Charnwood C4, C-FOUR Operating & Installation Instructions Manual

Page 1
Operating & Installation Instructions
charnwood
®
Page 2
Page 3
C O N T E N T S
O P E R AT I NG I N S T R U CT I O N S
Fuel
Lighting
Refuelling
Ash Clearance
Reduced Burning
Cleaning and Maintenance
Throat Plate & Flueway Clearing
Chimney Sweeping
Servicing
Trouble Shooting
CO Alarm
If you need further help
Health & Safety Precautions
CO Alarms
Specification
Chimney
Hearth & Fire Surround
Connection to Flues
Soot Doors
Pre Lighting Check
Commissioning
Clean Air Act Information
Dimensions
Parts Lists
Certification
4
4
5
5
5
6
6
6
6
6
7
7
7
9
10
11
11
11
11
12
13
14
INS TALLAT ION I NSTRUCT ION S
5
9
9
9
9
Controlling The Fire
Ref. C-FOUR v1 09.11
Page 4
Tools required for fitting the riddling grate:
10mm Spanner Pozidrive screwdriver
Before fitting the riddling grate (Fig. 1) remove the fuel retainer and
the wood ash retainer. The wood ash retainer is not required when
the riddling grate is fitted.
Undo the nut on the riddling blanking hole using a 10mm spanner.
Remove the cover and spacing washer (ensure you keep these in a
safe place as you will need to replace them if the riddling grate is
removed).
Feed the riddler rod through the hole on the right hand side of the
stove, and slide one washer onto the rod. (If there is not sufficient
room to the right of the stove to do this then remove the riddler
knob, fit one washer over the rod and then slide the rod through the
hole from the inside of the stove.)
Feed the rod through the two side fireplates and slide the other
washer on to the rod so that the washers end up outside the two side
fireplates. With the side fireplates pushed together fit the retaining
clips so that the washers come inside the clips.
Slide the side fireplates apart so that they rest against the sides of the
firebox. Slot in the front and rear support plates.
Fit the grate plates into position through the front and rear grate
support plates, making sure they locate correctly onto the riddler
rod. Fit the fuel retainer. Slide the ashpan under the grate.
Before lighting the stove check with the installer that the work and
checks described in the Installation Instructions have been carried out
correctly and that the chimney has been swept, is sound and free
from any obstructions. The stove is not suitable for use in a shared
flue system.
Remember that the stove will be hot and that it is made from hard
materials – ensure that you have good balance before operating the
fire.
Do not use an aerosol spray on or near the stove when it is alight.
There is a risk of explosion or flash ignition of the spray.
The stove is suitable for intermittent operation.
This stove has been designated to burn wood. Only dry, well
seasoned wood should be burnt on this appliance as burning wet
unseasoned wood will give rise to heavy tar deposits in the stove, on
the glass and within the chimney. For the same reason hard woods
(such as Ash, Beech and Oak) are better than soft woods (such as
Pine and Spruce). Burning wet unseasoned wood will also result in
considerably reduced outputs.
The wood should be cut and split and then left to season in a well
ventilated dry place for at least one year but preferably two years
before use. Approximate suitable log sizes are 255mm (10in) long
and 75mm (3in) diameter.
This stove is not designed to burn household waste.
For advice on other fuels please contact Charnwood.
This appliance has been approved by HETAS as an intermittent
operating appliance for burning dry seasoned wood logs only. HETAS
approval does not cover the use of other fuels either alone or mixed
with wood logs nor does it cover the instructions for use of other
fuels.
PETROLEUM COKE IS NOT SUITABLE FOR USE ON
THIS APPLIANCE. ITS USE WILL INVALIDATE THE
GUARANTEE.
When using the stove in situations where children, aged and/or
infirm persons are present a fireguard must be used to prevent
accidental contact with the stove. The fireguard should be
manufactured in accordance with BS 8423:2002.
FUE L
FIT T ING THE R IDDLI N G GRATE
®
OPERATING INSTRUCTIONS
4
Fig.1. Optional Grate Kit
Front Grate Support
RH Side Grate Support
Grate Plates
Rear Grate Support
Riddler Rod
Ashpan
LH Side Grate Support
Page 5
LIG H TING
CON T ROLL ING THE F IRE
On initial lighting, the stove may smoke and give off an odour as the
silicon paint with which the firebox is painted reacts to the heat. This
is normal and will cease after a short time, but meanwhile the room
should be kept well ventilated.
