Exploded Parts Drawing............................... 11
®
C H A R N W O O D B i s h o p s Wa y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m
T: + 4 4 ( 0 ) 19 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m
A D i v i s i o n o f A . J . W e l l s & S o n s L i m i t e d R e g i s t e r e d i n E n g l a n d N o . 0 3 8 0 9 3 71
Page 4
OPERATING INSTRUCTIONS FOR THE
CHARNWOOD LA20i
GENERAL POINTS
Before lighting the fire check with the
installer that the work and checks
described in the installation
instructions have been carried out
correctly and that the chimney has
been swept, is sound, and free from
any obstructions.
WARNING There must not be an
extractor fan fitted in the same room
as this appliance as this can cause the
appliance to emit smoke and fumes
into the room.
If the appliance is fitted in place of an
open fire then the chimney should be
swept one month after installation to
clear any soot falls which may have
occurred due to the difference in
combustion between the appliance and
the open fire.
When using the fire in situations
where children or infirm people are
present please use a fire guard to
prevent accidents. The fire guard
should be manufactured in accordance
with BS 6539.
This appliance obtained approval by
HETAS Ltd. in the safe and fit for
purpose category.
control areas your Housing Authority
will be able to advise you if other
fuels may be burnt. For instructions on
burning other fuels please ask your
your supplier or Housing Authority for
the “Charnwood Instruction
Supplement.”
PETROLEUM COKE IS
NOT SUITABLE FOR USE
ON THIS APPLIANCE, ITS
USE WILL INVALIDATE
THE GUARANTEE
At first you may find it helpful to try
several fuels to find the most suitable.
If you are unable to obtain the fuel
you want ask your supplier, an
approved fuel distributor, or the Solid
Fuel Association (tel. 0800 600 000)
to suggest an alternative.
DOOR OPERATION
Use the spanner type tool to open and
close the doors. Turn the knob on the
right hand door anti-clockwise to open
and clockwise to close. When closing
the doors do not push on the enamel
with the tool as this can chip the
enamel, instead push the doors on the
door knobs.
remove any clinker from the firebed
and empty the ashpan.
CONTROLLING THE
FIRE
The rate of burning and hence the
output is controlled by the control
knob on the left hand side of the
appliance, shown in Fig. 1. This is
linked to a thermostat which controls
the firebox temperature. The number
at the top of the knob is the number at
which it is set. Some experimentation
may be necessary to obtain the desired
heat output.
There is also a manual secondary air
control which is located above the
door opening as shown in Fig. 2. To
adjust the setting, open the doors and
use the door opening tool to move the
flap to the desired position. This
control should be in the closed
position when burning any of the
recommended smokeless fuels except
FUELS
HETAS Ltd. approval only covers the
use of the following smokeless fuels
on this appliance:
Approval does not cover the use of
other fuels either alone or mixed with
the above fuels, nor does it cover
instructions for the use of other fuels.
The above fuels are all suitable for use
in smoke control areas. In non-smoke
LIGHTING
Place some paper and dry kindling
wood or fire lighters on the grate and
cover with a small amount of fuel.
Turn the thermostat control knob to
the maximum setting and light the
paper or fire lighters. Close the doors
and allow the fire to burn until the fuel
is well ignited then load with more
fuel and adjust the thermostat to the
required level.
On initial lighting, the fire may smoke
and give off an odour as the silicon
paint with which the firebox is painted
reacts to the heat. This is normal and
will cease after a short time. In the
meantime the room should be kept
well ventilated.
Before relighting the fire, riddle,
Page 3
LA20i 3/99
5
0
4
3
2
1
Control
Knob
Air Inlet
Damper
Fig. 1. Thermostat Control
Page 5
Open
will seriously damage the grate bars.
Ensure that the air inlet damper is not
prevented from closing by spilled fuel
or ash.
