl FlexFill storage vessel is equipped with
a top and bottom ll circuit in place of the top oat assembly
so the driver can control the tank pressure while lling the
Perma-Cyl
uses the ullage technology adopted from our LNG fueling
system which allows the inner vessel to safely go liquid full
Once the meter on the Orca™ MicroBulk Delivery System
senses a ow rate reduction, the pump is automatically shut
down. This patented automatic dispensing system simulates
the same process drivers have used for years to safely ll
Perma-Cyl storage tanks without venting
The FlexFill feature is critical for applications like laser
assist gas and medical gas supply where a signicant drop in
downstream pressure during the Perma-Cyl tank rell could
result in equipment alarms. The new FlexFill feature works
with all Orca delivery unit models, both new and existing
units
*Perma-Cyl tanks with the FlexFill Piping Option are
presently not approved for service with CO2.
®
MicroBulk Storage System. The FlexFill option
Product Highlights
• Allows top and bottom lling for accurate pressure
control in the Perma-Cyl tank during rell
• Provides the same safe, single hose, no-loss, auto shutoff ll with the Orca delivery system as the top ll oat
design
Product Manual
This manual contains information regarding the safe
operation and maintenance of a Perma-Cyl tank w/ FlexFill
piping option. It should be thoroughly read and understood
by anyone that operates the equipment.
The safety requirements for operating the tank and handling
or transporting extremely cold liquid products are shown
in the Safety section Use this safety section as a “Safety
Checklist” each time the equipment is being used.
The Introduction/Operation section discusses the general
features of the tank and the theory of operation.
In the Installation section there are illustrations for how to
uncrate and install the tank
The remaining sections describe the specic tank models
covered by this manual. They contain warranty information,
troubleshooting help, technical specications/illustrations,
and parts lists. They should be reviewed rst and referred to
as the rest of the manual is read
The Illustrations & Parts Listing section contains schematics,
piping illustrations, and parts list that show a reference
number for each component used on the tank. The reference
numbers may refer to the same functional component
between the various models The reference numbers will be
used throughout this manual to draw specic attention to a
component while describing its function, operation, or repair.
• Backward compatible - works with new and existing Orca
delivery units without modications
• Incorporates the lling technology from the LNG vehicle
& dispenser system
• Comes standard with dual relief valves and rupture discs
Throughout this manual safety precautions will be designated
as follows:
Warning! Description of a condition that
can result in personal injury or
death.
Caution! Description of a condition that
can result in equipment or
component damage.
Note: A statement that contains information
that is important enough to emphasize or
repeat.
Acronyms / Abbreviations
The following acronyms / abbreviations are used throughout
this manual:
Ar Argon
ASME American Society of Mechanical Engineers
BARG Pressure (Metric) Gauge
CGA Compressed Gas Association
CO2 Carbon Dioxide
DOT Department of Transportation
FPT Female Pipe Thread
ID Inner Diameter
Kg Kilogram
LAR Liquid Argon
MA WP Maximum Allowable Working Pressure
N2 Nitrogen
Nm3 Normal Cubic Meters
Nm3h Normal Cubic Meters/Hour
NER Normal Evaporation Rate
NFPA National Fire Protection Association
NPT National Pipe Thread
O2 Oxygen
PB Pressure Builder
PSI Pounds per Square Inch
PSIG Pounds per Square Inch (Gauge)
SCF Standard Cubic Feet
SCFH Standard Cubic Feet/Hour
UFC Uniform Fire Code
While Chart equipment is designed and built to the most
rigid standards, no piece of mechanical equipment can
ever be made 100% foolproof. Strict compliance with
proper safety and handling practices are necessary when
using a cryogenic manifold device or other compressed
gas equipment. We recommend that all of our customers
re-emphasize safety and safe handling practices to all their
employees and customers. While every possible safety
feature has been designed into the Perma-Cyl® MicroBulk
Storage System w/ FlexFill
operations are anticipated, it is essential that the customer
carefully read and fully understand all Warning and Caution
notes listed below
Warning! The Perma-Cyl tank, with its
Warning! Any welding that is done on the
™
Piping Option and safe
stainless steel support system
is designed, manufactured, and
tested to function normally for
many years of service. It is never
safe to drop a liquid cylinder or
let it fall over in oxygen or any
cryogenic service. In the event
a liquid cylinder is inadvertently
dropped, tipped over, or abused,
slowly raise it to its normal
vertical position and immediately
open the vent valve to release
any excess pressure in a safe
manner. As soon as possible,
remove the liquid product from
the vessel in a safe manner.