At first only light a small fire and burn it slowly for two hours to allow
any residual moisture in the chimney to evaporate.
Light the stove using dry kindling wood and paper or fire lighters. Put
the paper, or fire lighters, and kindling in the firebox and cover with a
few small dry logs. Open the air control fully (see Fig. 2) Light the
paper or fire lighters. The door may be left cracked open for a few
minutes to assist the combustion and heat up the firebox more
quickly. When the kindling wood is well alight add a few more small
logs and close the door, but leave the air control fully open. When
the flames are established around these logs, load the stove with the
required fuel load. Maintain the air control at maximum at this stage.
Once the fire is up to temperature the airwash system will begin to
work, so allow the fire to become hot before adjusting the air control
to the required setting. During the lighting period, do not leave the
stove unattended. Do not leave the door open except as directed
above to avoid excessive smoke.
When relighting the stove, leave the ash on the base if burning wood,
unless it is becoming too deep, in which case some of it may be
removed. If burning high ash content fuel, clear the grate and empty
the ashpan before relighting.
The rate of burning and hence the output is controlled by the air
control (see Fig. 2).
Open the air control fully (boost position) when lighting or when
rapid burning is required. It should not be left fully open for long
periods as this can cause over-firing or excessive smoke production.
For high output move the air control to the ‘click position’ or for low
burning to the fully closed position.
When the fire is burning normally the air control gives enough
airwash to keep the glass clean. However, it will not always be
possible to keep the glass clean with the air control fully closed.
Keep the firebox well filled but do not allow fuel to spill over the top
of the fuel retainer.
Logs should be evenly distributed, filling the firebed to give the most
pleasing flame pattern. The air control must be fully opened after
refuelling until the flames are established above the fire. It is best to
refuel on to a hot bed of ash. If at this point the fire starts to die, the
door must be cracked open until the fire is revived. If the fire has
started to die down before refuelling, then more kindling wood must
be added, the air control opened fully and the door cracked open to
re-establish the firebed adding larger logs (see suitable log
sizes in Fuel section). This will avoid excessive smoke emission.
Care should be taken, especially when burning wood, that fuel does
not project over the fuel retainer or damage to the glass may be
caused when the door is closed. It can also cause the glass blackening
of the glass. Maximum filling height is such that logs cannot fall from
the fire when the door is opened. In smoke controlled areas do not
fill the stove above the level of the front firebars, as overloading can
cause excess smoke. Liquid fuels are not to be used on this appliance.
The ashpan should be emptied regularly before it becomes too full.
Never allow the ash to accumulate in the ashpan so that it comes in
contact with the underside of the grate as this will seriously damage
the grate bars. The ashpan is handled using the tool provided. Care
should be taken to ensure that ash is cool before emptying it into
plastic liners or bins.
To make ash removal easier there is a special Charnwood ash carrier
available. This may be purchased from your supplier or, in case of
difficulty, directly from Charnwood.
before
For
correct firing we recommend the use of a stove pipe thermometer
which may be purchased from your supplier or directly from
Charnwood.
REF U ELLIN G
ASH CLEARANCE
5
®
OPERATING INSTRUCTIONS
Fig.2. Stove Controls
Air Control Pull out to Open Push in to Close
Door Handle
Pull to Open
Low
Output
High
Output
(‘Click’)
Boost
Air Control
positions
Page 6
RED U CED BUR NING
CLE A NING AN D MAINT E NANCE
THR OAT PLAT E AND
FLUEWAY CLEA NING
For reduced burning the fire door must be closed.
When burning wood in areas that are not smoke controlled, load
some large logs on the fire and allow to burn for half an hour before
closing the air control (this will help to reduce tar deposits in the
chimney). Some experimentation may be necessary to find the setting
most suitable for the type of fuel being used and the draw on the
chimney.
To revive the fire, empty the ashpan, (if burning fuel other than
wood), riddle the fire, and open the air control to maximum. When
the fire is burning well load on more fuel as necessary and adjust the
air control to the desired setting.