Secondary Air
Flap (shown
closed)
Fig. 2. Secondary Air Control
for anthracite and homefire which
should be burnt with the secondary air
inlet open.
RUNNING THE FIRE
WITH THE DOORS
OPEN
The fire may be run with the doors
open. This will result in a reduction in
efficiency and hence heat output. The
more reactive fuels, like homefire, will
burn better when the doors are open
than fuels like phurnacite, sunbrite and
ancit.
For safety reasons, if the fire is to be
left unattended with the doors open
then use a spark guard which complies
with BS 3248.
ASH CLEARANCE
The ashpan should be emptied
regularly before it becomes too full.
The most convenient time to remove
the ash is just before riddling the fire
since the ash will then be at it’s
coolest. Use the tool provided to
remove the ashpan.
Never allow the ash to accumulate in
the ashpan so that it comes in contact
with the underside of the grate as this
Care should be taken to ensure that
ash is cool before emptying it into
plastic liners or bins.
To make ash removal easier there is a
special Charnwood ash carrier
available. This may be purchased from
your supplier or, in case of difficulty,
from ourselves.
RIDDLING
Riddling twice a day is usually
sufficient.
The fire should be riddled with all
doors shut. Place the tool on the knob
and rotate between the horizontal and
the 45 degree position several times as
shown in Fig. 3.
Caution: when riddling the grate using
solid fuel do not go beyond the 45
degree position as this can cause the
grate to jam.
If jamming does occur then the fire
should be allowed to burn for
approximately half an hour before
riddling the grate again as described
above.
Too much riddling can result in
emptying unburnt fuel into the ashpan
and should therefore be avoided.
Clinker should regularly be removed
from the firebed.
After riddling, the grate should be put
back into the solid fuel position (the
tool should be horizontal).
REFUELLING
Keep the firebox well filled (the fuel
may be sloped up from the front
firebars), but do not allow fuel to spill
over the top of the front fire bars. Take
care that fuel does not project over the
front fire bars or damage to the glass
may be caused when the doors are
closed.
OVERNIGHT
BURNING
Empty the ashpan, if necessary, and
then riddle the fire. If the fire is very
low then it may be necessary to add a
Do Not Go Beyond
45° Position
When Riddling
Riddle Between
Horizontal &
45° Positions
C W
After Riddling
Move Tool
To Horizontal
Position
Fig. 3. Grate Operation
little fuel and turn the thermostat
control up for a brief period until the
fire is burning well before filling with
fuel.
Some experimentation may be
necessary to find the thermostat
setting most suitable for the particular
fuel used and the draw on the
chimney, but generally the thermostat
should be turned down to the
minimum setting overnight.
For overnight burning the fire doors
must be closed.
To revive the fire, empty the ashpan if
necessary, riddle, and turn the
thermostat control knob to maximum.
When the fire is burning well load on
more fuel as necessary and turn the
thermostat to the desired setting.
THROAT PLATE AND
FLUEWAY CLEANING
It is important that the throat plate and
all the appliance flueways are kept
clean. When burning smokeless fuels
Page 4
LA20i 3/99
Page 6
they should be cleaned monthly. When
burning other fuels they should be
cleaned at least once a week, and more
frequently if necessary.
The throat plate and flueways may be
cleaned with a low fire still burning.
Use the scraper tool to scrape any
sooty deposits to the front of the plate
until they fall off into the fire.
More soot will be deposited on the
throat plate and in the flueways if the
appliance is run at low levels for long
periods. If this is the case then more
frequent cleaning will be necessary.
MAINTENANCE
Cleaning
The appliance is finished in vitreous
enamel. To clean the surfaces simply
wipe over with a dry cloth. Abrasive
pads and scouring cleaners must not
be used as these will damage the
finish. Care should be taken not to
knock the enamel with hard objects as
it will chip.