If the vessel has been used in
oxygen service, purge it with an
inert gas (nitrogen). If damage is
evident or suspected, return the
unit to Chart prominently marked
“LIQUID CYLINDER DROPPED,
INSPECT FOR DAMAGE”.
outside of the Perma-Cyl System
can cause loss of vacuum and
will VOID any warranty on the
unit.
Warning! Before removing cylinder parts
or loosening ttings, completely
empty the liquid cylinder of
liquid and release the entire
vapor pressure in a safe manner.
External valves and ttings can
become extremely cold and may
cause painful burns to personnel
unless properly protected.
Personnel must wear protective
gloves and eye protection
whenever removing parts or
loosening ttings. Failure to do
so may result in personal injury
because of extreme cold and
pressure in the cylinder.
Caution! Only use replacement equipment
which is compatible with liquid
oxygen and has been cleaned
for oxygen use. Do not use
regulators, ttings, hoses, etc.,
which have been previously
used in compressed air service.
Failure to comply with these
instructions may result in serious
damage to the liquid cylinder and
personal injury.
Caution! All valves on an empty Perma-
Cyl system should always be
kept closed to protect the inner
vessel and plumbing from being
contaminated.
Safety Bulletin
Portions of the following information are extracted from
Safety Bulletin SB-2 from the Compressed Gas Association,
Inc. Additional information on oxygen, nitrogen, argon, and
cryogenics is available from the CGA
Cryogenic containers, stationary or portable, are from time
to time subjected to assorted environmental conditions of
an unforeseen nature This safety bulletin is intended to call
attention to the fact that whenever a cryogenic container
is involved in any incident whereby the container or its
safety devices are damaged, good safety practices must be
followed The same holds true whenever the integrity or
function of a container is suspected of abnormal operation.
Incidents which require that such practices be followed
include: highway accidents, immersion of a container in
water, exposure to extreme heat or re, and exposure to most
adverse weather conditions (earthquake, tornadoes, etc.).
Under no circumstances should a damaged container be left
with product in it for an extended period of time.
Prior to reusing a damaged container, the unit must be
tested, evaluated, and repaired as necessary. It is highly
recommended that any damaged container be returned to
Chart for repair and re-certication.
In the event of known or suspected container vacuum
problems (even if extraordinary circumstances such as
those noted above has not occurred), do not continue to use
the unit Continued use of a cryogenic container that has a
vacuum problem can lead to embrittlement and cracking.
The remainder of this safety bulletin addresses those adverse
environments that may be encountered when a cryogenic
container has been severely damaged These are oxygen
decient atmospheres, oxygen enriched atmospheres, and
exposure to inert gases.
Caution! Before locating oxygen
equipment, become familiar
with the NFPA standard No.
55 “Compressed Gases and
Cryogenic Fluids Code” (www.
nfpa.org) and with all local safety
codes.
diagnosing the situation because the onset of symptoms
such as sleepiness, fatigue, lassitude, loss of coordination,
errors in judgment and confusion can be masked by a state of
“euphoria,” leaving the victim with a false sense of security
and well being
Human exposure to atmosphere containing 12% or less
oxygen leads to rapid unconsciousness. Unconsciousness can
occur so rapidly that the user is rendered essentially helpless.
This can occur if the condition is reached by an immediate
change of environment, or through the gradual depletion of
oxygen
Most individuals working in or around oxygen decient
atmospheres rely on the “buddy system” for protection obviously the “buddy” is equally susceptible to asphyxiation
if he or she enters the area to assist the unconscious partner
unless equipped with a portable air supply. Best protection
is obtainable by equipping all individuals with a portable
supply of respirable air. Life lines are acceptable only if the
area is essentially free of obstructions and individuals can
assist one another without constraint
If an oxygen decient atmosphere is suspected or known to
exist:
1 Use the “buddy system ” Use more than one “buddy” if
necessary to move a fellow worker in an emergency
2 Both the worker and “buddy” should be equipped with
self-contained or airline breathing equipment.
