Charnwood SLX45 MKII MULTI-FUEL Operating & Installation Instructions Manual

Page 1
SLX45M K I I
MULTI-FUEL
Operating & Installation Instructions
charnwood
®
Page 2
Page 3
C O N T E N T S
General points
Fuels 4
Door Operation 5
Multi Fuel Grate 5
Controlling The Fire 5
System Controls 5
Refuelling 6
Overnight Burning
Throat Plate & Flueway Clearing 6
Special Points when Burning Coal 7
Maintenance
Chimney Sweeping 7
Trouble Shooting 8
CO Alarm
If You Need Further Help
INS TALLAT ION I NSTRUCT ION S
Health & Safety Precautions 10
CO Alarms
Performance
Chimney 10
1. Installation as an Inset Stove 11
Preparation of the Fireplace
Fitting the Fire 13
Flue Connections & Infilling
2. Installation as a Freestanding Stove 13
Thermostat 15
Assembly 15
Pre Lighting Check 15
Commissioning 15
Dimensions 16
Parts Lists 17
Certification 18
4
Lighting 5
Ash Clearance 6
Riddling 6
6
7
9
9
10
10
Specification 10
Hearth & Fire Surround 11
11
Central Heating System 12
System Controls 12
13
Ref. SLX45MKII 10.12
SLX45M K I I
MULTI- FUEL
Page 4
®
ch arn wo od
OPERATING INSTRUCTIONS
SLX 4 5
MU LTI -FU EL
4
GENE RAL POIN T S
When using the fire in situations where children or infirm people are
present please use a fire guard to prevent accidents. The fire guard
should be manufactured in accordance with BS 8423:2010.
FUEL S
Coal
Housecoal doubles, trebles or cobbles may all be burnt. Do not use
singles, small nuts, or coal dust. It is important that large size coal is
used(i.e. larger than 2" or 50mm in size). The coal should be dry.
When burning bituminous coal a little extra care is needed. Please
take note of the section ‘‘Special Points For Burning Coal’’.
Before lighting the fire check with the installer that the work and
checks described in the installation instructions have been carried out
correctly and that the chimney has been swept, is sound, and free
from any obstructions.
Do not light the fire before the boiler and heating system
have been filled with water as this can damage the boiler.
If the appliance is fitted in place of an open fire then the chimney
should be swept one month after installation to clear any soot falls
which may have occurred due to the difference in combustion
between the appliance and the open fire.
Do not use an aerosol spray on or near the stove when it is alight.
There is a risk of explosion or flash ignition of the spray.
Your SLX45 stove has been designed to work with minimum effort. If
any operation - such as riddling the grate or opening and closing the
door - begins to require extra force then the cause must be
investigated to prev damage being caused to the
stove.
The stove is not suitable for use in a shared
flue system.
ent and correct
Remember that the stove will be hot and is made from hard material.
Ensure that you have good balance before operating the fire.
The following smokeless fuels are suitable for use on this appliance:
Ancit (Phurnacite Plus), Anthracite Large Nuts, Phurnacite,
Any fuel included on the HETAS list of Approved Smokeless Fuels for
Closed Appliances.
(http://guide.hetas.co.uk/guide/fuels_smokeless.html)
The above fuels are all suitable for use in smoke controlled areas. In
other areas the following fuels may also be burnt:
Wood
Only dry well seasoned wood should be burnt on this appliance as
burning wet unseasoned wood will give rise to heavy tar deposits.
For the same reason hard wood is better than soft wood. Burning
wet unseasoned wood will also result in considerably reduced
outputs. The wood should be cut and split and then left to season in a
well ventilated dry place for at least one year but preferably two
years before use.
Peat
Ensure that the peat is well dried before use. Burning wet peat will
give rise to heavy tar deposits and reduced outputs.
Fuel Type
Wood Logs
Smokeless Fuel
Output
5.8kW (19,800Btu/h)
6.3kW (21,500
Flue Gas Temp
326°C
336°C
Flue Gas Mass Flow
5.0 g/s
5.1 g/s
Max Hearth Temp.
90°C
182°C
Re-fuelling Cycle
0.84 hr (50 min)
4.0 hr
CO @ 13% O
2
0.16%
0.18%
Min Distance to Combustible
INSET
FREESTANDING
Side
100mm
250mm
Above (inset)/ Rear
300mm
700mm
Min Flue Draft
25Pa (0.1in wg)
Stove Weight
125kg
Add-in Boiler
2.0 kW
XV080-CPD-2011
WOOD LOGS
0.16%
326°C
5.8
75.7
INSET
100mm 300mm
ANTHRACITE
0.18%
336°C
6.3kW
72.1%
FREESTANDING
250mm 700mm
Thermostat flap (behind side panel)
Airwash Control
pull to open
Turn handle
clockwise to open
Fig. 1. Controls
Thermostat Control Knob
Page 5
PETROLEUM COKE IS NOT SUITABLE FOR USE ON THIS
APPLIANCE, ITS USE WILL INVALIDATE THE GUARANTEE
At first you may find it helpful to try several fuels to find the most
suitable. If you are unable to obtain the fuel you want, ask your
supplier or an approved fuel distributor to suggest an alternative
DOOR O PERATION
The doors are opened by raising the door handle as shown in Fig. 1.
When the fire is alight, avoid touching the doors other than on the
handle as the metal will become hot. When closing the doors do not
use excessive force.