Cleaning the Glass
The glass in the doors is a special
ceramic glass which is able to
withstand high temperatures. Before
cleaning the glass open the doors and
allow them to cool. Clean the glass
using a damp cloth and then wiping
over with a dry cloth. Any stubborn
deposits may be removed with a
proprietary stove glass cleaner or
ceramic hob cleaner. Some deposits on
the glass may be burnt off simply by
running the fire at a fast rate for a few
minutes. Do not use abrasive cleaners
or pads as these can scratch the
surface which will weaken the glass
and cause premature failure. Aerosol
spray cleaners should not be used near
the appliance whilst it is under fire.
When not in use
If the fire is going to be out of use for
a long period (for instance in the
summer) then to prevent condensation,
and hence corrosion, the thermostat
should be left at the maximum setting
and the main doors left ajar. It is also
advisable to sweep the chimney and
clean out the fire. Spraying the inside
of the doors and firebox with a light
oil, such as WD40, will also help to
keep all internal parts working well.
After long periods where the fire has
been out of use, the chimney and
appliance flueways should be cleaned
before lighting.
Door Seals
For the fire to operate correctly it is
important that the door seals are in
good condition. Check that they do not
become worn or frayed and replace
them when necessary.
Servicing
It is recommended that the fire is
serviced once a year to keep it in first
class working order. After cleaning out
the firebox thoroughly, check that all
internal parts are in good working
order, replacing any parts that are
beginning to show signs of wear.
Check that the doors seals are in good
condition and that the doors seal
correctly. Check the operation of the
thermostat, both when cold and hot. A
servicing guide, TIS 48. is available
on request.
CHIMNEY SWEEPING
The chimney should be swept at least
twice a year. In most installations it
will be possible to sweep the chimney
through the appliance.
First remove the front firebars and the
throat plate. Then sweep the chimney
ensuring that soot is removed from all
horizontal surfaces after sweeping.
In situations where it is not possible to
sweep through the appliance the
installer will have provided alternative
means, such as a soot door. After
sweeping the chimney the appliance
flue outlet and the flue pipe
connecting the appliance to the
chimney must be cleaned with a flue
brush.
After clearing any soot from within
the fire, replace the throat plate and
the front firebars.
Different types of sweep’s brushes are
available to suit different flueways.
For standard brick chimneys a wire
centre sweep’s brush fitted with a
guide wheel is recommended. For
prefabricated insulated chimneys the
manufacturers instructions with regard
to sweeping should be consulted.
TROUBLE SHOOTING
Fire Will Not Burn.
Check that:
a) the air inlet is not obstructed in any
way,
b) that chimneys and flueways are
clear,
c) that a suitable fuel is being used,
d) that there is an adequate air supply
into the room,
e) that an extractor fan is not fitted in
the same room as the fire.
Fire Blazing Out Of Control.
Check that:
a) the doors are tightly closed,
b) the thermostat knob is turned down
to the minimum setting,
c) the air inlet damper is closed (at the
bottom left of the appliance), and that
it is not prevented from closing
completely by a piece of ash,
d) a suitable fuel is being used,
e) the door seals are in good condition.
Over-Firing
If the fire is over-fired it will cause
premature failure of the internal fire
parts. Overfiring is occurring when
any internal parts of the fire begin to
glow red. To prevent over-firing
ensure that:
a) the door seals are kept in good
condition, and that the doors are
sealing correctly,
b) the thermostat on the fire is
working correctly,
c) a suitable fuel is being used.
Fume Emission.
Warning Note:
Properly installed and operated this
appliance will not emit fumes.
Occasional fume from de-ashing
and re-fuelling may occur.
Persistent fume emission is
potentially dangerous and must not
be tolerated. If fume emission does
persist then the following immediate
actions should be taken:
A) Open doors and windows to
ventilate the room.
B) Let the fire out and safely dispose
of fuel from the appliance.
C) Check for flue or chimney
blockage, and clean if required.