Oxygen Decient Atmospheres
Warning! Nitrogen and argon vapors in air
may dilute the concentration of
oxygen necessary to support or
sustain life. Exposure to such
an oxygen decient atmosphere
can lead to unconsciousness and
serious injury, including death.
The normal oxygen content of air is approximately 21%.
Depletion of oxygen content in air, either by combustion
or by displacement with inert gas, is a potential hazard and
users should exercise suitable precautions.
One aspect of this possible hazard is the response of humans
when exposed to an atmosphere containing only 8 to 12%
oxygen. In this environment, unconsciousness can be
immediate with virtually no warning
When the oxygen content of air is reduced to about 15
to 16%, the ame of ordinary combustible materials,
including those commonly used as fuel for heat or light,
may be extinguished. Somewhat below this concentration,
an individual breathing the air is mentally incapable of
Oxygen Cleaning
When replacing components, only use parts which are
considered compatible with liquid oxygen and have been
properly cleaned for oxygen service (Refer to CGA Bulletin
G-4.1 “Equipment Cleaned for Oxygen Service”). Do not
use regulators, ttings, or hoses which were previously
used in a compressed air environment on these tanks. Only
oxygen compatible sealants or Teon tape should be used on
threaded ttings. All new piping joints should be leak tested
with an oxygen compatible leak-test solution.
Caution! Failure to comply with these
instructions may result in serious
damage to the system and
personal injury.
An oxygen-enriched atmosphere occurs whenever the normal
oxygen content of air is allowed to rise above 23% While
oxygen is nonammable, ignition of combustible materials
can occur more readily in an oxygen-rich atmosphere than
in air; and combustion proceeds at a faster rate although no
more heat is released
It is important to locate an oxygen system in a well
ventilated location since oxygen-rich atmospheres may
collect temporarily in conned areas during the functioning
of a safety relief device or leakage from the system
Oxygen system components, including but not limited to,
containers, valves, valve seats, lubricants, ttings, gaskets
and interconnecting equipment including hoses, shall have
adequate compatibility with oxygen under the conditions
of temperature and pressure to which the components may
be exposed in the containment and use of oxygen. Easily
ignitable materials shall be avoided unless they are parts of
equipment or systems that are approved, listed, or proven
suitable by tests or by past experience.
Compatibility involves both combustibility and ease of
ignition. Materials that burn in air may burn violently in pure
oxygen at normal pressure, and explosively in pressurized
oxygen. In addition, many materials that do not burn in
air may do so in pure oxygen, particularly when under
pressure. Metals for containers and piping must be carefully
selected, depending on service conditions. The various steels
are acceptable for many applications, but some service
conditions may call for other materials (usually copper or
its alloy) because of their greater resistance to ignition and
lower rate of combustion
Nitrogen and Argon
Nitrogen and argon (inert gases) are simple asphyxiates.
Neither gas will support or sustain life and can produce
immediate hazardous conditions through the displacement
of oxygen. Under high pressure these gases may produce
narcosis even though an adequate oxygen supply sufcient
for life is present.
Nitrogen and argon vapors in air dilute the concentration
of oxygen necessary to support or sustain life. Inhalation
of high concentrations of these gases can cause anoxia,
resulting in dizziness, nausea, vomiting, or unconsciousness
and possibly death. Individuals should be prohibited from
entering areas where the oxygen content is below 19%
unless equipped with a self-contained breathing apparatus.
Unconsciousness and death may occur with virtually no
warning if the oxygen concentration is below approximately
8% Contact with cold nitrogen or argon gas or liquid can
cause cryogenic (extreme low temperature) burns and freeze
body tissue
Persons suffering from lack of oxygen should be
immediately moved to areas with normal atmospheres.
SELF-CONTAINED BREATHING APPARATUS MAY BE
REQUIRED TO PREVENT ASPHYXIATION OF RESCUE
WORKERS. Assisted respiration and supplemental oxygen
should be given if the victim is not breathing If cryogenic
liquid or cold boil-off gas contacts worker’s skin or eyes,
the affected tissue should be ooded or soaked with tepid
water (105-115ºF or 41-46ºC). DO NOT USE HOT WATER.