LIGH TING
Place some paper and dry kindling wood or fire lighters on the grate
and cover with a small amount of fuel. Turn the thermostat control
knob to the maximum setting and light the paper or fire lighters.
Close the doors and allow the fire to burn until the fuel is well ignited
then load with more fuel and adjust the thermostat to the required
level. On initial lighting, the fire may smoke and give off an odour as
the silicon paint with which the firebox is painted reacts to the heat.
or
ring the Solid Fuel Association Helpline on
NOTE: This appliance has been approved by HETAS as a continuous
operating appliance for burning dry seasoned wood logs or
smokeless fuel.
HETAS approval does not cover the use of other fuels either alone or
mixed with wood logs nor does it cover the instructions for use of
other fuels.
MULTIFUEL GRATE
Your Charnwood is fitted with a multifuel grate which enables solid
fuel, wood and peat to be burned equally effectively.
The grate has two positions. One for solid fuel, the other for wood
and peat. When in the solid fuel position ash can fall through the
grate and into the ashpan. When in the wood position ash is able to
build up on the grate as is necessary for effective wood or peat
burning. Movement of the grate from one position to the other is
effected using the tool supplied. The grate is put into the wood
position by moving the tool up until the tool is vertical. The grate is
put into the solid fuel position by moving the tool down until the tool
is horizontal.
If a mixture of wood and solid fuel, or peat and solid fuel, is to be
burnt then keep the grate in the solid fuel position.
0845 601 4406.
This is normal and will cease after a short time. In the meantime the
room should be kept well ventilated. Before relighting the fire, riddle,
remove any clinker from the firebed and empty the ashpan.
.
SYSTEM CON T ROLS
The heating system controls may consist of time switches, room
CONT ROLLI NG THE FIR E
The rate of burning and hence the output is controlled by the control
knob on the left hand side of the appliance and the airwash control
on the right, shown in fig. 1. The control knob is connected to the
water temperature sensing thermostat. Use the control knob on the
left to control the heat output from the fire and keep the airwash
control slightly open most of the time to keep the glass clean. It will
not be possible to keep the glass clean if the ashwash control is fully
closed, particularly after refuelling. The number at the top of the
control knob is the number at which it is set, the higher the number
the faster the burning rate.
For correct firing of the Freestanding model we recommend using a
stove pipe thermometer which may be purchased from your supplier
or from ourselves.
Liquid fuels are not to be used on this appliance
®
ch arn wo od
OPERATING INSTRUCTIONS
SLX 4 5
MU LTI -FU EL
5
For Wood
Do Not Go Beyond 45° Position When Riddling
Riddle Between Horizontal & 45° Positions
Tool To Be Horizontal For Solid Fuel
Vertical
Tool to be
Or Peat
Fig. 2. Grate Operation
Page 6
thermostats, outdoor temperature thermostats and thermostatic
radiator valves in virtually any combination. These will work in
conjunction with the thermostat control on the appliance. The
thermostat on the appliance will simply control the temperature of
the water coming from the boiler and hence the temperature of the
radiators and domestic hot water. The automatic controls (other than
thermostatic radiator valves) will switch the pump (and hence the
radiators) on and off. Your installer will be able to explain the
controls fitted to your system and how to operate them.
ASH CL EARANC E
The ashpan should be emptied regularly before it becomes too full.
The most convenient time to remove the ash is just before riddling
the fire since the ash will then be at it’s coolest. Use the
ashpan/riddling tool provided to remove the ashpan, the fold up
carrying handle should be held with a heat proof glove.
Never allow the ash to accumulate in the ashpan so that it comes in
contact with the underside of the grate as this will seriously damage
the grate bars. Ensure that the air inlet damper is not prevented from
closing by spilled fuel or ash.
Care should be taken to ensure that ash is cool before emptying it
into plastic liners or bins.
To make ash removal easier there is a special Charnwood ash
carrier available. This may be purchased from your supplier or, in
case of difficulty, from ourselves.
RIDD LING
The fire should be riddled with the doors shut. Place the tool on the
knob and rotate between the horizontal and the 45° position several
times as shown in Fig. 2.
Caution: when riddling the grate using solid fuel do not go beyond the
45° position as this can cause the grate to jam.
If jamming does occur then the fire should be allowed to burn for
approximately half an hour before riddling the grate again as
described above. Riddling twice a day is usually sufficient when
burning solid fuel. When burning wood, ash should be allowed to
build up and only riddled when the ash begins to cover the slots in the
rear fireplate.
Too much riddling can result in emptying unburnt fuel into the ashpan
and should therefore be avoided. Clinker should regularly be
removed from the firebed.
After riddling, the grate should be put back into the solid fuel or
wood position as required (the tool should be horizontal for solid
fuel or vertical for wood).
For overnight burning the fire doors must be closed.
When burning solid fuel the ashpans should be emptied and the fire
riddled. If the fire is very low then it may be necessary to add a little
fuel and turn the thermostat control up to maximum for a brief
period until the fire is burning brightly before filling with fuel. When
the new fuel has ignited, the thermostat control should be turned
down to the required setting and the airwash control moved to a low
setting. If the central heating pump is off overnight then the
thermostat may be left at the same setting for both day and night
operation. If the central heating pump is on overnight then set the
thermostat control to give the required level of heating.