The stove is finished with a high temperature paint which will
withstand the temperatures encountered in normal use. This may be
cleaned with a damp lint-free cloth when the stove is cold. Should re-
painting become necessary, high temperature paints are available
from your supplier or from stove shops.
Most deposits on the glass may be burnt off simply by running the fire
at a fast rate for a few minutes. If it becomes necessary to clean the
glass then open the door and allow it to cool. Clean the glass using a
damp cloth and then wiping over with a dry cloth. Any stubborn
deposits on the glass may be removed with a proprietary stove glass
cleaner or ceramic hob cleaner. Do not use abrasive cleaners or pads
as these can scratch the surface which will weaken the glass and cause
premature failure.
It is important that the throat plate and all the stove flueways are kept
clean in order to prevent potentially dangerous fume emission. They
should be cleaned at least monthly, and more frequently if necessary.
It is necessary to let the fire out to carry out these operations.
The front of the throat plate is pulled forward and then lowered as
shown in Fig. 3. Any sooty deposits should then be swept from the
plate and into the fire.
Return the throat plate to its correct position - raise the front of the
plate, push it back and then lower it onto the retaining lugs.
CHIMNEY SWEEPING
SERVIC ING
The chimney should be swept at least twice a year. Where the top
outlet or vertical rear flue connector is used it will generally be
possible to sweep the chimney through the appliance.
First remove the fuel retainer and the throat plate. Then sweep the
chimney ensuring that soot is removed from all horizontal surfaces
after sweeping.
In situations where it is not possible to sweep through the appliance
the installer will have provided alternative means, such as a soot door.
After sweeping the chimney the appliance flue outlet and the flue
pipe connecting the stove to the chimney must be cleaned with a flue
brush.
After clearing any soot from within the stove, replace the throat plate
(see Fig. 3) and the fuel retainer.
Different types of sweep’s brushes are available to suit different
flueways. For standard brick chimneys, a wire centre sweep’s brush
fitted with a guide wheel is recommended. For prefabricated
insulated chimneys the manufacturers instructions with regard to
sweeping should be consulted.
It is recommended that the fire is serviced once a year to keep it in
first class working order. After cleaning out the firebox thoroughly,
check that all internal parts are in good working order, replacing any
parts that are beginning to show signs of wear. Check that the doors
seals are in good condition and that the door seals correctly. A
servicing guide is available on request. Repairs or modifications may
only be carried out by the Manufacturer or their approved agents.
Use only genuine Charnwood replacement parts.
6
®
OPERATING INSTRUCTIONS
Throat Plate
Pull Up and Swing Down
Fig.3. Throat Plate Position and Lowering
Page 7
Persistent fume emission is potentially dangerous and must not be
tolerated. If fume emission does persist, then the following
immediate actions should be taken:
a) Open doors and windows to ventilate the room.
b) Let the fire out and safely dispose of the fuel from the
appliance.
c) Check for flue or chimney blockage, and clean if required.
d) Do not attempt to re-light the fire until cause of fume has been
identified. If necessary, seek professional advice.
Fire blazing out of control
Chimney Fires
The most common cause of fume emission is flueway or chimney
blockage. For your own safety these must be kept clean.
Check that:
a) The door is tightly closed.
b) The air control slider is fully closed.
c) A suitable fuel is being used.
d) Door seals and airwash slide are intact.
If the chimney is thoroughly and regularly swept, chimney fires should
not occur. However, if a chimney fire does occur close the air control,
and tightly close the door of the appliance. This should cause the
chimney fire to go out in which case the controls should be kept
closed until the stove has gone out. The chimney and flueways should
then be cleaned. If the chimney fire does not go out when the above
action is taken then the fire brigade should be called immediately.
After a chimney fire the chimney should be carefully examined for
any damage. Expert advice should be sought if necessary.
Your installer should have fitted a CO alarm in the same room as the
appliance. If the alarm sounds unexpectedly, follow the instructions
given under “Warning Noteabove.
If you need further help with your Charnwood then your Installer will
be able to provide the answers to most questions. Your Local
Charnwood Premier Dealer has a great deal of experience and will
also be able to provide helpful advice. Further help is available from
the Charnwood Customer Services department who will be pleased
to give advice, if necessary.