Cryogenic burns that result in blistering or deeper tissue
freezing should be examined promptly by a physician.
Similarly, materials that can be ignited in air have lower
ignition energies in oxygen Many such materials may
be ignited by friction at a valve seat or stem packing, or
by adiabatic compression produced when oxygen at high
pressure is rapidly introduced into a system initially at low
pressure.
Warning! If clothing should be splashed
with liquid oxygen it will become
highly ammable and easily
ignited while concentrated
oxygen remains. Such clothing
must be aired out immediately,
removing the clothing if possible,
and should not be considered
safe for at least 30 minutes.
Personal Protective Equipment
(PPE)
The following personal protective equipment is
recommended when working around cryogenic liquid:
• Safety glasses with side shields to prevent cryogenic
liquid from splashing into the eyes
• Chemical / Liquid resistant gloves to prevent cryogenic
burns on exposed hands
The Perma-Cyl® MicroBulk Storage System w/ FlexFill™
Piping Option is designed to store and deliver liquid
oxygen, nitrogen or argon as a cryogenic liquid or gas.
The Perma-Cyl tank can build and maintain pressure from
the automatically regulated pressure building circuit.
A continuous gas ow is provided from the cylinders.
Regardless of size, all Perma-Cyl tank models operate on the
same principals of operation.
Caution! Only use replacement equipment,
which is compatible with liquid
oxygen and has been cleaned
for oxygen use. Do not use
regulators, ttings, hoses, etc.,
which have been previously used
in compressed air. Failure to
comply with these instructions
may result in serious damage to
the system and personal injury.
Initial Inspection
Receiving inspection is one of the most important operations
in the life of the tank and should be done thoroughly and
conscientiously so as to nd any possible indications of
damage and prevent expensive surprises during the rst
use of the vessel at the site. Upon receipt of a Perma-Cyl
tank, remove the protective wrapping and inspect for the
following:
• Any shipping damage including dents, cuts, broken and
bent plumbing components. Report any ndings to the
shipping company immediately.
• Examine welded and brazed joints on plumbing for
cracks or deformation, especially on valves and ttings.
• On the 5500 Perma-Cyl tanks check the insulation space
pressure with a suitable thermocouple vacuum gauge
(follow procedure below). Make a note of the ambient
temperature when the vacuum is read. Temperature
changes affect the vacuum reading in a warm empty
vessel
– If warm vacuum is above 20 microns, consult factory.
Vacuum Check Procedure - Perma-Cyl
5500 Only
The standard Chart vacuum probe is a Teledyne-Hastings
DV-6R probe. Select a compatible instrument to read the
output of the vacuum probe.
Caution! Unauthorized changing of the
vacuum probe will void vessel
warranty.
1 Remove rubber cap on probe outlet to expose contact.
Note that the probe housing need not be opened to do
this
2 Plug the instrument in to the probe and calibrate the
instrument
3 Open the vacuum probe isolation valve. Wait for ve
minutes and take vacuum reading Note that valve
handle protrudes through protective housing and can be
turned without opening the housing.
4 Close the isolation valve and take a second reading
Monitor the rate of rise in vacuum probe with isolation
valve closed If the vacuum continues to rise at a
constant rate, it is possible that the probe assembly is
leaking Consult the factory
• Check burst discs and relief valves for dirt/damage
• Check to ensure there is positive pressure on the inner
vessel, normally about 20-25 psig. Tanks are shipped
with NF purity nitrogen gas. Purging is necessary prior to
lling.
• If the tank passes all the above criteria, it is ready for
rst ll. Follow the rst ll procedures in the Installation
portion of this manual.
Note: The PC5500 is the only Perma-Cyl
tank that is equipped with a vacuum
thermocouple.
5 Verify that the isolation valve is closed
6 Replace the rubber probe cap.
7 Compare the vacuum reading obtained now to the
Figure 1 - Schematic for 1000HP/VHP, 1500HP/VHP, 2000HP and 3000HP models.