Some experimentation will be necessary to find the settings most
suitable for the particular fuel used and the draw on the chimney. To
revive the fire, empty the ashpans, riddle, and open the air controls
to maximum. When the fire is burning well load on more fuel as
necessary and move the air controls to the desired setting.
When burning wood use large logs rather than small ones. Proceed
as above, but do not riddle the fire either when shutting down or
reviving.
REFU ELLING
OVERNIG H T BURNIN G
THROATPL AT E A ND FLU EWAY CLEAN I NG
It is important that the throat plate and all the appliance flueways are
kept clean. When burning smokeless fuels they should be cleaned at
least monthly and more frequently if it is found necessary.
The throat plate and flueways may be cleaned with a low fire still
burning. Use the scraper tool to scrape any sooty deposits off the
front of the plate until they fall into the fire. Also scrape any soot
deposits from the sides and top of the firebox. Ensure that soot
deposits are not allowed to build up on the sides because if the
Keep the firebox well filled (the fuel may be sloped up from the front
firebars), but do not allow fuel to spill over the top of the front fire
bars. Take care that fuel does not project over the front fire bars or
damage to the glass may be caused when the doors are closed.
®
ch arn wo od
OPERATING INSTRUCTIONS
SLX 4 5
MU LTI -FU EL
6
Page 7
throat plate becomes tight between the faces this can cause it to fail
prematurely.
More soot will be deposited on the throat plate and in the flueways if
the appliance is run at low levels for long periods. If this is the case
then more frequent cleaning will be necessary.
SPEC IAL POINT S W HEN BURNI N G COAL
When loading the appliance take
care not to smother the fire, instead fill the firebox in two stages
waiting between each stage for the flames to appear above the fire.
After a period of slumbering always turn the air control up to
maximum and wait until flames appear above the fuel bed before
opening the doors.
Burning coal will produce more soot deposits than other fuels,
especially if the fire is run at low levels for long periods. It is
therefore vital to clean the throat plate regularly, daily cleaning is
recommended.
MAIN TENANC E
Cleaning
To clean
the surfaces simply wipe over with a dry cloth. Abrasive pads and
scouring cleaners must not be used as these will damage the finish.
Care should be taken not to knock the enamel with hard objects as it
will chip.
Cleaning the Glass
The glass in the doors is a special ceramic glass which is able to
withstand high temperatures. Before cleaning the glass open the
doors and allow them to cool. Clean the glass using a damp cloth and
then wiping over with a dry cloth. Any stubborn deposits on the
glass may be removed with a proprietary stove glass cleaner or
ceramic hob cleaner. Some deposits on the glass may be burnt off
simply by running the fire at a fast rate for a few minutes. Do not use
abrasive cleaners or pads as these can scratch the surface which will
weaken the glass and cause premature failure. Aerosol spray cleaners
should not be used near the appliance whilst it is under fire.
When not in use
If the fire is going to be out of use for a long period, (for instance in
When burning housecoal keep the airwash control at least slightly
open all the time (refer to Fig. 1.)
The appliance is finished in silicone paint or vitreous enamel.
the summer,) then to prevent condensation, and hence corrosion,
the thermostat should be left at the maximum setting and the main
doors left ajar. It is also advisable to sweep the chimney and clean out
the fire. Spraying the inside of the doors and firebox with a light oil,
such as WD40, will also help to keep all internal parts working well.
After long periods where the fire has been out of use, the chimney
and appliance flueways should be cleaned before lighting.
Door Seals
For the fire to operate correctly it is important that the door seals
are in good condition. Check that they do not become worn or
frayed and replace them when necessary.
Servicing
It is recommended that the fire is serviced once a year to keep it in
first class working order. After cleaning out the firebox thoroughly,
check that all internal parts are in good working order, replacing any
parts that are beginning to show signs of wear. Check that the doors
seals are in good condition and that the doors seal correctly. Check
the operation of the thermostat, both when cold and hot. A servicing
guide, TIS 48. is available on request.
CHIM NEY SWEE P ING
The chimney should be swept at least twice a year. In most
installations it will be possible to sweep the chimney through the
appliance.
First remove the front firebars and the throat plate. Then sweep the
chimney ensuring that soot is removed from all horizontal surfaces
after sweeping.
In situations where it is not possible to sweep through the appliance
the installer will have provided alternative means, such as a soot
door. After sweeping the chimney the appliance flue outlet and the
flue pipe connecting the appliance to the chimney must be cleaned
with a flue brush.
After clearing any soot from within the fire, replace the throat plate
and the front firebars.
Where the chimney previously served an open fire, it is possible that
the higher flue gas temperature from a stove may loosen soot
deposits with the consequent risk of flue blockage. It is therefore
recommended that the chimney be swept a second time within a
month of regular use after installation.
®
ch arn wo od
OPERATING INSTRUCTIONS
SLX 4 5
MU LTI -FU EL
7
Page 8
Different types of sweep’s brushes are available to suit different
flueways. For standard brick chimneys a wire centre sweep’s brush
fitted with a guide wheel is recommended. For prefabricated
insulated chimneys the manufacturers instructions with regard to
sweeping should be consulted.
TRO UBLE SHO OTING
Fire Will Not Burn
Check that:
a) the air inlet is not obstructed in any way,
b) chimneys and flueways are clear,
c) a suitable fuel is being used,
d) there is an adequate air supply into the room,
e) an extractor fan is not fitted in the same room as the fire.