CO AL A RM
IF YOU NEED FURTHER HELP
TROUBLE SHOOTING
Fire Will Not Burn
Blackening of Door Glass
Fume Emission
Warning Note:
Properly installed and operated this appliance will not emit fumes.
Occasional fumes from de-ashing and re-fuelling may occur.
Check that:
a) the air inlet is not obstructed in any way,
b) chimneys and flueways are clear,
c) a suitable fuel is being used,
d) there is an adequate air supply into the room,
e) an extractor fan is not fitted in the same room as the stove.
f) there is sufficient draw in the chimney. Once the chimney is warm a
draught reading of at least 2.5 mm (0.10 inches) water gauge (25Pa)
should be obtained.
Differences in chimney draughts mean that the best settings of the air
controls will vary for different installations. A certain amount of
experimentation may be required, however the following points
should be noted and with a little care should enable the glass to be
kept clean in most situations:
a) Wet or unseasoned wood, or logs overhanging the front fence will
cause the glass to blacken.
b) The airwash relies on a supply of heated air to keep the glass clean.
Therefore, when lighting the stove, allow the firebed to become well
established before closing the air control. This may also be necessary
when re-fuelling the stove.
c) When re-fuelling keep the fuel as far back from the front fence as
possible. Do not try to fit too much fuel into the firebox.
d) Do not completely close the air control.
It is always more difficult to keep the glass clean when running the
stove very slowly for long periods.
If blackening of the glass still occurs check that all flue connections
and the blanking plate are well sealed. It is also important that the
chimney draw is sufficient and that it is not affected by down-draught.
When the chimney is warm a draught reading of at least 2.5 mm
(0.10 inches) water gauge (25Pa) should be obtained. Some
blackening of the glass may occur below the level of the fuel retainer.
This will not obscure the view of the fire or affect its performance.
7
®
OPERATING INSTRUCTIONS
Page 8
Page 9
HEALTH AND SAFETY PRECAUTIONS
SPE C IFICATI ON
CHI M NEY
Please take care when installing the stove that the requirements of
the Health and Safety at Work Act 1974 are met.
Some types of fire cement are caustic and should not be allowed to
come into contact with the skin. In case of contact, wash with plenty
of water.
If there is a possibility of disturbing any asbestos in the course of
installation then please use appropriate protective equipment.
There must not be an extractor fan fitted in the same room as the
stove as this can cause the appliance to emit fumes into the room.
As the output is below 5kW a permanent air supply is not normally
required. This stove is capable of intermittent operation.
This stove is not suitable for use in a shared flue system.
In addition to these instructions the requirements of BS 8303 and
BSEN 15287-1:2007 must be fulfilled. Local Authority Bylaws and
Building Regulations, including those referring to national and
European Standards, regarding the installation of Solid Fuel burning
appliances, flues and chimneys must also be observed.
Building regulations require that whenever a new or replacement
fixed solid fuel or wood/biomass appliance is installed in a dwelling a
carbon monoxide alarm must be fitted in the same room as the
appliance. Further guidance on the installation of the carbon
monoxide alarm is available in BS EN 50292:2002 and from the
alarm manufacturer's instructions. Provision of an alarm must not be
considered a substitute for either installing the appliance correctly or
ensuring regular servicing and maintenance of the appliance and
chimney system.
The nominal output of the C-FOUR is 4.9 kW (16,700 Btu/h). This
output is based on a 45minute re-fuelling cycle burning seasoned
hardwood logs. The average flue temperature at rated output is
281°C. The Flue gas mass flow is 4.2g/s and the stove weight is
62kg.
In order for the appliance to perform satisfactorily the chimney height
must not be less than 4 metres measured vertically from the outlet of
CO AL A RMS
the stove to the top of the chimney. The internal dimensions of the
chimney should preferably be 175 mm (7 inches) or 200mm (8
inches) either square or round and MUST NOT BE LESS THAN 125
mm (5 INCHES).
If an existing chimney is to be used it must be swept and checked, it
must be in good condition, free from cracks and blockages, and
should not have an excessive cross sectional area. If you find that the
chimney is in poor condition then expert advice should be sought
regarding the necessity of having the chimney lined. If it is found
necessary to line the chimney then a lining suitable for Solid Fuel must
be used.