Primary Plumbing Circuits
(Refer to Figure 1)
Fill
The Perma-Cyl w/ FlexFill has a top and bottom ll circuit
that replaces the top oat assembly so the driver can control
the tank pressure while lling the Perma-Cyl MicroBulk
Storage Tank. The ll circuit consists of a top ll valve (V-6),
a bottom ll valve (V-5), a ll check valve (CV-1), and a
hose drain valve (V-3). The ll line check valve has a service
tting on the inlet side that provides the sole connection for
the liquid delivery vehicle
The hose drain valve (V-3) can be used to both purge the ll
hose before lling the tank or to depressurize the ll hose
after lling the tank.
The driver controls the pressure in the vessel during the ll
process by adjusting the ow through the top and bottom ll
valves. Product owing into the bottom of the tank will raise
the pressure and product owing into the top of the tank will
lower the pressure. Adjusting each valve properly will allow
the driver to hold a consistent pressure in the tank throughout
the entire delivery
During a rst ll, only ll the vessel to 75% full to allow
liquid expansion experienced with a new "hot" tank. Each
ll there after can be lled to 100% full. Please refer to
the Installation section of this manual for detailed lling
procedures.
Caution! If liquid can be trapped in the
transfer system, a suitable relief
valve must be installed to prevent
over pressurization.
either into or out of this
vessel, be sure that protective
eyeglasses and gloves are being
worn. If the transfer is being
made to an open top vessel, the
transfer pressure should be as
low as possible and a phase
separator should be used to
eliminate splashing and hose
whip.
Pressure Build
The pressure build circuit is used to build pressure back in
the vessel after a delivery or to maintain pressure as liquid
is withdrawn from the vessel. The vessel pressure is set by
adjusting the PB regulator (R2). Standard PB set points are:
MP - 125 psig
HP - 300 psig
VHP - 450 psig
As the tank pressure drops below the PB set point, the
regulator opens and allows liquid to ow off the bottom of
the tank, through the internal PB vaporization coils, through
the R-1 and back into the gas phase of the tank. The pressure
build circuit can be isolated by closing valves V-12 & V-13.
Some models of Perma-Cyl tanks can be equipped with
external pressure build vaporizers which allow for much
quicker recoveries after the tank has been blown down to ll
it or for high ow applications.
Liquid Use
The liquid use circuit can be used for both a liquid
application or a high ow gas use application. This circuit
draws liquid directly up the dip tube and out through
the liquid use valve (V-4). Some models have a bottom
withdrawal valve that draws liquid out the bottom of the
inner. For a high ow gas use application the liquid can be
piped through a stand alone external process vaporizer. This
can more than double the standard ow rates that can be
achieved through the internal vaporization coils.
Gas Use
The gas use valve (V-1) leverages the internal vaporizer on
the Perma-Cyl system to supply gaseous product to the end
user
Note: The liquid is drawn up the dip tube,
through the top knuckle and back down
through the internal vaporization coil
before exiting out the gas use valve.
The internal vaporizer can support specic ow rates. The
gas use valve used is a 1/2" globe valve. The line size for the
gas use should be sized properly for the pressure and ow
rate that is desired
The Perma-Cyl tank will deliver gas at various ow rates and
temperatures for different applications. The equipment that
is being supplied gas from the Perma-Cyl tank controls the
ow rate. Higher ow rates may provide very cold gas that
could damage the equipment to which they are attached. To
supply gaseous product, follow this step by step procedure.
1 Connect the proper regulator/regulating manifold to the
liquid cylinder's gas use outlet
Economizer
The economizer circuit allows the customer to utilize the
natural heat leak that occurs in every cryogenic storage
vessel. When the pressure is above the setpoint of the
economizer regulator, the economizer regulator (R-1) opens.
This allows gas to be withdrawn directly off the headspace
of the tank and travel through the internal vaporization coils,
to warm the cold gas, and out the gas use valve. This will
result in lowering the pressure of the tank. The economizer
regulator can be isolated by closing valves V-2 and V-10
Note: The economizer circuit will only work if
the customer is using product out of the
vessel.
2 Connect the proper piping between the nal line
regulator and the receiving equipment.
3 Open the pressure building valve.
4 Allow pressure to build to the operating pressure (refer
to gauge).