Fire Blazing Out Of Control
Check that:
a) the doors are tightly closed,
b) the thermostat knob is turned down to the minimum setting,
c) the air inlet damper is closed (at the bottom left of the appliance,
see Fig. 1.), and that it is not prevented from closing completely by a
piece of ash,
d) a suitable fuel is being used,
e) the door seals are in good condition.
Over-Firing
If the fire is over-fired it will cause premature failure of the internal
fire parts. Overfiring is occurring when any internal parts of the fire
begin to glow red. To prevent over-firing ensure that:
a) the door seals are kept in good condition, and that the doors are
sealing correctly,
b) the thermostat on the fire is working correctly,
c) a suitable fuel is being used,
d) the fire is not fitted onto a heating system which is too large.
f) there is sufficient draw in the chimney. Once the chimney is warm a
draught reading of at least 2.5 mm (0.10 inches) water gauge (25Pa)
should be obtained.
Fume Emission
Warning Note: Properly installed, operated and maintained this
appliance will not emit fumes into the room. Occasional fumes
from de-ashing and re-fueling may occur. Persistent fume emission
is potentially dangerous and must not be tolerated. If fume
emission does persist then take the following immediate actions
should be taken:
c) Check for flue or chimney blockage, and clean if required.
d) Do not attempt to relight fire until cause of fume has been
identified and corrected, if necessary seek professional advise.
The most common cause of fume emission is flueway or chimney
blockage. For you own safety these must be kept clean.
a) Open doors and windows to ventilate the room and then leave
the premises..
b) Let the fire out and safely dispose of the fuel from the
appliance.
Freezing
Do not light the fire if there is any possibility that any parts of the
system may be frozen.
Chimney Fires
If the chimney is thoroughly and regularly swept, chimney fires
should not occur. However, if a chimney fire does occur then turn
the control knob to the minimum setting (see Fig. 1), and tightly
close the doors of the appliance. This should cause the chimney fire
to go out in which case the control should be kept at the minimum
setting until the fire in the appliance has gone out. The chimney and
flueways should then be cleaned. If the chimney fire does not go out
when the above action is taken then the fire brigade should be called
immediately.
After a chimney fire the chimney should be carefully examined for
any damage. Expert advice should be sought if necessary.
Lack of Heat To Radiators / Hot Water
Check that:
a) the fire is burning properly - if not then carry out the checks under
"Fire Will Not Burn".
b) the throat plate is fitted correctly, I.e. pushed back against the
®
ch arn wo od
OPERATING INSTRUCTIONS
SLX 4 5
MU LTI -FU EL
8
Page 9
boiler, and that it Is not distorted.
c) the door seals are in good condition.
d) If the hot water goes cold when the pump is turned on, or if some
radiators are hotter than others, then the system may need balancing,
the pump may be pumping the water too quickly around the system,
or the radiators may need bleeding. Please ask your installer to check
these points.
Door Glass Blacks Up
Differences in chimney draughts mean that the best setting of the air
controls will vary for different installations. A certain amount of
experimentation may be required, however the following points
should be noted and with a little care should enable the glass to be
kept clean in most situations:
a) The airwash relies on a supply of heated air to keep the glass clean,
therefore, when lighting the stove allow the firebed to become well
established before turning the thermostat down. It may sometimes be
beneficial to also keep the doors slightly ajar whilst the fire becomes
established. This can also apply when re-fuelling.
b) When re-fuelling keep the fuel back a little from the front firebars,
do not try to fit too much fuel into the firebox.
c) Never completely close the airwash control - as a guide it should
be at least a quarter open.
d) Wet wood or logs overhanging the front firebars will cause the
glass to blacken.
It is always more difficult to keep the glass clean when running the
stove very slowly for long periods.
If blackening of the glass still occurs check that all flue connections are
well sealed. It is also important that the chimney draw is sufficient and
that it is not affected by down-draught. When the chimney is warm a
draught reading of at least 2.5mm (0.10 inches) water gauge should
be obtained.
CO ALA RM
Your installer should have fitted a CO alarm in the same room as the
appliance. If the alarm sounds unexpectedly, follow the instructions
given under “ Warning Note” abo ve.
IF YOU NEED FURTHER HELP
If you need further help with your Charnwood then your Installer will
be able to provide the answers to most questions. Your Local
Charnwood Premier Dealer has a great deal of experience and will
also be able to provide helpful advice. Further help is available from
the Charnwood Customer Services department who will be pleased
to give advice, if necessary.
®
ch arn wo od
OPERATING INSTRUCTIONS
SLX 4 5
MU LTI -FU EL
9
Page 10
HEALTH AND SAF ET Y PRECAUTIONS
PERF ORMANC E
The rated outputs for the Charnwood SLX45 are shown in the
Specification table. These outputs are obtained during the standard
tests burning fuel with the doors closed over a 4 hourly re-fuelling
interval for solid fuel and 1.5 hourly period for wood.
WARNING please take care when installing the appliance that the
requirements of the Health and Safety at Work Act are met.
Some types of fire cement are caustic and should not be allowed to
come into contact with the skin. In case of contact wash with plenty
of water.
If there is a possibility of disturbing any asbestos in the course of
installation then please use appropriate equipment.
There must not be an extractor fan in the same room as the
appliance as this can cause the appliance to emit fumes into the room.