If there is no existing chimney then a prefabricated block chimney or
a twin walled insulated stainless steel flue to BSEN 15287-1:2007 can
be used either internally or externally. These chimneys must be fitted
in accordance with the manufacturers instructions and Building
Regulations.
Single wall flue pipe is suitable for connecting the stove to the
chimney but is not suitable for using for the complete chimney.
If it is found that there is excessive draw in the chimney then a
draught stabiliser should be fitted.
It is important that there is sufficient draw in the chimney and that
the chimney does not suffer from down-draught. When the chimney
is warm the draw should be not less than 2.5mm (0.10 inches) water
gauge (25 Pa). If in doubt about the chimney seek expert advice.
HEA RTH AND F IRE SUR ROUND
The stove must stand on a fireproof hearth and must not be situated
closer than 600mm from combustible materials to the sides or rear
above hearth level unless adequately fireproofed in accordance with
local building regulations. The hearth must be of fireproof material
and at least 12mm (½ inch) thick. The positioning of the stove and
the size of the hearth are governed by building regulations for Class 1
appliances. These building regulations state that the hearth must
extend in front of the stove by at least 300mm (12 inches) and to the
sides of the stove by at least 150mm (6 inches).
If in
doubt as to the positioning of the stove, expert advice should be
sought either from the supplier or the local building inspector.
The fireplace must allow good circulation of air around the appliance
to ensure that maximum heat is transferred to the room and also to
prevent the fireplace from overheating. A gap of 150mm (6 inches)
each side and 300mm (12 inches) above the appliance should give
When the fire door
is open, it extends beyond the flat front of the stove by 365mm.
9
®
INSTALLATION INSTRUCTIONS
Page 10
sufficient air circulation. If a wooden mantelpiece or beam is used in
the fireplace it should be a minimum of 460mm (18 inches), and
preferably 600mm (24 inches) from the appliance. In some situations
it may be necessary to shield the beam or mantelpiece to protect it.
In order for the fire to operate correctly and to allow for access,
there must be an air gap behind the appliance of at least 75mm, but
be aware that this distance will need to be greater in some cases to
meet Building Regulation requirements.
CON N ECTIO NS TO FLUES
The stove must be connected to the flue using 125mm (5") i/d pipe.
This may be stainless steel, cast iron, or thick wall steel pipe. Straight
lengths of Charnwood Pipe to match the stove are available if
required.
There are several ways of connecting the stove to the flue. These are
illustrated in Figs. 5 to 8.
If the optional vertical rear flue connector is used then the chimney
may be swept through the appliance.
Horizontal lengths of flue must be kept to a minimum and should not
be more than 125mm (5 inches) long.
The stove comes with the blanking plate fitted to the top flue outlet.
The seal for the outlet is a 180mm dia ring of rope seal. The seal
for the outlet is a length of adhesive backed fibre webbing
supplied with instructions. This is applied to the flue collar or the
Vertical Rear Flue adapter for rear outlet installations. For top outlet
installations, the blanking plate must be removed and the webbing
fitted to its sealing face, then fitted to the rear flue outlet.
top
rear
Ensure that
10
®
INSTALLATION INSTRUCTIONS
Fig. 4. Flue Blanking Plate.
Blanking Plate
Clamping plate finishes flush with inside face of firebox top and bottom.
with Glass Fibre Webbing
Seal Blanking Plate
Register Plate
Soot Door
In Side or Rear
Of Chimney
Register Plate With Soot Door
Alternative
Soot Door Positions
Register Plate
With Soot Door
Alternative
Soot Door Positions
Fig. 5. Vertical Register Plate With Bricked Up Fireplace
Fig. 6. Horizontal Register Plate With Rear Flue Connection
Fig. 7. Horizontal Register Plate With Top Flue Connection
Glass Fibre Webbing
Blanking Plate
Back of Stove
Clamping Plate
M8 Nut
Page 11
the fold on the clamping plate is in line with the lugs on the firebox as
shown in Fig.4. Ensure that the clamping plate does not prevent the
throat plate from seating correctly. All flue connections must be well
sealed.