5 Open the gas use valve.
6 Adjust the gas use regulator for the proper delivery
pressure.
Caution! All valves on an empty Perma-
Cyl tank should always be kept
closed to protect the inner
vessel and plumbing from being
contaminated.
The operator should review the safety precautions found
in the Safety section before conducting a gas or liquid
withdrawal operation. Protective eyeglasses and gloves
should always be worn
At low ow rates, the Perma-Cyl tank is capable of
delivering warm gas through the line regulator. As the ow
rate increases, the temperature of the gas decreases. If the
cold temperature becomes a problem at a desired ow rate,
an external vaporizer can be added. Attach this vaporizer
directly in series with the gas use connection and place the
line regulator at the exit of the vaporizer.
Safety Circuit
The Perma-Cyl w/ FlexFill Piping Option tanks are equipped
with dual spring operated relief valves (RV-2) and dual burst
discs (BD-1). The dual safety manifold with diverter valve
(V-8) is standard on these vessels. This allows for change
out of safety relief devices without the need to empty the
tank These devices are used to automatically relieve excess
pressure in the vessel and cannot be isolated by use of a
valve. Replacement of these relief devices should only be on
a "like for like" basis. Substitutes should be avoided unless
approved by the manufacturer. Purge valves (V-7) can be
used to relieve pressure before removing safety devices.
Vent/Full Trycock
gauge (Ll-1) which is used to indicate the amount of product
in the vessel The standard DP gauge used by Chart is the
Cyl-Tel
®
Liquid Level Gauge. Customers can specify other
models as options such as the WIKA Analog DP Gauge (see
photos 1 & 2 on next page).
Pressure
Gauge
Four-Way
Valve
Cyl-Tel®
Liquid Level
Gauge
Photo 1
Four-Way Valve (see photos 1 & 2)
The four-way valve (V-11) is used as the primary isolation
valve between the DP gauge and the phase lines from the
tank. This four-way valve also provides an easy method to
check the zero on the DP gauge By turning the valve into
the equalization position, the DP gauge can be zeroed and
isolated from the tank pressure for removal or replacement.
The vent valve (V-9) is used to relieve excess pressure in
the cylinder On Perma-Cyl systems the vent valve is a gray
handled globe valve. When installed indoors, the vent line
should be piped outdoors using 1/2" nominal copper or the
equivalent stainless steel hose The vent valve also serves as
the full trycock during lling operations. When the PermaCyl tank is lled by trucks other than Orca
™
MicroBulk
Delivery System trucks, the full trycock must be used to ll
the vessel. When liquid starts to spit out of this valve while
being lled, the lling process should be terminated.
Other Piping Circuits and
Components
Phase Lines and Liquid Level Gauges
The Perma-Cyl tank is equipped with both a low pressure
phase line (F) located on the top of the vessel and a high
pressure liquid phase line (E) located on the bottom of the
vessel. These lines are connected to a differential pressure
Pressure
Gauge
Four-Way
Valve
WIKA
Analog DP
Gauge
Photo 2
Pressure Gauge (see photos 1 & 2)
A single pressure gauge (R-1) on the Perma-Cyl tank is also
tied into the low phase line and gives the operator a pressure
reading in the gas phase of the vessel. This pressure gauge
can also be isolated with the four-way valve
Vacuum Evacuation Port
Unlike bulk tanks, Perma Cyl storage vessels are normally
not provided with an on-board method of taking a vacuum
reading. The vacuum evacuation port is sealed using a
stainless steel disk with O-rings and a protective cover is
placed over it (see Photo 3). Due to the relatively small
volume of the annular vacuum space, taking vacuum
readings is normally not recommended since the vacuum
level is slightly reduced when taking this reading The
troubleshooting portion of this manual gives steps on how
to determine if the vacuum might be weak In the event
that the vacuum does need to be checked, a trained vacuum
technician would have to bring the appropriate equipment
to get this done In most cases where a vacuum has been
compromised, it is often more economical to swap out the
The plumbing design for the 2000/3000 VHP Perma-Cyl
system is different from the models described in the previous
section. These models do not contain internal vaporization
or pressure build coils. For the 2000 and 3000 models, all
pressure building and process vaporization is provided by
two external vaporizers. This plumbing conguration is
commonly referred to as Option 09 or the ZX package.