There must be an adequate air supply to the room in which the
2 2
appliance is installed totalling at least 52 cm . (8 in ) to provide
combustion air. This is particularly necessary if the room is double
glazed.
This stove is capable of continuous operation when burning Wood
logs or Smokeless fuel.
This stove is not suitable for use in a shared flue system.
In addition to these instructions the requirements of BS.8303 and
BSEN 15287-1:2007 must be fulfilled. Local Authority Bylaws and
Building Regulations, including those referring to national and
European Standards, regarding the installation of Solid Fuel burning
appliances, flues and chimneys must also be observed.
CO ALA RMS
Building regulations require that whenever a new or replacement
fixed solid fuel or wood/biomass appliance is installed in a dwelling a
carbon monoxide alarm must be fitted in the same room as the
appliance. Further guidance on the installation of the carbon
monoxide alarm is available in BS EN 50292:2002 and from the
alarm manufacturer's instructions. Provision of an alarm must not be
considered a substitute for either installing the appliance correctly or
ensuring regular servicing and maintenance of the appliance and
chimney system.
®
ch arn wo od
INSTALLATIO N I N S TRUCTIONS
SLX 4 5
MU LTI -FU EL
10
Fuel Type
Wood Logs
Smokeless Fuel
Rated Output
12.3kW(41,970Btu/h)
14.3kw (48,791Btu/h)
Space Heating Output
6.0kw (20,472 Btu/h)
4.6kw (15,695 Btu/h)
Water Heating
6.3kw (21,496 Btu/h)
Flue Gas Temp
343°C
433°C
Flue Gas Mass Flow
7.8 g/s
10.8 g/s
Max Hearth Temp.
62.4°C
181.6°C
Re-fuelling Cycle
1.5hr
4.0 hr
CO @ 13% O
2
0.78%
0.14%
Min Distance to Combustible
INSET
FREESTANDING
Side
50mm
200mm
Above (inset)/ Rear
200mm
300mm
Max WaterPressure
1.5 Bar (50 foot water)
Boiler Volume
10.14 Litres
Min Flue Draft
25Pa (0.1in wg)
Stove Weight
135kg
9.7kw (33,096 Btu/h)
The heat output to the room is directly proportional to the heat
output to water as shown in Fig. 4. This means that if the water
heating load is less than the rated output then the room heating will
be reduced by the same proportion. This must be borne in mind
when calculating the heating requirements.
CHIM NEY
In order for the appliance to perform satisfactorily the chimney
height must not be less than 4 metres measured vertically from the
outlet of the fire to the top of the chimney. The chimney should
SPEC IFICATION
Page 11
preferably be 175 mm (7 inches) or 200mm (8 inches) internal
diameter or square with sides of 175mm or 200mm internally and
MUST NOT BE LESS THAN 150mm (6 INCHES) INTERNAL
DIAMETER OR 150 x 150mm INTERNAL SQUARE.
If an existing chimney is to be used it must be swept and checked, it
must be in good condition, free from cracks and blockages, and
should not have an excessive cross sectional area (e.g. greater than
250mm x 250mm). If you find that the chimney is in poor condition
then expert advice should be sought regarding the necessity of having
the chimney lined.
If the stove is fitted in place of an open fire then the chimney should
be swept one month after installation to clear any soot falls which
may have occurred due to the difference in combustion between the
stove and the open fire
If it is found necessary to line the chimney then a lining suitable for
Solid Fuel must be used. If there is no existing chimney then a
prefabricated block chimney or a twin walled insulated stainless steel
flue to can be used either internally or
externally. These chimneys must be fitted in accordance with the
manufacturers instructions and Building Regulations.
Single wall flue pipe is suitable for connecting the appliance to the
chimney but is not suitable for using for the complete chimney.
If it is found that there is excessive draw in the chimney then a
draught stabilizer should be fitted.
BSEN 15287-1:2007
0
2.0
4.0
6.0
8.0
10.0
2.0
Boiler
Output
(kW)
Space Output (kW)
Fig. 4. Performance Chart
4.0 6.0
Solid Fuel
W
ood
1. INSTALLATION AS AN INSET STOVE
The SLX 45 is supplied with one of two panel packs that makes it
either an Inset stove SLX45i or a Freestanding stove SLX45fs. The
following sections apply specifically to the Inset Installation. The
Freestanding installation is mentioned later
HEARTH AND FI RE SURRO UND
The appliance must be installed on a fireproof hearth. The positioning
of the appliance and the size of the hearth are governed by building
regulations for Solid Fuel appliances. These building regulations state
that the hearth must extend in front of the appliance by at least
300mm (12 inches) and to the sides by at least 150mm (6 inches). If
in doubt as to the positioning of the appliance expert advice should
be sought either from the supplier or the local building inspector.
The fireplace must allow sufficient airflow around the appliance to
provide combustion air and to allow the heat to be transferred to the
room. The fire surround must be able to withstand the temperatures
generated in normal use. If a wooden mantel is used it should be at
least 200mm (8 inches) above the appliance. Wooden surrounds
must be at least 100mm (4 inches) from the sides of the appliance. In
order for the appliance to fit into the fire surround there must be a
flat area around the opening, details are shown in Fig. 5.
PREPAR AT ION OF FIR E PLAC E
Before fitting the appliance into an existing fireplace remove the
fireback and any loose in-fill material.
The surround and opening for the appliance must conform with Fig.