It is possible to pass a 16 inch diameter sweep’s brush through the
appliance but in most back outlet installations it will be necessary to
have a soot door to enable the chimney to be swept. The optional
vertical rear flue connector does allow the chimney to be swept
through the stove.
SOO T DOORS
PRE L I GHTIN G CHECK
COM M ISSIO NING
Soot doors may either be in the actual brickwork of the chimney or
in the register plate. Various positions of soot doors are shown in
Figs. 5 to 8.
Ensure that the throat plate is fitted in the roof of the appliance. The
location and positioning of the throat plate is shown in Fig. 3.
Check that the front fence is fitted correctly and that the door closes
properly.
On completion of the installation allow a suitable period of time for
the fire cement and mortar to dry out before lighting the fire. If no
grate is fitted make a layer of ash or sand on the base of the stove
before lighting. Check to ensure that smoke and fumes are taken
from the appliance up the chimney and emitted safely. Also check all
joints and seals. On completion of the installation and commissioning
please leave the operating instructions with the customer and advise
them on the use of the appliance.
Under the Clean Air Act local authorities may declare the whole or
part of the district of the authority to be a smoke control area. It is an
offence to emit smoke from a chimney of a building, from a furnace
or from any fixed boiler if located in a designated smoke control area.
It is also an offence to acquire an "unauthorised fuel" for use within a
smoke control area unless it is used in an "exempt" appliance
("exempted" from the controls which generally apply in the smoke
control area).
The Secretary of State for Environment, Food and Rural Affairs has
powers under the Act to authorise smokeless fuels or exempt
appliances for use in smoke control areas in England. In Scotland and
Wales this power rests with Ministers in the devolved administrations
for those countries. Separate legislation, the Clean Air (Northern
Ireland) Order 1981, applies in Northern Ireland. Therefore it is a
requirement that fuels burnt or obtained for use in smoke control
areas have been "authorised" in Regulations and that appliances used
to burn solid fuel in those areas (other than "authorised" fuels) have
been exempted by an Order made and signed by the Secretary of
State or Minister in the devolved administrations.
The has been recommended as suitable for use
in smoke control areas when burning wood logs.
Further information on the requirements of the Clean Air Act can be
found here: http://smokecontrol.defra.gov.uk/
Your local authority is responsible for implementing the Clean Air Act
1993 including designation and supervision of smoke control areas
and you can contact them for details of Clean Air Act requirements.
CAA AN D SMOKE CO NTRO L
The Clean Air Act 1993 and Smoke Control Areas
Charnwood C-FOUR
11
®
INSTALLATION INSTRUCTIONS
Register Plate With Soot Door
Alternative
Soot Door Positions
Fig. 8. Horizontal Register Plate With Optional Vertical Rear Flue Connector
Page 12
®
C-FOUR DIMENSIONS (mm)
12
763
710
608
194.5
64.5 OD
458
62 ID
44.5
Dimensions of the
Optional Vertical
Rear Flue Connector
140 i/d to suit 125mm (5")
flue pipe
Page 13
Issue K
19
®
char n w ood BI SH OPS WAY, NEWPORT, IS LE OF WIGHT PO3 0 5W S, U NI TED KINGDOM
T: +4 4 (0 )19 83 53 77 99 • F:+ 44 (0 )19 83 53 77 88 • SP AR ES@ CH AR NWO OD. CO M • WW W.CH AR NWO OD .C OM