Page 5
LA20i 3/99
Page 7
D) Do not attempt to relight fire
until cause of fume has been
identified, if necessary seek
professional advice.
The most common cause of fume
emission is flueway or chimney
blockage. For your own safety these
must be kept clean.
Freezing
If a boiler is fitted do not light the fire
if there is any possibility that any parts
of the system may be frozen.
Chimney Fires.
If the chimney is thoroughly and
regularly swept, chimney fires should
not occur. However, if a chimney fire
does occur turn the control knob to the
minimum setting, and tightly close the
doors of the appliance. This should
cause the chimney fire to go out in
which case the control should be kept
at the minimum setting until the fire in
the appliance has gone out. The
chimney and flueways should then be
cleaned. If the chimney fire does not
go out when the above action is taken
then the fire brigade should be called
immediately.
After a chimney fire the chimney
should be carefully examined for any
damage. Expert advice should be
sought if necessary.
Page 6
LA20i 3/99
Page 8
INSTALLATION INSTRUCTIONS FOR THE
CHARNWOOD LA20i
HEALTH AND SAFETY
PRECAUTIONS
WARNING
Please take care when installing the
appliance that the requirements of the
Health and Safety at Work Act 1974
are met.
Some types of fire cement are caustic
and should not be allowed to come
into contact with the skin. In case of
contact wash with plenty of water.
If there is a possibility of disturbing
any asbestos in the course of
installation then please use appropriate
protective equipment.
There must not be an extractor fan
fitted in the same room as the
appliance as this can cause the
appliance to emit fumes into the room.
There must be an adequate air supply
into the room in which the appliance is
installed totalling at least 100 square
cm. (16 square inches) to provide
combustion air. This is particularly
necessary if the room is double glazed.
In addition to these instructions the
requirements of BS:8303 and BS:6461
Pt 1&2; 1984 must be fulfilled. Local
Authority Bylaws and Building
Regulations regarding the installation
of Solid Fuel burning appliances, flues
and chimneys must also be observed.
PERFORMANCE
The rated output for the LA20i is 5.4
kW (18800 btu/h) to the room.
This is the output obtained burning
Sunbrite Doubles at a rate of 1.0 kg/hr
with the doors closed over a 4 hourly
re-fuelling interval.
There is an optional add-in domestic
hot water boiler available with an
output of 2.0 kW (6800 btu/h). If this
is fitted then the output to the room
will be reduced by a corresponding
amount.
CHIMNEY
In order for the appliance to perform
satisfactorily the chimney height must
not be less than 4 metres measured
vertically from the outlet of the fire to
the top of the chimney. The chimney
should preferably be 175 mm (7
inches) or 200mm (8 inches) internal
diameter or square with sides of
175mm or 200mm internally and
MUST NOT BE LESS THAN 150mm
(6 INCHES) INTERNAL
DIAMETER OR 150 x 150mm
INTERNAL SQUARE.
If an existing chimney is to be used it
must be swept and checked, it must be
in good condition, free from cracks
and blockages, and should not have an
excessive cross sectional area (e.g.
greater than 250mm x 250mm). If you
find that the chimney is in poor
condition then expert advice should be
sought regarding the necessity of
having the chimney lined. If it is
found necessary to line the chimney
then a lining suitable for Solid Fuel
must be used.
If there is no existing chimney then a
prefabricated block chimney or a twin
walled insulated stainless steel flue to
BS:4543 can be used either internally
or externally. These chimneys must be
fitted in accordance with the
manufacturers instructions and
Building Regulations.
Single wall flue pipe is suitable for
connecting the appliance to the
chimney but is not suitable for using
for the complete chimney.
If it is found that there is excessive
draw in the chimney then a draught
stabilizer should be fitted.
HEARTH
The appliance must be installed on a
fireproof hearth and must be situated
at least 300 mm (12 inches) from any
combustible material. The positioning
of the appliance and the size of the
hearth are governed by building
regulations for Class 1 appliances.