2000 and 3000 VHP Primary Plumbing
Circuits
(Refer to Figure 2)
Fill
The Fill Plumbing Circuit on these two models is the same as
the models described in the previous section (see page 8).
The pressure build circuit for the 2000 and 3000 VHP
Perma-Cyl models is used to build pressure back in the
vessel after a delivery or to maintain pressure as liquid is
withdrawn from the vessel. The vessel pressure is set by
adjusting the PB Regulator (R1) shown in Figure 2. Standard
PB set points found in the 09 plumbing option kits are:
MP - 125-09
HP - 300-09
VHP - 450-09
Liquid is drawn off the bottom of the tank, runs through the
PB regulator (R-1), then is vaporized by running through
both the PB vaporizer and the gas use vaporizer. The
vaporized gas then splits and a portion ows through check
valve CV-3 and back to the headspace of the tank. The other
portion goes directly to the customer through the gas use
valve V-1 Liquid serving both the PB and gas use can be
shut off by closing valve V-2
Note: Closing valve V-1 or V-2 will cut off any
process gas going to the customer through
the gas use valve.
Gas Use
The gas use valve (V-1) on the 2000 and 3000 VHP PermaCyl models is the primary connection point to supply process
gas to the customer. Unlike the other Perma-Cyl models,
the liquid for the process gas comes directly off the bottom
of the tank (C) and travels through the PB regulator (R-1).
The unique design of this model allows for both the PB
vaporizer and the gas use vaporizer to be utilized for process
gas vaporization. After exiting the gas use vaporizer, the gas
splits and supplies both the pressure build and the gas use as
explained in the pressure build explanation for this particular
model of tank
Note: Since all the liquid for both the PB and gas
use requirements of this model tank travels
through one regulator (R-1), the limiting
factor on ow is this regulator. A high
ow kit is offered for the 2000 and 3000
VHP tanks. This kit adds an additional PB
regulator in parallel with the existing PB
regulator (R-1) allowing for ows up to
3500 SCFH (see Photo 4).
Economizer
The economizer circuit allows for the customer to utilize
the natural heat leak that occurs in every cryogenic storage
vessel The economizer circuit for the 2000 and 3000 VHP
models is comprised of a check valve (CV-4) which draws
gas directly off the top of the tank and sends it through the
gas use vaporizer in order to warm up the cold vapor prior
to exiting the tank through the gas use valve Flow through
the 1 psig cracking pressure check valve (CV-4) only
occurs when regulator R-1 closes Valve V-10 shuts off the
economizer circuit
Liquid Use
The liquid use circuit for both the 2000 and 3000 VHP
models is similar to the other Perma-Cyl models This circuit
draws liquid directly up the dip tube and out through the
liquid use valve (V-4). For high ow gas use applications,
the liquid can be piped from the liquid use valve (V-4) to a
stand-alone external vaporizer that is properly sized for the
owrate. In this scenario, the gas use valve on the tank is not
used so the PB and gas use external vaporizers on the tank
become dedicated to pressure building only.
Photo 4 - High Flow Kit
All other plumbing circuits that are covered on pages 9 and
10 of this manual also apply to the 2000 and 3000 VHP
Perma-Cyl models. These include the safety circuit, vent/
full trycock, high/low phase lines, liquid level gauges and
pressure gauges.
Figure 3 - Schematic with vaporizer for 5500 MP/VHP models.
5500 MP/VHP Operation
For the 5500 model, a single external vaporizer provides
all pressure building vaporization. An optional 3500 SCFH
hang-on or optional 5000 SCFH stand alone vaporizer may
be added to the plumbing to provide all process vaporization.
This plumbing conguration is referred to as Option 07 and
is unique to the 5500 model
5500 MP/VHP Primary Plumbing Circuits
(Refer to Figure 3)
Fill
The standard ll plumbing circuit is exactly the same as all
the other Perma-Cyl models (refer to page 8, Fill). A bulk
ll connection option kit is offered to add a 1-1/2" CGA
connection in place of a standard are tting.