5. The flat area around the opening should be a minimum of 750 mm
wide and 660 mm high. Ensure that the hearth and the base in the
opening are flat, level, and at right angles to the surround.
®
ch arn wo od
INSTALLATIO N I N S TRUCTIONS
SLX 4 5
MU LTI -FU EL
11
Fig. 5. Limiting Dimensions Of Surround And Opening
A
B
Dim. A:
Dim. B: Max. 575mm (22 2/3") Min. 555mm (21 3/4")
Max. 470mm (18 1/2") Min. 405mm (16")
The shaded area on the face of the surround is the minimum flat area required for Inset Installation.
660 mm
750 mm
Page 12
Make two holes in the chimney breast, one in the front to give access
for infilling and fixing the flue pipe, and one in the side to give access
for the pipework.
CENT RAL HEATIN G SYSTE M
The central heating system must comply with BS:5449 part 1.
If the system is to be a combined heating and domestic hot water
system then a double feed indirect hot water storage cylinder to
BS:1566 part 1 should be used. In order to prevent the build up of
scale and corrosion a suitable inhibitor should be used. The system
must be correctly vented as shown in Figs. 6 and 7. The height
differential between the header tank and the appliance must not
exceed 15.2 metres (50 feet).
If all four boiler tappings are used then, if possible, diagonal pairs
should be connected for domestic hot water and central heating.
Where a common return is used an injector tee must be
incorporated into the system as shown in Fig. 8. This will ensure that
a good domestic hot water supply is maintained when the central
heating pump is operating.
The system must incorporate a gravity circuit which will normally heat
the domestic hot water and an unvalved radiator with an output of at
least 1 kW. When the appliance is not connected to a domestic hot
water system the unvalved radiator(s) on the gravity circuit must have
an output of at least 1.25 kW. This is to prevent boiling in case of
pump failure. All pipework in the primary circuit must be 28 mm
diameter and the gravity flow pipe must rise continuously from the
boiler to the open vent. Two typical systems are shown in Figures 6.
and 7.
If the appliance is used to heat a small central heating system then the
heat output to the room from the fire will be reduced. Fig. 4. shows
the ratio of space heating to water heating which can be expected.
Fitting a radiator in the same room as the fire is recommended as it
will allow greater flexibility In the way that the system is operated as
well as ensuring that there is sufficient heat.
SYSTEM CON T ROLS
The circulating pump may be controlled by means of time switches,
room thermostats or outdoor thermostats. Radiators may be either
manually or thermostatically controlled. These controls will all work
in conjunction with the thermostat on the appliance and the minimum
®
ch arn wo od
INSTALLATIO N I N S TRUCTIONS
SLX 4 5
MU LTI -FU EL
Gravity Return
(28mm Pipe)
Central Heating Return
Common Return to Boiler
(28mm Pipe)
Fig. 8. Injector Tee
Fig. 7. Typical Central Heating & Hot Water System Using 3 Tappings
Central Heating Return
Drain Cock at Lowest Point
Drain Cock
Gravity
Return
28mm
Gravity
Flow
28mm
Indirect Hot Water Cylinder
Domestic Hot Water Draw Off
Cold Water Tank
Overflow
Overflow
Feed and Expansion Tank
22mm Open Vents
Gravity Radiator
Circulating Pump
Injector Tee
Minimum Return Thermostat
Central Heating Flow
12
Fig. 6. Typical Central Heating & Hot Water System Using 4 Boiler Tappings
Central Heating Flow
Central Heating Return
Drain Cock at Lowest Point
Drain Cock
Gravity
Return
28mm
Gravity
Flow
28mm
Indirect Hot Water Cylinder
Cold Water Tank
Overflow
Feed and Expansion Tank
22mm Open Vents
Gravity Radiator
Circulating Pump
Minimum Return Thermostat
Overflow
Domestic Hot Water Draw Off
Page 13
return thermostat.
We recommend fitting a pipe thermostat onto the gravity return pipe
and wiring it into the mains supply to the pump so that if the gravity
return temperature drops below 45° C then the pump will cut out.
This will help to prevent condensation forming on the boiler faces and
will thereby increase the life of the boiler. It will also ensure that
priority is given to the domestic hot water. These thermostats are
available from ourselves if you are unable to obtain them locally.
FITT ING THE FI R E
In some cases it may be necessary to place the connecting flue pipe in
the chimney before fitting the fire into the fireplace.
Apply fire cement to the rear face of the sealing flange on the
appliance. Fit the appliance into the opening ensuring that it is central
and that a good seal is made between the sealing flange and the face
of the surround.
Remove any excess fire cement from around the sealing flange. The
fire should be screwed to the hearth through the holes at the base of
the sealing flange.
Connect the heating system to the boiler ensuring that the primary
flow pipe rises from the appliance. Fill the system with water and
check for leaks.
FLU E CONNEC TION AND I N FILLIN G
Make the flue connection with a short length of 150mm (6’’) internal
diameter flue pipe (cast iron to BS41:1973, 1.0 mm thick stainless
steel, or 5.0mm thick mild steel).
The end of the flue pipe must line up with the centre-line of the
chimney, and must also extend to the point where the chimney
narrows to its final size. Any large voids must be filled and flaunched
to the flue pipe to ensure that all soot deposits can be cleared when
the chimney is swept. If necessary a flue offset is available. The offset
may be used directly with stainless steel flue pipe or may be used with
cast iron flue pipe in conjunction with a cast iron adaptor. If the flue
pipe has to be set at an angle then cut the ends so that it sits
correctly.