®
C-FOUR PART S L I S T
Item Part No. Description
1# 002/BR001/A Door Assembly 2 008/FFW026 1/4 Heavy Brass Washer 3 006/PV19 Glass (inc seal) 4 008/BR014 Handle Pivot Pin 5 004/BW23 Glass Retainer 6 008/FFS018 M6x16 C'sunk Skt Hd Screw 7 008/PV21 Rope Door Seal 8 004/BR005 Air Box Control Plate 9 004/BR007 Air Inlet Slide 10# 001/BR010 Firebox 11 004/BR016 Control Rod 12 002/BR017 Fuel Retainer BR 13 010/BR031 Throat Plate 14 010/BR029 RH Sideplate 15 010/BR030 Inner Backplate 16 004/BR040 Airbox Cover 17 002/DY21 Riddler Knob 18 008/BR044 Gasket Blanking Plate 19 008/BR006 Gasket Airbox 20 008/FFB034 M8 Nyloc nut 21 012/BR011 Serial No. Label 22 002/PV13 Door Latch 23 008/FFW025 M8 Wavy Washer 24 008/FFW007 3/8" Plain Light Washer 25 008/FFS050 M8 Bolt 30mm Long 26 008/AY37 Air Control Knob 27 002/BR034 Wood Ash Retainer 28 008/BR045 Air Box Gasket
34 008/FFS025 M6 x 12 Bright Pozi Pan Hd 35 008/BR047 Back Gasket 36 008/FFS059 M8 x 20 Hex Hd Bolt 37 008/BR052 Felt Washer 38 011/PV26 Side Gasket 39 004/BR053 Air Inlet Spigot assy 40 004/BR054 Blanking Plate 41 004/DY22 Riddler Blanking Disk 42 010/EY12 Serial Number Hanger Bracket 43# 010/PV33 Vert Rear Flue Adaptor 44 002/PV12B Flue Collar 45 012/PV09 Blanking Plate 46 002/BR020 Hinge 48 004/BR033 Ashpan 49 002/EY03 Grate Plate 50 010/EY04 L.H. Grate Support 51 010/EY05 R.H. Grate Support 52 010/EY06 Front Grate Support 53 010/BR035 Rear Grate Support 54 010/EY13 Riddler Rod Assy 55* 008/PV55 Glass Seal 56* 008/FW29 Door Seal Adhesive 57# 002/BR012 Handle Casting 58 004/BR015 Clicker Retainer Plate 59 008/ES36/01 Brass Ball Catch 60 010/BR022 Grate Kit 61* 010/EW51 Ash Carrier (Optional Extra) 62 008/BW39/S Hinge Pin Set 63 008/FFW015 Spring Washer (Thackery Type) 64 008/FFB007 M8 x 100mm Allen Head Bolt 65# 010/BR050 Store Stand 66* 010/BR057 Heat Shield
29 010/BR028 LH Sideplate 30 008/BR012 Wooden Handle 31 008/FFS003 Pan Head Screw M5 x 10 32 008/FFS078 Pozi Pan Head 4.2 x 9.5 33 008/FFB003 Coach Bolt M6 x 20
(Optional Extra)
Item Part No. Description
To obtain spare parts please contact your local stockist giving Model, Part No. and Description. In case of difficulty contact the manufacturer at the address shown.
* These items are not shown on the drawing. # Please specify colour when ordering. This drawing is for identification purposes only.
17
52
50
48
51
53
49
68
60
54
Optional Grate Kit
14
15
13
46
12
27
22
5
333145
21
34
19
8
9
16
18
4025 11 17 26
28
37
29
32
42
43 44
32
20
24
23
7
30
1
2
3
6
10 35
58
59
57
38
38
36
62
41
65
6364
67
4
39
Page 14
14
EN13240:2001
ROOMHEATERS FIRED BY SOLID FUEL
EC certificate of conformity no:
Fuel types:
Minimum distance to combustible materials: Side: Rear:
Emission of CO in combustion products:
Flue gas temperature:
Space heating thermal output:
Energy efficiency:
A Division of A .J.Wells & Sons Limited Registered in England No. 03809371
11
Bishops Way, Newport, Isle of Wight PO30 5WS, United Kingdom
A.J WELLS & SONS LTDA.J WELLS & SONS LTD
BR080-CPD-2011
600 mm 600 mm
0.18%
281°C
4.9kW
78.3%
Wood Logs
Page 15
Page 16
A D i v i s i o n o f A . J . W e l l s & S o n s L i m i t e d R e g i s t e r e d i n E n g l a n d N o . 0 3 8 0 9 3 7 1
char n w ood BI SH OPS WAY, NEWPORT, IS LE OF WIGHT PO3 0 5W S, U NI TED KINGDOM
T:+ 44 (0)198 3 537 777 • F :+ 44 (0) 198 3 5377 88 • CH ARNWO OD @AJWELL S.CO.UK • WWW.CH ARN WOO D. CO M
y ou r p re m ie r d e al e r
REV.C-FOUR v1 08.
11
®
Loading...