These building regulations state that
the hearth must extend in front of the
appliance by at least 300 mm (12
inches) and to the sides by at least 150
mm (6 inches). If in doubt as to the
positioning of the appliance expert
advice should be sought either from
the supplier or the local building
inspector.
PREPARATION OF
FIREPLACE
Before fitting the appliance into an
existing fireplace remove the fireback
and any loose in-fill material.
The hearth, surround and opening for
the appliance must conform with Figs.
4 and 5. The flat area around the
opening must be a minimum of 750
mm wide and 660 mm high. Ensure
that the hearth and the base in the
opening are flat, level, and at right
angles to the surround.
Make a hole in the front of the
chimney breast to give access for
infilling and fixing the flue pipe. If the
optional boiler is to be fitted it will
also be necessary to make a hole in the
side of the chimney breast to give
access for the pipework.
FITTING THE FIRE
In some cases it may be necessary to
place the connecting flue pipe in the
chimney before fitting the fire into the
fireplace.
Apply fire cement to the rear face of
the sealing flange on the appliance. Fit
the appliance into the opening
ensuring that it is central and that a
good seal is made between the sealing
flange and the face of the surround.
Remove any excess fire cement from
around the sealing flange.
The appliance should be screwed to
the hearth through the holes at the
base of the sealing flange.
Page 7
LA20i 3/99
Page 9
This Dimension Is The
Minimum Level Area
Required To Enable The
Doors To Be Opened.
For Overall Sizes Of
Hearth See The
Section Titled "Hearth".
405 mm
400 mm
Minimum
Fig. 4. Limiting Dimensions
Of Hearth
The shaded area on the face of
the surround is the minimum flat
area required.
750 mm
appliance is to be fitted in a soft water
area in which case the stainless steel
boiler may be used with a direct hot
water cylinder.
All pipework in the primary circuit
must be 28mm diameter and the flow
pipe must rise continuously from the
boiler to the open vent.
If an indirect cylinder is used then the
primary circuit should be filled with a
suitable inhibitor to prevent the build
up of scale and corrosion.
FITTING THE
OPTIONAL ADD-IN
BOILER
The boiler replaces the rear firebrick
and is reversible so that the 1’’ B.S.P.
male tappings may come on either the
left or the right hand side of the boiler.
The boiler tappings protrude from the
sides of the appliance and it will
therefore be necessary to fit the boiler
into the appliance after positioning the
appliance in the fireplace if the fire
surround is already fitted.
Remove the backnuts and fibre
washers from the boiler tappings and
fit the boiler into the appliance. Place
the fibre washers over the tappings on
the outside of the appliance and fit the
backnuts, ensuring that the boiler is
held tightly against the rear inside face
of the appliance and that the top edge
of the boiler is level or runs uphill to
the flow tapping.
When re-fitting the firebricks, note
that the short side firebrick supplied
with the boiler must be fitted on the
same side as the boiler tappings. One
of the original side firebricks is fitted
on the other side, and the rear firebrick
is discarded. The firebricks must be
fire cemented into position, wetting
the firebox will improve the adhesion.
Replace the back fireplate, the side
fireplates, the front firebar and the
throat plate.
Connect the boiler to the heating
system ensuring that the flow pipe
rises from the boiler. Fill the system
with water and check for leaks.
The optional add-in boiler which may
be fitted in the appliance has an output
sufficient for domestic hot water
heating. If the boiler is fitted then the
room heating will be reduced.
The hot water system should be a
gravity circuit and must be correctly
vented as shown in Fig. 6.
The steel boiler in conjunction with a
double feed indirect hot water storage
cylinder to BS:1566 part 1 should be
used in most situations, unless the
Before fitting the boiler, remove the
front firebars, the side and back fire
plates and the firebricks. Knock out
the knock-outs for the boiler tappings
on the appropriate side of the firebox.