Ensure that the flue pipe is not obstructed or restricted in any way
and that all joints are well sealed.
Before infilling cover the front of the appliance to protect it. Ensure
that the flue pipe is central and then fill the space between the body
of the appliance and the structural brickwork with vermiculite (e.g.
Micafil or similar) concrete. Ensure that there are no air pockets. The
recommended mix is six volumes of vermiculite granules to one
volume of Portland cement thoroughly mixed together. Enough
water should be added so that no more than one or two drops of
water are released when a handful of the mixture is squeezed.
After filling with vermiculite flaunch the top of the flue connector
pipe to the chimney with lime mortar.
Make good the holes in the front and side of the chimney breast
making sure that they are completely airtight. A typical installation is
shown in Fig. 9.
In most installations it will be possible to sweep the chimney through
the appliance. If this is not possible then some alternative means (such
as a soot door), must be provided.
The free inset method of installation may be used instead of infilling.
Details are available on request.
2. INS TA L LATION AS A FREE STA NDING STOV E
The SLX45 may be installed as a Freestanding Stove when supplied
with the Freestanding Panel Pack 020/KV52. Typical installations are
®
ch arn wo od
INSTALLATIO N I N S TRUCTIONS
SLX 4 5
MU LTI -FU EL
Fig. 9. Typical Installation into standard chimney
Vermiculite Infill
Flaunching
Short Length
or Flue Offset.
Of Flue Pipe,
13
Page 14
shown in Figs. 10 & 11 and may be either on a freestanding hearth or
in an ‘Inglenook’ type fireplace. In these configurations the minimum
distances to combustible materials must be 200mm from the sides of
the stove and 300mm from the back. Stud wall is counted as
combustible, and if this distance is required to be reduced, then
additional shielding must be provided.
The Hearth requirements are the same as the Inset Installation.
If the stove is to be installed on a freestanding hearth, as shown in
Fig.10, then the fireplace may be bricked up and filled with non-
combustible material, and the chimney breast broken into higher up
the wall, and a sleeve inserted to take the Fluepipe. The angle
between the vertical and the sleeve/fluepipe must be not less than
135°. It is advisable for the vertical section of the Fluepipe to be at
least 600mm long. A soot door for debris clearance / chimney
sweeping must be provided and this may be in the side or front of the
chimney breast, or outside.
If the stove is to be installed in an ‘Inglenook’ type Fireplace, then
there must be sufficient space around and above it for air to circulate,
and for access for servicing. This requires a minimum of 150mm each
side and 300mm above. There must not be any combustible materials
within these distances. A steel ‘Register’ plate will be fixed into the
chimney, preferably at a height where the chimney narrows down so
as to avoid having a large air void above the register plate. The
®
ch arn wo od
INSTALLATIO N I N S TRUCTIONS
SLX 4 5
MU LTI -FU EL
14
Fig. 10. Freestanding Installation with Chimney Connection above the Fireplace
Alternative positions for Soot Door for sweeping and debris clearance
Masonry Chimney
135° Min
150mm(6") Fluepipe sleeved through chimney wall
Old fireplace filled with non­combustible material and bricked up.
Metal Closure Plate or ‘Register Plate’
Min 300mm from combustible materials
Recommended min vertical section 600mm(24")
Alternative Soot Door Positions
Metal Closure Plate or ‘Register Plate’ With Soot Door
Masonry Chimney
Fig. 11. Freestanding Installation with Chimney Connection in ‘Inglenook’ type Fireplace
Page 15
®
ch arn wo od
INSTALLATIO N I N S TRUCTIONS
SLX 4 5
MU LTI -FU EL
15
fluepipe from the stove will protrude a small amount through the
hole in the register plate, and will be sealed in position. This is shown
in Fig.11.
THER MOSTAT
Before lighting the fire check the cold setting distance of the
thermostat.
With the control knob at the minimum setting the flap should be just
closed as shown in Fig. 12. To adjust the distance slacken the locking
nut and adjust as necessary. When set correctly re-tighten the locking
nut. Ensure that the flap opens and closes freely as the knob is
turned.
ASSE MBLY
Fit the side panels and hood onto the appliance. Instructions for this
are enclosed with the panel pack. Replace any internal parts
previously removed.
PRE LI GHTING C H ECK
Before initial lighting check the following points:
1. The bottom grate bars must all be fitted and should move freely
and easily when the riddling mechanism is operated.
2. The plates round the sides and back of the grate must be in
position and sitting correctly.
3. The throat plate must be fitted in the roof of the appliance and
should be pushed back so that it touches the knee of the boiler.
COMM ISSION I NG
On completion of the installation and after allowing a suitable period
of time for the fire cement and mortar to dry out, the fire should be
lit and checked to ensure that smoke and fumes are taken from the
appliance up the chimney and emitted safely. Also check all joints and
seals.
The central heating pump should be adjusted to give the correct
water flow against the circuit resistance and the system should be
correctly balanced.
On completion of the installation and commissioning please leave the
operating instructions with the customer and advise on the use of the
appliance and any controls on the system.
