Charles Bentley & Son Solid Power AE User Manual

FERRORESONANT BATTERY CHARGERS
C-CHARGER®AE SERIES
MANUAL FLOAT/EQUALIZE BATTERY CHARGERS
Safe to say, there’s no other float charger built like a C-Charger from Charles Industries. Rugged #304 grade stainless steel forms the sturdy housing that withstands virtually all environmental challenges; including heat, humidity, vibration, and other stress factors. The steel cover is hinged to ease installation
Electrically, the C-Charger is a paragon of efficiency and simplicity. It uses a ferroresonant transformer with integral self­regulation. It has been intelligently designed to be completely devoid of any complicated switching circuits that could possibly burn out. There are no tubes nor delicate electronics to fail or to cause radio frequency interference (RFI). By simplifying our design, Charles has increased reliability
without sacrificing performance or usability.
Voltage output to the batteries remains at a safe and constant DC level from full load to no load, even if AC power runs as high as 132 VAC or as low as 108 VAC. This automatic voltage regulation relieves strain on internal electrical components and lengthens the lifespan of the unit. All components are designed to operate safely and continuously in an ambient temperature as high as 122º F.
AE Series Battery Chargers are available in 12, 24 and 32 Volt models and may be used with
both lead acid and nickel cadmium battery banks.
Features
UL Listed
• DC ammeter and voltmeter
• Float/equalize switch
• Equalize light
• AC circuit breaker
• Terminal board
Cannot discharge battery during AC failure
• Stainless steel for corrosion resistance
• Ferroresonant transformer for reliability
• Sealed silicon diodes
• Isolated output: no direct AC to DC connection
• Isolated positive and negative: can be used as a negative voltage charger
• Two year limited warranty
Ordering Information
Optional Accessories
• 0-24 hour equalize timer
• Automatic 24 hour equalize timer
• Low DC voltage alarm relay
• High DC voltage alarm relay
• Current failure relay
• AC power failure relay
• DC cranking disconnect relay
• AC pilot light
Specifications
AC Input 108-132 volts/60 Hz (220 volts/50 Hz optional)
Operating Temperature 0º to 50º C (32º to 122º F)
Storage Temperature -20º to 60º C (-4º to 140º F)
Cooling Convection
DC Output
- Float 2.16 VPC for lead Acid, 1.45 VPC for nickel cadmium
- Equalize 2.33 VPC for lead Acid, 1.55 VPC for nickel cadmium
Current Limit Approximately 135%
Enclosure 304 stainless steel hinged cover to facilitate installation
0 102030405060708090100
% OF RATED CHARGING CURRENT (AMPS)
VPC
2.5
2.4
2.3
2.2
2.1
2.0
1.9
1.8
Equalize
Float
Typical Output Curve
Contact your Charles sales representative for specific product information.
When ordering, please specify:
1. Model number
2. AC input: voltage & frequency
3. Battery type and number of cells
4. Ampere-hour capacity of battery
5. Recharge time desired
6. Description of load
7. Options
D-IND001-B01 Rev. 3
12 Volt
Model
Number
Height Inches
Width
Inches
Depth
Inches
Approx.
Weight
D.C. Output
Amps
System Voltage
24 Volt
32 Volt
AE1206* 6 12 11 9 8.5 12 AE1210* 10 12 11 9 8.5 14 AE1220* 20 12 11 9 8.5 22 AE1230 30 12 11 9 8.5 26
AE2406* 6 24 11 9 8.5 14 AE2410* 10 24 11 9 8.5 22 AE2420* 20 24 16.5 15 8.5 38 AE2430 30 24 16.5 15 8.5 55
AE3210 10 32 11 9 8.5 26 AE3230 30 32 16 17 14.5 74
*UL Listed
Charles Industries, Ltd. Industrial Group 5600 Apollo Drive Rolling Meadows, IL 60008 USA
Voice: (847) 806-6300 Fax: (847) 806-6352 E-mail: mktserv@charlesindustries.com