Feed and Expansion Tank
Overflow
Drain Cock at Lowest Point
22mm Open Vents
Gravity Flow 28mm
Gravity Return 28mm
Fig. 6. Typical Gravity Hot Water System
Cold Water Tank
Overflow
Domestic Hot Water Draw Off
Drain Cock
Indirect Hot Water Cylinder
Page 8
LA20i 3/99
Page 10
FLUE CONNECTION
AND INFILLING
Make the flue connection with the
special 150°elbow part no. 010/AV12.
Please note that this item is ordered
separately from the appliance. The
legs of the elbow may be cut on site to
suit the chimney. Also note that the
legs of the elbow are different lengths
to enable some situations to be catered
for by turning the elbow around.
The end of the flue pipe must line up
with the centre-line of the chimney,
and must also extend to the point
where the chimney narrows to its final
size. Any large voids must be filled
and flaunched to the flue pipe to
ensure that all soot deposits can be
cleared when the appliance is swept,
and to prevent problems with the
operation of the appliance.
Ensure that the flue pipe is not
obstructed or restricted in any way and
that all joints are well sealed.
Before infilling cover the front of the
appliance to protect it. Ensure that the
flue pipe is central and then fill the
space between the body of the
appliance and the structural brickwork
with vermiculite (e.g. micafil or
similar) concrete. Ensure that there are
Flaunching
Take Flue Pipe
Up To Narrowest
Part Of Chimney.
150° Elbow
Part No. 010/AV12
150°
Vermiculite
Infill
1
2
3
045
no air pockets. The recommended mix
is six volumes of vermiculite granules
to one volume of Portland cement
thoroughly mixed together. Enough
water should be added so that no more
than one or two drops of water are
released when a handful of the
mixture is squeezed.
After filling with vermiculite concrete
flaunch the top of the flue connector
pipe to the chimney with lime mortar.
Ensure that the flue pipe is well sealed
to the chimney.
Make good the hole(s) in the chimney
breast making sure that it is
completely airtight. A typical
installation is shown in Fig. 7.
In most installations it will be possible
to sweep the chimney through the
appliance. If this is not possible then
some alternative means (such as a soot
door), must be provided.
The free inset method of installation
may be used instead of infilling.
Details are available on request.
THERMOSTAT
Before lighting the fire check the cold
setting distance of the thermostat.
With the control knob at the maximum
setting the flap should be 18 mm from
the air inlet as shown in Fig. 8. To
adjust the distance slacken the locking
nut and adjust as necessary. When set
correctly re-tighten the locking nut.
Ensure that the flap opens and closes
freely as the knob is turned.
ASSEMBLY
Fit the side panels and hood onto the
appliance. Instructions for this are
enclosed with the panel pack.
Replace any internal parts previously
removed.
PRE LIGHTING
CHECK
Before initial lighting check the
following points:
operated.
2. The plates round the sides and back
of the grate must be in position and
sitting correctly.
3. The throat plate must be fitted in the
roof of the appliance.
COMMISSIONING
On completion of the installation and
18mm
Locking Nut
Thermostat Flap
Fig. 8. Thermostat Setting
after allowing a suitable period of time
for the fire cement and mortar to dry
out, the fire should be lit and checked
to ensure that smoke and fumes are
taken from the appliance up the
chimney and emitted safely. Also
check all joints and seals.
On completion of the installation and
commissioning please leave the
operating instructions with the
customer and advise on the use of the
appliance.
FREESTANDING KIT
A freestanding kit is available. Details
of dimensions and outputs are
available on request.
Fig. 7. Typical Installation
1. The bottom grate bars must all be
fitted and should move freely and
easily when the riddling mechanism is
Page 9
LA20i 3/99
Page 11
CHARNWOOD LA20i
OVERALL DIMENSIONS
(All dimensions are in mm)
Add-In Boiler May Be Fitted With
Tappings Either Side.