Fig. 12. Thermostat Setting
Thermostat Flap
Locking Nut
Flap Just Closed With
Knob Set To Minimum
Page 16
170
548
147
547
250
464
280
357
394
236
ø168
608
1
0
4
5
2
3
2 Boiler tappings each side 1” B.S.P. Female.
®
ch arn wo od
SLX45 DIMENSIONS (MM)
SLX 4 5
MU LTI -FU EL
601
126
610
469
546
135
408
590
531
549
Height to Top
of Flue Ring
Flue Centre Line
16
Page 17
Issue A
®
ch arn wo od
SLX45 MKII PARTS LIST
SLX 4 5
MU LTI -FU EL
®
char n w o od
T: +4 4 (0) 1983 5 377 99 • F :+44 ( 0) 198 3 5 377 88 • S PAR ES @C HA RNW OOD .C OM • W WW. CH ARNW OO D.CO M
BI SHOPS WAY, NE WP ORT, ISLE OF WI GHT P O30 5 WS , U NI TE D K IN GDOM
To obtain spare parts please contact your local stockist giving Model, Part No. and Description. In case of difficulty contact the manufacturer at the address shown. This drawing is for identification purposes only.
* These items are not shown on the drawing. ## Please specify colour when ordering. ** These items are included in the Freestanding Panel Pack
17
Item Part No Description Item Part No Description
1* 008/KV35S Door Seal Set Inc. Adhesive 26 012/KV19 Riddler Rod 2* 008/FW29 Door Seal Adhesive 27 012/CG05 Idler Rod 3 006/KV18 Glass (Inc Seal) 28 008/FW48 Thermostat 4* 008/KV55 Glass Seal Kit 29 008/FV49 Thermostat Flap 5 004/KV23 Glass Retainer 30 005/KV04/## L.H. Side Panel 6 008/TV27 Hinge Post 31 005/KV05/## R.H. Side Panel 7 008/BW39/S Hinge Pin Set 32 005/KV06/## Lower Hood Panel 8 008/KV16 R.H. Door Handle 33 005/KV09/## Top Hood Panel 9 002/KV14 Door Catch Cam 34 003/TV01/## L.H. Door 10 008/KV13 L.H. Door Knob 35 003/TV02/## R.H. Door 11 010/RW21 Ashpan/Riddling Tool 36 009/SLX45/A Replacement Firebox/Boiler Assy. 12 012/FW34 Scraper Tool 37 012/KV12 Serial No. Label 13 008/BW50 Thermostat Knob 38 008/FFW010 Washer 14 002/KV07 Front Firebar 39 008/FFW015 M12 Double Coil Spring 15 002/KV11 Front Firebar Back Plate 40 004/ST008 Tabbed Locking Washer 16 002/KV08 Deepening Bar 41** 010/KV29 Freestanding Panel Fixing Bracket 17 002/AV31 Throat Plate 42** 020/KV52/## Freestanding Panel Pack 18 002/FW15 Side Fire Plate 43* 010/FW51 Ash Carrier (Optional Extra) 19 002/FW16 Back Fire Plate 44 008/FFN001 12mm Halfnut 20 002/CG01 Bottom Grate Bar 45 010/XV05 Airwash Manifold 21 002/CG01S10 Set of Grate Bars (10) 46 002/TW13 Air Slide Knob 22 004/KV17 Ashpan 47 012/XV09 Airwash Slide 23 012/KV33 Mover Bar 48 010/KV34 Air Inlet Manifold 24 002/KV30 Carrier Bar 49 012/XV09/03 Airwash Slide 24a 008/BW40 Carrier Bar Roll Pin (pair) 50 012/XV09/02 Airwash Slide guide 25 002/CG06 Riddler knob
24a215
42
49
11
42
3
42
25
30
29
41
12
28
36
18 22 23
67 8
42
32
9
24
35
34
26
14
15
3
50
10
16
13
18
19
31
45
47
46
17
33
48
27
20
37
9
40
39
44
38
Page 18
1818
A Division of A.J.Wells & Sons Limited Registered in England No. 03809371
12
Bishops Way, Newport, Isle of Wight PO30 5WS, United Kingdom
A.J WELLS & SONS LTDA.J WELLS & SONS LTD
BSEN 13229:2001 EN13240:2001
SLX45M KI I
MULT I -F UE L
ROOMHE AT E R & BOILE R F I R E D BY S O LID FUE L
EC Certificate of conformity no:
KV080-CPD-2011
Maximum operating pressure:
1.5 bar
Fuel types:
WOOD LOGS
ANTHRACITE
Emission of CO in combustion products:
0.78%
0.14%
Mean flue gas temperature:
343°C
433°C
Thermal output:
12.3kW
14.3kW
Space heating output:
6.0kW
4.6kW
Water heating output:
6.3kW
9.7kW
Energy efficiency
75.5%
70.6%
Minimum distance to combustible materials Side: Above (inset) / rear:
INSET
50mm
200mm
FREESTANDING
200mm 300mm
Page 19
Page 20
A D i v i s i o n o f A . J . W e l l s & S o n s L i m i t e d R e g i s t e r e d i n E n g l a n d N o . 0 3 8 0 9 3 71
char n w o od
T : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 7 7 • F : + 4 4 ( 0 ) 19 83 5 3 7 7 8 8 • C O N T A C T U S A T W W W. C H A R N W O O D . C O M
BI SHOPS WAY, NE WP ORT, ISLE OF WI GHT P O30 5 WS , U NI TE D K IN GDOM
y ou r p re m ie r d ea l er
REV. SLX45MKII 10.12
®
Loading...