The pressure build circuit for the 5500 Perma-Cyl model is
used to build pressure back in the vessel after a delivery or to
maintain pressure as liquid is withdrawn from the vessel. The
vessel pressure is set by adjusting the PB regulator (R-1).
Standard PB set points found in the 07 option kits are:
LP - 35-07 (MP version only)
MP - 125-07
HP - 300-07
VHP - 450-07
the gas use circuit The economizer feature can be turned off
by closing V-5 The economizer regulator can be serviced by
closing V-5 and V -7
Photo 8 - Economizer Plumbing Circuit
As long as both economizer valves are open, the economizer
feature will always work. This includes all gas use vaporizer
options. Even if the customer supplies their own vaporizer,
the economizer function is never lost. For the LP (35-07)
plumbing option, the economizer regulator is plumbed so it
vents to atmosphere. This is common for liquid applications.
Photo 7 - External PB Vaporizer Option 07
As the tank pressure drops below the PB set point, the
regulator opens and allows liquid to ow out the bottom of
the tank, run through the PB regulator, vaporize in the PB
coil, then go back into the gas phase of the tank. The pressure
build circuit can be shut off by closing V-8 (see Photo 10).
The PB regulator can be serviced by also closing V-9
Note: In a high ow scenario, the limiting factor
in ow is the regulator. A high ow kit
is offered that adds an additional PB
regulator in parallel with the existing one
(R-1) to allow for higher ows (see Photo
4).
Economizer
The economizer circuit allows for the customer to utilize
the natural heat leak that occurs in every cryogenic storage
vessel The economizer circuit for the 5500 VHP model is
comprised of an economizer regulator (R-2) set at 15 psi
above the PB regulator. When the tank pressure reaches the
economizer regulator's set point, the economizer regulator
opens and allows gas to ow directly from the head space to
Liquid Use - VHP
The liquid use circuit for the 5500 VHP model is different
than the other Perma-Cyl models Liquid can be withdrawn
from the bottom of the tank through the PB circuit (C) from
C-2 (see Photo 10). For high ow gas applications, see the
Gas Use section on the next page.
Liquid Use - MP
The liquid use circuit for the 5500 MP model is the same
as the 5500 VHP model except it has an auxiliary liquid
withdrawal port. The tank can be ordered with a plugged
1/2" FPT connection or a 1/2" ACME VJ valve. The VJ
valve is available on either the left or right side of the tank
Photo 9 - VJ Valve
Gas Use /
Dip Tube
Valve
PB
Circuit
Valve
Photo 10 - Gas Use and PB Isolation Valve
Gas Use
The gas use circuit on the 5500 VHP model is the primary
connection point to supply process gas to the customer.
The gas use circuit on this model is different from other
Perma-Cyl models The gas use coil shown in Figure 3 is
the optional 3500 SCFH vaporizer. Without this gas use coil
option, the gas use circuit stops at the gas use isolation valve
(V-2) (see Photo 10). Gas use coil options include a 3500
SCFH hang-on vaporizer (see Photo 11) or a stand alone
5000 SCFH vaporizer (to be plumbed on-site).
The gas use circuit works by the pressure in the vessel
forcing the liquid out the gas use connection (K) and up a
tube in the annular space. It then connects to the economizer
inlet above the height of the liquid so the economizer works
regardless of the amount of liquid in the vessel The line goes
back down to the bottom of the annular space before exiting
and passing through either the optional hang on process
vaporizer or stand alone process vaporizer.
Photo 11 - 5500VHP with optional hang on vaporizer
Vacuum Integrity
The 5500 model vessels are equipped with PN 4210049
Hastings 1415671S #DV-6R vacuum thermocouple gauge
tubes (see Photo 12). Vacuum integrity may be tested with
a vacuum meter Deterioration or loss of vacuum will be
apparent by cold spots, frost or condensation on the jacket, or
evidenced by abnormally rapid pressure buildup. Unless one
of these conditions is evident, the vacuum level should not
be suspected. In the event one of the above conditions exist,
see Vacuum Check Procedure on page 7 of this manual.
15
TC Gauge
Tube
Photo 12 - Thermocouple gauge tube
Loading...
+ 44 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.