394
154
i/d
84
260
547
506
FLUELC
405
265
150°
260
200
1
2
3
4
5
0
120
619
554
164
Page 10
LA20i 3/99
Page 12
Item Part Description Item Part Description
Issue J
CHARNWOOD LA20 PARTS LIST
41 41a
40a
44
36
29
5
0
4
3
15
2
1
2827131442
43
32a
32
45
31
33
30
19 26 18 20 25 1216 75 35
40a
17
39
39
39
50
49
51
47 48
Freestanding Kit
101134892323241822
3*008/RW35/S Door Seal Set Incl. Adhesive 39 011/AV28S Set Of Firebricks4*008/FW29 Door Seal Adhesive 40a 011/AV28BS Set Of Firebricks (Use with boiler)5006/RW18 Glass Inc Glass Channel 41 010/AV25 Add-In Boiler (Steel)6*008/RW44/S Glass Channel - set of 8 41a 010/AV25/SS Add-In Boiler (Stainless Steel)7004/EW23 Glazing Bar 42 012/FW34 Scraper Tool8008/FW27 Hinge Post 43 008/RW09 Secondary Air Flap9008/BW39/S Hinge Pin Set (4 per set) 44 010/AV12 150° Flue Pipe (Optional Extra)10008/RW43/A Door Catch Assembly R.H. 45 012/AV11 Serial Number Label11002/HV12 Door Knob L.H. (Round) 46* 010/EW51 Ash Carrier (Optional Extra)12002/CG06 Riddler Knob47005/AV23 Side Panel L.H. (Freestanding Kit)13002/BW20 Riddler/Ashpan Tool 48 005/AV24 Side Panel R.H. (Freestanding Kit)14002/BW26 Door Opening Tool 49 005/AV22 Hood Panel (Freestanding Kit)15008/BW50 Thermostat Knob 50002/AV13 150° Flue Elbow (Freestanding Kit)16002/FW07 Front Firebar 51 010/AV26 Rear Panel Bracket (Freestanding Kit)17002/AV31 Throat Plate18002/HW15 Side Fire Plate19002/HW16 Back Fire Plate20002/CG01 Bottom Grate Bar21002/CG01S7 Set Of Grate Bars (7per set)22004/EW17 Ashpan23002/HW30 Carrier Bar24012/HW33 Mover Bar25012/FW14 Riddler Rod26012/CG05 Idler Rod27008/BW49 Thermostat28008/BW57 Thermostat Flap 90mm dia29005/RW05 Side Panel L.H.30005/RW04 Side Panel R.H.31005/RW06 Hood Panel32004/RW13 Panel Fixing Bracket32a012/RW30 Hood & Panel Fixing Kit33008/WW14S Hood Fixing Pin Set (4)34003/RW01 Door L.H.35003/RW02 Door R.H.36001/AV10 Firebox (LA20i)
* These items are not shown on the drawing. To obtain spare parts please contact your local stockist giving Model, Part No. and Description. In case of difficulty contact the manufacturer at the address shown.This drawing is for identification purposes only.
®
C H A R N W O O D B i s h o p s Wa y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m
T: + 4 4 ( 0 ) 19 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m
Page 13
Notes
Page 14
Notes
Page 15
Page 16
Your Local Charnwood Dealer:
®
C H A R N W O O D B i s h o p s Wa y , N e w p o r t , I s l e o f W i g h t P O 3 0 5 W S , U n i t e d K i n g d o m
T: + 4 4 ( 0 ) 19 8 3 5 3 7 7 9 9 F : + 4 4 ( 0 ) 1 9 8 3 5 3 7 7 8 8 c h a r n w o o d @ a j w e l l s . c o . u k w w w . c h a r n w o o d . c o m
A D i v i s i o n o f A . J . W e l l s & S o n s L i m i t e d R e g i s t e r e d i n E n g l a n d N o . 0 3 8 0 9 3 71
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.